- PresSura RPC30 Room Pressure Controller
Room pressure controller · BACnet points list
TSI PresSura RPC30 Room Pressure Controller BACnet points list
Updated 6 November 2026
The RPC30 measures room pressure and drives the exhaust and supply air valves (and optionally reheat) to keep a room positive, negative or at no isolation. Over BACnet MS/TP it exposes room pressure, flows, temperatures, control outputs, the pressure and temperature setpoints, flow limits, alarm limits, the room mode and a Status Index alarm code.
This page lists 81 BACnet objects for the TSI PresSura RPC30 Room Pressure Controller — 51 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.
- Manufacturer
- TSI
- Model
- PresSura RPC30 Room Pressure Controller
- Equipment
- Room pressure controller
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 81 (51 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- RPC30, PresSura RPC30, RPC30 PresSura
Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.
BMS integration notes: TSI PresSura RPC30 Room Pressure Controller
Write the room mode (MV 11) and, if needed, the negative or positive pressure setpoint (AV 12/13). Read room pressure, flows, the control outputs and the Status Index (MV 16) for alarms. Occupancy is a wired input (BI 4) that switches between the occupied and unoccupied flow and temperature setpoints.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 11 | Room 1 Mode | 1 = positive, 2 = negative, 3 = no isolation | Write |
| AV 12 | Room 1 Neg Setpoint | Negative-mode pressure setpoint, in. W.C. | Write |
| AV 13 | Room 1 Pos Setpoint | Positive-mode pressure setpoint, in. W.C. | Write |
| AI 1 | Room1 Pressure | Room differential pressure | Read |
| AI 2 | Supply Flow Rate | Supply airflow | Read |
| AI 6 | Exhaust Flow Rate | Exhaust airflow | Read |
| AI 5 | Room Temperature | Room temperature | Read |
| AI 14 | Exhaust Control Output | Exhaust valve output, % open | Read |
| BI 4 | Room 1 Occupancy | 0 = occupied, 1 = unoccupied | Read |
| MV 16 | Status Index | Active alarm code; 1 = normal | Read |
Sensors & values from the BMS
Relative humidity can come from the BMS: set BV 10 to Enable and write AV 56.
Network setup
- Set Comm Type to BACnet in the Interface menu (Modbus is the default); Address (1-127) is the MS/TP MAC and MAC ID is the BACnet device ID.
- BACnet MS/TP baud: 9600, 19200, 38400, 76800 or AutoBaud.
Watch out for
- Engineering units follow Units Value (MV 18): 1 = in. W.C./cfm/°F (default), 2 = Pa/lps/°C, 3 = Pa/CMH/°C.
- In No Isolation mode the controller holds the No Isolation setpoint (AV 14) by position, flow or pressure, per MV 13.
- Setpoints, flow limits and alarm limits are stored settings; do not write them cyclically.
