Easy BACnet
  1. Home
  2. BACnet points lists
  3. TSI
  4. Laboratory Room Controller (LRC)

Laboratory room airflow and pressure controller · BACnet points list

TSI Laboratory Room Controller (LRC) BACnet points list

Updated 6 November 2026

Short answer

The TSI LRC controls a lab room by tracking supply, general exhaust and fume hood flows to hold an airflow offset and room pressure, with per-supply temperature control. Its BACnet object set is almost entirely Analog, Binary and Multi-state Values: setup values (flow ranges, setpoints, alarm limits, sensor calibration) plus live flows, temperatures, room pressure and alarm states. The list is long because every supply, exhaust and hood channel has its own block.

This page lists 1714 BACnet objects for the TSI Laboratory Room Controller (LRC) — 1251 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
Laboratory Room Controller (LRC)
Equipment
Laboratory room airflow and pressure controller
Equipment type
Thermostats, sensors & meters
BACnet objects
1714 (1251 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Firmware 1.14.17191.1 (PICS); application software 1.8.17191.284
Also known as
LRC, LRC00, LRC00-LPS, LRC00-CMH, TSI LRC, Lab Room Controller
Source document
Laboratory Room Controller Model LRC Operation and Service Manual · P/N 6013156 · rev. Revision E, December 2021
Download CSV 1714 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI Laboratory Room Controller (LRC)

Integration in brief

Read room pressure, total supply and exhaust flow, the controller flow mode and the alarm status MVs. The BMS can set occupancy per supply (BV 24-27), trigger emergency or shutdown mode (BV 22/23) and change the room pressure setpoint (AV 268). TSI suggests picking only the points you need instead of auto-discovering the whole set.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 24Supply 1 Occupancy ModeSupply 1 occupancy: 0 = occupied, 1 = unoccupiedWrite
BV 22Emergency ModeEmergency mode: 1 = activeWrite
AV 268Room Pressure SetpointRoom pressure setpoint, in. W.C.Write
MV 91Current Controller Flow ModeStandard, Emergency, Shutdown or BalancerRead
AV 697Room PressureMeasured room pressure, in. W.C.Read
AV 660Current Total Supply FlowTotal supply airflow, CFMRead
AV 661Current Total Exhaust FlowTotal exhaust airflow, CFMRead
AV 689Supply 1 Room TempSupply 1 zone room temperatureRead
MV 86Current Room Pressure Alarm Status1 = normal, 2 = low alarm, 3 = high alarmRead
MV 76Current Supply 1 Flow Alarm StatusSupply 1 flow: 1 = normal, 2 = low, 3 = high alarmRead

Enable & remote start

No separate BMS enable is described. Occupancy per supply (BV 24-27, BV 297/298 for supplies 5-6), Emergency Mode (BV 22) and Shutdown Mode (BV 23) are writable and switch the controller between its occupied, unoccupied, emergency and shutdown flow setpoints.

Network setup

Watch out for

TSI Laboratory Room Controller (LRC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

