Room pressure controller · BACnet points list

TSI SureFlow 8636 Room Pressure Controller BACnet points list

Updated 6 November 2026

Short answer

The SureFlow 8636 holds a room at a pressure setpoint by modulating supply and exhaust dampers, with supply flow tracking, temperature control through a reheat valve and occupied/unoccupied flow and temperature setpoints. Over BACnet MS/TP it exposes room pressure, supply flow, temperature, damper and valve positions, all setpoints and alarm limits, occupancy and emergency commands, and a Status Index alarm code.

This page lists 30 BACnet objects for the TSI SureFlow 8636 Room Pressure Controller — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
SureFlow 8636 Room Pressure Controller
Equipment
Room pressure controller
Equipment type
Thermostats, sensors & meters
BACnet objects
30 (21 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS)
Default device instance
863001
Also known as
8636, 8636-BAC, SureFlow 8636
Source document
SureFlow Room Pressure Controller Models 8636/8636-BAC Operation and Service Manual · P/N 1980441 · rev. Revision H, February 2013
Download CSV 30 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI SureFlow 8636 Room Pressure Controller

Integration in brief

Command occupancy with Occ/Unocc Mode (BV 2) and use Emergency Mode (MV 2) for purge. Read room pressure, supply flow, temperature, damper positions and the Status Index (MI 1) for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2Occ/Unocc Mode0 = occupied, 1 = unoccupiedWrite
MV 2Emergency Mode1 = exit, 2 = enter emergency mode, 3 = normalWrite
AV 2Room Pressure SetpointRoom pressure setpointWrite
AV 12Temperature SetpointOccupied room temperature setpointWrite
AI 1Room PressureRoom differential pressureRead
AI 2Supply Flow RateSupply airflowRead
AI 4TemperatureRoom temperatureRead
AI 6Exhaust Damper PositionExhaust damper positionRead
MI 1Status IndexAlarm state; 1 = normal, 6 = emergencyRead

Enable & remote start

Occ/Unocc Mode (BV 2) switches between the occupied and unoccupied flow and temperature setpoints; Emergency Mode (MV 2) works like the EMERGENCY key.

Network setup

Watch out for

TSI SureFlow 8636 Room Pressure Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

30 of 30 shown
Type
BinaryOther
Access
Show
TSI SureFlow 8636 Room Pressure Controller BACnet Points List
DescriptionStates
AImin1Room Pressureft/min, m/s, in. H2O, PaRead
AImin2Supply Flow Ratecfm, l/sRead
AI3Supply Flow Setpointcfm, l/sRead
AImin4Temperature°F, °CRead
AI5Supply Damper Position% openRead
AImin6Exhaust Damper Position% openRead
AI7Reheat Valve Position% openRead
AV1MAC AddressRange 1 to 127Write
AVmin2Room Pressure SetpointRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV3Door Pressure SetpointRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV4Low Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV5High Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV6Door Low Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV7Door High Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV8Vent Min SetpointRange 0 to 30,000 cfmcfm, l/sWrite
AV9Cooling Flow SetpointRange 0 to 30,000 cfmcfm, l/sWrite
AV10Unocc Flow SetpointRange 0 to 30,000 cfmcfm, l/sWrite
AV11Min Supply AlarmRange 0 to 30,000 cfmcfm, l/sWrite
AVmin12Temperature SetpointRange 50 to 85 °F°F, °CWrite
AV13Unocc Temp SetpointRange 50 to 85 °F°F, °CWrite
AV14Min Sup Damp SetpointRange 0 to 100%% openWrite
AV15Max Sup Damp SetpointRange 0 to 100%% openWrite
AV16Min Exh Damp SetpointRange 0 to 100%% openWrite
AV17Max Exh Damp SetpointRange 0 to 100%% openWrite
BV1Control ModeWrite0=Normal, 1=Door Mode
BVmin2Occ/Unocc ModeWrite0=Occupied, 1=Unoccupied
MImin1Status IndexRead1=Normal, 2=Low Press Alarm, 3=High Press Alarm, 4=Min Supply Alarm, 5=Data Error, 6=Emergency
MVmin2Emergency ModeWrite1=Exit Emergency Mode, 2=Enter Emergency Mode, 3=Normal
MV3Units ValueWrite1=ft/min, 2=m/s, 3=in. H2O, 4=Pa
DEV863001TSI8636Device object; instance = 863000 + MAC addressRead
Object ID lookup: TSI SureFlow 8636 Room Pressure Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SureFlow 8636 Room Pressure Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI SureFlow 8636 Room Pressure Controller

How many BACnet points does the TSI SureFlow 8636 Room Pressure Controller have?

This list has 30 BACnet objects: 7 analog inputs, 17 analog values, 2 binary values, 1 device, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI SureFlow 8636 Room Pressure Controller BACnet points are writable?

21 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official TSI SureFlow 8636 Room Pressure Controller BACnet documentation?

The source is SureFlow Room Pressure Controller Models 8636/8636-BAC Operation and Service Manual (P/N 1980441), revision Revision H, February 2013, published free by TSI at https://tsi.com/getmedia/2df9628e-24cc-42f2-8ec5-a0e717143bd8/1980441G-8636?ext=.pdf.

What are the minimum BACnet points to integrate the TSI SureFlow 8636 Room Pressure Controller?

Start with BV 2 Occ/Unocc Mode (0 = occupied, 1 = unoccupied); MV 2 Emergency Mode (1 = exit, 2 = enter emergency mode, 3 = normal); AV 2 Room Pressure Setpoint (Room pressure setpoint); AV 12 Temperature Setpoint (Occupied room temperature setpoint); AI 1 Room Pressure (Room differential pressure); AI 2 Supply Flow Rate (Supply airflow); AI 4 Temperature (Room temperature); AI 6 Exhaust Damper Position (Exhaust damper position); MI 1 Status Index (Alarm state; 1 = normal, 6 = emergency).

How do I enable BMS control of the TSI SureFlow 8636 Room Pressure Controller?

Occ/Unocc Mode (BV 2) switches between the occupied and unoccupied flow and temperature setpoints; Emergency Mode (MV 2) works like the EMERGENCY key.

How do I check these points on the real SureFlow 8636 Room Pressure Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: SureFlow Room Pressure Controller Models 8636/8636-BAC Operation and Service Manual · P/N 1980441 · rev. Revision H, February 2013. Object names, instances and units are reproduced as published; descriptions are our own.