Room pressure controller · BACnet points list

TSI PresSura RPC30 Room Pressure Controller BACnet points list

Updated 6 November 2026

Short answer

The RPC30 measures room pressure and drives the exhaust and supply air valves (and optionally reheat) to keep a room positive, negative or at no isolation. Over BACnet MS/TP it exposes room pressure, flows, temperatures, control outputs, the pressure and temperature setpoints, flow limits, alarm limits, the room mode and a Status Index alarm code.

This page lists 81 BACnet objects for the TSI PresSura RPC30 Room Pressure Controller — 51 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
PresSura RPC30 Room Pressure Controller
Equipment
Room pressure controller
Equipment type
Thermostats, sensors & meters
BACnet objects
81 (51 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
RPC30, PresSura RPC30, RPC30 PresSura
Source document
PresSura Room Pressure Controller Model RPC30 Operation and Service Manual · P/N 6006643 · rev. Revision L, February 2023
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI PresSura RPC30 Room Pressure Controller

Integration in brief

Write the room mode (MV 11) and, if needed, the negative or positive pressure setpoint (AV 12/13). Read room pressure, flows, the control outputs and the Status Index (MV 16) for alarms. Occupancy is a wired input (BI 4) that switches between the occupied and unoccupied flow and temperature setpoints.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 11Room 1 Mode1 = positive, 2 = negative, 3 = no isolationWrite
AV 12Room 1 Neg SetpointNegative-mode pressure setpoint, in. W.C.Write
AV 13Room 1 Pos SetpointPositive-mode pressure setpoint, in. W.C.Write
AI 1Room1 PressureRoom differential pressureRead
AI 2Supply Flow RateSupply airflowRead
AI 6Exhaust Flow RateExhaust airflowRead
AI 5Room TemperatureRoom temperatureRead
AI 14Exhaust Control OutputExhaust valve output, % openRead
BI 4Room 1 Occupancy0 = occupied, 1 = unoccupiedRead
MV 16Status IndexActive alarm code; 1 = normalRead

Sensors & values from the BMS

Relative humidity can come from the BMS: set BV 10 to Enable and write AV 56.

Network setup

Watch out for

TSI PresSura RPC30 Room Pressure Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

