The TSI LRC controls a lab room by tracking supply, general exhaust and fume hood flows to hold an airflow offset and room pressure, with per-supply temperature control. Its BACnet object set is almost entirely Analog, Binary and Multi-state Values: setup values (flow ranges, setpoints, alarm limits, sensor calibration) plus live flows, temperatures, room pressure and alarm states. The list is long because every supply, exhaust and hood channel has its own block.
This page lists 1714 BACnet objects for the TSI Laboratory Room Controller (LRC) — 1251 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.
- Manufacturer
- TSI
- Model
- Laboratory Room Controller (LRC)
- Equipment
- Laboratory room airflow and pressure controller
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 1714 (1251 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Firmware 1.14.17191.1 (PICS); application software 1.8.17191.284
- Also known as
- LRC, LRC00, LRC00-LPS, LRC00-CMH, TSI LRC, Lab Room Controller
Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.
BMS integration notes: TSI Laboratory Room Controller (LRC)
Read room pressure, total supply and exhaust flow, the controller flow mode and the alarm status MVs. The BMS can set occupancy per supply (BV 24-27), trigger emergency or shutdown mode (BV 22/23) and change the room pressure setpoint (AV 268). TSI suggests picking only the points you need instead of auto-discovering the whole set.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 24 | Supply 1 Occupancy Mode | Supply 1 occupancy: 0 = occupied, 1 = unoccupied | Write |
| BV 22 | Emergency Mode | Emergency mode: 1 = active | Write |
| AV 268 | Room Pressure Setpoint | Room pressure setpoint, in. W.C. | Write |
| MV 91 | Current Controller Flow Mode | Standard, Emergency, Shutdown or Balancer | Read |
| AV 697 | Room Pressure | Measured room pressure, in. W.C. | Read |
| AV 660 | Current Total Supply Flow | Total supply airflow, CFM | Read |
| AV 661 | Current Total Exhaust Flow | Total exhaust airflow, CFM | Read |
| AV 689 | Supply 1 Room Temp | Supply 1 zone room temperature | Read |
| MV 86 | Current Room Pressure Alarm Status | 1 = normal, 2 = low alarm, 3 = high alarm | Read |
| MV 76 | Current Supply 1 Flow Alarm Status | Supply 1 flow: 1 = normal, 2 = low, 3 = high alarm | Read |
Enable & remote start
No separate BMS enable is described. Occupancy per supply (BV 24-27, BV 297/298 for supplies 5-6), Emergency Mode (BV 22) and Shutdown Mode (BV 23) are writable and switch the controller between its occupied, unoccupied, emergency and shutdown flow setpoints.
Network setup
- BACnet MS/TP runs at 9600, 19200, 38400 or 76800 baud; the end-of-line resistors on the LRC00 are DIP switches, off by default.
- BACnet IP uses the two RJ-45 ports. TSI says the Ethernet IP is dynamic (DHCP) by default, but a new controller loaded with its initial file comes up at static 192.168.200.90 (set a laptop to 192.168.200.1 to reach it); change it in the controller web interface.
- The PICS lists the LRC as a BACnet Building Controller (B-BC).
Watch out for
- TSI warns that writing values can upset room control; leave objects marked DO NOT OVERWRITE (live readings, calibration and calculated values) alone.
- Most objects are commissioning settings (flow ranges, K-factors, calibration, PID tuning); do not write them cyclically.
- Auto-discovery of the full object set takes a long time; map only the points you need.
- Units differ between the LRC00, LRC00-LPS and LRC00-CMH versions.
TSI Laboratory Room Controller (LRC) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | Supply 1 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 2 | Supply 1 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 3 | Supply 1 Venturi Minimum Flow | CFM | Write | ||
| AV | 4 | Supply 1 Venturi Maximum Flow | CFM | Write | ||
| AV | 5 | Supply 1 Flow K Factor | Write | |||
| AV | 6 | Supply 1 Venturi Setup Position | % open | Write | ||
| AV | 7 | Supply 1 Venturi LOM Esc Time | s | Write | ||
| AV | 8 | Supply 1 Linear Duct Area | ft² | Write | ||
| AV | 10 | Supply 1 Linear Top Velocity | ft/min | Write | ||
| AV | 11 | Supply 1 Linear Signal Minimum | V | Write | ||
| AV | 12 | Supply 1 Linear Signal Maximum | V | Write | ||
| AV | 13 | Supply 1 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 14 | Supply 1 Transducer Signal Minimum | V | Write | ||
| AV | 15 | Supply 1 Transducer Signal Maximum | V | Write | ||
| AV | 16 | Supply 1 Pitot Duct Area | ft² | Write | ||
| AV | 17 | Supply 5 Flow Error | TSI: do not read or overwrite | Read | ||
| AV | 18 | Supply 1 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 19 | Supply 1 Pitot Low Cal Pos | % open | Write | ||
| AV | 20 | Supply 1 Pitot High Cal Pos | % open | Write | ||
| AV | 21 | Supply 1 Pitot Low Cal Flow | CFM | Write | ||
| AV | 22 | Supply 1 Pitot High Cal Flow | CFM | Write | ||
| AV | 23 | Supply 2 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 24 | Supply 2 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 25 | Supply 2 Venturi Minimum Flow | CFM | Write | ||
| AV | 26 | Supply 2 Venturi Maximum Flow | CFM | Write | ||
| AV | 27 | Supply 2 Flow K Factor | Write | |||
| AV | 28 | Supply 2 Venturi Setup Position | % open | Write | ||
| AV | 29 | Supply 2 Venturi LOM Esc Time | s | Write | ||
| AV | 30 | Supply 2 Linear Duct Area | ft² | Write | ||
| AV | 32 | Supply 2 Linear Top Velocity | ft/min | Write | ||
| AV | 33 | Supply 2 Linear Signal Minimum | V | Write | ||
| AV | 34 | Supply 2 Linear Signal Maximum | V | Write | ||
| AV | 35 | Supply 2 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 36 | Supply 2 Pitot Low Cal Pos | % open | Write | ||
| AV | 37 | Supply 2 Transducer Signal Minimum | V | Write | ||
| AV | 38 | Supply 2 Pitot High Cal Pos | % open | Write | ||