1714 of 1714 shown
Type
AnalogBinaryMulti-state
Access
Show
TSI Laboratory Room Controller (LRC) BACnet Points List
DescriptionStates
AV1Supply 1 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV2Supply 1 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV3Supply 1 Venturi Minimum FlowCFMWrite
AV4Supply 1 Venturi Maximum FlowCFMWrite
AV5Supply 1 Flow K FactorWrite
AV6Supply 1 Venturi Setup Position% openWrite
AV7Supply 1 Venturi LOM Esc TimesWrite
AV8Supply 1 Linear Duct Areaft²Write
AV10Supply 1 Linear Top Velocityft/minWrite
AV11Supply 1 Linear Signal MinimumVWrite
AV12Supply 1 Linear Signal MaximumVWrite
AV13Supply 1 Pitot Sensor ZeroTSI: do not overwriteVRead
AV14Supply 1 Transducer Signal MinimumVWrite
AV15Supply 1 Transducer Signal MaximumVWrite
AV16Supply 1 Pitot Duct Areaft²Write
AV17Supply 5 Flow ErrorTSI: do not read or overwriteRead
AV18Supply 1 Transducer Sensor Maximumin. W.C.Write
AV19Supply 1 Pitot Low Cal Pos% openWrite
AV20Supply 1 Pitot High Cal Pos% openWrite
AV21Supply 1 Pitot Low Cal FlowCFMWrite
AV22Supply 1 Pitot High Cal FlowCFMWrite
AV23Supply 2 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV24Supply 2 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV25Supply 2 Venturi Minimum FlowCFMWrite
AV26Supply 2 Venturi Maximum FlowCFMWrite
AV27Supply 2 Flow K FactorWrite
AV28Supply 2 Venturi Setup Position% openWrite
AV29Supply 2 Venturi LOM Esc TimesWrite
AV30Supply 2 Linear Duct Areaft²Write
AV32Supply 2 Linear Top Velocityft/minWrite
AV33Supply 2 Linear Signal MinimumVWrite
AV34Supply 2 Linear Signal MaximumVWrite
AV35Supply 2 Pitot Sensor ZeroTSI: do not overwriteVRead
AV36Supply 2 Pitot Low Cal Pos% openWrite
AV37Supply 2 Transducer Signal MinimumVWrite
AV38Supply 2 Pitot High Cal Pos% openWrite
AV39Supply 2 Transducer Signal MaximumVWrite
AV40Supply 2 Pitot Low Cal FlowCFMWrite
AV41Supply 2 Pitot Duct Areaft²Write
AV42Supply 2 Pitot High Cal FlowCFMWrite
AV43Supply 6 Flow ErrorTSI: do not read or overwriteRead
AV44Supply 2 Transducer Sensor Maximumin. W.C.Write
AV45Supply 3 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV46Supply 3 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV47Supply 3 Venturi Minimum FlowCFMWrite
AV48Supply 3 Venturi Maximum FlowCFMWrite
AV49Supply 3 Flow K FactorWrite
AV50Supply 3 Venturi Setup Position% openWrite
AV51Supply 3 Venturi LOM Esc TimesWrite
AV52Supply 3 Linear Duct Areaft²Write
AV54Supply 3 Linear Top Velocityft/minWrite
AV55Supply 3 Linear Signal MinimumVWrite
AV56Supply 3 Linear Signal MaximumVWrite
AV57Supply 3 Pitot Sensor ZeroTSI: do not overwriteVRead
AV58Supply 3 Pitot Low Cal Pos% openWrite
AV59Supply 3 Transducer Signal MinimumVWrite
AV60Supply 3 Pitot High Cal Pos% openWrite
AV61Supply 3 Transducer Signal MaximumVWrite
AV62Supply 3 Pitot Low Cal FlowCFMWrite
AV63Supply 3 Pitot Duct Areaft²Write
AV64Supply 3 Pitot High Cal FlowCFMWrite
AV65Old Supply 5 ErrorTSI: do not read or overwriteRead
AV66Supply 3 Transducer Sensor Maximumin. W.C.Write
AV67Supply 4 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV68Supply 4 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV69Supply 4 Venturi Minimum FlowCFMWrite
AV70Supply 4 Venturi Maximum FlowCFMWrite
AV71Supply 4 Flow K FactorWrite
AV72Supply 4 Venturi Setup Position% openWrite
AV73Supply 4 Venturi LOM Esc TimesWrite
AV74Supply 4 Linear Duct Areaft²Write
AV76Supply 4 Linear Top Velocityft/minWrite
AV77Supply 4 Linear Signal MinimumVWrite
AV78Supply 4 Linear Signal MaximumVWrite
AV79Supply 4 Pitot Sensor ZeroTSI: do not overwriteVRead
AV80Supply 4 Pitot Low Cal Pos% openWrite
AV81Supply 4 Transducer Signal MinimumVWrite
AV82Supply 4 Pitot High Cal Pos% openWrite
AV83Supply 4 Transducer Signal MaximumVWrite
AV84Supply 4 Pitot Low Cal FlowCFMWrite
AV85Supply 4 Pitot Duct Areaft²Write
AV86Supply 4 Pitot High Cal FlowCFMWrite
AV87Old Supply 5 ErrorTSI: do not read or overwriteRead
AV88Supply 4 Transducer Sensor Maximumin. W.C.Write
AV89Exhaust 1 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV90Exhaust 1 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV91Exhaust 1 Venturi Minimum FlowCFMWrite
AV92Exhaust 1 Venturi Maximum FlowCFMWrite
AV93Exhaust 1 Flow K FactorWrite
AV94Exhaust 1 Venturi Setup Position% openWrite
AV95Exhaust 1 Venturi LOM Esc TimesWrite
AV96Exhaust 1 Linear Duct Areaft²Write
AV98Exhaust 1 Linear Top Velocityft/minWrite
AV99Exhaust 1 Linear Signal MinimumVWrite
AV100Exhaust 1 Linear Signal MaximumVWrite
AV101Exhaust 1 Pitot Sensor ZeroTSI: do not overwriteVRead
AV102Exhaust 1 Pitot Low Cal Pos% openWrite
AV103Exhaust 1 Transducer Signal MinimumVWrite
AV104Exhaust 1 Pitot High Cal Pos% openWrite
AV105Exhaust 1 Transducer Signal MaximumVWrite
AV106Exhaust 1 Pitot Low Cal FlowCFMWrite
AV107Exhaust 1 Pitot Duct Areaft²Write
AV108Exhaust 1 Pitot High Cal FlowCFMWrite
AV110Exhaust 1 Transducer Sensor Maximumin. W.C.Write
AV111Exhaust 2 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV112Exhaust 2 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV113Exhaust 2 Venturi Minimum FlowCFMWrite
AV114Exhaust 2 Venturi Maximum FlowCFMWrite
AV115Exhaust 2 Flow K FactorWrite
AV116Exhaust 2 Venturi Setup Position% openWrite
AV117Exhaust 2 Venturi LOM Esc TimesWrite
AV118Exhaust 2 Linear Duct Areaft²Write
AV120Exhaust 2 Linear Top Velocityft/minWrite
AV121Exhaust 2 Linear Signal MinimumVWrite
AV122Exhaust 2 Linear Signal MaximumVWrite
AV123Exhaust 2 Pitot Sensor ZeroTSI: do not overwriteVRead
AV124Exhaust 2 Pitot Low Cal Pos% openWrite
AV125Exhaust 2 Transducer Signal MinimumVWrite
AV126Exhaust 2 Pitot High Cal Pos% openWrite
AV127Exhaust 2 Transducer Signal MaximumVWrite
AV128Exhaust 2 Pitot Low Cal FlowCFMWrite
AV129Exhaust 2 Pitot Duct Areaft²Write
AV130Exhaust 2 Pitot High Cal FlowCFMWrite
AV132Exhaust 2 Transducer Sensor Maximumin. W.C.Write
AV133Supply 1 Room Temp Offset°FWrite
AV134Supply 2 Room Temp Offset°FWrite
AV135Supply 3 Room Temp Offset°FWrite
AV136Supply 4 Room Temp Offset°FWrite
AV137Supply 1 DAT Offset°FWrite
AV138Supply 2 DAT Offset°FWrite
AV139Supply 3 DAT Offset°FWrite
AV140Supply 4 DAT Offset°FWrite
AV141Supply 1 DAT Signal MinimumVWrite
AV142Supply 1 DAT Signal MaximumVWrite
AV143Supply 1 DAT Sensor Minimum°FWrite
AV144Supply 1 DAT Sensor Maximum°FWrite
AV146Supply 2 DAT Signal MinimumVWrite
AV147Supply 2 DAT Signal MaximumVWrite
AV148Supply 2 DAT Sensor Minimum°FWrite
AV149Supply 2 DAT Sensor Maximum°FWrite
AV151Supply 3 DAT Signal MinimumVWrite
AV152Supply 3 DAT Signal MaximumVWrite
AV153Supply 3 DAT Sensor Minimum°FWrite
AV154Supply 3 DAT Sensor Maximum°FWrite
AV156Supply 4 DAT Signal MinimumVWrite
AV157Supply 4 DAT Signal MaximumVWrite
AV158Supply 4 DAT Sensor Minimum°FWrite
AV159Supply 4 DAT Sensor Maximum°FWrite
AV161Supply 1 Room Temp Adj Signal MinimumVWrite
AV162Supply 1 Room Temp Adj Signal MaximumVWrite
AV163Supply 1 Room Temp Adj Sensor Minimum°FWrite
AV164Supply 1 Room Temp Adj Sensor Maximum°FWrite
AV165Supply 2 Room Temp Adj Signal MinimumVWrite
AV166Supply 2 Room Temp Adj Signal MaximumVWrite
AV167Supply 2 Room Temp Adj Sensor Minimum°FWrite
AV168Supply 2 Room Temp Adj Sensor Maximum°FWrite
AV169Supply 3 Room Temp Adj Signal MinimumVWrite
AV170Supply 3 Room Temp Adj Signal MaximumVWrite
AV171Supply 3 Room Temp Adj Sensor Minimum°FWrite
AV172Supply 3 Room Temp Adj Sensor Maximum°FWrite
AV173Supply 4 Room Temp Adj Signal MinimumVWrite
AV174Supply 4 Room Temp Adj Signal MaximumVWrite
AV175Supply 4 Room Temp Adj Sensor Minimum°FWrite
AV176Supply 4 Room Temp Adj Sensor Maximum°FWrite
AV177Relative Humidity Signal MinimumVWrite
AV178Relative Humidity Signal MaximumVWrite
AV179Relative Humidity Sensor Minimum%RHWrite
AV180Relative Humidity Sensor Maximum%RHWrite
AV181Relative Humidity Offset%RHWrite
AV182Pressure Transducer Signal MaximumVWrite
AV183Pressure Transducer Signal MinimumVWrite
AV184Pressure Transducer Sensor Minimumin. W.C.Write
AV185Pressure Transducer Sensor Maximumin. W.C.Write
AV186Room Pressure Sensor ZeroTSI: do not overwriteVRead
AV188TTW Sensor Velocity K-FactorWrite
AV189TTW Sensor ElevationftWrite
AV190Supply 1 Minimum FlowCFMWrite
AV191Supply 1 Cooling FlowCFMWrite
AV192Supply 1 Heating FlowCFMWrite
AV193Supply 1 Maximum FlowCFMWrite
AV194Supply 1 Minimum Position% openWrite
AV195Supply 1 Maximum Position% openWrite
AV196Supply 1 Unocc Minimum FlowCFMWrite
AV197Supply 1 Unocc Cooling FlowCFMWrite
AV198Supply 1 Unocc Heating FlowCFMWrite
AV199Supply 1 Unocc Maximum FlowCFMWrite
AV200Supply 1 Emergency FlowCFMWrite
AV201Supply 1 Shutdown FlowCFMWrite
AV202Supply 2 Minimum FlowCFMWrite
AV203Supply 2 Unocc Minimum FlowCFMWrite
AV204Supply 2 Cooling FlowCFMWrite
AV205Supply 2 Unocc Cooling FlowCFMWrite
AV206Supply 2 Heating FlowCFMWrite
AV207Supply 2 Unocc Heating FlowCFMWrite
AV208Supply 2 Maximum FlowCFMWrite
AV209Supply 2 Unocc Maximum FlowCFMWrite
AV210Supply 2 Emergency FlowCFMWrite
AV211Supply 2 Minimum Position% openWrite
AV212Supply 2 Shutdown FlowCFMWrite
AV213Supply 2 Maximum Position% openWrite
AV214Supply 3 Minimum FlowCFMWrite
AV215Supply 3 Unocc Minimum FlowCFMWrite
AV216Supply 3 Cooling FlowCFMWrite
AV217Supply 3 Unocc Cooling FlowCFMWrite
AV218Supply 3 Heating FlowCFMWrite
AV219Supply 3 Unocc Heating FlowCFMWrite
AV220Supply 3 Maximum FlowCFMWrite
AV221Supply 3 Unocc Maximum FlowCFMWrite
AV222Supply 3 Emergency FlowCFMWrite
AV223Supply 3 Minimum Position% openWrite
AV224Supply 3 Shutdown FlowCFMWrite
AV225Supply 3 Maximum Position% openWrite
AV226Supply 4 Minimum FlowCFMWrite
AV227Supply 4 Unocc Minimum FlowCFMWrite
AV228Supply 4 Cooling FlowCFMWrite
AV229Supply 4 Unocc Cooling FlowCFMWrite
AV230Supply 4 Heating FlowCFMWrite
AV231Supply 4 Unocc Heating FlowCFMWrite
AV232Supply 4 Maximum FlowCFMWrite
AV233Supply 4 Unocc Maximum FlowCFMWrite
AV234Supply 4 Emergency FlowCFMWrite
AV235Supply 4 Minimum Position% openWrite
AV236Supply 4 Shutdown FlowCFMWrite
AV237Supply 4 Maximum Position% openWrite
AV238Exhaust 1 Minimum FlowCFMWrite
AV239Exhaust 1 Maximum FlowCFMWrite
AV240Exhaust 1 Minimum Position% openWrite
AV241Exhaust 1 Maximum Position% openWrite
AV242Exhaust 1 Emergency FlowCFMWrite
AV243Exhaust 2 Minimum FlowCFMWrite
AV244Exhaust 2 Maximum FlowCFMWrite
AV245Exhaust 2 Minimum Position% openWrite
AV246Exhaust 2 Maximum Position% openWrite
AV247Exhaust 2 Emergency FlowCFMWrite
AV248Supply 1 Heat Setpoint°FWrite
AV249Supply 1 Cool Setpoint°FWrite
AV250Supply 1 Unocc Heat Setpoint°FWrite
AV251Supply 1 Unocc Cool Setpoint°FWrite
AV252Supply 1 DAT DeltaΔ°FWrite
AV253Supply 2 Heat Setpoint°FWrite
AV254Supply 2 Cool Setpoint°FWrite
AV255Supply 2 Unocc Heat Setpoint°FWrite
AV256Supply 2 Unocc Cool Setpoint°FWrite
AV257Supply 2 DAT DeltaΔ°FWrite
AV258Supply 3 Heat Setpoint°FWrite
AV259Supply 3 Cool Setpoint°FWrite
AV260Supply 3 Unocc Heat Setpoint°FWrite
AV261Supply 3 Unocc Cool Setpoint°FWrite
AV262Supply 3 DAT DeltaΔ°FWrite
AV263Supply 4 Heat Setpoint°FWrite
AV264Supply 4 Cool Setpoint°FWrite
AV265Supply 4 Unocc Heat Setpoint°FWrite
AV266Supply 4 Unocc Cool Setpoint°FWrite
AV267Supply 4 DAT DeltaΔ°FWrite
AVmin268Room Pressure Setpointin. W.C.Write
AV269Door Room Pressure Setpointin. W.C.Write
AV270Minimum OffsetCFMWrite
AV271Maximum OffsetCFMWrite
AV272Supply 1 Low Flow AlarmCFMWrite
AV273Supply 1 High Flow AlarmCFMWrite
AV274Supply 1 Unocc Low Flow AlarmCFMWrite
AV275Supply 1 Unocc High Flow AlarmCFMWrite
AV276Supply 2 Low Flow AlarmCFMWrite
AV277Supply 2 High Flow AlarmCFMWrite
AV278Supply 2 Unocc Low Flow AlarmCFMWrite
AV279Supply 2 Unocc High Flow AlarmCFMWrite
AV280Supply 3 Low Flow AlarmCFMWrite
AV281Supply 3 High Flow AlarmCFMWrite
AV282Supply 3 Unocc Low Flow AlarmCFMWrite
AV283Supply 3 Unocc High Flow AlarmCFMWrite
AV284Supply 4 Low Flow AlarmCFMWrite
AV285Supply 4 High Flow AlarmCFMWrite
AV286Supply 4 Unocc Low Flow AlarmCFMWrite
AV287Supply 4 Unocc High Flow AlarmCFMWrite
AV288Exhaust 1 Low Flow AlarmCFMWrite
AV289Exhaust 1 High Flow AlarmCFMWrite
AV290Exhaust 2 Low Flow AlarmCFMWrite
AV291Exhaust 2 High Flow AlarmCFMWrite
AV292Supply 1 Low Temperature Alarm°FWrite
AV293Supply 1 High Temperature Alarm°FWrite
AV294Supply 1 Unocc Low Temperature Alarm°FWrite
AV295Supply 1 Unocc High Temperature Alarm°FWrite
AV296Supply 2 Low Temperature Alarm°FWrite
AV297Supply 2 High Temperature Alarm°FWrite
AV298Supply 2 Unocc Low Temperature Alarm°FWrite
AV299Supply 2 Unocc High Temperature Alarm°FWrite
AV300Supply 3 Low Temperature Alarm°FWrite
AV301Supply 3 High Temperature Alarm°FWrite
AV302Supply 3 Unocc Low Temperature Alarm°FWrite
AV303Supply 3 Unocc High Temperature Alarm°FWrite
AV304Supply 4 Low Temperature Alarm°FWrite
AV305Supply 4 High Temperature Alarm°FWrite
AV306Supply 4 Unocc Low Temperature Alarm°FWrite
AV307Supply 4 Unocc High Temperature Alarm°FWrite
AV308Low Pressure Alarmin. W.C.Write
AV309High Pressure Alarmin. W.C.Write
AV310Door Low Pressure Alarmin. W.C.Write
AV311Door High Pressure Alarmin. W.C.Write
AV312Alarm DelaysWrite
AV313Door Alarm DelaysWrite
AV314Supply 1 Flow Manual Position% openWrite
AV315Supply 2 Flow Manual Position% openWrite
AV316Supply 3 Flow Manual Position% openWrite
AV317Supply 4 Flow Manual Position% openWrite
AV318Supply 1 Temp Manual Position% openWrite
AV319Supply 2 Temp Manual Position% openWrite
AV320Supply 3 Temp Manual Position% openWrite
AV321Supply 4 Temp Manual Position% openWrite
AV322Exhaust 1 Flow Manual Position% openWrite
AV323Exhaust 2 Flow Manual Position% openWrite
AV324Supply 5 Flow Manual Position% openWrite
AV325Supply 6 Flow Manual Position% openWrite
AV326Supply 1 Balancer FlowCFMWrite
AV327Supply 2 Balancer FlowCFMWrite
AV328Supply 3 Balancer FlowCFMWrite
AV329Supply 4 Balancer FlowCFMWrite
AV330Exhaust 1 Balancer FlowCFMWrite
AV331Exhaust 2 Balancer FlowCFMWrite
AV332Supply 1 High DAT Alarm°FWrite
AV333Supply 2 High DAT Alarm°FWrite
AV334Supply 3 High DAT Alarm°FWrite
AV335Supply 4 High DAT Alarm°FWrite
AV336Minimum Offset AlarmCFMWrite
