Room humidity and temperature sensor (wall) · BACnet points list
Veris HW2 Protocol Series humidity and temperature room sensor BACnet points list
Updated 6 November 2026
The HW2 is a wall room sensor that reports temperature and humidity over BACnet MS/TP (or Modbus, DIP-selectable). Touchscreen models add occupant setpoints for temperature and humidity, a fan speed selection, an occupancy override and display settings as writable values.
This page lists 13 BACnet objects for the Veris HW2 Protocol Series humidity and temperature room sensor — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.
- Manufacturer
- Veris
- Model
- HW2 Protocol Series humidity and temperature room sensor
- Equipment
- Room humidity and temperature sensor (wall)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 13 (11 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Vendor ID + MS/TP address (nnn)
- Also known as
- HW2, HW2 Protocol, HW2TP2A, Living Space Room Unit, Veris HW2 BACnet
Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.
BMS integration notes: Veris HW2 Protocol Series humidity and temperature room sensor
Set the MS/TP address and BACnet mode on the DIP switches, then read room temperature and humidity. On touchscreen models also read the occupant setpoint, fan speed and override.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Room Temperature | Room temperature | Read |
| AI 2 | Room Humidity | Room relative humidity, % | Read |
| AV 1 | Temperature Setpoint* | Occupant temperature setpoint, 0-50 | Write |
| BV 5 | Occupancy Override | Override button state: active = not occupied | Write |
| MV 2 | Fan Speed* | Occupant fan speed selection, 1-5 | Write |
Network setup
- BACnet MS/TP on RS-485: DIP switch ADDRESS positions 1-7 set the MAC (0-127 for BACnet), position 8 selects BACnet or Modbus.
- Baud rates for BACnet: 9600, 19200, 38400, 76800, set on the CONFIG DIP switch.
- Device instance = Vendor_ID followed by the MS/TP address (e.g. 133nnn); it can be rewritten in the device object.
Watch out for
- Occupancy Override logic is inverted: active means not occupied.
- Setpoint range is limited by each AV's Min/Max_Pres_Value (0-50 temp, 0-100 RH).
Veris HW2 Protocol Series humidity and temperature room sensor BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Room Temperature | Room temperature | °C or °F | Read | |
| AImin | 2 | Room Humidity | Room relative humidity | %RH | Read | |
| AVmin | 1 | Temperature Setpoint* | Temperature setpoint, 0-50 | °C | Write | |
| AV | 2 | Humidity Setpoint* | Humidity setpoint, 0-100 | %RH | Write | |
| BV | 2 | Touch Disable* | Disables touch response when active | Write | 0=Touch enabled, 1=Touch disabled | |
| BV | 4 | Temperature Units* | Display units | Write | 0=Celsius, 1=Fahrenheit | |
| BVmin | 5 | Occupancy Override | Occupancy override (active = room not occupied) | Write | 0=Occupied, 1=Not occupied | |
| BV | 6 | Screen Timeout* | Enables screen timeout | Write | 0=Disabled, 1=Enabled | |
| BV | 7 | Display Humidity* | Shows humidity on the screen | Write | 0=Hidden, 1=Shown | |
| BV | 11 | Select Temperature Display* | Main screen shows setpoint (active) or room temperature | Write | 0=Room temp on main screen, 1=Setpoint on main screen | |
| BV | 13 | Display Setpoint* | Shows temperature setpoint on home screen | Write | 0=Hidden, 1=Shown | |
| MV | 1 | Screen Color Set* | Screen color theme, 1-4 | Write | ||
| MVmin | 2 | Fan Speed* | Fan speed selection, 1-5 | Write |
No points match these filters.
Object ID lookup: Veris HW2 Protocol Series humidity and temperature room sensor point IDs by name
Integration notes
- Names with * are preserved through power outages; avoid writing them cyclically.
- Touchscreen setpoint, fan speed, display and color objects only matter on touchscreen models.
- The guide's range table also lists Temp Offset and Humidity Offset, but its objects table has no offset objects; the SpaceLogic SLP twin lists them as AV 7/AV 8.
- Occupancy Override is active when the room is NOT occupied (as printed).
- Source: HW2 Protocol Series Installation Guide Z207936-0K, objects table p7-8.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HW2 Protocol Series humidity and temperature room sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Veris HW2 Protocol Series humidity and temperature room sensor
How many BACnet points does the Veris HW2 Protocol Series humidity and temperature room sensor have?
This list has 13 BACnet objects: 2 analog inputs, 2 analog values, 7 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Veris HW2 Protocol Series humidity and temperature room sensor BACnet points are writable?
11 of the 13 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Veris HW2 Protocol Series humidity and temperature room sensor BACnet documentation?
The source is HW2 Protocol Series Installation Guide (Z207936-0K), revision 2024-06, published free by Veris at https://download.se.com/files?p_Doc_Ref=Z207936.
What are the minimum BACnet points to integrate the Veris HW2 Protocol Series humidity and temperature room sensor?
Start with AI 1 Room Temperature (Room temperature); AI 2 Room Humidity (Room relative humidity, %); AV 1 Temperature Setpoint* (Occupant temperature setpoint, 0-50); BV 5 Occupancy Override (Override button state: active = not occupied); MV 2 Fan Speed* (Occupant fan speed selection, 1-5).
How do I check these points on the real HW2 Protocol Series humidity and temperature room sensor?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Veris BACnet points lists
- Indoor air quality sensor (CO2, VOC, temperature, humidity)
Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor
Veris CW2 Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP Air Quality Series, on BACnet MS/TP.
Also known as: CW2, CW2 Protocol, SpaceLogic SLP Air Quality, SLP Series Air Quality, Z207902, Living Space Room Unit - Power and energy meter
Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)
Veris E50H2 and E50H5 DIN-rail power and energy meters with BACnet MS/TP; the E50H5 adds data logging and a real-time clock alert.
Also known as: E50H2, E50H5, E50H2A, E50H5A, Veris E50, E50Hx, ZL0071 - Gas detection sensor (wall platform)
Veris GWNP Series wall gas sensor platform (AG sensors)
Veris GWNP wall-mounted gas platforms fitted with a Veris AG Series gas sensor, on BACnet MS/TP.
Also known as: GWNP, GWNPxx, GWN, Veris gas platform BACnet, AG Series gas sensor - Indoor air quality sensor (PM, CO2, VOC, temperature, humidity)
Veris PMW Protocol Series particulate (PM), CO2 and VOC room sensor
Veris PMW Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP PM Series, on BACnet MS/TP.
Also known as: PMW, PMW Protocol, SpaceLogic SLP PM, SLP Series PM, ZL0199, Veris PM sensor BACnet - Room temperature sensor (wall)
Veris TW2 Protocol Series temperature room sensor
Veris TW2 Protocol Series wall temperature sensors (optional touchscreen) set to BACnet MS/TP.
Also known as: TW2, TW2 Protocol, Living Space Room Unit, Veris TW2 BACnet
Source: HW2 Protocol Series Installation Guide · Z207936-0K · rev. 2024-06. Object names, instances and units are reproduced as published; descriptions are our own.