TSI PresSura RPC30 Room Pressure Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Room1 Pressure | in. W.C. | Read | ||
| AImin | 2 | Supply Flow Rate | cfm | Read | ||
| AI | 3 | Air Changes Per Hour | Read | |||
| AI | 4 | Relative Humidity | %RH | Read | ||
| AImin | 5 | Room Temperature | °F | Read | ||
| AImin | 6 | Exhaust Flow Rate | cfm | Read | ||
| AI | 7 | Anteroom Pressure | Anteroom configs only | in. W.C. | Read | |
| AI | 9 | Supply Air Temperature | °F | Read | ||
| AI | 10 | Room 1 Label | Object name holds the room label; write the name to change it | Read | ||
| AI | 11 | Anteroom Label | Object name holds the room label; write the name to change it | Read | ||
| AI | 13 | Supply Control Output | 0-100; reads 0 unless AO2 Sig Type is Supply Control | % open | Read | |
| AImin | 14 | Exhaust Control Output | 0-100; reads 0 unless AO1 Sig Type is Exhaust Control | % open | Read | |
| AI | 15 | Reheat Control Output | 0-100; reads 0 unless AO2 Sig Type is Temp Control | % open | Read | |
| AV | 1 | Room 1 Neg Low Alarm | Range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 2 | Room 1 Neg High Alarm | Range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 3 | Room 1 Pos Low Alarm | Range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 4 | Room 1 Pos High Alarm | Range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 5 | Room 1 Low Exhaust Alarm | Range 0 to 30,000 cfm | cfm | Write | |
| AV | 6 | Room 1 Low Supply Alarm | Range 0 to 30,000 cfm | cfm | Write | |
| AV | 7 | Room 1 Low Temperature Alarm | Range 50 to 85°F | °F | Write | |
| AV | 8 | Room 1 High Temperature Alarm | Range 50 to 85°F | °F | Write | |
| AV | 9 | Room 1 Low RH Alarm | Range 0 to 100 | %RH | Write | |
| AV | 10 | Room 1 High RH Alarm | Range 0 to 100 | %RH | Write | |
| AV | 11 | Room 1 Volume | Range 0 to 20,000 | ft³ | Write | |
| AVmin | 12 | Room 1 Neg Setpoint | Range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | Write | ||
| AVmin | 13 | Room 1 Pos Setpoint | Range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | Write | ||
| AV | 14 | Room 1 No Isolation Setpoint | Flow 0-30,000 or 0-100 % open (per control type) | cfm | Write | |
| AV | 15 | Occupied Mode Heating Setpoint | Range 55 to 85 °F | °F | Write | |
| AV | 16 | Occupied Mode Cooling Setpoint | Range 55 to 85 °F | °F | Write | |
| AV | 17 | Unoccupied Mode Heating Setpoint | Range 55 to 85 °F | °F | Write | |
| AV | 18 | Unoccupied Mode Cooling Setpoint | Range 55 to 85 °F | °F | Write | |
| AV | 19 | Heating Mode Supply Temperature Delta | Range 10 to 40°F | °F | Write | |
| AV | 20 | Occupied Mode Minimum Supply Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 21 | Maximum Supply Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 22 | Occupied Mode Heating Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 23 | Occupied Mode Cooling Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 24 | Unoccupied Mode Minimum Supply Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 25 | Minimum Supply Control Output | Range 0 to 100 | % open | Write | |
| AV | 26 | Maximum Supply Control Output | Range 0 to 100 | % open | Write | |
| AV | 27 | Min Exhaust Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 28 | Max Exhaust Flow | Range 0 to 10,000 cfm | cfm | Write | |
| AV | 29 | Minimum Exhaust Control Out | Range 0 to 100 | % open | Write | |
| AV | 30 | Maximum Exhaust Control Output | Range 0 to 100 | % open | Write | |