AV337Maximum Offset AlarmCFMWrite
AV338Supply 1 Flow Input NumberTSI: do not overwriteRead
AV339Supply 1 DAT Input NumberTSI: do not overwriteRead
AV340Supply 1 Room Temp Input NumberTSI: do not overwriteRead
AV341Supply 1 Room Temp Adj Input NumberTSI: do not overwriteRead
AV342Supply 1 Occupancy Input NumberTSI: do not overwriteRead
AV343Supply 2 Flow Input NumberTSI: do not overwriteRead
AV344Supply 2 DAT Input NumberTSI: do not overwriteRead
AV345Supply 2 Room Temp Input NumberTSI: do not overwriteRead
AV346Supply 2 Room Temp Adj Input NumberTSI: do not overwriteRead
AV347Supply 2 Occupancy Input NumberTSI: do not overwriteRead
AV348Supply 3 Flow Input NumberTSI: do not overwriteRead
AV349Supply 3 DAT Input NumberTSI: do not overwriteRead
AV350Supply 3 Room Temp Input NumberTSI: do not overwriteRead
AV351Supply 3 Room Temp Adj Input NumberTSI: do not overwriteRead
AV352Supply 3 Occupancy Input NumberTSI: do not overwriteRead
AV353Supply 4 Flow Input NumberTSI: do not overwriteRead
AV354Supply 4 DAT Input NumberTSI: do not overwriteRead
AV355Supply 4 Room Temp Input NumberTSI: do not overwriteRead
AV356Supply 4 Room Temp Adj Input NumberTSI: do not overwriteRead
AV357Supply 4 Occupancy Input NumberTSI: do not overwriteRead
AV358Exhaust 1 Flow Input NumberTSI: do not overwriteRead
AV359Exhaust 2 Flow Input NumberTSI: do not overwriteRead
AV360Room Pressure Input NumberTSI: do not overwriteRead
AV361Relative Humidity Input NumberTSI: do not overwriteRead
AV362Door Switch Input NumberTSI: do not overwriteRead
AV363Emergency Input NumberTSI: do not overwriteRead
AV364Shutdown Input NumberTSI: do not overwriteRead
AV365Hood 1 Flow Input NumberTSI: do not overwriteRead
AV366Hood 2 Flow Input NumberTSI: do not overwriteRead
AV367Hood 3 Flow Input NumberTSI: do not overwriteRead
AV368Hood 4 Flow Input NumberTSI: do not overwriteRead
AV369Hood 5 Flow Input NumberTSI: do not overwriteRead
AV370Hood 6 Flow Input NumberTSI: do not overwriteRead
AV371Hood 7 Flow Input NumberTSI: do not overwriteRead
AV372Supply 1 Flow ChangeCFMWrite
AV373Supply 2 Flow ChangeCFMWrite
AV374Supply 3 Flow ChangeCFMWrite
AV375Supply 4 Flow ChangeCFMWrite
AV376Supply 1 Reheat/Cooling DelaysWrite
AV377Supply 2 Reheat/Cooling DelaysWrite
AV378Supply 3 Reheat/Cooling DelaysWrite
AV379Supply 4 Reheat/Cooling DelaysWrite
AV392Supply 5 Temp Manual Position% openWrite
AV393Supply 6 Temp Manual Position% openWrite
AV395Current Alarm DelayTSI: do not overwritesRead
AV396Current OffsetTSI: do not overwriteCFMRead
AV398Current Supply 1 Minimum FlowTSI: do not overwriteCFMRead
AV399Current Supply 1 Cooling FlowTSI: do not overwriteCFMRead
AV400Current Supply 1 Heating FlowTSI: do not overwriteCFMRead
AV401Current Supply 1 Maximum FlowTSI: do not overwriteCFMRead
AV402Current Supply 2 Minimum FlowTSI: do not overwriteCFMRead
AV403Current Supply 2 Cooling FlowTSI: do not overwriteCFMRead
AV404Current Supply 2 Heating FlowTSI: do not overwriteCFMRead
AV405Current Supply 2 Maximum FlowTSI: do not overwriteCFMRead
AV406Current Supply 3 Minimum FlowTSI: do not overwriteCFMRead
AV407Current Supply 3 Cooling FlowTSI: do not overwriteCFMRead
AV408Current Supply 3 Heating FlowTSI: do not overwriteCFMRead
AV409Current Supply 3 Maximum FlowTSI: do not overwriteCFMRead
AV410Current Supply 4 Minimum FlowTSI: do not overwriteCFMRead
AV411Current Supply 4 Cooling FlowTSI: do not overwriteCFMRead
AV412Current Supply 4 Heating FlowTSI: do not overwriteCFMRead
AV413Current Supply 4 Maximum FlowTSI: do not overwriteCFMRead
AV414Current Supply 1 Heat SetpointTSI: do not overwrite°FRead
AV415Current Supply 1 Cool SetpointTSI: do not overwrite°FRead
AV416Current Supply 2 Heat SetpointTSI: do not overwrite°FRead
AV417Current Supply 2 Cool SetpointTSI: do not overwrite°FRead
AV418Current Supply 3 Heat SetpointTSI: do not overwrite°FRead
AV419Current Supply 3 Cool SetpointTSI: do not overwrite°FRead
AV420Current Supply 4 Heat SetpointTSI: do not overwrite°FRead
AV421Current Supply 4 Cool SetpointTSI: do not overwrite°FRead
AV422Current Room Pressure SetpointTSI: do not overwritein. W.C.Read
AV423Current Supply 1 Low Flow AlarmTSI: do not overwriteCFMRead
AV424Current Supply 1 High Flow AlarmTSI: do not overwriteCFMRead
AV425Current Supply 2 Low Flow AlarmTSI: do not overwriteCFMRead
AV426Current Supply 2 High Flow AlarmTSI: do not overwriteCFMRead
AV427Current Supply 3 Low Flow AlarmTSI: do not overwriteCFMRead
AV428Current Supply 3 High Flow AlarmTSI: do not overwriteCFMRead
AV429Current Supply 4 Low Flow AlarmTSI: do not overwriteCFMRead
AV430Current Supply 4 High Flow AlarmTSI: do not overwriteCFMRead
AV431Current Low Pressure AlarmTSI: do not overwritein. W.C.Read
AV432Current High Pressure AlarmTSI: do not overwritein. W.C.Read
AV433Current Supply 1 Low Temperature AlarmTSI: do not overwrite°FRead
AV434Current Supply 1 High Temperature AlarmTSI: do not overwrite°FRead
AV435Current Supply 2 Low Temperature AlarmTSI: do not overwrite°FRead
AV436Current Supply 2 High Temperature AlarmTSI: do not overwrite°FRead
AV437Current Supply 3 Low Temperature AlarmTSI: do not overwrite°FRead
AV438Current Supply 3 High Temperature AlarmTSI: do not overwrite°FRead
AV439Current Supply 4 Low Temperature AlarmTSI: do not overwrite°FRead
AV440Current Supply 4 High Temperature AlarmTSI: do not overwrite°FRead
AV441Hood 1 Venturi Minimum FlowCFMWrite
AV442Hood 1 Venturi Maximum FlowCFMWrite
AV443Hood 1 Flow K factorWrite
AV445Hood 1 Venturi LOM ESC TimesWrite
AV446Hood 1 Linear Duct Areaft²Write
AV448Hood 1 Linear Top Velocityft/minWrite
AV449Hood 1 Linear Signal MinimumVWrite
AV450Hood 1 Linear Signal MaximumVWrite
AV451Hood 1 Pitot Sensor ZeroTSI: do not overwriteVRead
AV452Hood 1 Transducer Signal MinimumVWrite
AV453Hood 1 Transducer Signal MaximumVWrite
AV454Hood 1 Pitot Duct Areaft²Write
AV456Hood 1 Transducer Sensor Maximumin. W.C.Write
AV459Hood 1 Pitot Low Cal FlowCFMWrite
AV460Hood 1 Pitot High Cal FlowCFMWrite
AV461Hood 1 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV462Hood 1 Pitot High Cal VoltageTSI: do not overwriteVRead
AV463Hood 1 TP Min FlowCFMWrite
AV464Hood 1 TP Max FlowCFMWrite
AV465Hood 2 Venturi Minimum FlowCFMWrite
AV466Hood 2 Venturi Maximum FlowCFMWrite
AV467Hood 2 Flow K factorWrite
AV469Hood 2 Venturi LOM ESC TimesWrite
AV470Hood 2 Linear Duct Areaft²Write
AV472Hood 2 Linear Top Velocityft/minWrite
AV473Hood 2 Linear Signal MinimumVWrite
AV474Hood 2 Linear Signal MaximumVWrite
AV475Hood 2 Pitot Sensor ZeroTSI: do not overwriteVRead
AV476Hood 2 Transducer Signal MinimumVWrite
AV477Hood 2 Transducer Signal MaximumVWrite
AV478Hood 2 Pitot Duct Areaft²Write
AV480Hood 2 Transducer Sensor Maximumin. W.C.Write
AV483Hood 2 Pitot Low Cal FlowCFMWrite
AV484Hood 2 Pitot High Cal FlowCFMWrite
AV485Hood 2 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV486Hood 2 Pitot High Cal VoltageTSI: do not overwriteVRead
AV487Hood 2 TP Min FlowCFMWrite
AV488Hood 2 TP Max FlowCFMWrite
AV489Hood 3 Venturi Minimum FlowCFMWrite
AV490Hood 3 Venturi Maximum FlowCFMWrite
AV491Hood 3 Flow K factorWrite
AV493Hood 3 Venturi LOM ESC TimesWrite
AV494Hood 3 Linear Duct Areaft²Write
AV496Hood 3 Linear Top Velocityft/minWrite
AV497Hood 3 Linear Signal MinimumVWrite
AV498Hood 3 Linear Signal MaximumVWrite
AV499Hood 3 Pitot Sensor ZeroTSI: do not overwriteVRead
AV500Hood 3 Transducer Signal MinimumVWrite
AV501Hood 3 Transducer Signal MaximumVWrite
AV502Hood 3 Pitot Duct Areaft²Write
AV504Hood 3 Transducer Sensor Maximumin. W.C.Write
AV507Hood 3 Pitot Low Cal FlowCFMWrite
AV508Hood 3 Pitot High Cal FlowCFMWrite
AV509Hood 3 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV510Hood 3 Pitot High Cal VoltageTSI: do not overwriteVRead
AV511Hood 3 TP Min FlowCFMWrite
AV512Hood 3 TP Max FlowCFMWrite
AV513Hood 4 Venturi Minimum FlowCFMWrite
AV514Hood 4 Venturi Maximum FlowCFMWrite
AV515Hood 4 Flow K factorWrite
AV517Hood 4 Venturi LOM ESC TimesWrite
AV518Hood 4 Linear Duct Areaft²Write
AV520Hood 4 Linear Top Velocityft/minWrite
AV521Hood 4 Linear Signal MinimumVWrite
AV522Hood 4 Linear Signal MaximumVWrite
AV523Hood 4 Pitot Sensor ZeroTSI: do not overwriteVRead
AV524Hood 4 Transducer Signal MinimumVWrite
AV525Hood 4 Transducer Signal MaximumVWrite
AV526Hood 4 Pitot Duct Areaft²Write
AV528Hood 4 Transducer Sensor Maximumin. W.C.Write
AV531Hood 4 Pitot Low Cal FlowCFMWrite
AV532Hood 4 Pitot High Cal FlowCFMWrite
AV533Hood 4 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV534Hood 4 Pitot High Cal VoltageTSI: do not overwriteVRead
AV535Hood 4 TP Min FlowCFMWrite
AV536Hood 4 TP Max FlowCFMWrite
AV537Hood 5 Venturi Minimum FlowCFMWrite
AV538Hood 5 Venturi Maximum FlowCFMWrite
AV539Hood 5 Flow K factorWrite
AV541Hood 5 Venturi LOM ESC TimesWrite
AV542Hood 5 Linear Duct Areaft²Write
AV544Hood 5 Linear Top Velocityft/minWrite
AV545Hood 5 Linear Signal MinimumVWrite
AV546Hood 5 Linear Signal MaximumVWrite
AV547Hood 5 Pitot Sensor ZeroTSI: do not overwriteVRead
AV548Hood 5 Transducer Signal MinimumVWrite
AV549Hood 5 Transducer Signal MaximumVWrite
AV550Hood 5 Pitot Duct Areaft²Write
AV552Hood 5 Transducer Sensor Maximumin. W.C.Write
AV555Hood 5 Pitot Low Cal FlowCFMWrite
AV556Hood 5 Pitot High Cal FlowCFMWrite
AV557Hood 5 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV558Hood 5 Pitot High Cal VoltageTSI: do not overwriteVRead
AV559Hood 5 TP Min FlowCFMWrite
AV560Hood 5 TP Max FlowCFMWrite
AV561Hood 6 Venturi Minimum FlowCFMWrite
AV562Hood 6 Venturi Maximum FlowCFMWrite
AV563Hood 6 Flow K factorWrite
AV565Hood 6 Venturi LOM ESC TimesWrite
AV566Hood 6 Linear Duct Areaft²Write
AV568Hood 6 Linear Top Velocityft/minWrite
AV569Hood 6 Linear Signal MinimumVWrite
AV570Hood 6 Linear Signal MaximumVWrite
AV571Hood 6 Pitot Sensor ZeroTSI: do not overwriteVRead
AV572Hood 6 Transducer Signal MinimumVWrite
AV573Hood 6 Transducer Signal MaximumVWrite
AV574Hood 6 Pitot Duct Areaft²Write
AV576Hood 6 Transducer Sensor Maximumin. W.C.Write
AV579Hood 6 Pitot Low Cal FlowCFMWrite
AV580Hood 6 Pitot High Cal FlowCFMWrite
AV581Hood 6 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV582Hood 6 Pitot High Cal VoltageTSI: do not overwriteVRead
AV583Hood 6 TP Min FlowCFMWrite
AV584Hood 6 TP Max FlowCFMWrite
AV585Hood 7 Venturi Minimum FlowCFMWrite
AV586Hood 7 Venturi Maximum FlowCFMWrite
AV587Hood 7 Flow K factorWrite
AV589Hood 7 Venturi LOM ESC TimesWrite
AV590Hood 7 Linear Duct Areaft²Write
AV592Hood 7 Linear Top Velocityft/minWrite
AV593Hood 7 Linear Signal MinimumVWrite
AV594Hood 7 Linear Signal MaximumVWrite
AV595Hood 7 Pitot Sensor ZeroTSI: do not overwriteVRead
AV596Hood 7 Transducer Signal MinimumVWrite
AV597Hood 7 Transducer Signal MaximumVWrite
AV598Hood 7 Pitot Duct Areaft²Write
AV600Hood 7 Transducer Sensor Maximumin. W.C.Write
AV603Hood 7 Pitot Low Cal FlowCFMWrite
AV604Hood 7 Pitot High Cal FlowCFMWrite
AV605Hood 7 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV606Hood 7 Pitot High Cal VoltageTSI: do not overwriteVRead
AV607Hood 7 TP Min FlowCFMWrite
AV608Hood 7 TP Max FlowCFMWrite
AV609Hood 1 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV610Hood 1 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV611Hood 2 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV612Hood 2 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV613Hood 3 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV614Hood 3 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV615Hood 4 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV616Hood 4 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV617Hood 5 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV618Hood 5 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV619Hood 6 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV620Hood 6 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV621Hood 7 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV622Hood 7 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV623TTW Sensor UnSpanned VelocityTSI: do not overwriteft/minRead
AV624TTW Sensor Spanned VelocityTSI: do not overwriteft/minRead
AV625Supply 1 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV626Supply 1 Pitot High Cal VoltageTSI: do not overwriteVRead
AV627Supply 2 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV628Supply 2 Pitot High Cal VoltageTSI: do not overwriteVRead
AV629Supply 3 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV630Supply 3 Pitot High Cal VoltageTSI: do not overwriteVRead
AV631Supply 4 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV632Supply 4 Pitot High Cal VoltageTSI: do not overwriteVRead
AV633Exhaust 1 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV634Exhaust 1 Pitot High Cal VoltageTSI: do not overwriteVRead
AV635Exhaust 2 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV636Exhaust 2 Pitot High Cal VoltageTSI: do not overwriteVRead
AV653Supply 5 Balancer FlowCFMWrite
AV654Supply 6 Balancer FlowCFMWrite
AV655Current Supply 1 Minimum Flow SetpointTSI: do not overwriteCFMRead
AV656Current Supply 2 Minimum Flow SetpointTSI: do not overwriteCFMRead
AV657Current Supply 3 Minimum Flow SetpointTSI: do not overwriteCFMRead
AV658Current Supply 4 Minimum Flow SetpointTSI: do not overwriteCFMRead
AV659Offset SetpointTSI: do not overwriteCFMRead
AVmin660Current Total Supply FlowTSI: do not overwriteCFMRead
AVmin661Current Total Exhaust FlowTSI: do not overwriteCFMRead
AV662Supply 1 FlowTSI: do not overwriteCFMRead
AV663Supply 2 FlowTSI: do not overwriteCFMRead
AV664Supply 3 FlowTSI: do not overwriteCFMRead
AV665Supply 4 FlowTSI: do not overwriteCFMRead
AV666Exhaust 1 FlowTSI: do not overwriteCFMRead
AV667Exhaust 2 FlowTSI: do not overwriteCFMRead
AV668Hood 1 FlowTSI: do not overwriteCFMRead
AV669Hood 2 FlowTSI: do not overwriteCFMRead
AV670Hood 3 FlowTSI: do not overwriteCFMRead
AV671Hood 4 FlowTSI: do not overwriteCFMRead
AV672Hood 5 FlowTSI: do not overwriteCFMRead
AV673Hood 6 FlowTSI: do not overwriteCFMRead
AV674Hood 7 FlowTSI: do not overwriteCFMRead