| AV | 39 | Supply 2 Transducer Signal Maximum | V | Write | ||
| AV | 40 | Supply 2 Pitot Low Cal Flow | CFM | Write | ||
| AV | 41 | Supply 2 Pitot Duct Area | ft² | Write | ||
| AV | 42 | Supply 2 Pitot High Cal Flow | CFM | Write | ||
| AV | 43 | Supply 6 Flow Error | TSI: do not read or overwrite | Read | ||
| AV | 44 | Supply 2 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 45 | Supply 3 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 46 | Supply 3 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 47 | Supply 3 Venturi Minimum Flow | CFM | Write | ||
| AV | 48 | Supply 3 Venturi Maximum Flow | CFM | Write | ||
| AV | 49 | Supply 3 Flow K Factor | Write | |||
| AV | 50 | Supply 3 Venturi Setup Position | % open | Write | ||
| AV | 51 | Supply 3 Venturi LOM Esc Time | s | Write | ||
| AV | 52 | Supply 3 Linear Duct Area | ft² | Write | ||
| AV | 54 | Supply 3 Linear Top Velocity | ft/min | Write | ||
| AV | 55 | Supply 3 Linear Signal Minimum | V | Write | ||
| AV | 56 | Supply 3 Linear Signal Maximum | V | Write | ||
| AV | 57 | Supply 3 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 58 | Supply 3 Pitot Low Cal Pos | % open | Write | ||
| AV | 59 | Supply 3 Transducer Signal Minimum | V | Write | ||
| AV | 60 | Supply 3 Pitot High Cal Pos | % open | Write | ||
| AV | 61 | Supply 3 Transducer Signal Maximum | V | Write | ||
| AV | 62 | Supply 3 Pitot Low Cal Flow | CFM | Write | ||
| AV | 63 | Supply 3 Pitot Duct Area | ft² | Write | ||
| AV | 64 | Supply 3 Pitot High Cal Flow | CFM | Write | ||
| AV | 65 | Old Supply 5 Error | TSI: do not read or overwrite | Read | ||
| AV | 66 | Supply 3 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 67 | Supply 4 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 68 | Supply 4 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 69 | Supply 4 Venturi Minimum Flow | CFM | Write | ||
| AV | 70 | Supply 4 Venturi Maximum Flow | CFM | Write | ||
| AV | 71 | Supply 4 Flow K Factor | Write | |||
| AV | 72 | Supply 4 Venturi Setup Position | % open | Write | ||
| AV | 73 | Supply 4 Venturi LOM Esc Time | s | Write | ||
| AV | 74 | Supply 4 Linear Duct Area | ft² | Write | ||
| AV | 76 | Supply 4 Linear Top Velocity | ft/min | Write | ||
| AV | 77 | Supply 4 Linear Signal Minimum | V | Write | ||
| AV | 78 | Supply 4 Linear Signal Maximum | V | Write | ||
| AV | 79 | Supply 4 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 80 | Supply 4 Pitot Low Cal Pos | % open | Write | ||
| AV | 81 | Supply 4 Transducer Signal Minimum | V | Write | ||
| AV | 82 | Supply 4 Pitot High Cal Pos | % open | Write | ||
| AV | 83 | Supply 4 Transducer Signal Maximum | V | Write | ||
| AV | 84 | Supply 4 Pitot Low Cal Flow | CFM | Write | ||
| AV | 85 | Supply 4 Pitot Duct Area | ft² | Write | ||
| AV | 86 | Supply 4 Pitot High Cal Flow | CFM | Write | ||
| AV | 87 | Old Supply 5 Error | TSI: do not read or overwrite | Read | ||
| AV | 88 | Supply 4 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 89 | Exhaust 1 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 90 | Exhaust 1 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 91 | Exhaust 1 Venturi Minimum Flow | CFM | Write | ||
| AV | 92 | Exhaust 1 Venturi Maximum Flow | CFM | Write | ||
| AV | 93 | Exhaust 1 Flow K Factor | Write | |||
| AV | 94 | Exhaust 1 Venturi Setup Position | % open | Write | ||
| AV | 95 | Exhaust 1 Venturi LOM Esc Time | s | Write | ||
| AV | 96 | Exhaust 1 Linear Duct Area | ft² | Write | ||
| AV | 98 | Exhaust 1 Linear Top Velocity | ft/min | Write | ||
| AV | 99 | Exhaust 1 Linear Signal Minimum | V | Write | ||
| AV | 100 | Exhaust 1 Linear Signal Maximum | V | Write | ||
| AV | 101 | Exhaust 1 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 102 | Exhaust 1 Pitot Low Cal Pos | % open | Write | ||
| AV | 103 | Exhaust 1 Transducer Signal Minimum | V | Write | ||
| AV | 104 | Exhaust 1 Pitot High Cal Pos | % open | Write | ||
| AV | 105 | Exhaust 1 Transducer Signal Maximum | V | Write | ||
| AV | 106 | Exhaust 1 Pitot Low Cal Flow | CFM | Write | ||
| AV | 107 | Exhaust 1 Pitot Duct Area | ft² | Write | ||
| AV | 108 | Exhaust 1 Pitot High Cal Flow | CFM | Write | ||
| AV | 110 | Exhaust 1 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 111 | Exhaust 2 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 112 | Exhaust 2 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 113 | Exhaust 2 Venturi Minimum Flow | CFM | Write | ||
| AV | 114 | Exhaust 2 Venturi Maximum Flow | CFM | Write | ||
| AV | 115 | Exhaust 2 Flow K Factor | Write | |||
| AV | 116 | Exhaust 2 Venturi Setup Position | % open | Write | ||
| AV | 117 | Exhaust 2 Venturi LOM Esc Time | s | Write | ||
| AV | 118 | Exhaust 2 Linear Duct Area | ft² | Write | ||
| AV | 120 | Exhaust 2 Linear Top Velocity | ft/min | Write | ||
| AV | 121 | Exhaust 2 Linear Signal Minimum | V | Write | ||
| AV | 122 | Exhaust 2 Linear Signal Maximum | V | Write | ||
| AV | 123 | Exhaust 2 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 124 | Exhaust 2 Pitot Low Cal Pos | % open | Write | ||
| AV | 125 | Exhaust 2 Transducer Signal Minimum | V | Write | ||
| AV | 126 | Exhaust 2 Pitot High Cal Pos | % open | Write | ||
| AV | 127 | Exhaust 2 Transducer Signal Maximum | V | Write | ||
| AV | 128 | Exhaust 2 Pitot Low Cal Flow | CFM | Write | ||
| AV | 129 | Exhaust 2 Pitot Duct Area | ft² | Write | ||
| AV | 130 | Exhaust 2 Pitot High Cal Flow | CFM | Write | ||
| AV | 132 | Exhaust 2 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 133 | Supply 1 Room Temp Offset | °F | Write | ||
| AV | 134 | Supply 2 Room Temp Offset | °F | Write | ||
| AV | 135 | Supply 3 Room Temp Offset | °F | Write | ||
| AV | 136 | Supply 4 Room Temp Offset | °F | Write | ||
| AV | 137 | Supply 1 DAT Offset | °F | Write | ||
| AV | 138 | Supply 2 DAT Offset | °F | Write | ||
