Duct air quality sensor (CO2, VOC, PM, humidity, temperature) · BACnet points list

Veris CD2 Protocol Series duct / plant-room air quality sensor BACnet points list

Updated 12 November 2026

Short answer

The CD2 Protocol Series is a duct or plant-room sensor that reports temperature, humidity, CO2, VOC and four particulate sizes (PM1, PM2.5, PM4, PM10) over BACnet MS/TP or Modbus. Three binary values handle CO2 automatic baseline calibration, display units and a forced 400 ppm baseline. It is a different, smaller object set than the CW2 wall sensor.

This page lists 11 BACnet objects for the Veris CD2 Protocol Series duct / plant-room air quality sensor — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.

Manufacturer
Veris
Model
CD2 Protocol Series duct / plant-room air quality sensor
Equipment
Duct air quality sensor (CO2, VOC, PM, humidity, temperature)
Equipment type
Thermostats, sensors & meters
BACnet objects
11 (3 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Vendor ID + nnn (nnn = MS/TP address)
Also known as
CD2, CD2 Protocol, CD2XPXXXX, Plant Room Air Quality Unit, SpaceLogic SCD2, SCD2 Series, GEX55250, GEX55240
Source document
CD2 Protocol Series Installation Guide · GEX55250-03 · rev. 2026-09
Download CSV 11 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.

BMS integration notes: Veris CD2 Protocol Series duct / plant-room air quality sensor

Integration in brief

Set the MS/TP address and protocol, then read the measurements you need. The BVs are only for calibration and display.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3CO2 SensorCO2, ppmRead
AI 1Room TemperatureAir temperatureRead
AI 2Room HumidityRelative humidity, %Read
AI 4VOC SensorVOC levelRead
AI 6PM2.5 SensorPM2.5 levelRead
AI 8PM10 SensorPM10 levelRead

Network setup

Watch out for

Veris CD2 Protocol Series duct / plant-room air quality sensor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

11 of 11 shown
Type
AnalogBinary
Access
Show
Veris CD2 Protocol Series duct / plant-room air quality sensor BACnet Points List
DescriptionStates
AImin1Room TemperatureTemperature°CRead
AImin2Room HumidityRelative humidity%RHRead
AImin3CO2 SensorCO2 concentrationppmRead
AImin4VOC SensorVOC levelRead
AI5PM1 SensorPM1.0 levelRead
AImin6PM2.5 SensorPM2.5 levelRead
AI7PM4 SensorPM4.0 levelRead
AImin8PM10 SensorPM10.0 levelRead
BV3CO2 ABC Cal*Automatic baseline calibration on/offWriteActive=ABC enabled; Inactive=ABC disabled
BV4Temperature Units*Display units (LCD models)WriteActive=Fahrenheit; Inactive=Celsius
BV10CO2 FRC 400Sets 400 ppm CO2 baseline when written activeWriteActive=Set 400 ppm baseline; Inactive=No action
Object ID lookup: Veris CD2 Protocol Series duct / plant-room air quality sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CD2 Protocol Series duct / plant-room air quality sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veris CD2 Protocol Series duct / plant-room air quality sensor

How many BACnet points does the Veris CD2 Protocol Series duct / plant-room air quality sensor have?

This list has 11 BACnet objects: 8 analog inputs, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veris CD2 Protocol Series duct / plant-room air quality sensor BACnet points are writable?

3 of the 11 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Veris CD2 Protocol Series duct / plant-room air quality sensor BACnet documentation?

The source is CD2 Protocol Series Installation Guide (GEX55250-03), revision 2026-09, published free by Veris at https://download.schneider-electric.com/files?p_Doc_Ref=GEX55250.

What are the minimum BACnet points to integrate the Veris CD2 Protocol Series duct / plant-room air quality sensor?

Start with AI 3 CO2 Sensor (CO2, ppm); AI 1 Room Temperature (Air temperature); AI 2 Room Humidity (Relative humidity, %); AI 4 VOC Sensor (VOC level); AI 6 PM2.5 Sensor (PM2.5 level); AI 8 PM10 Sensor (PM10 level).

How do I check these points on the real CD2 Protocol Series duct / plant-room air quality sensor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Veris BACnet points lists

Source: CD2 Protocol Series Installation Guide · GEX55250-03 · rev. 2026-09. Object names, instances and units are reproduced as published; descriptions are our own.