AV675Current Supply 1 Temperature Control PositionTSI: do not overwrite% openRead
AV676Current Supply 1 Flow Control PositionTSI: do not overwrite% openRead
AV677Current Supply 2 Temperature Control PositionTSI: do not overwrite% openRead
AV678Current Supply 2 Flow Control PositionTSI: do not overwrite% openRead
AV679Current Supply 3 Temperature Control PositionTSI: do not overwrite% openRead
AV680Current Supply 3 Flow Control PositionTSI: do not overwrite% openRead
AV681Current Supply 4 Temperature Control PositionTSI: do not overwrite% openRead
AV682Current Supply 4 Flow Control PositionTSI: do not overwrite% openRead
AV683Current Exhaust 1 Flow Control PositionTSI: do not overwrite% openRead
AV684Current Exhaust 2 Flow Control PositionTSI: do not overwrite% openRead
AV685Supply 1 DATTSI: do not overwrite°FRead
AV686Supply 2 DATTSI: do not overwrite°FRead
AV687Supply 3 DATTSI: do not overwrite°FRead
AV688Supply 4 DATTSI: do not overwrite°FRead
AVmin689Supply 1 Room TempTSI: do not overwrite°FRead
AV690Supply 2 Room TempTSI: do not overwrite°FRead
AV691Supply 3 Room TempTSI: do not overwrite°FRead
AV692Supply 4 Room TempTSI: do not overwrite°FRead
AV693Supply 1 Room Temp AdjTSI: do not overwrite°FRead
AV694Supply 2 Room Temp AdjTSI: do not overwrite°FRead
AV695Supply 3 Room Temp AdjTSI: do not overwrite°FRead
AV696Supply 4 Room Temp AdjTSI: do not overwrite°FRead
AVmin697Room PressureTSI: do not overwritein. W.C.Read
AV698Relative HumidityTSI: do not overwrite%RHRead
AV699Hood 8 Flow Input NumberTSI: do not overwriteRead
AV700Hood 9 Flow Input NumberTSI: do not overwriteRead
AV701Hood 10 Flow Input NumberTSI: do not overwriteRead
AV702Hood 11 Flow Input NumberTSI: do not overwriteRead
AV703Hood 12 Flow Input NumberTSI: do not overwriteRead
AV704Hood 13 Flow Input NumberTSI: do not overwriteRead
AV705Hood 14 Flow Input NumberTSI: do not overwriteRead
AV706Hood 15 Flow Input NumberTSI: do not overwriteRead
AV707Hood 16 Flow Input NumberTSI: do not overwriteRead
AV708Hood 17 Flow Input NumberTSI: do not overwriteRead
AV709Hood 18 Flow Input NumberTSI: do not overwriteRead
AV710Hood 19 Flow Input NumberTSI: do not overwriteRead
AV711Hood 20 Flow Input NumberTSI: do not overwriteRead
AV713Supply 1 Flow VoltageTSI: do not overwriteVRead
AV714Supply 2 Flow VoltageTSI: do not overwriteVRead
AV715Supply 3 Flow VoltageTSI: do not overwriteVRead
AV716Supply 4 Flow VoltageTSI: do not overwriteVRead
AV717Exhaust 1 Flow VoltageTSI: do not overwriteVRead
AV718Exhaust 2 Flow VoltageTSI: do not overwriteVRead
AV719Hood 1 Flow VoltageTSI: do not overwriteVRead
AV720Hood 2 Flow VoltageTSI: do not overwriteVRead
AV721Hood 3 Flow VoltageTSI: do not overwriteVRead
AV722Hood 4 Flow VoltageTSI: do not overwriteVRead
AV723Hood 5 Flow VoltageTSI: do not overwriteVRead
AV724Hood 6 Flow VoltageTSI: do not overwriteVRead
AV725Hood 7 Flow VoltageTSI: do not overwriteVRead
AV726Supply 1 DAT VoltageTSI: do not overwriteVRead
AV727Supply 2 DAT VoltageTSI: do not overwriteVRead
AV728Supply 3 DAT VoltageTSI: do not overwriteVRead
AV729Supply 4 DAT VoltageTSI: do not overwriteVRead
AV730Room Pressure VoltageTSI: do not overwriteVRead
AV731Relative Humidity VoltageTSI: do not overwriteVRead
AV732Supply 1 Room Temp Adjustment VoltageTSI: do not overwriteVRead
AV733Supply 2 Room Temp Adjustment VoltageTSI: do not overwriteVRead
AV734Supply 3 Room Temp Adjustment VoltageTSI: do not overwriteVRead
AV735Supply 4 Room Temp Adjustment VoltageTSI: do not overwriteVRead
AV736Supply 1 Flow Proportional GainWrite
AV737Supply 2 Flow Proportional GainWrite
AV738Supply 3 Flow Proportional GainWrite
AV739Supply 4 Flow Proportional GainWrite
AV740Exhaust 1 Flow Proportional GainWrite
AV741Exhaust 2 Flow Proportional GainWrite
AV742Supply 1 Flow Integral TimeWrite
AV743Supply 2 Flow Integral TimeWrite
AV744Supply 3 Flow Integral TimeWrite
AV745Supply 4 Flow Integral TimeWrite
AV746Exhaust 1 Flow Integral TimeWrite
AV747Exhaust 2 Flow Integral TimeWrite
AV748Pressure Control GainWrite
AV749Supply 1 Temp Throttling Range°FWrite
AV750Supply 2 Temp Throttling Range°FWrite
AV751Supply 3 Temp Throttling Range°FWrite
AV752Supply 4 Temp Throttling Range°FWrite
AV753Supply 1 Temp Integral TimesWrite
AV754Supply 2 Temp Integral TimesWrite
AV755Supply 3 Temp Integral TimesWrite
AV756Supply 4 Temp Integral TimesWrite
AV757Supply 1 Flow Speed%Write
AV758Supply 2 Flow Speed%Write
AV759Supply 3 Flow Speed%Write
AV760Supply 4 Flow Speed%Write
AV761Exhaust 1 Flow Speed%Write
AV762Exhaust 2 Flow Speed%Write
AV763Supply 1 Flow Sensitivity%Write
AV764Supply 2 Flow Sensitivity%Write
AV765Supply 3 Flow Sensitivity%Write
AV766Supply 4 Flow Sensitivity%Write
AV767Exhaust 1 Flow Sensitivity%Write
AV768Exhaust 2 Flow Sensitivity%Write
AV769Supply 1 Shutdown Low Flow AlarmCFMWrite
AV770Supply 1 Shutdown High Flow AlarmCFMWrite
AV771Supply 2 Shutdown Low Flow AlarmCFMWrite
AV772Supply 2 Shutdown High Flow AlarmCFMWrite
AV773Supply 3 Shutdown Low Flow AlarmCFMWrite
AV774Supply 3 Shutdown High Flow AlarmCFMWrite
AV775Supply 4 Shutdown Low Flow AlarmCFMWrite
AV776Supply 4 Shutdown High Flow AlarmCFMWrite
AV777Exhaust 1 Shutdown Low Flow AlarmCFMWrite
AV778Exhaust 1 Shutdown High Flow AlarmCFMWrite
AV779Exhaust 2 Shutdown Low Flow AlarmCFMWrite
AV780Exhaust 2 Shutdown High Flow AlarmCFMWrite
AV781Exhaust 1 Unocc Low Flow AlarmCFMWrite
AV782Exhaust 1 Unocc High Flow AlarmCFMWrite
AV783Exhaust 2 Unocc Low Flow AlarmCFMWrite
AV784Exhaust 2 Unocc High Flow AlarmCFMWrite
AV785Current Exhaust 1 Low Flow AlarmCFMWrite
AV786Current Exhaust 1 High Flow AlarmCFMWrite
AV787Current Exhaust 2 Low Flow AlarmCFMWrite
AV788Current Exhaust 2 High Flow AlarmCFMWrite
AV789Hood 8 FlowCFMWrite
AV790Hood 9 FlowCFMWrite
AV791Hood 10 FlowCFMWrite
AV792Hood 11 FlowCFMWrite
AV793Hood 12 FlowCFMWrite
AV794Hood 13 FlowCFMWrite
AV795Hood 14 FlowCFMWrite
AV796Hood 15 FlowCFMWrite
AV797Hood 16 FlowCFMWrite
AV798Hood 17 FlowCFMWrite
AV799Hood 18 FlowCFMWrite
AV800Hood 19 FlowCFMWrite
AV801Hood 20 FlowCFMWrite
AV802Hood 8 Flow VoltageTSI: do not overwriteVRead
AV803Hood 9 Flow VoltageTSI: do not overwriteVRead
AV804Hood 10 Flow VoltageTSI: do not overwriteVRead
AV805Hood 11 Flow VoltageTSI: do not overwriteVRead
AV806Hood 12 Flow VoltageTSI: do not overwriteVRead
AV807Hood 13 Flow VoltageTSI: do not overwriteVRead
AV808Hood 14 Flow VoltageTSI: do not overwriteVRead
AV809Hood 15 Flow VoltageTSI: do not overwriteVRead
AV810Hood 16 Flow VoltageTSI: do not overwriteVRead
AV811Hood 17 Flow VoltageTSI: do not overwriteVRead
AV812Hood 18 Flow VoltageTSI: do not overwriteVRead
AV813Hood 19 Flow VoltageTSI: do not overwriteVRead
AV814Hood 20 Flow VoltageTSI: do not overwriteVRead
AV815Hood 8 Venturi Minimum FlowCFMWrite
AV816Hood 8 Venturi Maximum FlowCFMWrite
AV817Hood 8 Venturi LOM ESC TimesWrite
AV818Hood 8 Linear Duct Areaft²Write
AV819Hood 8 Linear Top Velocityft/minWrite
AV820Hood 8 Linear Signal MinimumVWrite
AV821Hood 8 Linear Signal MaximumVWrite
AV822Hood 8 Pitot Sensor ZeroTSI: do not overwriteVRead
AV823Hood 8 Transducer Signal MinimumVWrite
AV824Hood 8 Transducer Signal MaximumVWrite
AV825Hood 8 Pitot Duct Areaft²Write
AV826Hood 8 Transducer Sensor Maximumin. W.C.Write
AV827Hood 8 Pitot Low Cal FlowCFMWrite
AV828Hood 8 Pitot High Cal FlowCFMWrite
AV829Hood 8 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV830Hood 8 Pitot High Cal VoltageTSI: do not overwriteVRead
AV831Hood 8 TP Min FlowCFMWrite
AV832Hood 8 TP Max FlowCFMWrite
AV833Hood 9 Venturi Minimum FlowCFMWrite
AV834Hood 9 Venturi Maximum FlowCFMWrite
AV835Hood 9 Venturi LOM ESC TimesWrite
AV836Hood 9 Linear Duct Areaft²Write
AV837Hood 9 Linear Top Velocityft/minWrite
AV838Hood 9 Linear Signal MinimumVWrite
AV839Hood 9 Linear Signal MaximumVWrite
AV840Hood 9 Pitot Sensor ZeroTSI: do not overwriteVRead
AV841Hood 9 Transducer Signal MinimumVWrite
AV842Hood 9 Transducer Signal MaximumVWrite
AV843Hood 9 Pitot Duct Areaft²Write
AV844Hood 9 Transducer Sensor Maximumin. W.C.Write
AV845Hood 9 Pitot Low Cal FlowCFMWrite
AV846Hood 9 Pitot High Cal FlowCFMWrite
AV847Hood 9 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV848Hood 9 Pitot High Cal VoltageTSI: do not overwriteVRead
AV849Hood 9 TP Min FlowCFMWrite
AV850Hood 9 TP Max FlowCFMWrite
AV851Hood 10 Venturi Minimum FlowCFMWrite
AV852Hood 10 Venturi Maximum FlowCFMWrite
AV853Hood 10 Venturi LOM ESC TimesWrite
AV854Hood 10 Linear Duct Areaft²Write
AV855Hood 10 Linear Top Velocityft/minWrite
AV856Hood 10 Linear Signal MinimumVWrite
AV857Hood 10 Linear Signal MaximumVWrite
AV858Hood 10 Pitot Sensor ZeroTSI: do not overwriteVRead
AV859Hood 10 Transducer Signal MinimumVWrite
AV860Hood 10 Transducer Signal MaximumVWrite
AV861Hood 10 Pitot Duct Areaft²Write
AV862Hood 10 Transducer Sensor Maximumin. W.C.Write
AV863Hood 10 Pitot Low Cal FlowCFMWrite
AV864Hood 10 Pitot High Cal FlowCFMWrite
AV865Hood 10 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV866Hood 10 Pitot High Cal VoltageTSI: do not overwriteVRead
AV867Hood 10 TP Min FlowCFMWrite
AV868Hood 10 TP Max FlowCFMWrite
AV869Hood 11 Venturi Minimum FlowCFMWrite
AV870Hood 11 Venturi Maximum FlowCFMWrite
AV871Hood 11 Venturi LOM ESC TimesWrite
AV872Hood 11 Linear Duct Areaft²Write
AV873Hood 11 Linear Top Velocityft/minWrite
AV874Hood 11 Linear Signal MinimumVWrite
AV875Hood 11 Linear Signal MaximumVWrite
AV876Hood 11 Pitot Sensor ZeroTSI: do not overwriteVRead
AV877Hood 11 Transducer Signal MinimumVWrite
AV878Hood 11 Transducer Signal MaximumVWrite
AV879Hood 11 Pitot Duct Areaft²Write
AV880Hood 11 Transducer Sensor Maximumin. W.C.Write
AV881Hood 11 Pitot Low Cal FlowCFMWrite
AV882Hood 11 Pitot High Cal FlowCFMWrite
AV883Hood 11 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV884Hood 11 Pitot High Cal VoltageTSI: do not overwriteVRead
AV885Hood 11 TP Min FlowCFMWrite
AV886Hood 11 TP Max FlowCFMWrite
AV887Hood 12 Venturi Minimum FlowCFMWrite
AV888Hood 12 Venturi Maximum FlowCFMWrite
AV889Hood 12 Venturi LOM ESC TimesWrite
AV890Hood 12 Linear Duct Areaft²Write
AV891Hood 12 Linear Top Velocityft/minWrite
AV892Hood 12 Linear Signal MinimumVWrite
AV893Hood 12 Linear Signal MaximumVWrite
AV894Hood 12 Pitot Sensor ZeroTSI: do not overwriteVRead
AV895Hood 12 Transducer Signal MinimumVWrite
AV896Hood 12 Transducer Signal MaximumVWrite
AV897Hood 12 Pitot Duct Areaft²Write
AV898Hood 12 Transducer Sensor Maximumin. W.C.Write
AV899Hood 12 Pitot Low Cal FlowCFMWrite
AV900Hood 12 Pitot High Cal FlowCFMWrite
AV901Hood 12 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV902Hood 12 Pitot High Cal VoltageTSI: do not overwriteVRead
AV903Hood 12 TP Min FlowCFMWrite
AV904Hood 12 TP Max FlowCFMWrite
AV905Hood 13 Venturi Minimum FlowCFMWrite
AV906Hood 13 Venturi Maximum FlowCFMWrite
AV907Hood 13 Venturi LOM ESC TimesWrite
AV908Hood 13 Linear Duct Areaft²Write
AV909Hood 13 Linear Top Velocityft/minWrite
AV910Hood 13 Linear Signal MinimumVWrite
AV911Hood 13 Linear Signal MaximumVWrite
AV912Hood 13 Pitot Sensor ZeroTSI: do not overwriteVRead
AV913Hood 13 Transducer Signal MinimumVWrite
AV914Hood 13 Transducer Signal MaximumVWrite
AV915Hood 13 Pitot Duct Areaft²Write
AV916Hood 13 Transducer Sensor Maximumin. W.C.Write
AV917Hood 13 Pitot Low Cal FlowCFMWrite
AV918Hood 13 Pitot High Cal FlowCFMWrite
AV919Hood 13 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV920Hood 13 Pitot High Cal VoltageTSI: do not overwriteVRead
AV921Hood 13 TP Min FlowCFMWrite
AV922Hood 13 TP Max FlowCFMWrite
AV923Hood 14 Venturi Minimum FlowCFMWrite
AV924Hood 14 Venturi Maximum FlowCFMWrite
AV925Hood 14 Venturi LOM ESC TimesWrite
AV926Hood 14 Linear Duct Areaft²Write
AV927Hood 14 Linear Top Velocityft/minWrite
AV928Hood 14 Linear Signal MinimumVWrite
AV929Hood 14 Linear Signal MaximumVWrite
AV930Hood 14 Pitot Sensor ZeroTSI: do not overwriteVRead
AV931Hood 14 Transducer Signal MinimumVWrite
AV932Hood 14 Transducer Signal MaximumVWrite
AV933Hood 14 Pitot Duct Areaft²Write
AV934Hood 14 Transducer Sensor Maximumin. W.C.Write
AV935Hood 14 Pitot Low Cal FlowCFMWrite
AV936Hood 14 Pitot High Cal FlowCFMWrite
AV937Hood 14 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV938Hood 14 Pitot High Cal VoltageTSI: do not overwriteVRead
AV939Hood 14 TP Min FlowCFMWrite
AV940Hood 14 TP Max FlowCFMWrite
AV941Hood 15 Venturi Minimum FlowCFMWrite
AV942Hood 15 Venturi Maximum FlowCFMWrite
AV943Hood 15 Venturi LOM ESC TimesWrite
AV944Hood 15 Linear Duct Areaft²Write
AV945Hood 15 Linear Top Velocityft/minWrite
AV946Hood 15 Linear Signal MinimumVWrite
AV947Hood 15 Linear Signal MaximumVWrite
AV948Hood 15 Pitot Sensor ZeroTSI: do not overwriteVRead
AV949Hood 15 Transducer Signal MinimumVWrite
AV950Hood 15 Transducer Signal MaximumVWrite
AV951Hood 15 Pitot Duct Areaft²Write
AV952Hood 15 Transducer Sensor Maximumin. W.C.Write
AV953Hood 15 Pitot Low Cal FlowCFMWrite
AV954Hood 15 Pitot High Cal FlowCFMWrite
AV955Hood 15 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV956Hood 15 Pitot High Cal VoltageTSI: do not overwriteVRead
AV957Hood 15 TP Min FlowCFMWrite
AV958Hood 15 TP Max FlowCFMWrite
AV959Hood 16 Venturi Minimum FlowCFMWrite
AV960Hood 16 Venturi Maximum FlowCFMWrite
AV961Hood 16 Venturi LOM ESC TimesWrite
AV962Hood 16 Linear Duct Areaft²Write
AV963Hood 16 Linear Top Velocityft/minWrite
AV964Hood 16 Linear Signal MinimumVWrite
AV965Hood 16 Linear Signal MaximumVWrite
AV966Hood 16 Pitot Sensor ZeroTSI: do not overwriteVRead
AV967Hood 16 Transducer Signal MinimumVWrite
AV968Hood 16 Transducer Signal MaximumVWrite
AV969Hood 16 Pitot Duct Areaft²Write
AV970Hood 16 Transducer Sensor Maximumin. W.C.Write
AV971Hood 16 Pitot Low Cal FlowCFMWrite
AV972Hood 16 Pitot High Cal FlowCFMWrite
AV973Hood 16 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV974Hood 16 Pitot High Cal VoltageTSI: do not overwriteVRead
AV975Hood 16 TP Min FlowCFMWrite
AV976Hood 16 TP Max FlowCFMWrite
AV977Hood 17 Venturi Minimum FlowCFMWrite
AV978Hood 17 Venturi Maximum FlowCFMWrite
AV979Hood 17 Venturi LOM ESC TimesWrite
AV980Hood 17 Linear Duct Areaft²Write
AV981Hood 17 Linear Top Velocityft/minWrite
AV982Hood 17 Linear Signal MinimumVWrite
AV983Hood 17 Linear Signal MaximumVWrite
AV984Hood 17 Pitot Sensor ZeroTSI: do not overwriteVRead
AV985Hood 17 Transducer Signal MinimumVWrite
AV986Hood 17 Transducer Signal MaximumVWrite
AV987Hood 17 Pitot Duct Areaft²Write
AV988Hood 17 Transducer Sensor Maximumin. W.C.Write
AV989Hood 17 Pitot Low Cal FlowCFMWrite
AV990Hood 17 Pitot High Cal FlowCFMWrite
AV991Hood 17 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV992Hood 17 Pitot High Cal VoltageTSI: do not overwriteVRead
AV993Hood 17 TP Min FlowCFMWrite
AV994Hood 17 TP Max FlowCFMWrite
AV995Hood 18 Venturi Minimum FlowCFMWrite
AV996Hood 18 Venturi Maximum FlowCFMWrite
AV997Hood 18 Venturi LOM ESC TimesWrite
AV998Hood 18 Linear Duct Areaft²Write
AV999Hood 18 Linear Top Velocityft/minWrite
AV1000Hood 18 Linear Signal MinimumVWrite
AV1001Hood 18 Linear Signal MaximumVWrite
AV1002Hood 18 Pitot Sensor ZeroTSI: do not overwriteVRead
AV1003Hood 18 Transducer Signal MinimumVWrite
AV1004Hood 18 Transducer Signal MaximumVWrite
AV1005Hood 18 Pitot Duct Areaft²Write
AV1006Hood 18 Transducer Sensor Maximumin. W.C.Write
AV1007Hood 18 Pitot Low Cal FlowCFMWrite
AV1008Hood 18 Pitot High Cal FlowCFMWrite
AV1009Hood 18 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV1010Hood 18 Pitot High Cal VoltageTSI: do not overwriteVRead
AV1011Hood 18 TP Min FlowCFMWrite
AV1012Hood 18 TP Max FlowCFMWrite
AV1013Hood 19 Venturi Minimum FlowCFMWrite
AV1014Hood 19 Venturi Maximum FlowCFMWrite
AV1015Hood 19 Venturi LOM ESC TimesWrite
AV1016Hood 19 Linear Duct Areaft²Write
AV1017Hood 19 Linear Top Velocityft/minWrite
AV1018Hood 19 Linear Signal MinimumVWrite
AV1019Hood 19 Linear Signal MaximumVWrite
AV1020Hood 19 Pitot Sensor ZeroTSI: do not overwriteVRead
AV1021Hood 19 Transducer Signal MinimumVWrite
AV1022Hood 19 Transducer Signal MaximumVWrite
AV1023Hood 19 Pitot Duct Areaft²Write
AV1024Hood 19 Transducer Sensor Maximumin. W.C.Write
AV1025Hood 19 Pitot Low Cal FlowCFMWrite
AV1026Hood 19 Pitot High Cal FlowCFMWrite
AV1027Hood 19 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV1028Hood 19 Pitot High Cal VoltageTSI: do not overwriteVRead
AV1029Hood 19 TP Min FlowCFMWrite
AV1030Hood 19 TP Max FlowCFMWrite
AV1031Hood 20 Venturi Minimum FlowCFMWrite
AV1032Hood 20 Venturi Maximum FlowCFMWrite
AV1033Hood 20 Venturi LOM ESC TimesWrite
AV1034Hood 20 Linear Duct Areaft²Write
AV1035Hood 20 Linear Top Velocityft/minWrite
AV1036Hood 20 Linear Signal MinimumVWrite
AV1037Hood 20 Linear Signal MaximumVWrite
AV1038Hood 20 Pitot Sensor ZeroTSI: do not overwriteVRead
AV1039Hood 20 Transducer Signal MinimumVWrite
AV1040Hood 20 Transducer Signal MaximumVWrite
AV1041Hood 20 Pitot Duct Areaft²Write
AV1042Hood 20 Transducer Sensor Maximumin. W.C.Write
AV1043Hood 20 Pitot Low Cal FlowCFMWrite
AV1044Hood 20 Pitot High Cal FlowCFMWrite
AV1045Hood 20 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV1046Hood 20 Pitot High Cal VoltageTSI: do not overwriteVRead
AV1047Hood 20 TP Min FlowCFMWrite
AV1048Hood 20 TP Max FlowCFMWrite
AV1049Hood 8 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1050Hood 8 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1051Hood 9 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1052Hood 9 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1053Hood 10 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1054Hood 10 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1055Hood 11 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1056Hood 11 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1057Hood 12 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1058Hood 12 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1059Hood 13 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1060Hood 13 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1061Hood 14 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1062Hood 14 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1063Hood 15 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1064Hood 15 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1065Hood 16 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1066Hood 16 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1067Hood 17 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1068Hood 17 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1069Hood 18 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1070Hood 18 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1071Hood 19 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1072Hood 19 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1073Hood 20 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1074Hood 20 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1075Hood 8 Flow K factorWrite
AV1076Hood 9 Flow K factorWrite
AV1077Hood 10 Flow K factorWrite
AV1078Hood 11 Flow K factorWrite
AV1079Hood 12 Flow K factorWrite
AV1080Hood 13 Flow K factorWrite
AV1081Hood 14 Flow K factorWrite
AV1082Hood 15 Flow K factorWrite
AV1083Hood 16 Flow K factorWrite
AV1084Hood 17 Flow K factorWrite
AV1085Hood 18 Flow K factorWrite
AV1086Hood 19 Flow K factorWrite
AV1087Hood 20 Flow K factorWrite
AV1088Supply 1 Flow SetpointTSI: do not overwriteCFMRead
AV1089Supply 2 Flow SetpointTSI: do not overwriteCFMRead
AV1090Supply 3 Flow SetpointTSI: do not overwriteCFMRead
AV1091Supply 4 Flow SetpointTSI: do not overwriteCFMRead
AV1092Exhaust 1 Flow SetpointTSI: do not overwriteCFMRead
AV1093Exhaust 2 Flow SetpointTSI: do not overwriteCFMRead
AV1094Supply 5 Flow Proportional GainWrite
AV1095Supply 5 Flow Integral TimesWrite
AV1096Supply 5 Flow Speed%Write
AV1097Supply 5 Flow Sensitivity%Write
AV1098Supply 6 Flow Proportional GainWrite
AV1099Supply 6 Flow Integral TimesWrite
AV1100Supply 6 Flow Speed%Write
AV1101Supply 6 Flow Sensitivity%Write
AV1102Supply 5 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1103Supply 5 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1104Supply 5 Venturi Minimum FlowTSI: do not overwriteCFMRead
AV1105Supply 5 Venturi Minimum FlowTSI: do not overwriteCFMRead
AV1106Supply 5 Flow K FactorWrite
AV1107Supply 5 Venturi Setup Position%Write
AV1108Supply 5 Venturi LOM Esc TimesWrite
AV1109Supply 5 Linear Duct Areaft²Write
AV1110Supply 5 Linear Top Velocityft/minWrite
AV1111Supply 5 Linear Signal MinimumVWrite
AV1112Supply 5 Linear Signal MaximumVWrite
AV1113Supply 5 Pitot Sensor ZeroVWrite
AV1114Supply 5 Pitot Low Cal Pos%Write
AV1115Supply 5 Transducer Signal MinimumVWrite
AV1116Supply 5 Pitot High Cal Pos%Write
AV1117Supply 5 Transducer Signal MaximumVWrite
AV1118Supply 5 Pitot Low Cal FlowTSI: do not overwriteCFMRead
AV1119Supply 5 Pitot Duct Areaft²Write
AV1120Supply 5 Pitot High Cal FlowTSI: do not overwriteCFMRead
AV1121Supply 5 Transducer Sensor Maximumin. W.C.Write
AV1122Supply 6 Pitot Uncal Low Cal FlowTSI: do not overwriteCFMRead
AV1123Supply 6 Pitot Uncal High Cal FlowTSI: do not overwriteCFMRead
AV1124Supply 6 Venturi Minimum FlowTSI: do not overwriteCFMRead
AV1125Supply 6 Venturi Maximum FlowTSI: do not overwriteCFMRead
AV1126Supply 6 Flow K FactorWrite
AV1127Supply 6 Venturi Setup Position%Write
AV1128Supply 6 Venturi LOM Esc TimesWrite
AV1129Supply 6 Linear Duct Areaft²Write
AV1130Supply 6 Linear Top VelocityWrite
AV1131Supply 6 Linear Signal MinimumVWrite
AV1132Supply 6 Linear Signal MaximumVWrite
AV1133Supply 6 Pitot Sensor ZeroVWrite
AV1134Supply 6 Pitot Low Cal Pos%Write
AV1135Supply 6 Transducer Signal MinimumVWrite
AV1136Supply 6 Pitot High Cal Pos%Write
AV1137Supply 6 Transducer Signal MaximumVWrite
AV1138Supply 6 Pitot Low Cal FlowTSI: do not overwriteCFMRead
AV1139Supply 6 Pitot Duct Areaft²Write
AV1140Supply 6 Pitot High Cal FlowTSI: do not overwriteCFMRead
AV1141Supply 6 Transducer Sensor Maximumin. W.C.Write
AV1142Supply 5 Room Temp Offset°FWrite
AV1143Supply 6 Room Temp Offset°FWrite
AV1144Supply 5 Room Temp Adj Signal MinimumVWrite
AV1145Supply 5 Room Temp Adj Signal MaximumVWrite
AV1146Supply 5 Room Temp Adj Sensor Minimum°FWrite
AV1147Supply 5 Room Temp Adj Sensor Maximum°FWrite
AV1148Supply 6 Room Temp Adj Signal MinimumVWrite
AV1149Supply 6 Room Temp Adj Signal MaximumVWrite
AV1150Supply 6 Room Temp Adj Sensor Minimum°FWrite
AV1151Supply 6 Room Temp Adj Sensor Maximum°FWrite
AV1152Supply 5 Reheat/Cooling DelaysWrite
AV1153Supply 6 Reheat/Cooling DelaysWrite
AV1154Supply 5 Room Temp Signal MinimumVWrite
AV1155Supply 5 Room Temp Signal MaximumVWrite
AV1156Supply 5 Room Temp Sensor Minimum°FWrite
AV1157Supply 5 Room Temp Sensor Maximum°FWrite
AV1158Supply 6 Room Temp Signal MinimumVWrite
AV1159Supply 6 Room Temp Signal MaximumVWrite
AV1160Supply 6 Room Temp Sensor Minimum°FWrite
AV1161Supply 6 Room Temp Sensor Maximum°FWrite
AV1162Supply 5 Temp Throttling Range°FWrite
AV1163Supply 6 Temp Throttling Range°FWrite
AV1164Supply 5 Temp Integral TimesWrite
AV1165Supply 6 Temp Integral TimesWrite
AV1166Current Supply 5 Minimum Flow SetpointTSI: do not overwriteCFMRead
AV1167Current Supply 5 Minimum FlowTSI: do not overwriteCFMRead
AV1168Current Supply 5 Cooling FlowTSI: do not overwriteCFMRead
AV1169Current Supply 5 Heating FlowTSI: do not overwriteCFMRead
AV1170Current Supply 5 Maximum FlowTSI: do not overwriteCFMRead
AV1171Current Supply 6 Minimum Flow SetpointTSI: do not overwriteCFMRead
AV1172Current Supply 6 Minimum FlowTSI: do not overwriteCFMRead
AV1173Current Supply 6 Cooling FlowTSI: do not overwriteCFMRead
AV1174Current Supply 6 Heating FlowTSI: do not overwriteCFMRead
AV1175Current Supply 6 Maximum FlowTSI: do not overwriteCFMRead
AV1176Current Supply 5 Heat SetpointTSI: do not overwrite°FRead
AV1177Current Supply 5 Cool SetpointTSI: do not overwrite°FRead
AV1178Current Supply 6 Heat SetpointTSI: do not overwrite°FRead
AV1179Current Supply 6 Cool SetpointTSI: do not overwrite°FRead
AV1180Supply 5 FlowTSI: do not overwriteCFMRead
AV1181Supply 6 FlowTSI: do not overwriteCFMRead
AV1182Current Supply 5 Temperature Control PositionTSI: do not overwrite%Read
AV1183Current Supply 5 Flow Control PositionTSI: do not overwrite%Read
AV1184Current Supply 6 Temperature Control PositionTSI: do not overwrite%Read
AV1185Current Supply 6 Flow Control PositionTSI: do not overwrite%Read
AV1186Supply 5 Room TempTSI: do not overwrite°FRead
AV1187Supply 6 Room TempTSI: do not overwrite°FRead
AV1188Supply 5 Room Temp AdjTSI: do not overwrite°FRead
AV1189Supply 6 Room Temp AdjTSI: do not overwrite°FRead
AV1190Supply 5 Flow VoltageTSI: do not overwriteVRead
AV1191Supply 6 Flow VoltageTSI: do not overwriteVRead
AV1192Supply 5 Room Temp VoltageTSI: do not overwriteVRead
AV1193Supply 6 Room Temp VoltageTSI: do not overwriteVRead
AV1194Supply 5 Room Temp Adjustment VoltageTSI: do not overwriteVRead
AV1195Supply 6 Room Temp Adjustment VoltageTSI: do not overwriteVRead
AV1196Supply 5 Flow SetpointCFMWrite
AV1197Supply 6 Flow SetpointCFMWrite
AV1198Supply 5 Minimum FlowCFMWrite
AV1199Supply 5 Cooling FlowCFMWrite
AV1200Supply 5 Heating FlowCFMWrite
AV1201Supply 5 Maximum FlowCFMWrite
AV1202Supply 5 Minimum Position%Write
AV1203Supply 5 Maximum Position%Write
AV1204Supply 5 Emergency FlowCFMWrite
AV1205Supply 5 Shutdown FlowCFMWrite
AV1206Supply 6 Minimum FlowCFMWrite
AV1207Supply 6 Cooling FlowCFMWrite
AV1208Supply 6 Heating FlowCFMWrite
AV1209Supply 6 Maximum FlowCFMWrite
AV1210Supply 6 Minimum Position%Write
AV1211Supply 6 Maximum Position%Write
AV1212Supply 6 Emergency FlowCFMWrite
AV1213Supply 6 Shutdown FlowCFMWrite
AV1214Supply 5 Heat Setpoint°FWrite
AV1215Supply 5 Cool Setpoint°FWrite
AV1216Supply 6 Heat Setpoint°FWrite
AV1217Supply 6 Cool Setpoint°FWrite
AV1218Supply 5 Low Flow AlarmCFMWrite
AV1219Supply 5 High Flow AlarmCFMWrite
AV1220Supply 6 Low Flow AlarmCFMWrite
AV1221Supply 6 High Flow AlarmCFMWrite
AV1222Supply 5 Low Temperature Alarm°FWrite
AV1223Supply 5 High Temperature Alarm°FWrite
AV1224Supply 6 Low Temperature Alarm°FWrite
AV1225Supply 6 High Temperature Alarm°FWrite
AV1226Supply 5 Shutdown Low Flow AlarmCFMWrite
AV1227Supply 5 Shutdown High Flow AlarmCFMWrite
AV1228Supply 6 Shutdown Low Flow AlarmCFMWrite
AV1229Supply 6 Shutdown High Flow AlarmCFMWrite
AV1230Supply 5 Flow ChangeCFMWrite
AV1231Supply 6 Flow ChangeCFMWrite
AV1232Supply 5 Flow Input NumberTSI: do not overwriteRead
AV1233Supply 5 Room Temp Input NumberTSI: do not overwriteRead
AV1234Supply 5 Room Temp Adj Input NumberTSI: do not overwriteRead
AV1235Supply 6 Flow Input NumberTSI: do not overwriteRead
AV1236Supply 6 Room Temp Input NumberTSI: do not overwriteRead
AV1237Supply 6 Room Temp Adj Input NumberTSI: do not overwriteRead
AV1238Current Supply 5 Low Flow AlarmTSI: do not overwriteCFMRead
AV1239Current Supply 5 High Flow AlarmTSI: do not overwriteCFMRead
AV1240Current Supply 6 Low Flow AlarmTSI: do not overwriteCFMRead
AV1241Current Supply 6 High Flow AlarmTSI: do not overwriteCFMRead
AV1242Current Supply 5 Low Temperature AlarmTSI: do not overwrite°FRead
AV1243Current Supply 5 High Temperature AlarmTSI: do not overwrite°FRead
AV1244Current Supply 6 Low Temperature AlarmTSI: do not overwrite°FRead
AV1245Current Supply 6 High Temperature AlarmTSI: do not overwrite°FRead
AV1246Supply 5 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV1247Supply 5 Pitot High Cal VoltageTSI: do not overwriteVRead
AV1248Supply 6 Pitot Low Cal VoltageTSI: do not overwriteVRead
AV1249Supply 6 Pitot High Cal VoltageTSI: do not overwriteVRead
AV1250Supply 5 DAT Offset°FWrite
AV1251Supply 6 DAT Offset°FWrite
AV1252Supply 5 Unocc Minimum FlowCFMWrite
AV1253Supply 5 Unocc Cooling FlowCFMWrite
AV1254Supply 5 Unocc Heating FlowCFMWrite
AV1255Supply 5 Unocc Maximum FlowCFMWrite
AV1256Supply 6 Unocc Minimum FlowCFMWrite
AV1257Supply 6 Unocc Cooling FlowCFMWrite
AV1258Supply 6 Unocc Heating FlowCFMWrite
AV1259Supply 6 Unocc Maximum FlowCFMWrite