| AV | 139 | Supply 3 DAT Offset | °F | Write | ||
| AV | 140 | Supply 4 DAT Offset | °F | Write | ||
| AV | 141 | Supply 1 DAT Signal Minimum | V | Write | ||
| AV | 142 | Supply 1 DAT Signal Maximum | V | Write | ||
| AV | 143 | Supply 1 DAT Sensor Minimum | °F | Write | ||
| AV | 144 | Supply 1 DAT Sensor Maximum | °F | Write | ||
| AV | 146 | Supply 2 DAT Signal Minimum | V | Write | ||
| AV | 147 | Supply 2 DAT Signal Maximum | V | Write | ||
| AV | 148 | Supply 2 DAT Sensor Minimum | °F | Write | ||
| AV | 149 | Supply 2 DAT Sensor Maximum | °F | Write | ||
| AV | 151 | Supply 3 DAT Signal Minimum | V | Write | ||
| AV | 152 | Supply 3 DAT Signal Maximum | V | Write | ||
| AV | 153 | Supply 3 DAT Sensor Minimum | °F | Write | ||
| AV | 154 | Supply 3 DAT Sensor Maximum | °F | Write | ||
| AV | 156 | Supply 4 DAT Signal Minimum | V | Write | ||
| AV | 157 | Supply 4 DAT Signal Maximum | V | Write | ||
| AV | 158 | Supply 4 DAT Sensor Minimum | °F | Write | ||
| AV | 159 | Supply 4 DAT Sensor Maximum | °F | Write | ||
| AV | 161 | Supply 1 Room Temp Adj Signal Minimum | V | Write | ||
| AV | 162 | Supply 1 Room Temp Adj Signal Maximum | V | Write | ||
| AV | 163 | Supply 1 Room Temp Adj Sensor Minimum | °F | Write | ||
| AV | 164 | Supply 1 Room Temp Adj Sensor Maximum | °F | Write | ||
| AV | 165 | Supply 2 Room Temp Adj Signal Minimum | V | Write | ||
| AV | 166 | Supply 2 Room Temp Adj Signal Maximum | V | Write | ||
| AV | 167 | Supply 2 Room Temp Adj Sensor Minimum | °F | Write | ||
| AV | 168 | Supply 2 Room Temp Adj Sensor Maximum | °F | Write | ||
| AV | 169 | Supply 3 Room Temp Adj Signal Minimum | V | Write | ||
| AV | 170 | Supply 3 Room Temp Adj Signal Maximum | V | Write | ||
| AV | 171 | Supply 3 Room Temp Adj Sensor Minimum | °F | Write | ||
| AV | 172 | Supply 3 Room Temp Adj Sensor Maximum | °F | Write | ||
| AV | 173 | Supply 4 Room Temp Adj Signal Minimum | V | Write | ||
| AV | 174 | Supply 4 Room Temp Adj Signal Maximum | V | Write | ||
| AV | 175 | Supply 4 Room Temp Adj Sensor Minimum | °F | Write | ||
| AV | 176 | Supply 4 Room Temp Adj Sensor Maximum | °F | Write | ||
| AV | 177 | Relative Humidity Signal Minimum | V | Write | ||
| AV | 178 | Relative Humidity Signal Maximum | V | Write | ||
| AV | 179 | Relative Humidity Sensor Minimum | %RH | Write | ||
| AV | 180 | Relative Humidity Sensor Maximum | %RH | Write | ||
| AV | 181 | Relative Humidity Offset | %RH | Write | ||
| AV | 182 | Pressure Transducer Signal Maximum | V | Write | ||
| AV | 183 | Pressure Transducer Signal Minimum | V | Write | ||
| AV | 184 | Pressure Transducer Sensor Minimum | in. W.C. | Write | ||
| AV | 185 | Pressure Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 186 | Room Pressure Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 188 | TTW Sensor Velocity K-Factor | Write | |||
| AV | 189 | TTW Sensor Elevation | ft | Write | ||
| AV | 190 | Supply 1 Minimum Flow | CFM | Write | ||
| AV | 191 | Supply 1 Cooling Flow | CFM | Write | ||
| AV | 192 | Supply 1 Heating Flow | CFM | Write | ||
| AV | 193 | Supply 1 Maximum Flow | CFM | Write | ||
| AV | 194 | Supply 1 Minimum Position | % open | Write | ||
| AV | 195 | Supply 1 Maximum Position | % open | Write | ||
| AV | 196 | Supply 1 Unocc Minimum Flow | CFM | Write | ||
| AV | 197 | Supply 1 Unocc Cooling Flow | CFM | Write | ||
| AV | 198 | Supply 1 Unocc Heating Flow | CFM | Write | ||
| AV | 199 | Supply 1 Unocc Maximum Flow | CFM | Write | ||
| AV | 200 | Supply 1 Emergency Flow | CFM | Write | ||
| AV | 201 | Supply 1 Shutdown Flow | CFM | Write | ||
| AV | 202 | Supply 2 Minimum Flow | CFM | Write | ||
| AV | 203 | Supply 2 Unocc Minimum Flow | CFM | Write | ||
| AV | 204 | Supply 2 Cooling Flow | CFM | Write | ||
| AV | 205 | Supply 2 Unocc Cooling Flow | CFM | Write | ||
| AV | 206 | Supply 2 Heating Flow | CFM | Write | ||
| AV | 207 | Supply 2 Unocc Heating Flow | CFM | Write | ||
| AV | 208 | Supply 2 Maximum Flow | CFM | Write | ||
| AV | 209 | Supply 2 Unocc Maximum Flow | CFM | Write | ||
| AV | 210 | Supply 2 Emergency Flow | CFM | Write | ||
| AV | 211 | Supply 2 Minimum Position | % open | Write | ||
| AV | 212 | Supply 2 Shutdown Flow | CFM | Write | ||
| AV | 213 | Supply 2 Maximum Position | % open | Write | ||
| AV | 214 | Supply 3 Minimum Flow | CFM | Write | ||
| AV | 215 | Supply 3 Unocc Minimum Flow | CFM | Write | ||
| AV | 216 | Supply 3 Cooling Flow | CFM | Write | ||
| AV | 217 | Supply 3 Unocc Cooling Flow | CFM | Write | ||
| AV | 218 | Supply 3 Heating Flow | CFM | Write | ||
| AV | 219 | Supply 3 Unocc Heating Flow | CFM | Write | ||
| AV | 220 | Supply 3 Maximum Flow | CFM | Write | ||
| AV | 221 | Supply 3 Unocc Maximum Flow | CFM | Write | ||
| AV | 222 | Supply 3 Emergency Flow | CFM | Write | ||
| AV | 223 | Supply 3 Minimum Position | % open | Write | ||
| AV | 224 | Supply 3 Shutdown Flow | CFM | Write | ||
| AV | 225 | Supply 3 Maximum Position | % open | Write | ||
| AV | 226 | Supply 4 Minimum Flow | CFM | Write | ||
| AV | 227 | Supply 4 Unocc Minimum Flow | CFM | Write | ||
| AV | 228 | Supply 4 Cooling Flow | CFM | Write | ||
| AV | 229 | Supply 4 Unocc Cooling Flow | CFM | Write | ||
| AV | 230 | Supply 4 Heating Flow | CFM | Write | ||
| AV | 231 | Supply 4 Unocc Heating Flow | CFM | Write | ||
| AV | 232 | Supply 4 Maximum Flow | CFM | Write | ||
| AV | 233 | Supply 4 Unocc Maximum Flow | CFM | Write | ||
| AV | 234 | Supply 4 Emergency Flow | CFM | Write | ||
| AV | 235 | Supply 4 Minimum Position | % open | Write | ||
| AV | 236 | Supply 4 Shutdown Flow | CFM | Write | ||
| AV | 237 | Supply 4 Maximum Position | % open | Write | ||
| AV | 238 | Exhaust 1 Minimum Flow | CFM | Write | ||
| AV | 239 | Exhaust 1 Maximum Flow | CFM | Write | ||
| AV | 240 | Exhaust 1 Minimum Position | % open | Write | ||
| AV | 241 | Exhaust 1 Maximum Position | % open | Write | ||