| AV | 31 | Anteroom Neg Low Alarm | Two-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 32 | Anteroom Neg High Alarm | Two-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 33 | Anteroom Pos Low Alarm | Two-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 34 | Anteroom Pos High Alarm | Two-room config only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer) | in. W.C. | Write | |
| AV | 39 | Alarm Delay | Range 1 to 600 seconds | Write | ||
| AV | 40 | Mute Timeout | Range 1 to 60 minutes | Write | ||
| AV | 41 | Door Delay | Range 1 to 600 seconds | Write | ||
| AV | 42 | Address | Range 1 to 127 | Write | ||
| AV | 43 | MAC ID (Device ID) | Range 0 to 4,194,302 | Write | ||
| AV | 44 | Current Heating Control Setpoint | Range 55 to 85°F | Read | ||
| AV | 45 | Current Cooling Control Setpoint | Range 55 to 85°F | Read | ||
| AV | 56 | Relative Humidity over BACnet | Range 0 to 100% | %RH | Write | |
| BI | 1 | Room 1 Door Switch | Read | 0=Door Closed (Normal), 1=Door Open | ||
| BI | 2 | Anteroom Door Switch | Read | 0=Door Closed (Normal), 1=Door Open | ||
| BImin | 4 | Room 1 Occupancy | Read | 0=Occupied (Normal), 1=Unoccupied | ||
| BI | 5 | Anteroom Occupancy | Read | 0=Occupied (Normal), 1=Unoccupied | ||
| BV | 1 | Room 1 High Alarm | Write | 0=Disable, 1=Enable | ||
| BV | 2 | Room 1 Low Alarm | Write | 0=Disable, 1=Enable | ||
| BV | 3 | Anteroom High Alarm | Write | 0=Disable, 1=Enable | ||
| BV | 4 | Anteroom Low Alarm | Write | 0=Disable, 1=Enable | ||
| BV | 10 | Relative Humidity over BACnet Enable | Write | 0=Disable, 1=Enable | ||
| MV | 1 | Number of Rooms | Read | 1=Single, 2=Single + Anteroom | ||
| MV | 2 | Devices Controlled | Read | 1=None, 2=Exhaust, 3=Exhaust / Supply / Temp | ||
| MV | 3 | Passcode Enable | Write | 1=No Password, 2=Room Mode Password, 3=Menu Password, 4=Menu & Room Mode Passwords | ||
| MV | 4 | Input 1 Configuration | Read | 1=TSI Sensor, 2=Pressure Transducer | ||
| MV | 5 | Input 2 Configuration | Read | 1=TSI Sensor, 2=Pressure Transducer, 3=Temperature Setpoint, 4=None | ||
| MV | 6 | Input 3 Configuration | Read | 1=Supply Pressure Flow, 2=Supply Linear Flow, 3=Supply Venturi Flow, 4=Supply Switch, 7=None | ||
| MV | 7 | Input 4 Configuration | Read | 1=Room 1 Door Switch, 2=Room 1 Occupancy Sensor, 3=None | ||
| MV | 8 | Input 5 Configuration | Read | 1=Room 1 Key Switch, 2=Relative Humidity, 3=None | ||
| MV | 9 | Input 6 Configuration | Read | 1=Room 1 Temp Sensor, 2=Anteroom Occupancy Sensor, 5=Anteroom Door Switch, 6=None | ||
| MV | 10 | Input 7 Configuration | Read | 1=Room 1 Supply Air Temp, 2=Exhaust Pressure Flow, 3=Exhaust Linear Flow, 4=Exhaust Venturi Flow, 5=Exhaust Switch, 7=Anteroom Key Switch, 8=None | ||
| MVmin | 11 | Room 1 Mode | Write | 1=Positive, 2=Negative, 3=No Isolation | ||
| MV | 12 | ACH Duct | Write | 1=Supply, 2=Exhaust, 3=Off | ||
| MV | 13 | No Isolation Control Type | Write | 1=Position, 2=Flow, 3=Pressure | ||
| MV | 14 | Anteroom Mode | Write | 1=Positive, 2=Negative, 3=No Isolation | ||
| MVmin | 16 | Status Index | Read | 1=Normal, 2=Room 1 Negative Low Alarm, 3=Room 1 Negative High Alarm, 4=Room 1 Positive Low Alarm, 5=Room 1 Positive High Alarm, 6=Low Exhaust Alarm, 7=Low Supply Alarm, 8=Low Temperature Alarm, 9=High Temperature Alarm, 10=Low RH Alarm, 11=High RH Alarm, 12=Anteroom Negative Low Alarm, 13=Anteroom Negative High Alarm, 14=Anteroom Positive Low Alarm, 15=Anteroom Positive High Alarm, 20=Data Error | ||
| MV | 17 | Device Type | Read | 1=RPC30 | ||
| MV | 18 | Units Value | Write | 1=in. W.C., cfm, F, 2=Pa, lps, C, 3=Pa, CMH, C |
No points match these filters.