AV1260Supply 5 Unocc Heat Setpoint°FWrite
AV1261Supply 5 Unocc Cool Setpoint°FWrite
AV1262Supply 5 DAT Delta°FWrite
AV1263Supply 6 Unocc Heat Setpoint°FWrite
AV1264Supply 6 Unocc Cool Setpoint°FWrite
AV1265Supply 6 DAT Delta°FWrite
AV1266Supply 5 Unocc Low Flow AlarmCFMWrite
AV1267Supply 5 Unocc High Flow AlarmCFMWrite
AV1268Supply 6 Unocc Low Flow AlarmCFMWrite
AV1269Supply 6 Unocc High Flow AlarmCFMWrite
AV1270Supply 5 Unocc Low Temperature Alarm°FWrite
AV1271Supply 5 Unocc High Temperature Alarm°FWrite
AV1272Supply 6 Unocc Low Temperature Alarm°FWrite
AV1273Supply 6 Unocc High Temperature Alarm°FWrite
AV1274Supply 5 High DAT Alarm°FWrite
AV1275Supply 6 High DAT Alarm°FWrite
AV1276Supply 5 DAT Signal MinimumVWrite
AV1277Supply 5 DAT Signal MaximumVWrite
AV1278Supply 5 DAT Sensor Minimum°FWrite
AV1279Supply 5 DAT Sensor Maximum°FWrite
AV1280Supply 6 DAT Signal MinimumVWrite
AV1281Supply 6 DAT Signal MaximumVWrite
AV1282Supply 6 DAT Sensor Minimum°FWrite
AV1283Supply 6 DAT Sensor Maximum°FWrite
AV1284Supply 5 DAT Input NumberTSI: do not overwriteRead
AV1285Supply 5 Occupancy Input NumberTSI: do not overwriteRead
AV1286Supply 6 DAT Input NumberTSI: do not overwriteRead
AV1287Supply 6 Occupancy Input NumberTSI: do not overwriteRead
AV1288Supply 5 DATTSI: do not overwrite°FRead
AV1289Supply 6 DATTSI: do not overwrite°FRead
AV1290Supply 5 DAT VoltageTSI: do not overwriteVRead
AV1291Supply 6 DAT VoltageTSI: do not overwriteVRead
BV1Reset VariablesWrite0=No, 1=Yes
BV2Reset ControlWrite0=No, 1=Yes
BV3Supply 1 Flow Control ModeWrite0=Auto, 1=Manual
BV4Supply 2 Flow Control ModeWrite0=Auto, 1=Manual
BV5Supply 3 Flow Control ModeWrite0=Auto, 1=Manual
BV6Supply 4 Flow Control ModeWrite0=Auto, 1=Manual
BV7Supply 1 Temp Control ModeWrite0=Auto, 1=Manual
BV8Supply 2 Temp Control ModeWrite0=Auto, 1=Manual
BV9Supply 3 Temp Control ModeWrite0=Auto, 1=Manual
BV10Supply 4 Temp Control ModeWrite0=Auto, 1=Manual
BV11Exhaust 1 Flow Control ModeWrite0=Auto, 1=Manual
BV12Exhaust 2 Flow Control ModeWrite0=Auto, 1=Manual
BV15Supply 1 Balancer ModeWrite0=Off, 1=On
BV16Supply 2 Balancer ModeWrite0=Off, 1=On
BV17Supply 3 Balancer ModeWrite0=Off, 1=On
BV18Supply 4 Balancer ModeWrite0=Off, 1=On
BV19Exhaust 1 Balancer ModeWrite0=Off, 1=On
BV20Exhaust 2 Balancer ModeWrite0=Off, 1=On
BV21Door ModeWrite0=Closed, 1=Open
BVmin22Emergency ModeWrite0=Inactive, 1=Active
BV23Shutdown ModeWrite0=Inactive, 1=Active
BVmin24Supply 1 Occupancy ModeWrite0=Occupied, 1=Unoccupied
BV25Supply 2 Occupancy ModeWrite0=Occupied, 1=Unoccupied
BV26Supply 3 Occupancy ModeWrite0=Occupied, 1=Unoccupied
BV27Supply 4 Occupancy ModeWrite0=Occupied, 1=Unoccupied
BV28Supply 1 Venturi VisibleWrite
BV29Supply 1 Linear VisibleWrite
BV30Supply 1 Pitot VisibleWrite
BV31Supply 2 Venturi VisibleWrite
BV32Supply 2 Linear VisibleWrite
BV33Supply 2 Pitot VisibleWrite
BV34Supply 3 Venturi VisibleWrite
BV35Supply 3 Linear VisibleWrite
BV36Supply 3 Pitot VisibleWrite
BV37Supply 4 Venturi VisibleWrite
BV38Supply 4 Linear VisibleWrite
BV39Supply 4 Pitot VisibleWrite
BV40Exhaust 1 Venturi VisibleWrite
BV41Exhaust 1 Linear VisibleWrite
BV42Exhaust 1 Pitot VisibleWrite
BV43Exhaust 2 Venturi VisibleWrite
BV44Exhaust 2 Linear VisibleWrite
BV45Exhaust 2 Pitot VisibleWrite
BV46Supply 1 DAT RTD VisibleWrite
BV47Supply 1 DAT Voltage VisibleWrite
BV48Supply 2 DAT RTD VisibleWrite
BV49Supply 2 DAT Voltage VisibleWrite
BV50Supply 3 DAT RTD VisibleWrite
BV51Supply 3 DAT Voltage VisibleWrite
BV52Supply 4 DAT RTD VisibleWrite
BV53Supply 4 DAT Voltage VisibleWrite
BV54Room Pressure TTW VisibleWrite
BV55Room Pressure Transducer VisibleWrite
BV56Hood 1 Venturi VisibleWrite
BV57Hood 1 Linear VisibleWrite
BV58Hood 1 Pitot VisibleWrite
BV59Hood 1 Two Position VisibleWrite
BV60Hood 2 Venturi VisibleWrite
BV61Hood 2 Linear VisibleWrite
BV62Hood 2 Pitot VisibleWrite
BV63Hood 2 Two Position VisibleWrite
BV64Hood 3 Venturi VisibleWrite
BV65Hood 3 Linear VisibleWrite
BV66Hood 3 Pitot VisibleWrite
BV67Hood 3 Two Position VisibleWrite
BV68Hood 4 Venturi VisibleWrite
BV69Hood 4 Linear VisibleWrite
BV70Hood 4 Pitot VisibleWrite
BV71Hood 4 Two Position VisibleWrite
BV72Hood 5 Venturi VisibleWrite
BV73Hood 5 Linear VisibleWrite
BV74Hood 5 Pitot VisibleWrite
BV75Hood 5 Two Position VisibleWrite
BV76Hood 6 Venturi VisibleWrite
BV77Hood 6 Linear VisibleWrite
BV78Hood 6 Pitot VisibleWrite
BV79Hood 6 Two Position VisibleWrite
BV80Hood 7 Venturi VisibleWrite
BV81Hood 7 Linear VisibleWrite
BV82Hood 7 Pitot VisibleWrite
BV83Hood 7 Two Position VisibleWrite
BV84Door Switch DirectionWrite0=Direct, 1=Reverse
BV85Emergency Switch DirectionWrite0=Direct, 1=Reverse
BV86Shutdown Switch DirectionWrite0=Direct, 1=Reverse
BV87Supply 1 Occupancy DirectionWrite0=Direct, 1=Reverse
BV88Supply 2 Occupancy DirectionWrite0=Direct, 1=Reverse
BV89Supply 3 Occupancy DirectionWrite0=Direct, 1=Reverse
BV90Supply 4 Occupancy DirectionWrite0=Direct, 1=Reverse
BV91Supply 1 Reheat ModeWrite
BV92Supply 2 Reheat ModeWrite
BV93Supply 3 Reheat ModeWrite
BV94Supply 1 PID Control ModeWrite
BV95Supply 2 PID Control ModeWrite
BV96Supply 3 PID Control ModeWrite
BV97Supply 4 PID Control ModeWrite
BV98Exhaust 1 PID Control ModeWrite
BV99Exhaust 2 PID Control ModeWrite
BV100Hood 8 Venturi VisibleWrite
BV101Hood 8 Linear VisibleWrite
BV102Hood 8 Pitot VisibleWrite
BV103Hood 8 Two Position VisibleWrite
BV104Hood 9 Venturi VisibleWrite
BV105Hood 9 Linear VisibleWrite
BV106Hood 9 Pitot VisibleWrite
BV107Hood 9 Two Position VisibleWrite
BV108Hood 10 Venturi VisibleWrite
BV109Hood 10 Linear VisibleWrite
BV110Hood 10 Pitot VisibleWrite
BV111Hood 10 Two Position VisibleWrite
BV112Hood 11 Venturi VisibleWrite
BV113Hood 11 Linear VisibleWrite
BV114Hood 11 Pitot VisibleWrite
BV115Hood 11 Two Position VisibleWrite
BV116Hood 12 Venturi VisibleWrite
BV117Hood 12 Linear VisibleWrite
BV118Hood 12 Pitot VisibleWrite
BV119Hood 12 Two Position VisibleWrite
BV120Hood 13 Venturi VisibleWrite
BV121Hood 13 Linear VisibleWrite
BV122Hood 13 Pitot VisibleWrite
BV123Hood 13 Two Position VisibleWrite
BV124Hood 14 Venturi VisibleWrite
BV125Hood 14 Linear VisibleWrite
BV126Hood 14 Pitot VisibleWrite
BV127Hood 14 Two Position VisibleWrite
BV128Hood 15 Venturi VisibleWrite
BV129Hood 15 Linear VisibleWrite
BV130Hood 15 Pitot VisibleWrite
BV131Hood 15 Two Position VisibleWrite
BV132Hood 16 Venturi VisibleWrite
BV133Hood 16 Linear VisibleWrite
BV134Hood 16 Pitot VisibleWrite
BV135Hood 16 Two Position VisibleWrite
BV136Hood 17 Venturi VisibleWrite
BV137Hood 17 Linear VisibleWrite
BV138Hood 17 Pitot VisibleWrite
BV139Hood 17 Two Position VisibleWrite
BV140Hood 18 Venturi VisibleWrite
BV141Hood 18 Linear VisibleWrite
BV142Hood 18 Pitot VisibleWrite
BV143Hood 18 Two Position VisibleWrite
BV144Hood 19 Venturi VisibleWrite
BV145Hood 19 Linear VisibleWrite
BV146Hood 19 Pitot VisibleWrite
BV147Hood 19 Two Position VisibleWrite
BV148Hood 20 Venturi VisibleWrite
BV149Hood 20 Linear VisibleWrite
BV150Hood 20 Pitot VisibleWrite
BV151Hood 20 Two Position VisibleWrite
BV152Supply 4 Reheat ModeWrite
BV153Hood 1 TP Max Flow SignalWrite0=Open, 1=Closed
BV154Hood 2 TP Max Flow SignalWrite0=Open, 1=Closed
BV155Hood 3 TP Max Flow SignalWrite0=Open, 1=Closed
BV156Hood 4 TP Max Flow SignalWrite0=Open, 1=Closed
BV157Hood 5 TP Max Flow SignalWrite0=Open, 1=Closed
BV158Hood 6 TP Max Flow SignalWrite0=Open, 1=Closed
BV159Hood 7 TP Max Flow SignalWrite0=Open, 1=Closed
BV160Hood 8 TP Max Flow SignalWrite0=Open, 1=Closed
BV161Hood 9 TP Max Flow SignalWrite0=Open, 1=Closed
BV162Hood 10 TP Max Flow SignalWrite0=Open, 1=Closed
BV163Hood 11 TP Max Flow SignalWrite0=Open, 1=Closed
BV164Hood 12 TP Max Flow SignalWrite0=Open, 1=Closed
BV165Hood 13 TP Max Flow SignalWrite0=Open, 1=Closed
BV166Hood 14 TP Max Flow SignalWrite0=Open, 1=Closed
BV167Hood 15 TP Max Flow SignalWrite0=Open, 1=Closed
BV168Hood 16 TP Max Flow SignalWrite0=Open, 1=Closed
BV169Hood 17 TP Max Flow SignalWrite0=Open, 1=Closed
BV170Hood 18 TP Max Flow SignalWrite0=Open, 1=Closed
BV171Hood 19 TP Max Flow SignalWrite0=Open, 1=Closed
BV172Hood 20 TP Max Flow SignalWrite0=Open, 1=Closed
BV173Supply 1 Flow Control DirectionWrite0=Reverse, 1=Direct
BV174Supply 2 Flow Control DirectionWrite0=Reverse, 1=Direct
BV175Supply 3 Flow Control DirectionWrite0=Reverse, 1=Direct
BV176Supply 4 Flow Control DirectionWrite0=Reverse, 1=Direct
BV177Exhaust 1 Flow Control DirectionWrite0=Reverse, 1=Direct
BV178Exhaust 2 Flow Control DirectionWrite0=Reverse, 1=Direct
BV179Supply 1 Temp Control DirectionWrite0=Reverse, 1=Direct
BV180Supply 2 Temp Control DirectionWrite0=Reverse, 1=Direct
BV181Supply 3 Temp Control DirectionWrite0=Reverse, 1=Direct
BV182Supply 4 Temp Control DirectionWrite0=Reverse, 1=Direct
BV183Supply 1 Flow Control ActiveWrite
BV184Supply 2 Flow Control ActiveWrite
BV185Supply 3 Flow Control ActiveWrite
BV186Supply 4 Flow Control ActiveWrite
BV187Exhaust 1 Flow Control ActiveWrite
BV188Exhaust 2 Flow Control ActiveWrite
BV189Supply 1 Temp Control ActiveWrite
BV190Supply 2 Temp Control ActiveWrite
BV191Supply 3 Temp Control ActiveWrite
BV192Supply 4 Temp Control ActiveWrite
BV193Reset Output SelectionWrite
BV194Reconfigure OutputsWrite
BV195Supply 1 Flow Input ActiveWrite
BV196Supply 1 DAT Input ActiveWrite
BV197Supply 1 Room Temp Input ActiveWrite
BV198Supply 1 Temp Setp Input ActiveWrite
BV199Supply 1 Occupancy Input ActiveWrite
BV200Supply 2 Flow Input ActiveWrite
BV201Supply 2 DAT Input ActiveWrite
BV202Supply 2 Room Temp Input ActiveWrite
BV203Supply 2 Temp Setp Input ActiveWrite
BV204Supply 2 Occupancy Input ActiveWrite
BV205Supply 3 Flow Input ActiveWrite
BV206Supply 3 DAT Input ActiveWrite
BV207Supply 3 Room Temp Input ActiveWrite
BV208Supply 3 Temp Setp Input ActiveWrite
BV209Supply 3 Occupancy Input ActiveWrite
BV210Supply 4 Flow Input ActiveWrite
BV211Supply 4 DAT Input ActiveWrite
BV212Supply 4 Room Temp Input ActiveWrite
BV213Supply 4 Temp Setp Input ActiveWrite
BV214Supply 4 Occupancy Input ActiveWrite
BV215Exhaust 1 Flow Input ActiveWrite
BV216Exhaust 2 Flow Input ActiveWrite
BV217Hood 1 Flow Input ActiveWrite
BV218Hood 2 Flow Input ActiveWrite
BV219Hood 3 Flow Input ActiveWrite
BV220Hood 4 Flow Input ActiveWrite
BV221Hood 5 Flow Input ActiveWrite
BV222Hood 6 Flow Input ActiveWrite
BV223Hood 7 Flow Input ActiveWrite
BV224Room Pressure Input ActiveWrite
BV225Relative Humidity Input ActiveWrite
BV226Door Switch Input ActiveWrite
BV227Emergency Switch Input ActiveWrite
BV228Shutdown Switch Input ActiveWrite
BV229Hood 8 Flow Input ActiveWrite
BV230Hood 9 Flow Input ActiveWrite
BV231Hood 10 Flow Input ActiveWrite
BV232Hood 11 Flow Input ActiveWrite
BV233Hood 12 Flow Input ActiveWrite
BV234Hood 13 Flow Input ActiveWrite
BV235Hood 14 Flow Input ActiveWrite
BV236Hood 15 Flow Input ActiveWrite
BV237Hood 16 Flow Input ActiveWrite
BV238Hood 17 Flow Input ActiveWrite
BV239Hood 18 Flow Input ActiveWrite
BV240Hood 19 Flow Input ActiveWrite
BV241Hood 20 Flow Input ActiveWrite
BV242Supply 1 DAT Delta ActiveWrite
BV243Supply 2 DAT Delta ActiveWrite
BV244Supply 3 DAT Delta ActiveWrite
BV245Supply 4 DAT Delta ActiveWrite
BV246Exhaust ConfigurationWrite0=Unganged, 1=Ganged
BV247Reset Supply 1 Flow TuningWrite0=No, 1=Yes
BV248Reset Supply 2 Flow TuningWrite0=No, 1=Yes
BV249Reset Supply 3 Flow TuningWrite0=No, 1=Yes
BV250Reset Supply 4 Flow TuningWrite0=No, 1=Yes
BV251Reset Exhaust 1 Flow TuningWrite0=No, 1=Yes
BV252Reset Exhaust 2 Flow TuningWrite0=No, 1=Yes
BV253Supply 1 Room Temp RTD VisibleWrite0=No, 1=Yes
BV254Supply 1 Room Temp Voltage VisibleWrite0=No, 1=Yes
BV255Supply 2 Room Temp RTD VisibleWrite0=No, 1=Yes
BV256Supply 2 Room Temp Voltage VisibleWrite0=No, 1=Yes
BV257Supply 3 Room Temp RTD VisibleWrite0=No, 1=Yes
BV258Supply 3 Room Temp Voltage VisibleWrite0=No, 1=Yes
BV259Supply 4 Room Temp RTD VisibleWrite0=No, 1=Yes
BV260Supply 4 Room Temp Voltage VisibleWrite0=No, 1=Yes
BV261Reset Supply 5 Flow TuningWrite0=No, 1=Yes
BV262Reset Supply 6 Flow TuningWrite0=No, 1=Yes
BV263Supply 5 Flow Control ModeWrite0=Auto, 1=Manual
BV264Supply 6 Flow Control ModeWrite0=Auto, 1=Manual
BV265Supply 5 Temp Control ModeWrite0=Auto, 1=Manual
BV266Supply 6 Temp Control ModeWrite0=Auto, 1=Manual
BV267Supply 5 Balancer ModeWrite0=Off, 1=On
BV268Supply 6 Balancer ModeWrite0=Off, 1=On
BV269Supply 5 Flow Control DirectionWrite0=Reverse, 1=Direct
BV270Supply 6 Flow Control DirectionWrite0=Reverse, 1=Direct
BV271Supply 5 Temp Control DirectionWrite0=Reverse, 1=Direct
BV272Supply 6 Temp Control DirectionWrite0=Reverse, 1=Direct
BV273Supply 5 Venturi VisibleWrite
BV274Supply 5 Linear VisibleWrite
BV275Supply 5 Pitot VisibleWrite
BV276Supply 6 Venturi VisibleWrite
BV277Supply 6 Linear VisibleWrite
BV278Supply 6 Pitot VisibleWrite
BV279Supply 5 Room Temp Voltage VisibleWrite
BV280Supply 6 Room Temp Voltage VisibleWrite
BV281Supply 5 Flow Control ActiveWrite
BV282Supply 6 Flow Control ActiveWrite
BV283Supply 5 Temp Control ActiveWrite
BV284Supply 6 Temp Control ActiveWrite
BV285Supply 5 Flow Input ActiveWrite
BV286Supply 5 Room Temp Input ActiveWrite
BV287Supply 5 Room Temp Adj Input ActiveWrite
BV288Supply 6 Flow Input ActiveWrite
BV289Supply 6 Room Temp Input ActiveWrite
BV290Supply 6 Room Temp Adj Input ActiveWrite
BV291Supply 5 Room Temp RTD VisibleWrite
BV292Supply 6 Room Temp RTD VisibleWrite
BV293Supply 5 Reheat ModeWrite
BV294Supply 6 Reheat ModeWrite
BV295Supply 5 PID Control ModeWrite
BV296Supply 6 PID Control ModeWrite
BV297Supply 5 Occupancy ModeWrite0=Occupied, 1=Unoccupied
BV298Supply 6 Occupancy ModeWrite0=Occupied, 1=Unoccupied
BV299Supply 5 Occupancy DirectionWrite0=Reverse, 1=Direct
BV300Supply 6 Occupancy DirectionWrite0=Reverse, 1=Direct
BV301Supply 5 DAT Voltage VisibleWrite
BV302Supply 6 DAT Voltage VisibleWrite
BV303Supply 5 DAT Input ActiveWrite
BV304Supply 5 Occupancy Input ActiveWrite
BV305Supply 6 DAT Input ActiveWrite
BV306Supply 6 Occupancy Input ActiveWrite
BV307Supply 5 DAT Delta ActiveWrite