| AV | 242 | Exhaust 1 Emergency Flow | CFM | Write | ||
| AV | 243 | Exhaust 2 Minimum Flow | CFM | Write | ||
| AV | 244 | Exhaust 2 Maximum Flow | CFM | Write | ||
| AV | 245 | Exhaust 2 Minimum Position | % open | Write | ||
| AV | 246 | Exhaust 2 Maximum Position | % open | Write | ||
| AV | 247 | Exhaust 2 Emergency Flow | CFM | Write | ||
| AV | 248 | Supply 1 Heat Setpoint | °F | Write | ||
| AV | 249 | Supply 1 Cool Setpoint | °F | Write | ||
| AV | 250 | Supply 1 Unocc Heat Setpoint | °F | Write | ||
| AV | 251 | Supply 1 Unocc Cool Setpoint | °F | Write | ||
| AV | 252 | Supply 1 DAT Delta | Δ°F | Write | ||
| AV | 253 | Supply 2 Heat Setpoint | °F | Write | ||
| AV | 254 | Supply 2 Cool Setpoint | °F | Write | ||
| AV | 255 | Supply 2 Unocc Heat Setpoint | °F | Write | ||
| AV | 256 | Supply 2 Unocc Cool Setpoint | °F | Write | ||
| AV | 257 | Supply 2 DAT Delta | Δ°F | Write | ||
| AV | 258 | Supply 3 Heat Setpoint | °F | Write | ||
| AV | 259 | Supply 3 Cool Setpoint | °F | Write | ||
| AV | 260 | Supply 3 Unocc Heat Setpoint | °F | Write | ||
| AV | 261 | Supply 3 Unocc Cool Setpoint | °F | Write | ||
| AV | 262 | Supply 3 DAT Delta | Δ°F | Write | ||
| AV | 263 | Supply 4 Heat Setpoint | °F | Write | ||
| AV | 264 | Supply 4 Cool Setpoint | °F | Write | ||
| AV | 265 | Supply 4 Unocc Heat Setpoint | °F | Write | ||
| AV | 266 | Supply 4 Unocc Cool Setpoint | °F | Write | ||
| AV | 267 | Supply 4 DAT Delta | Δ°F | Write | ||
| AVmin | 268 | Room Pressure Setpoint | in. W.C. | Write | ||
| AV | 269 | Door Room Pressure Setpoint | in. W.C. | Write | ||
| AV | 270 | Minimum Offset | CFM | Write | ||
| AV | 271 | Maximum Offset | CFM | Write | ||
| AV | 272 | Supply 1 Low Flow Alarm | CFM | Write | ||
| AV | 273 | Supply 1 High Flow Alarm | CFM | Write | ||
| AV | 274 | Supply 1 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 275 | Supply 1 Unocc High Flow Alarm | CFM | Write | ||
| AV | 276 | Supply 2 Low Flow Alarm | CFM | Write | ||
| AV | 277 | Supply 2 High Flow Alarm | CFM | Write | ||
| AV | 278 | Supply 2 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 279 | Supply 2 Unocc High Flow Alarm | CFM | Write | ||
| AV | 280 | Supply 3 Low Flow Alarm | CFM | Write | ||
| AV | 281 | Supply 3 High Flow Alarm | CFM | Write | ||
| AV | 282 | Supply 3 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 283 | Supply 3 Unocc High Flow Alarm | CFM | Write | ||
| AV | 284 | Supply 4 Low Flow Alarm | CFM | Write | ||
| AV | 285 | Supply 4 High Flow Alarm | CFM | Write | ||
| AV | 286 | Supply 4 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 287 | Supply 4 Unocc High Flow Alarm | CFM | Write | ||
| AV | 288 | Exhaust 1 Low Flow Alarm | CFM | Write | ||
| AV | 289 | Exhaust 1 High Flow Alarm | CFM | Write | ||
| AV | 290 | Exhaust 2 Low Flow Alarm | CFM | Write | ||
| AV | 291 | Exhaust 2 High Flow Alarm | CFM | Write | ||
| AV | 292 | Supply 1 Low Temperature Alarm | °F | Write | ||
| AV | 293 | Supply 1 High Temperature Alarm | °F | Write | ||
| AV | 294 | Supply 1 Unocc Low Temperature Alarm | °F | Write | ||
| AV | 295 | Supply 1 Unocc High Temperature Alarm | °F | Write | ||
| AV | 296 | Supply 2 Low Temperature Alarm | °F | Write | ||
| AV | 297 | Supply 2 High Temperature Alarm | °F | Write | ||
| AV | 298 | Supply 2 Unocc Low Temperature Alarm | °F | Write | ||
| AV | 299 | Supply 2 Unocc High Temperature Alarm | °F | Write | ||
| AV | 300 | Supply 3 Low Temperature Alarm | °F | Write | ||
| AV | 301 | Supply 3 High Temperature Alarm | °F | Write | ||
| AV | 302 | Supply 3 Unocc Low Temperature Alarm | °F | Write | ||
| AV | 303 | Supply 3 Unocc High Temperature Alarm | °F | Write | ||
| AV | 304 | Supply 4 Low Temperature Alarm | °F | Write | ||
| AV | 305 | Supply 4 High Temperature Alarm | °F | Write | ||
| AV | 306 | Supply 4 Unocc Low Temperature Alarm | °F | Write | ||
| AV | 307 | Supply 4 Unocc High Temperature Alarm | °F | Write | ||
| AV | 308 | Low Pressure Alarm | in. W.C. | Write | ||
| AV | 309 | High Pressure Alarm | in. W.C. | Write | ||
| AV | 310 | Door Low Pressure Alarm | in. W.C. | Write | ||
| AV | 311 | Door High Pressure Alarm | in. W.C. | Write | ||
| AV | 312 | Alarm Delay | s | Write | ||
| AV | 313 | Door Alarm Delay | s | Write | ||
| AV | 314 | Supply 1 Flow Manual Position | % open | Write | ||
| AV | 315 | Supply 2 Flow Manual Position | % open | Write | ||
| AV | 316 | Supply 3 Flow Manual Position | % open | Write | ||
| AV | 317 | Supply 4 Flow Manual Position | % open | Write | ||
| AV | 318 | Supply 1 Temp Manual Position | % open | Write | ||
| AV | 319 | Supply 2 Temp Manual Position | % open | Write | ||
| AV | 320 | Supply 3 Temp Manual Position | % open | Write | ||
| AV | 321 | Supply 4 Temp Manual Position | % open | Write | ||
| AV | 322 | Exhaust 1 Flow Manual Position | % open | Write | ||
| AV | 323 | Exhaust 2 Flow Manual Position | % open | Write | ||
| AV | 324 | Supply 5 Flow Manual Position | % open | Write | ||
| AV | 325 | Supply 6 Flow Manual Position | % open | Write | ||
| AV | 326 | Supply 1 Balancer Flow | CFM | Write | ||
| AV | 327 | Supply 2 Balancer Flow | CFM | Write | ||
| AV | 328 | Supply 3 Balancer Flow | CFM | Write | ||
| AV | 329 | Supply 4 Balancer Flow | CFM | Write | ||
| AV | 330 | Exhaust 1 Balancer Flow | CFM | Write | ||
| AV | 331 | Exhaust 2 Balancer Flow | CFM | Write | ||
| AV | 332 | Supply 1 High DAT Alarm | °F | Write | ||
| AV | 333 | Supply 2 High DAT Alarm | °F | Write | ||
| AV | 334 | Supply 3 High DAT Alarm | °F | Write | ||
| AV | 335 | Supply 4 High DAT Alarm | °F | Write | ||
| AV | 336 | Minimum Offset Alarm | CFM | Write | ||
| AV | 337 | Maximum Offset Alarm | CFM | Write | ||
| AV | 338 | Supply 1 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 339 | Supply 1 DAT Input Number | TSI: do not overwrite | Read | ||
