Room pressure monitor · BACnet points list

TSI PresSura RPM10 Room Pressure Monitor BACnet points list

Updated 6 November 2026

Short answer

The RPM10 is a single-room pressure monitor with a touch screen that shows room pressure, supply and exhaust flow and air changes per hour, and raises alarms. Over BACnet MS/TP it exposes the room readings, alarm limits, room mode and the Status Index alarm code. Supply and exhaust flow can be written in over BACnet instead of being wired.

This page lists 37 BACnet objects for the TSI PresSura RPM10 Room Pressure Monitor — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
PresSura RPM10 Room Pressure Monitor
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
37 (19 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
RPM10, PresSura RPM10, RPM10 PresSura
Source document
PresSura Room Pressure Monitor Models RPM10 and RPM20 Operation and Service Manual · P/N 6006644 · rev. Revision N, February 2023
Download CSV 37 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI PresSura RPM10 Room Pressure Monitor

Integration in brief

Read room pressure, the flows and the Status Index (MV 16) for alarms; door and occupancy inputs are BIs. The room mode (positive, negative, no isolation) is writable from the BMS. The monitor can also take some readings from the BMS instead of wired sensors.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 11Room 1 Mode1 = positive, 2 = negative, 3 = no isolationWrite
AI 1Room1 PressureRoom differential pressureRead
AI 2Supply Flow RateSupply airflowRead
AI 6Exhaust Flow RateExhaust airflowRead
AI 3Air Changes Per HourCalculated air changes per hourRead
BI 1Room 1 Door Switch0 = closed, 1 = openRead
BI 4Room 1 Occupancy0 = occupied, 1 = unoccupiedRead
MV 16Status IndexActive alarm code; 1 = normalRead

Sensors & values from the BMS

Supply and exhaust flow can come from the BMS: enable BV 9 / BV 12 and write the value to AV 55 / AV 58.

Network setup

Watch out for

TSI PresSura RPM10 Room Pressure Monitor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

37 of 37 shown
Type
Multi-state
Access
Show
TSI PresSura RPM10 Room Pressure Monitor BACnet Points List
DescriptionStates
AImin1Room1 PressureObject name is writablein. W.C.Read
AImin2Supply Flow RatecfmRead
AImin3Air Changes Per HourRead
AImin6Exhaust Flow RatecfmRead
AI10Room 1 LabelObject name holds the room label; write the name to change itRead
AV1Room 1 Neg Low AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV2Room 1 Neg High AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV3Room 1 Pos Low AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV4Room 1 Pos High AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV5Room 1 Low Exhaust AlarmRange 0 to 30,000 cfmcfmWrite
AV11Room 1 VolumeRange 0 to 20,000ft³Write
AV39Alarm DelayRange 20 to 600 secondsWrite
AV40Mute TimeoutRange 1 to 60 minutesWrite
AV41Door DelayRange 20 to 600 secondsWrite
AV42AddressRange 1 to 127Write
AV43MAC ID (Device ID)Range 0 to 4,194,302Write
AV55Supply Flow over BACnetRange 0 to 10,000 cfmcfmWrite
AV58Exhaust Flow over BACnetRange 0 to 10,000 cfmcfmWrite
BImin1Room 1 Door SwitchRead0=Door Closed (Normal), 1=Door Open
BImin4Room 1 OccupancyRead0=Occupied (Normal), 1=Unoccupied
BV1Room 1 High AlarmRead0=Disable, 1=Enable
BV2Room 1 Low AlarmRead0=Disable, 1=Enable
BV9Supply Flow over BACnet EnableWrite0=Disable, 1=Enable
BV12Exhaust Flow over BACnet EnableWrite0=Disable, 1=Enable
MV3Passcode EnableWrite1=No Password, 2=Room Mode Password, 3=Menu Password, 4=Menu & Room Mode Passwords
MV4Input 1 ConfigurationRead1=TSI Sensor, 2=Pressure Transducer
MV5Input 2 ConfigurationRead4=None
MV6Input 3 ConfigurationRead1=Supply Pressure Flow, 2=Supply Linear Flow, 3=Supply Venturi Flow, 4=Supply Switch, 7=None
MV7Input 4 ConfigurationRead1=Room 1 Door Switch, 2=Room 1 Occupancy Sensor, 3=None
MV8Input 5 ConfigurationRead1=Room 1 Key Switch, 3=None
MV9Input 6 ConfigurationRead6=None
MV10Input 7 ConfigurationRead2=Exhaust Pressure Flow, 3=Exhaust Linear Flow, 4=Exhaust Venturi Flow, 5=Exhaust Switch, 8=None
MVmin11Room 1 ModeWrite1=Positive, 2=Negative, 3=No Isolation
MV12ACH DuctWrite1=Supply, 2=Exhaust, 3=Off
MVmin16Status IndexRead1=Normal, 2=Room 1 Negative Low Alarm, 3=Room 1 Negative High Alarm, 4=Room 1 Positive Low Alarm, 5=Room 1 Positive High Alarm, 6=Low Exhaust Alarm, 7=Low Supply Alarm, 20=Data Error
MV17Device TypeRead3=RPM10
MV18Units ValueWrite1=in. W.C., cfm, 2=Pa, lps, 3=Pa, m3/hr
Object ID lookup: TSI PresSura RPM10 Room Pressure Monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura RPM10 Room Pressure Monitor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI PresSura RPM10 Room Pressure Monitor

How many BACnet points does the TSI PresSura RPM10 Room Pressure Monitor have?

This list has 37 BACnet objects: 5 analog inputs, 13 analog values, 2 binary inputs, 4 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI PresSura RPM10 Room Pressure Monitor BACnet points are writable?

19 of the 37 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TSI PresSura RPM10 Room Pressure Monitor BACnet documentation?

The source is PresSura Room Pressure Monitor Models RPM10 and RPM20 Operation and Service Manual (P/N 6006644), revision Revision N, February 2023, published free by TSI at https://tsi.com/getmedia/8220cb07-6f38-4cec-9e7a-900fecd113e9/RPM10-RPM20_PresSura_Monitor_6006644J-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI PresSura RPM10 Room Pressure Monitor?

Start with MV 11 Room 1 Mode (1 = positive, 2 = negative, 3 = no isolation); AI 1 Room1 Pressure (Room differential pressure); AI 2 Supply Flow Rate (Supply airflow); AI 6 Exhaust Flow Rate (Exhaust airflow); AI 3 Air Changes Per Hour (Calculated air changes per hour); BI 1 Room 1 Door Switch (0 = closed, 1 = open); BI 4 Room 1 Occupancy (0 = occupied, 1 = unoccupied); MV 16 Status Index (Active alarm code; 1 = normal).

Can the BMS supply sensor values to the TSI PresSura RPM10 Room Pressure Monitor?

Supply and exhaust flow can come from the BMS: enable BV 9 / BV 12 and write the value to AV 55 / AV 58.

How do I check these points on the real PresSura RPM10 Room Pressure Monitor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists