  4. PresSura 8631-CRC Clean Room Pressure Controller

Room pressure controller · BACnet points list

TSI PresSura 8631-CRC Clean Room Pressure Controller BACnet points list

Updated 6 November 2026

Short answer

The 8631-CRC controls clean room pressure by modulating supply and exhaust dampers, with a second pressure sensor and two supply flow inputs for monitoring. With the BACnet board it is a BACnet MS/TP device exposing pressures, flows, damper positions, the pressure and supply setpoints, alarm limits, a Status Index alarm code and an emergency mode command.

This page lists 19 BACnet objects for the TSI PresSura 8631-CRC Clean Room Pressure Controller — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
PresSura 8631-CRC Clean Room Pressure Controller
Equipment
Room pressure controller
Equipment type
Thermostats, sensors & meters
BACnet objects
19 (10 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS)
Default device instance
863001
Also known as
8631-CRC, 8631-CRC-BAC, PresSura 8631-CRC
Source document
PresSura Clean Room Pressure Monitor/Controller with LON/BACnet, Models 8631-CRM/8631-CRM-BAC/8631-CRC/8631-CRC-BAC Operation and Service Manual · P/N 1980489 · rev. Revision F
Download CSV 19 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI PresSura 8631-CRC Clean Room Pressure Controller

Integration in brief

Write the room pressure setpoint (AV 2) and supply setpoint (AV 3) if the BMS manages them, and use Emergency Mode (MV 3) for purge. Read room pressure, flows, damper positions and the Status Index (MI 1) for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3Emergency Mode1 = exit, 2 = enter emergency mode, 3 = normalWrite
AV 2Pressure SetpointRoom pressure setpointWrite
AV 3Supply SetpointSupply airflow setpointWrite
AI 1Room PressureRoom differential pressureRead
AI 3Supply #1 Flow RateSupply 1 airflowRead
AI 6Supply Damper PositionSupply damper position, %Read
AI 7Exhaust Damper PositionExhaust damper position, %Read
MI 1Status IndexAlarm state; 1 = normal, 8 = emergencyRead

Enable & remote start

Emergency Mode (MV 3) is the only mode command. Emergency drives the room to maximum negative or positive pressure, the same as the red EMERGENCY key.

Network setup

Watch out for

TSI PresSura 8631-CRC Clean Room Pressure Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

19 of 19 shown
Type
Other
Access
Show
TSI PresSura 8631-CRC Clean Room Pressure Controller BACnet Points List
DescriptionStates
AImin1Room Pressureft/min, m/s, in. H2O, PaRead
AI2Sec Sens PressureSecond pressure sensorft/min, m/s, in. H2O, PaRead
AImin3Supply #1 Flow Ratecfm, l/sRead
AI4Supply #2 Flow Ratecfm, l/sRead
AI5Air Changes Per HourRead
AImin6Supply Damper Position%Read
AImin7Exhaust Damper Position%Read
AV1MAC AddressRange 1 to 127Write
AVmin2Pressure SetpointRange -0.195 to -0.195 in. H2O as printedft/min, m/s, in. H2O, PaWrite
AVmin3Supply SetpointRange 0 to 30,000 cfmcfm, l/sWrite
AV4Low AlarmRange -0.195 to -0.195 in. H2O as printedft/min, m/s, in. H2O, PaWrite
AV5High AlarmRange -0.195 to -0.195 in. H2O as printedft/min, m/s, in. H2O, PaWrite
AV6Sec Low AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV7Sec High AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV8Min Supply AlarmRange 0 to 30,000 cfmcfm, l/sWrite
MImin1Status IndexRead1=Normal, 2=Low Alarm, 3=High Alarm, 4=Min Supply Alarm, 5=Sec Sens Low Alarm, 6=Sec Sens High Alarm, 7=Data Error, 8=Emergency
MV2Units ValueWrite1=ft/min, 2=m/s, 3="H2O, 4=Pa
MVmin3Emergency ModeWrite1=Exit Emergency Mode, 2=Enter Emergency Mode, 3=Normal
DEV863001TSI8631-CRCDevice object; instance = 863000 + MAC addressRead
Object ID lookup: TSI PresSura 8631-CRC Clean Room Pressure Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura 8631-CRC Clean Room Pressure Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI PresSura 8631-CRC Clean Room Pressure Controller

How many BACnet points does the TSI PresSura 8631-CRC Clean Room Pressure Controller have?

This list has 19 BACnet objects: 7 analog inputs, 8 analog values, 1 device, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI PresSura 8631-CRC Clean Room Pressure Controller BACnet points are writable?

10 of the 19 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official TSI PresSura 8631-CRC Clean Room Pressure Controller BACnet documentation?

The source is PresSura Clean Room Pressure Monitor/Controller with LON/BACnet, Models 8631-CRM/8631-CRM-BAC/8631-CRC/8631-CRC-BAC Operation and Service Manual (P/N 1980489), revision Revision F, published free by TSI at https://tsi.com/getmedia/44b7bb16-9f83-4176-b2f6-a3610aa87c8c/1980489-8631CRx-Pressura-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI PresSura 8631-CRC Clean Room Pressure Controller?

Start with MV 3 Emergency Mode (1 = exit, 2 = enter emergency mode, 3 = normal); AV 2 Pressure Setpoint (Room pressure setpoint); AV 3 Supply Setpoint (Supply airflow setpoint); AI 1 Room Pressure (Room differential pressure); AI 3 Supply #1 Flow Rate (Supply 1 airflow); AI 6 Supply Damper Position (Supply damper position, %); AI 7 Exhaust Damper Position (Exhaust damper position, %); MI 1 Status Index (Alarm state; 1 = normal, 8 = emergency).

How do I enable BMS control of the TSI PresSura 8631-CRC Clean Room Pressure Controller?

Emergency Mode (MV 3) is the only mode command. Emergency drives the room to maximum negative or positive pressure, the same as the red EMERGENCY key.

How do I check these points on the real PresSura 8631-CRC Clean Room Pressure Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: PresSura Clean Room Pressure Monitor/Controller with LON/BACnet, Models 8631-CRM/8631-CRM-BAC/8631-CRC/8631-CRC-BAC Operation and Service Manual · P/N 1980489 · rev. Revision F. Object names, instances and units are reproduced as published; descriptions are our own.