| AV | 340 | Supply 1 Room Temp Input Number | TSI: do not overwrite | Read | ||
| AV | 341 | Supply 1 Room Temp Adj Input Number | TSI: do not overwrite | Read | ||
| AV | 342 | Supply 1 Occupancy Input Number | TSI: do not overwrite | Read | ||
| AV | 343 | Supply 2 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 344 | Supply 2 DAT Input Number | TSI: do not overwrite | Read | ||
| AV | 345 | Supply 2 Room Temp Input Number | TSI: do not overwrite | Read | ||
| AV | 346 | Supply 2 Room Temp Adj Input Number | TSI: do not overwrite | Read | ||
| AV | 347 | Supply 2 Occupancy Input Number | TSI: do not overwrite | Read | ||
| AV | 348 | Supply 3 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 349 | Supply 3 DAT Input Number | TSI: do not overwrite | Read | ||
| AV | 350 | Supply 3 Room Temp Input Number | TSI: do not overwrite | Read | ||
| AV | 351 | Supply 3 Room Temp Adj Input Number | TSI: do not overwrite | Read | ||
| AV | 352 | Supply 3 Occupancy Input Number | TSI: do not overwrite | Read | ||
| AV | 353 | Supply 4 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 354 | Supply 4 DAT Input Number | TSI: do not overwrite | Read | ||
| AV | 355 | Supply 4 Room Temp Input Number | TSI: do not overwrite | Read | ||
| AV | 356 | Supply 4 Room Temp Adj Input Number | TSI: do not overwrite | Read | ||
| AV | 357 | Supply 4 Occupancy Input Number | TSI: do not overwrite | Read | ||
| AV | 358 | Exhaust 1 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 359 | Exhaust 2 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 360 | Room Pressure Input Number | TSI: do not overwrite | Read | ||
| AV | 361 | Relative Humidity Input Number | TSI: do not overwrite | Read | ||
| AV | 362 | Door Switch Input Number | TSI: do not overwrite | Read | ||
| AV | 363 | Emergency Input Number | TSI: do not overwrite | Read | ||
| AV | 364 | Shutdown Input Number | TSI: do not overwrite | Read | ||
| AV | 365 | Hood 1 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 366 | Hood 2 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 367 | Hood 3 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 368 | Hood 4 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 369 | Hood 5 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 370 | Hood 6 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 371 | Hood 7 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 372 | Supply 1 Flow Change | CFM | Write | ||
| AV | 373 | Supply 2 Flow Change | CFM | Write | ||
| AV | 374 | Supply 3 Flow Change | CFM | Write | ||
| AV | 375 | Supply 4 Flow Change | CFM | Write | ||
| AV | 376 | Supply 1 Reheat/Cooling Delay | s | Write | ||
| AV | 377 | Supply 2 Reheat/Cooling Delay | s | Write | ||
| AV | 378 | Supply 3 Reheat/Cooling Delay | s | Write | ||
| AV | 379 | Supply 4 Reheat/Cooling Delay | s | Write | ||
| AV | 392 | Supply 5 Temp Manual Position | % open | Write | ||
| AV | 393 | Supply 6 Temp Manual Position | % open | Write | ||
| AV | 395 | Current Alarm Delay | TSI: do not overwrite | s | Read | |
| AV | 396 | Current Offset | TSI: do not overwrite | CFM | Read | |
| AV | 398 | Current Supply 1 Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 399 | Current Supply 1 Cooling Flow | TSI: do not overwrite | CFM | Read | |
| AV | 400 | Current Supply 1 Heating Flow | TSI: do not overwrite | CFM | Read | |
| AV | 401 | Current Supply 1 Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 402 | Current Supply 2 Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 403 | Current Supply 2 Cooling Flow | TSI: do not overwrite | CFM | Read | |
| AV | 404 | Current Supply 2 Heating Flow | TSI: do not overwrite | CFM | Read | |
| AV | 405 | Current Supply 2 Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 406 | Current Supply 3 Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 407 | Current Supply 3 Cooling Flow | TSI: do not overwrite | CFM | Read | |
| AV | 408 | Current Supply 3 Heating Flow | TSI: do not overwrite | CFM | Read | |
| AV | 409 | Current Supply 3 Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 410 | Current Supply 4 Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 411 | Current Supply 4 Cooling Flow | TSI: do not overwrite | CFM | Read | |
| AV | 412 | Current Supply 4 Heating Flow | TSI: do not overwrite | CFM | Read | |
| AV | 413 | Current Supply 4 Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 414 | Current Supply 1 Heat Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 415 | Current Supply 1 Cool Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 416 | Current Supply 2 Heat Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 417 | Current Supply 2 Cool Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 418 | Current Supply 3 Heat Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 419 | Current Supply 3 Cool Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 420 | Current Supply 4 Heat Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 421 | Current Supply 4 Cool Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 422 | Current Room Pressure Setpoint | TSI: do not overwrite | in. W.C. | Read | |
| AV | 423 | Current Supply 1 Low Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 424 | Current Supply 1 High Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 425 | Current Supply 2 Low Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 426 | Current Supply 2 High Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 427 | Current Supply 3 Low Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 428 | Current Supply 3 High Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 429 | Current Supply 4 Low Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 430 | Current Supply 4 High Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 431 | Current Low Pressure Alarm | TSI: do not overwrite | in. W.C. | Read | |