Object ID lookup: TSI PresSura RPC30 Room Pressure Controller point IDs by name
AI1Room1 PressureAI2Supply Flow RateAI3Air Changes Per HourAI4Relative HumidityAI5Room TemperatureAI6Exhaust Flow RateAI7Anteroom PressureAI9Supply Air TemperatureAI10Room 1 LabelAI11Anteroom LabelAI13Supply Control OutputAI14Exhaust Control OutputAI15Reheat Control OutputAV1Room 1 Neg Low AlarmAV2Room 1 Neg High AlarmAV3Room 1 Pos Low AlarmAV4Room 1 Pos High AlarmAV5Room 1 Low Exhaust AlarmAV6Room 1 Low Supply AlarmAV7Room 1 Low Temperature AlarmAV8Room 1 High Temperature AlarmAV9Room 1 Low RH AlarmAV10Room 1 High RH AlarmAV11Room 1 VolumeAV12Room 1 Neg SetpointAV13Room 1 Pos SetpointAV14Room 1 No Isolation SetpointAV15Occupied Mode Heating SetpointAV16Occupied Mode Cooling SetpointAV17Unoccupied Mode Heating SetpointAV18Unoccupied Mode Cooling SetpointAV19Heating Mode Supply Temperature DeltaAV20Occupied Mode Minimum Supply FlowAV21Maximum Supply FlowAV22Occupied Mode Heating FlowAV23Occupied Mode Cooling FlowAV24Unoccupied Mode Minimum Supply FlowAV25Minimum Supply Control OutputAV26Maximum Supply Control OutputAV27Min Exhaust FlowAV28Max Exhaust FlowAV29Minimum Exhaust Control OutAV30Maximum Exhaust Control OutputAV31Anteroom Neg Low AlarmAV32Anteroom Neg High AlarmAV33Anteroom Pos Low AlarmAV34Anteroom Pos High AlarmAV39Alarm DelayAV40Mute TimeoutAV41Door DelayAV42AddressAV43MAC ID (Device ID)AV44Current Heating Control SetpointAV45Current Cooling Control SetpointAV56Relative Humidity over BACnetBI1Room 1 Door SwitchBI2Anteroom Door SwitchBI4Room 1 OccupancyBI5Anteroom OccupancyBV1Room 1 High AlarmBV2Room 1 Low AlarmBV3Anteroom High AlarmBV4Anteroom Low AlarmBV10Relative Humidity over BACnet EnableMV1Number of RoomsMV2Devices ControlledMV3Passcode EnableMV4Input 1 ConfigurationMV5Input 2 ConfigurationMV6Input 3 ConfigurationMV7Input 4 ConfigurationMV8Input 5 ConfigurationMV9Input 6 ConfigurationMV10Input 7 ConfigurationMV11Room 1 ModeMV12ACH DuctMV13No Isolation Control TypeMV14Anteroom ModeMV16Status IndexMV17Device TypeMV18Units Value
Integration notes
- From the RPC30 BACnet MS/TP Object Set appendix (manual pages 102-106).
- Access follows the Writable Value column; AI 10 and AI 11 have a writable object name (the room label) and are shown here as read-only values.
- Units shown are the English set; the table lists Pa, l/s, CMH and °C alternatives, chosen with Units Value (MV 18).
- AV 12 and AV 13 (pressure setpoints) and AV 44/45 have no units printed in the table.
- The Revision J link for this manual serves the same file (Revision L).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura RPC30 Room Pressure Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the TSI PresSura RPC30 Room Pressure Controller
How many BACnet points does the TSI PresSura RPC30 Room Pressure Controller have?
This list has 81 BACnet objects: 13 analog inputs, 42 analog values, 4 binary inputs, 5 binary values, 17 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which TSI PresSura RPC30 Room Pressure Controller BACnet points are writable?
51 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official TSI PresSura RPC30 Room Pressure Controller BACnet documentation?
The source is PresSura Room Pressure Controller Model RPC30 Operation and Service Manual (P/N 6006643), revision Revision L, February 2023, published free by TSI at https://tsi.com/getmedia/a6941791-3bdc-4d01-abe2-b7d1fd9eae4e/RPC30_PresSura_Controller_6006643L-web?ext=.pdf.
What are the minimum BACnet points to integrate the TSI PresSura RPC30 Room Pressure Controller?