81 of 81 shown
Type
Multi-state
Access
Show
TSI PresSura RPC30 Room Pressure Controller BACnet Points List
DescriptionStates
AImin1Room1 Pressurein. W.C.Read
AImin2Supply Flow RatecfmRead
AI3Air Changes Per HourRead
AI4Relative Humidity%RHRead
AImin5Room Temperature°FRead
AImin6Exhaust Flow RatecfmRead
AI7Anteroom PressureAnteroom configs onlyin. W.C.Read
AI9Supply Air Temperature°FRead
AI10Room 1 LabelObject name holds the room label; write the name to change itRead
AI11Anteroom LabelObject name holds the room label; write the name to change itRead
AI13Supply Control Output0-100; reads 0 unless AO2 Sig Type is Supply Control% openRead
AImin14Exhaust Control Output0-100; reads 0 unless AO1 Sig Type is Exhaust Control% openRead
AI15Reheat Control Output0-100; reads 0 unless AO2 Sig Type is Temp Control% openRead
AV1Room 1 Neg Low AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV2Room 1 Neg High AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV3Room 1 Pos Low AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV4Room 1 Pos High AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV5Room 1 Low Exhaust AlarmRange 0 to 30,000 cfmcfmWrite
AV6Room 1 Low Supply AlarmRange 0 to 30,000 cfmcfmWrite
AV7Room 1 Low Temperature AlarmRange 50 to 85°F°FWrite
AV8Room 1 High Temperature AlarmRange 50 to 85°F°FWrite
AV9Room 1 Low RH AlarmRange 0 to 100%RHWrite
AV10Room 1 High RH AlarmRange 0 to 100%RHWrite
AV11Room 1 VolumeRange 0 to 20,000ft³Write
AVmin12Room 1 Neg SetpointRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)Write
AVmin13Room 1 Pos SetpointRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)Write
AV14Room 1 No Isolation SetpointFlow 0-30,000 or 0-100 % open (per control type)cfmWrite
AV15Occupied Mode Heating SetpointRange 55 to 85 °F°FWrite
AV16Occupied Mode Cooling SetpointRange 55 to 85 °F°FWrite
AV17Unoccupied Mode Heating SetpointRange 55 to 85 °F°FWrite
AV18Unoccupied Mode Cooling SetpointRange 55 to 85 °F°FWrite
AV19Heating Mode Supply Temperature DeltaRange 10 to 40°F°FWrite
AV20Occupied Mode Minimum Supply FlowRange 0 to 10,000 cfmcfmWrite
AV21Maximum Supply FlowRange 0 to 10,000 cfmcfmWrite
AV22Occupied Mode Heating FlowRange 0 to 10,000 cfmcfmWrite
AV23Occupied Mode Cooling FlowRange 0 to 10,000 cfmcfmWrite
AV24Unoccupied Mode Minimum Supply FlowRange 0 to 10,000 cfmcfmWrite
AV25Minimum Supply Control OutputRange 0 to 100% openWrite
AV26Maximum Supply Control OutputRange 0 to 100% openWrite
AV27Min Exhaust FlowRange 0 to 10,000 cfmcfmWrite
AV28Max Exhaust FlowRange 0 to 10,000 cfmcfmWrite
AV29Minimum Exhaust Control OutRange 0 to 100% openWrite
AV30Maximum Exhaust Control OutputRange 0 to 100% openWrite
AV31Anteroom Neg Low AlarmTwo-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV32Anteroom Neg High AlarmTwo-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV33Anteroom Pos Low AlarmTwo-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV34Anteroom Pos High AlarmTwo-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV39Alarm DelayRange 1 to 600 secondsWrite
AV40Mute TimeoutRange 1 to 60 minutesWrite
AV41Door DelayRange 1 to 600 secondsWrite
AV42AddressRange 1 to 127Write
AV43MAC ID (Device ID)Range 0 to 4,194,302Write
AV44Current Heating Control SetpointRange 55 to 85°FRead
AV45Current Cooling Control SetpointRange 55 to 85°FRead
AV56Relative Humidity over BACnetRange 0 to 100%%RHWrite
BI1Room 1 Door SwitchRead0=Door Closed (Normal), 1=Door Open
BI2Anteroom Door SwitchRead0=Door Closed (Normal), 1=Door Open
BImin4Room 1 OccupancyRead0=Occupied (Normal), 1=Unoccupied
BI5Anteroom OccupancyRead0=Occupied (Normal), 1=Unoccupied
BV1Room 1 High AlarmWrite0=Disable, 1=Enable
BV2Room 1 Low AlarmWrite0=Disable, 1=Enable
BV3Anteroom High AlarmWrite0=Disable, 1=Enable
BV4Anteroom Low AlarmWrite0=Disable, 1=Enable
BV10Relative Humidity over BACnet EnableWrite0=Disable, 1=Enable
MV1Number of RoomsRead1=Single, 2=Single + Anteroom
MV2Devices ControlledRead1=None, 2=Exhaust, 3=Exhaust / Supply / Temp
MV3Passcode EnableWrite1=No Password, 2=Room Mode Password, 3=Menu Password, 4=Menu & Room Mode Passwords
MV4Input 1 ConfigurationRead1=TSI Sensor, 2=Pressure Transducer
MV5Input 2 ConfigurationRead1=TSI Sensor, 2=Pressure Transducer, 3=Temperature Setpoint, 4=None
MV6Input 3 ConfigurationRead1=Supply Pressure Flow, 2=Supply Linear Flow, 3=Supply Venturi Flow, 4=Supply Switch, 7=None
MV7Input 4 ConfigurationRead1=Room 1 Door Switch, 2=Room 1 Occupancy Sensor, 3=None
MV8Input 5 ConfigurationRead1=Room 1 Key Switch, 2=Relative Humidity, 3=None
MV9Input 6 ConfigurationRead1=Room 1 Temp Sensor, 2=Anteroom Occupancy Sensor, 5=Anteroom Door Switch, 6=None
MV10Input 7 ConfigurationRead1=Room 1 Supply Air Temp, 2=Exhaust Pressure Flow, 3=Exhaust Linear Flow, 4=Exhaust Venturi Flow, 5=Exhaust Switch, 7=Anteroom Key Switch, 8=None
MVmin11Room 1 ModeWrite1=Positive, 2=Negative, 3=No Isolation
MV12ACH DuctWrite1=Supply, 2=Exhaust, 3=Off
MV13No Isolation Control TypeWrite1=Position, 2=Flow, 3=Pressure
MV14Anteroom ModeWrite1=Positive, 2=Negative, 3=No Isolation
MVmin16Status IndexRead1=Normal, 2=Room 1 Negative Low Alarm, 3=Room 1 Negative High Alarm, 4=Room 1 Positive Low Alarm, 5=Room 1 Positive High Alarm, 6=Low Exhaust Alarm, 7=Low Supply Alarm, 8=Low Temperature Alarm, 9=High Temperature Alarm, 10=Low RH Alarm, 11=High RH Alarm, 12=Anteroom Negative Low Alarm, 13=Anteroom Negative High Alarm, 14=Anteroom Positive Low Alarm, 15=Anteroom Positive High Alarm, 20=Data Error
MV17Device TypeRead1=RPC30
MV18Units ValueWrite1=in. W.C., cfm, F, 2=Pa, lps, C, 3=Pa, CMH, C
Object ID lookup: TSI PresSura RPC30 Room Pressure Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura RPC30 Room Pressure Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI PresSura RPC30 Room Pressure Controller

