  4. PresSura 8631-CRM Clean Room Pressure Monitor

Room pressure monitor · BACnet points list

TSI PresSura 8631-CRM Clean Room Pressure Monitor BACnet points list

Updated 6 November 2026

Short answer

The 8631-CRM watches clean room pressure with up to two pressure sensors and two supply flow inputs, and alarms on pressure and minimum supply flow. With the BACnet board it is a BACnet MS/TP device with a short fixed object list: pressures, flows, air changes per hour, alarm limits, a Status Index alarm code, the units selector and a mute command.

This page lists 15 BACnet objects for the TSI PresSura 8631-CRM Clean Room Pressure Monitor — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
PresSura 8631-CRM Clean Room Pressure Monitor
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
15 (8 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS)
Default device instance
863001
Also known as
8631-CRM, 8631-CRM-BAC, PresSura 8631-CRM
Source document
PresSura Clean Room Pressure Monitor/Controller with LON/BACnet, Models 8631-CRM/8631-CRM-BAC/8631-CRC/8631-CRC-BAC Operation and Service Manual · P/N 1980489 · rev. Revision F
Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI PresSura 8631-CRM Clean Room Pressure Monitor

Integration in brief

Read room pressure, the supply flows and the Status Index (MI 1) for alarms. Mute Mode (MV 3) can silence or restore the local audible alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Room PressureRoom differential pressureRead
AI 2Sec Sens PressureSecond sensor pressure (e.g. airlock)Read
AI 3Supply#1 Flow RateSupply 1 airflowRead
AI 5Air Changes Per HourCalculated air changes per hourRead
MI 1Status IndexAlarm state; 1 = normalRead

Network setup

Watch out for

TSI PresSura 8631-CRM Clean Room Pressure Monitor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

15 of 15 shown
Type
Other
Access
Show
TSI PresSura 8631-CRM Clean Room Pressure Monitor BACnet Points List
DescriptionStates
AImin1Room Pressureft/min, m/s, in. H2O, PaRead
AImin2Sec Sens PressureSecond pressure sensorft/min, m/s, in. H2O, PaRead
AImin3Supply#1 Flow Ratecfm, l/sRead
AI4Supply#2 Flow Ratecfm, l/sRead
AImin5Air Changes Per HourRead
AV1MAC AddressRange 1 to 127Write
AV2Low AlarmRange -0.195 to +0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV3High AlarmRange -0.195 to +0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV4Sec Low AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV5Sec High AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV6Min Supply AlarmRange 0 to 30,000 cfmcfm, l/sWrite
MImin1Status IndexRead1=Normal, 2=Low Alarm, 3=High Alarm, 4=Min Supply Alarm, 5=Sec Sens Low Alarm, 6=Sec Sens High Alarm, 7=Data Error
MV2Units ValueWrite1=ft/min, 2=m/s, 3="H2O, 4=Pa
MV3Mute ModeWrite1=Take out of mute mode, 2=Put into mute mode, 3=Normal mode
DEV863001TSI8631-CRMDevice object; instance = 863000 + MAC addressRead
Object ID lookup: TSI PresSura 8631-CRM Clean Room Pressure Monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura 8631-CRM Clean Room Pressure Monitor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI PresSura 8631-CRM Clean Room Pressure Monitor

How many BACnet points does the TSI PresSura 8631-CRM Clean Room Pressure Monitor have?

This list has 15 BACnet objects: 5 analog inputs, 6 analog values, 1 device, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI PresSura 8631-CRM Clean Room Pressure Monitor BACnet points are writable?

8 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official TSI PresSura 8631-CRM Clean Room Pressure Monitor BACnet documentation?

The source is PresSura Clean Room Pressure Monitor/Controller with LON/BACnet, Models 8631-CRM/8631-CRM-BAC/8631-CRC/8631-CRC-BAC Operation and Service Manual (P/N 1980489), revision Revision F, published free by TSI at https://tsi.com/getmedia/44b7bb16-9f83-4176-b2f6-a3610aa87c8c/1980489-8631CRx-Pressura-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI PresSura 8631-CRM Clean Room Pressure Monitor?

Start with AI 1 Room Pressure (Room differential pressure); AI 2 Sec Sens Pressure (Second sensor pressure (e.g. airlock)); AI 3 Supply#1 Flow Rate (Supply 1 airflow); AI 5 Air Changes Per Hour (Calculated air changes per hour); MI 1 Status Index (Alarm state; 1 = normal).

How do I check these points on the real PresSura 8631-CRM Clean Room Pressure Monitor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: PresSura Clean Room Pressure Monitor/Controller with LON/BACnet, Models 8631-CRM/8631-CRM-BAC/8631-CRC/8631-CRC-BAC Operation and Service Manual · P/N 1980489 · rev. Revision F. Object names, instances and units are reproduced as published; descriptions are our own.