| AV | 432 | Current High Pressure Alarm | TSI: do not overwrite | in. W.C. | Read | |
| AV | 433 | Current Supply 1 Low Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 434 | Current Supply 1 High Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 435 | Current Supply 2 Low Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 436 | Current Supply 2 High Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 437 | Current Supply 3 Low Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 438 | Current Supply 3 High Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 439 | Current Supply 4 Low Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 440 | Current Supply 4 High Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 441 | Hood 1 Venturi Minimum Flow | CFM | Write | ||
| AV | 442 | Hood 1 Venturi Maximum Flow | CFM | Write | ||
| AV | 443 | Hood 1 Flow K factor | Write | |||
| AV | 445 | Hood 1 Venturi LOM ESC Time | s | Write | ||
| AV | 446 | Hood 1 Linear Duct Area | ft² | Write | ||
| AV | 448 | Hood 1 Linear Top Velocity | ft/min | Write | ||
| AV | 449 | Hood 1 Linear Signal Minimum | V | Write | ||
| AV | 450 | Hood 1 Linear Signal Maximum | V | Write | ||
| AV | 451 | Hood 1 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 452 | Hood 1 Transducer Signal Minimum | V | Write | ||
| AV | 453 | Hood 1 Transducer Signal Maximum | V | Write | ||
| AV | 454 | Hood 1 Pitot Duct Area | ft² | Write | ||
| AV | 456 | Hood 1 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 459 | Hood 1 Pitot Low Cal Flow | CFM | Write | ||
| AV | 460 | Hood 1 Pitot High Cal Flow | CFM | Write | ||
| AV | 461 | Hood 1 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 462 | Hood 1 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 463 | Hood 1 TP Min Flow | CFM | Write | ||
| AV | 464 | Hood 1 TP Max Flow | CFM | Write | ||
| AV | 465 | Hood 2 Venturi Minimum Flow | CFM | Write | ||
| AV | 466 | Hood 2 Venturi Maximum Flow | CFM | Write | ||
| AV | 467 | Hood 2 Flow K factor | Write | |||
| AV | 469 | Hood 2 Venturi LOM ESC Time | s | Write | ||
| AV | 470 | Hood 2 Linear Duct Area | ft² | Write | ||
| AV | 472 | Hood 2 Linear Top Velocity | ft/min | Write | ||
| AV | 473 | Hood 2 Linear Signal Minimum | V | Write | ||
| AV | 474 | Hood 2 Linear Signal Maximum | V | Write | ||
| AV | 475 | Hood 2 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 476 | Hood 2 Transducer Signal Minimum | V | Write | ||
| AV | 477 | Hood 2 Transducer Signal Maximum | V | Write | ||
| AV | 478 | Hood 2 Pitot Duct Area | ft² | Write | ||
| AV | 480 | Hood 2 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 483 | Hood 2 Pitot Low Cal Flow | CFM | Write | ||
| AV | 484 | Hood 2 Pitot High Cal Flow | CFM | Write | ||
| AV | 485 | Hood 2 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 486 | Hood 2 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 487 | Hood 2 TP Min Flow | CFM | Write | ||
| AV | 488 | Hood 2 TP Max Flow | CFM | Write | ||
| AV | 489 | Hood 3 Venturi Minimum Flow | CFM | Write | ||
| AV | 490 | Hood 3 Venturi Maximum Flow | CFM | Write | ||
| AV | 491 | Hood 3 Flow K factor | Write | |||
| AV | 493 | Hood 3 Venturi LOM ESC Time | s | Write | ||
| AV | 494 | Hood 3 Linear Duct Area | ft² | Write | ||
| AV | 496 | Hood 3 Linear Top Velocity | ft/min | Write | ||
| AV | 497 | Hood 3 Linear Signal Minimum | V | Write | ||
| AV | 498 | Hood 3 Linear Signal Maximum | V | Write | ||
| AV | 499 | Hood 3 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 500 | Hood 3 Transducer Signal Minimum | V | Write | ||
| AV | 501 | Hood 3 Transducer Signal Maximum | V | Write | ||
| AV | 502 | Hood 3 Pitot Duct Area | ft² | Write | ||
| AV | 504 | Hood 3 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 507 | Hood 3 Pitot Low Cal Flow | CFM | Write | ||
| AV | 508 | Hood 3 Pitot High Cal Flow | CFM | Write | ||
| AV | 509 | Hood 3 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 510 | Hood 3 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 511 | Hood 3 TP Min Flow | CFM | Write | ||
| AV | 512 | Hood 3 TP Max Flow | CFM | Write | ||
| AV | 513 | Hood 4 Venturi Minimum Flow | CFM | Write | ||
| AV | 514 | Hood 4 Venturi Maximum Flow | CFM | Write | ||
| AV | 515 | Hood 4 Flow K factor | Write | |||
| AV | 517 | Hood 4 Venturi LOM ESC Time | s | Write | ||
| AV | 518 | Hood 4 Linear Duct Area | ft² | Write | ||
| AV | 520 | Hood 4 Linear Top Velocity | ft/min | Write | ||
| AV | 521 | Hood 4 Linear Signal Minimum | V | Write | ||
| AV | 522 | Hood 4 Linear Signal Maximum | V | Write | ||
| AV | 523 | Hood 4 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 524 | Hood 4 Transducer Signal Minimum | V | Write | ||
| AV | 525 | Hood 4 Transducer Signal Maximum | V | Write | ||
| AV | 526 | Hood 4 Pitot Duct Area | ft² | Write | ||
| AV | 528 | Hood 4 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 531 | Hood 4 Pitot Low Cal Flow | CFM | Write | ||
| AV | 532 | Hood 4 Pitot High Cal Flow | CFM | Write | ||
| AV | 533 | Hood 4 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 534 | Hood 4 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 535 | Hood 4 TP Min Flow | CFM | Write | ||
| AV | 536 | Hood 4 TP Max Flow | CFM | Write | ||
| AV | 537 | Hood 5 Venturi Minimum Flow | CFM | Write | ||
| AV | 538 | Hood 5 Venturi Maximum Flow | CFM | Write | ||
| AV | 539 | Hood 5 Flow K factor | Write | |||
| AV | 541 | Hood 5 Venturi LOM ESC Time | s | Write | ||
| AV | 542 | Hood 5 Linear Duct Area | ft² | Write | ||
| AV | 544 | Hood 5 Linear Top Velocity | ft/min | Write | ||
| AV | 545 | Hood 5 Linear Signal Minimum | V | Write | ||
| AV | 546 | Hood 5 Linear Signal Maximum | V | Write | ||
| AV | 547 | Hood 5 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 548 | Hood 5 Transducer Signal Minimum | V | Write | ||