BV308Supply 6 DAT Delta ActiveWrite
BV309Supply 5 DAT RTD VisibleWrite
BV310Supply 6 DAT RTD VisibleWrite
MV1Input 1 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV2Input 2 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV3Input 3 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV4Input 4 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV5Input 5 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV6Input 6 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV7Input 7 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV8Input 8 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV9Input 9 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV10Input 10 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV11Input 11 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV12Input 12 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV13Input 13 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV14Input 14 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV15Input 15 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV16Input 16 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV17Input 17 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV18Input 18 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV19Input 19 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV20Input 20 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV21Input 21 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV22Input 22 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV23Input 23 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV24Input 24 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV25Input 25 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV26Input 26 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV27Input 27 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV28Input 28 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV29Input 29 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV30Input 30 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV31Input 31 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV32Input 32 Input TypeWrite1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow
MV33Output 1 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV34Output 2 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV35Output 3 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV36Output 4 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV37Output 5 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV38Output 6 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV39Output 7 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV40Output 8 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV41Output 9 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV42Output 10 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV43Output 11 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV44Output 12 Output TypeWrite1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow
MV45Supply 1 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV46Supply 2 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV47Supply 3 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV48Supply 4 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV49Exhaust 1 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV50Exhaust 2 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV51Hood 1 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV52Hood 2 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV53Hood 3 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV54Hood 4 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV55Hood 5 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV56Hood 6 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV57Hood 7 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position
MV58Supply 1 DAT TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV59Supply 2 DAT TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV60Supply 3 DAT TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV61Supply 4 DAT TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV62Room Pressure TypeWrite1=Unconfigured, 2=TTW Sensor, 3=Pressure Transducer
MV63Supply 1 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV64Supply 2 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV65Supply 3 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV66Supply 4 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV67Exhaust 1 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV68Exhaust 2 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV69Hood 1 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV70Hood 2 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV71Hood 3 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV72Hood 4 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV73Hood 5 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV74Hood 6 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV75Hood 7 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MVmin76Current Supply 1 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV77Current Supply 2 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV78Current Supply 3 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV79Current Supply 4 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV80Current Exhaust 1 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV81Current Exhaust 2 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV82Current Supply 1 Temp Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV83Current Supply 2 Temp Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV84Current Supply 3 Temp Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV85Current Supply 4 Temp Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MVmin86Current Room Pressure Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV87Current Supply 1 DAT Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV88Current Supply 2 DAT Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV89Current Supply 3 DAT Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV90Current Supply 4 DAT Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MVmin91Current Controller Flow ModeTSI: do not overwriteRead1=Standard, 2=Emergency, 3=Shutdown, 4=Balancer
MV92Current Controller Pressure ModeTSI: do not overwriteRead1=Normal, 2=Door Open
MV93Current Supply 1 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV94Current Supply 2 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV95Current Supply 3 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV96Current Supply 4 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV97Current Supply 1 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV98Current Supply 2 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV99Current Supply 3 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV100Current Supply 4 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV101Current Exhaust 1 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV102Current Exhaust 2 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV103Current Exhaust 1 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV104Current Exhaust 2 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV105Current Hood 1 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV106Current Hood 2 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV107Current Hood 3 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV108Current Hood 4 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV109Current Hood 5 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV110Current Hood 6 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV111Current Hood 7 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV112Current Hood 1 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV113Current Hood 2 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV114Current Hood 3 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV115Current Hood 4 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV116Current Hood 5 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV117Current Hood 6 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV118Current Hood 7 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV119Room Pressure Cal ModeWrite1=Save, 2=Sensor Zero
MV120Current Offset Alarm StatusTSI: do not overwriteRead1=Normal, 2=Minimum Offset Alarm, 3=Maximum Offset Alarm
MV121Hood 8 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV122Hood 9 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV123Hood 10 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV124Hood 11 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV125Hood 12 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV126Hood 13 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV127Hood 14 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV128Hood 15 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV129Hood 16 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV130Hood 17 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV131Hood 18 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV132Hood 19 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV133Hood 20 Flow TypeWrite1=Normal, 2=Feedback Alarm
MV134Hood 8 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV135Hood 9 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV136Hood 10 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV137Hood 11 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV138Hood 12 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV139Hood 13 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV140Hood 14 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV141Hood 15 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV142Hood 16 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV143Hood 17 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV144Hood 18 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV145Hood 19 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV146Hood 20 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV147Current Hood 8 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV148Current Hood 9 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV149Current Hood 10 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV150Current Hood 11 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV151Current Hood 12 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV152Current Hood 13 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV153Current Hood 14 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV154Current Hood 15 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV155Current Hood 16 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV156Current Hood 17 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV157Current Hood 18 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV158Current Hood 19 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV159Current Hood 20 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=No Flow Alarm
MV160Current Hood 8 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV161Current Hood 9 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV162Current Hood 10 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV163Current Hood 11 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV164Current Hood 12 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV165Current Hood 13 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV166Current Hood 14 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV167Current Hood 15 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV168Current Hood 16 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV169Current Hood 17 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV170Current Hood 18 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV171Current Hood 19 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV172Current Hood 20 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Feedback Alarm
MV173Supply 1 Room Temp TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV174Supply 2 Room Temp TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV175Supply 3 Room Temp TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV176Supply 4 Room Temp TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV177Supply 5 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV178Supply 6 Flow TypeWrite1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot
MV179Supply 5 Room Temp TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV180Supply 6 Room Temp TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV181Supply 5 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV182Supply 6 Pitot Cal modeWrite1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero
MV183Current Supply 5 Temp Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV184Current Supply 6 Temp Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV185Current Supply 5 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV186Current Supply 6 Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV187Current Supply 5 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV188Current Supply 6 No Flow Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV189Current Supply 5 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV190Current Supply 6 Feedback Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV191Supply 5 DAT TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV192Supply 6 DAT TypeWrite1=Unconfigured, 2=0 to 10V, 3=RTD
MV193Current Supply 5 DAT Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
MV194Current Supply 6 DAT Alarm StatusTSI: do not overwriteRead1=Normal, 2=Low Alarm, 3=High Alarm
Object ID lookup: TSI Laboratory Room Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Laboratory Room Controller (LRC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI Laboratory Room Controller (LRC)