Start with MV 11 Room 1 Mode (1 = positive, 2 = negative, 3 = no isolation); AV 12 Room 1 Neg Setpoint (Negative-mode pressure setpoint, in. W.C); AV 13 Room 1 Pos Setpoint (Positive-mode pressure setpoint, in. W.C); AI 1 Room1 Pressure (Room differential pressure); AI 2 Supply Flow Rate (Supply airflow); AI 6 Exhaust Flow Rate (Exhaust airflow); AI 5 Room Temperature (Room temperature); AI 14 Exhaust Control Output (Exhaust valve output, % open); BI 4 Room 1 Occupancy (0 = occupied, 1 = unoccupied); MV 16 Status Index (Active alarm code; 1 = normal).
Can the BMS supply sensor values to the TSI PresSura RPC30 Room Pressure Controller?
Relative humidity can come from the BMS: set BV 10 to Enable and write AV 56.
How do I check these points on the real PresSura RPC30 Room Pressure Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More TSI BACnet points lists
- Laboratory room airflow and pressure controller
TSI Laboratory Room Controller (LRC)
TSI LRC modular laboratory room controllers handling up to 6 supplies, 2 general exhausts and 20 fume hoods.
Also known as: LRC, LRC00, LRC00-LPS, LRC00-CMH, TSI LRC, Lab Room Controller - Room pressure controller
TSI PresSura 8631-CRC Clean Room Pressure Controller
TSI PresSura Model 8631-CRC-BAC clean room pressure controllers with the BACnet board.
Also known as: 8631-CRC, 8631-CRC-BAC, PresSura 8631-CRC - Room pressure monitor
TSI PresSura 8631-CRM Clean Room Pressure Monitor
TSI PresSura Model 8631-CRM-BAC clean room pressure monitors with the BACnet board.
Also known as: 8631-CRM, 8631-CRM-BAC, PresSura 8631-CRM - Room pressure controller
TSI PresSura 8631-HC Hospital Room Pressure Controller
TSI PresSura Model 8631-HC hospital isolation room pressure controllers with the BACnet board.
Also known as: 8631-HC, 8631-HC-BAC, PresSura 8631-HC - Room pressure monitor
TSI PresSura 8631-HM Hospital Room Pressure Monitor
TSI PresSura Model 8631-HM hospital isolation room pressure monitors with the BACnet board.
Also known as: 8631-HM, 8631-HM-BAC, PresSura 8631-HM - Room pressure monitor
TSI PresSura RPM10 Room Pressure Monitor
TSI PresSura RPM10 single-room pressure monitors.
Also known as: RPM10, PresSura RPM10, RPM10 PresSura - Room pressure monitor
TSI PresSura RPM20 Room Pressure Monitor
TSI PresSura RPM20 room pressure monitors for one room, a room with anteroom, or two rooms with an anteroom.
Also known as: RPM20, PresSura RPM20, RPM20 PresSura - Room pressure monitor
TSI PresSura RPM20-CC Room Pressure Monitor (particle counting)
TSI PresSura RPM20-CC room pressure monitors with particle counter channels, for clean rooms.
Also known as: RPM20-CC, PresSura RPM20-CC, RPM20 CC - Room pressure controller
TSI SureFlow 8636 Room Pressure Controller
TSI SureFlow Model 8636-BAC room pressure controllers with the BACnet MS/TP board.
Also known as: 8636, 8636-BAC, SureFlow 8636 - Laboratory room pressure and airflow offset controller
TSI SureFlow 8681 Adaptive Offset Controller
TSI SureFlow Model 8681-BAC adaptive offset (lab room) controllers with the BACnet MS/TP board.
Also known as: 8681, 8681-BAC, SureFlow 8681 - Laboratory room pressure and airflow offset controller
TSI SureFlow 8682 Adaptive Offset Controller
TSI SureFlow Model 8682-BAC adaptive offset controllers (up to 4 supplies, 2 general exhausts and 7 hoods) with the BACnet MS/TP board.
Also known as: 8682, 8682-BAC, SureFlow 8682
Source: PresSura Room Pressure Controller Model RPC30 Operation and Service Manual · P/N 6006643 · rev. Revision L, February 2023. Object names, instances and units are reproduced as published; descriptions are our own.