| AV | 549 | Hood 5 Transducer Signal Maximum | V | Write | ||
| AV | 550 | Hood 5 Pitot Duct Area | ft² | Write | ||
| AV | 552 | Hood 5 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 555 | Hood 5 Pitot Low Cal Flow | CFM | Write | ||
| AV | 556 | Hood 5 Pitot High Cal Flow | CFM | Write | ||
| AV | 557 | Hood 5 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 558 | Hood 5 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 559 | Hood 5 TP Min Flow | CFM | Write | ||
| AV | 560 | Hood 5 TP Max Flow | CFM | Write | ||
| AV | 561 | Hood 6 Venturi Minimum Flow | CFM | Write | ||
| AV | 562 | Hood 6 Venturi Maximum Flow | CFM | Write | ||
| AV | 563 | Hood 6 Flow K factor | Write | |||
| AV | 565 | Hood 6 Venturi LOM ESC Time | s | Write | ||
| AV | 566 | Hood 6 Linear Duct Area | ft² | Write | ||
| AV | 568 | Hood 6 Linear Top Velocity | ft/min | Write | ||
| AV | 569 | Hood 6 Linear Signal Minimum | V | Write | ||
| AV | 570 | Hood 6 Linear Signal Maximum | V | Write | ||
| AV | 571 | Hood 6 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 572 | Hood 6 Transducer Signal Minimum | V | Write | ||
| AV | 573 | Hood 6 Transducer Signal Maximum | V | Write | ||
| AV | 574 | Hood 6 Pitot Duct Area | ft² | Write | ||
| AV | 576 | Hood 6 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 579 | Hood 6 Pitot Low Cal Flow | CFM | Write | ||
| AV | 580 | Hood 6 Pitot High Cal Flow | CFM | Write | ||
| AV | 581 | Hood 6 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 582 | Hood 6 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 583 | Hood 6 TP Min Flow | CFM | Write | ||
| AV | 584 | Hood 6 TP Max Flow | CFM | Write | ||
| AV | 585 | Hood 7 Venturi Minimum Flow | CFM | Write | ||
| AV | 586 | Hood 7 Venturi Maximum Flow | CFM | Write | ||
| AV | 587 | Hood 7 Flow K factor | Write | |||
| AV | 589 | Hood 7 Venturi LOM ESC Time | s | Write | ||
| AV | 590 | Hood 7 Linear Duct Area | ft² | Write | ||
| AV | 592 | Hood 7 Linear Top Velocity | ft/min | Write | ||
| AV | 593 | Hood 7 Linear Signal Minimum | V | Write | ||
| AV | 594 | Hood 7 Linear Signal Maximum | V | Write | ||
| AV | 595 | Hood 7 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 596 | Hood 7 Transducer Signal Minimum | V | Write | ||
| AV | 597 | Hood 7 Transducer Signal Maximum | V | Write | ||
| AV | 598 | Hood 7 Pitot Duct Area | ft² | Write | ||
| AV | 600 | Hood 7 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 603 | Hood 7 Pitot Low Cal Flow | CFM | Write | ||
| AV | 604 | Hood 7 Pitot High Cal Flow | CFM | Write | ||
| AV | 605 | Hood 7 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 606 | Hood 7 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 607 | Hood 7 TP Min Flow | CFM | Write | ||
| AV | 608 | Hood 7 TP Max Flow | CFM | Write | ||
| AV | 609 | Hood 1 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 610 | Hood 1 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 611 | Hood 2 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 612 | Hood 2 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 613 | Hood 3 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 614 | Hood 3 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 615 | Hood 4 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 616 | Hood 4 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 617 | Hood 5 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 618 | Hood 5 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 619 | Hood 6 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 620 | Hood 6 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 621 | Hood 7 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 622 | Hood 7 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 623 | TTW Sensor UnSpanned Velocity | TSI: do not overwrite | ft/min | Read | |
| AV | 624 | TTW Sensor Spanned Velocity | TSI: do not overwrite | ft/min | Read | |
| AV | 625 | Supply 1 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 626 | Supply 1 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 627 | Supply 2 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 628 | Supply 2 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 629 | Supply 3 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 630 | Supply 3 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 631 | Supply 4 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 632 | Supply 4 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 633 | Exhaust 1 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 634 | Exhaust 1 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 635 | Exhaust 2 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 636 | Exhaust 2 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 653 | Supply 5 Balancer Flow | CFM | Write | ||
| AV | 654 | Supply 6 Balancer Flow | CFM | Write | ||
| AV | 655 | Current Supply 1 Minimum Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 656 | Current Supply 2 Minimum Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 657 | Current Supply 3 Minimum Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 658 | Current Supply 4 Minimum Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 659 | Offset Setpoint | TSI: do not overwrite | CFM | Read | |
| AVmin | 660 | Current Total Supply Flow | TSI: do not overwrite | CFM | Read | |
| AVmin | 661 | Current Total Exhaust Flow | TSI: do not overwrite | CFM | Read | |
