Gas detection sensor (wall platform) · BACnet points list

Veris GWNP Series wall gas sensor platform (AG sensors) BACnet points list

Updated 6 November 2026

Short answer

The GWNP is a wall platform that carries one replaceable Veris AG gas sensor (single or dual gas) and reports it over BACnet MS/TP or Modbus. It exposes the gas readings, sensor life and runtime, writable high/low alarm setpoints and hysteresis, two setpoint-exceeded BIs and BVs to override the two relays.

This page lists 22 BACnet objects for the Veris GWNP Series wall gas sensor platform (AG sensors) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.

Manufacturer
Veris
Model
GWNP Series wall gas sensor platform (AG sensors)
Equipment
Gas detection sensor (wall platform)
Equipment type
Thermostats, sensors & meters
BACnet objects
22 (16 writable)
Transport
BACnet MS/TP
Firmware
1.1.2 (application 1.2)
Default device instance
Vendor ID + MS/TP address (nnn)
Also known as
GWNP, GWNPxx, GWN, Veris gas platform BACnet, AG Series gas sensor
Source document
GWNP Series Installation Guide · Z207135-0F · rev. 2021-08
Download CSV 22 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.

BMS integration notes: Veris GWNP Series wall gas sensor platform (AG sensors)

Integration in brief

Set the MS/TP address and BACnet mode on the DIP switches, then read the gas concentration(s) and the two setpoint-exceeded BIs; watch Lifetime for sensor replacement. Setpoints can be set over BACnet once BV 6 Lock_Settings hands control to the registers.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Sensor1*Gas concentration, sensor 1 (NO2 reads 10x)Read
AI 2Sensor2*Gas concentration, sensor 2 (dual gas)Read
BI 1High_Set-Point_ExceededHigh gas alarm (high relay state)Read
BI 2Low_Set-point_ExceededLow gas alarm (low relay state)Read
AI 3LifetimeHours left before sensor replacementRead

Network setup

Watch out for

Veris GWNP Series wall gas sensor platform (AG sensors) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

22 of 22 shown
Type
Access
Show
Veris GWNP Series wall gas sensor platform (AG sensors) BACnet Points List
DescriptionStates
AImin1Sensor1*Gas concentration, sensor 1 (NO2 reads 10x)ppmRead
AImin2Sensor2*Gas concentration, sensor 2 (dual gas only)ppmRead
AImin3LifetimeHours left until sensor replacementhRead
AI4RuntimeSensor run hourshRead
AV1Device_InstanceAlternative way to set the device instanceWrite
AV2Identifier_Value_PrefixPrefix before the MAC in the device instance (initially 133)Write
AV3Sensor1_High_Set-point*Sensor 1 high setpointppmWrite
AV4Sensor1_High_Hysteresis*Sensor 1 high hysteresisppmWrite
AV5Sensor1_Low_Set-Point*Sensor 1 low setpointppmWrite
AV6Sensor1_Low_Hysteresis*Sensor 1 low hysteresisppmWrite
AV7Sensor2_High_Set-Point*Sensor 2 high setpointppmWrite
AV8Sensor2_High_Hysteresis*Sensor 2 high hysteresisppmWrite
AV9Sensor2_Low_Set-point*Sensor 2 low setpointppmWrite
AV10Sensor2_Low_Hysteresis*Sensor 2 low hysteresisppmWrite
BImin1High_Set-Point_ExceededActive when a sensor is at or above its high setpointRead0=Inactive, 1=Active
BImin2Low_Set-point_ExceededActive when a sensor is at or above its low setpointRead0=Inactive, 1=Active
BV1Device_Object_ResetWrite active to reset device name and instance; reads inactiveWrite
BV2High_Relay_OverrideActive: BV 3 drives the high relay instead of BI 1Write
BV3High_Relay_LevelHigh relay command when BV 2 is activeWrite
BV4Low_Relay_OverrideActive: BV 5 drives the low relay instead of BI 2Write
BV5Low_Relay_LevelLow relay command when BV 4 is activeWrite
BV6Lock_SettingsActive: registers, not DIP switches, control settingsWrite
Object ID lookup: Veris GWNP Series wall gas sensor platform point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GWNP Series wall gas sensor platform (AG sensors) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veris GWNP Series wall gas sensor platform (AG sensors)

How many BACnet points does the Veris GWNP Series wall gas sensor platform (AG sensors) have?

This list has 22 BACnet objects: 4 analog inputs, 10 analog values, 2 binary inputs, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veris GWNP Series wall gas sensor platform (AG sensors) BACnet points are writable?

16 of the 22 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Veris GWNP Series wall gas sensor platform (AG sensors) BACnet documentation?

The source is GWNP Series Installation Guide (Z207135-0F), revision 2021-08, published free by Veris at https://download.se.com/files?p_Doc_Ref=Z207135.

What are the minimum BACnet points to integrate the Veris GWNP Series wall gas sensor platform (AG sensors)?

Start with AI 1 Sensor1* (Gas concentration, sensor 1 (NO2 reads 10x)); AI 2 Sensor2* (Gas concentration, sensor 2 (dual gas)); BI 1 High_Set-Point_Exceeded (High gas alarm (high relay state)); BI 2 Low_Set-point_Exceeded (Low gas alarm (low relay state)); AI 3 Lifetime (Hours left before sensor replacement).

How do I check these points on the real GWNP Series wall gas sensor platform (AG sensors)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Veris BACnet points lists

Source: GWNP Series Installation Guide · Z207135-0F · rev. 2021-08. Object names, instances and units are reproduced as published; descriptions are our own.