How many BACnet points does the TSI PresSura RPC30 Room Pressure Controller have?

This list has 81 BACnet objects: 13 analog inputs, 42 analog values, 4 binary inputs, 5 binary values, 17 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI PresSura RPC30 Room Pressure Controller BACnet points are writable?

51 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TSI PresSura RPC30 Room Pressure Controller BACnet documentation?

The source is PresSura Room Pressure Controller Model RPC30 Operation and Service Manual (P/N 6006643), revision Revision L, February 2023, published free by TSI at https://tsi.com/getmedia/a6941791-3bdc-4d01-abe2-b7d1fd9eae4e/RPC30_PresSura_Controller_6006643L-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI PresSura RPC30 Room Pressure Controller?

Start with MV 11 Room 1 Mode (1 = positive, 2 = negative, 3 = no isolation); AV 12 Room 1 Neg Setpoint (Negative-mode pressure setpoint, in. W.C); AV 13 Room 1 Pos Setpoint (Positive-mode pressure setpoint, in. W.C); AI 1 Room1 Pressure (Room differential pressure); AI 2 Supply Flow Rate (Supply airflow); AI 6 Exhaust Flow Rate (Exhaust airflow); AI 5 Room Temperature (Room temperature); AI 14 Exhaust Control Output (Exhaust valve output, % open); BI 4 Room 1 Occupancy (0 = occupied, 1 = unoccupied); MV 16 Status Index (Active alarm code; 1 = normal).

Can the BMS supply sensor values to the TSI PresSura RPC30 Room Pressure Controller?

Relative humidity can come from the BMS: set BV 10 to Enable and write AV 56.

How do I check these points on the real PresSura RPC30 Room Pressure Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: PresSura Room Pressure Controller Model RPC30 Operation and Service Manual · P/N 6006643 · rev. Revision L, February 2023. Object names, instances and units are reproduced as published; descriptions are our own.