How many BACnet points does the TSI Laboratory Room Controller (LRC) have?

This list has 1714 BACnet objects: 1212 analog values, 308 binary values, 194 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI Laboratory Room Controller (LRC) BACnet points are writable?

1251 of the 1714 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TSI Laboratory Room Controller (LRC) BACnet documentation?

The source is Laboratory Room Controller Model LRC Operation and Service Manual (P/N 6013156), revision Revision E, December 2021, published free by TSI at https://tsi.com/getmedia/76e6ed5c-8c9c-407c-a413-5aa72c00268b/LRC_Lab_Room_Controller_Op_Svc_Mnl_6013156E-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI Laboratory Room Controller (LRC)?

Start with BV 24 Supply 1 Occupancy Mode (Supply 1 occupancy: 0 = occupied, 1 = unoccupied); BV 22 Emergency Mode (Emergency mode: 1 = active); AV 268 Room Pressure Setpoint (Room pressure setpoint, in. W.C); MV 91 Current Controller Flow Mode (Standard, Emergency, Shutdown or Balancer); AV 697 Room Pressure (Measured room pressure, in. W.C); AV 660 Current Total Supply Flow (Total supply airflow, CFM); AV 661 Current Total Exhaust Flow (Total exhaust airflow, CFM); AV 689 Supply 1 Room Temp (Supply 1 zone room temperature); MV 86 Current Room Pressure Alarm Status (1 = normal, 2 = low alarm, 3 = high alarm); MV 76 Current Supply 1 Flow Alarm Status (Supply 1 flow: 1 = normal, 2 = low, 3 = high alarm).

How do I enable BMS control of the TSI Laboratory Room Controller (LRC)?

No separate BMS enable is described. Occupancy per supply (BV 24-27, BV 297/298 for supplies 5-6), Emergency Mode (BV 22) and Shutdown Mode (BV 23) are writable and switch the controller between its occupied, unoccupied, emergency and shutdown flow setpoints.

How do I check these points on the real Laboratory Room Controller (LRC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: Laboratory Room Controller Model LRC Operation and Service Manual · P/N 6013156 · rev. Revision E, December 2021. Object names, instances and units are reproduced as published; descriptions are our own.