| AV | 662 | Supply 1 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 663 | Supply 2 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 664 | Supply 3 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 665 | Supply 4 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 666 | Exhaust 1 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 667 | Exhaust 2 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 668 | Hood 1 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 669 | Hood 2 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 670 | Hood 3 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 671 | Hood 4 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 672 | Hood 5 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 673 | Hood 6 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 674 | Hood 7 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 675 | Current Supply 1 Temperature Control Position | TSI: do not overwrite | % open | Read | |
| AV | 676 | Current Supply 1 Flow Control Position | TSI: do not overwrite | % open | Read | |
| AV | 677 | Current Supply 2 Temperature Control Position | TSI: do not overwrite | % open | Read | |
| AV | 678 | Current Supply 2 Flow Control Position | TSI: do not overwrite | % open | Read | |
| AV | 679 | Current Supply 3 Temperature Control Position | TSI: do not overwrite | % open | Read | |
| AV | 680 | Current Supply 3 Flow Control Position | TSI: do not overwrite | % open | Read | |
| AV | 681 | Current Supply 4 Temperature Control Position | TSI: do not overwrite | % open | Read | |
| AV | 682 | Current Supply 4 Flow Control Position | TSI: do not overwrite | % open | Read | |
| AV | 683 | Current Exhaust 1 Flow Control Position | TSI: do not overwrite | % open | Read | |
| AV | 684 | Current Exhaust 2 Flow Control Position | TSI: do not overwrite | % open | Read | |
| AV | 685 | Supply 1 DAT | TSI: do not overwrite | °F | Read | |
| AV | 686 | Supply 2 DAT | TSI: do not overwrite | °F | Read | |
| AV | 687 | Supply 3 DAT | TSI: do not overwrite | °F | Read | |
| AV | 688 | Supply 4 DAT | TSI: do not overwrite | °F | Read | |
| AVmin | 689 | Supply 1 Room Temp | TSI: do not overwrite | °F | Read | |
| AV | 690 | Supply 2 Room Temp | TSI: do not overwrite | °F | Read | |
| AV | 691 | Supply 3 Room Temp | TSI: do not overwrite | °F | Read | |
| AV | 692 | Supply 4 Room Temp | TSI: do not overwrite | °F | Read | |
| AV | 693 | Supply 1 Room Temp Adj | TSI: do not overwrite | °F | Read | |
| AV | 694 | Supply 2 Room Temp Adj | TSI: do not overwrite | °F | Read | |
| AV | 695 | Supply 3 Room Temp Adj | TSI: do not overwrite | °F | Read | |
| AV | 696 | Supply 4 Room Temp Adj | TSI: do not overwrite | °F | Read | |
| AVmin | 697 | Room Pressure | TSI: do not overwrite | in. W.C. | Read | |
| AV | 698 | Relative Humidity | TSI: do not overwrite | %RH | Read | |
| AV | 699 | Hood 8 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 700 | Hood 9 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 701 | Hood 10 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 702 | Hood 11 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 703 | Hood 12 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 704 | Hood 13 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 705 | Hood 14 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 706 | Hood 15 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 707 | Hood 16 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 708 | Hood 17 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 709 | Hood 18 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 710 | Hood 19 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 711 | Hood 20 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 713 | Supply 1 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 714 | Supply 2 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 715 | Supply 3 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 716 | Supply 4 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 717 | Exhaust 1 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 718 | Exhaust 2 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 719 | Hood 1 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 720 | Hood 2 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 721 | Hood 3 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 722 | Hood 4 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 723 | Hood 5 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 724 | Hood 6 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 725 | Hood 7 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 726 | Supply 1 DAT Voltage | TSI: do not overwrite | V | Read | |
| AV | 727 | Supply 2 DAT Voltage | TSI: do not overwrite | V | Read | |
| AV | 728 | Supply 3 DAT Voltage | TSI: do not overwrite | V | Read | |
| AV | 729 | Supply 4 DAT Voltage | TSI: do not overwrite | V | Read | |
| AV | 730 | Room Pressure Voltage | TSI: do not overwrite | V | Read | |
| AV | 731 | Relative Humidity Voltage | TSI: do not overwrite | V | Read | |
| AV | 732 | Supply 1 Room Temp Adjustment Voltage | TSI: do not overwrite | V | Read | |
| AV | 733 | Supply 2 Room Temp Adjustment Voltage | TSI: do not overwrite | V | Read | |
| AV | 734 | Supply 3 Room Temp Adjustment Voltage | TSI: do not overwrite | V | Read | |
| AV | 735 | Supply 4 Room Temp Adjustment Voltage | TSI: do not overwrite | V | Read | |
| AV | 736 | Supply 1 Flow Proportional Gain | Write | |||
| AV | 737 | Supply 2 Flow Proportional Gain | Write | |||
| AV | 738 | Supply 3 Flow Proportional Gain | Write | |||
| AV | 739 | Supply 4 Flow Proportional Gain | Write | |||
| AV | 740 | Exhaust 1 Flow Proportional Gain | Write | |||
| AV | 741 | Exhaust 2 Flow Proportional Gain | Write | |||
| AV | 742 | Supply 1 Flow Integral Time | Write | |||
| AV | 743 | Supply 2 Flow Integral Time | Write | |||
| AV | 744 | Supply 3 Flow Integral Time | Write | |||
| AV | 745 | Supply 4 Flow Integral Time | Write | |||
| AV | 746 | Exhaust 1 Flow Integral Time | Write | |||
| AV | 747 | Exhaust 2 Flow Integral Time | Write | |||
| AV | 748 | Pressure Control Gain | Write | |||
| AV | 749 | Supply 1 Temp Throttling Range | °F | Write | ||
| AV | 750 | Supply 2 Temp Throttling Range | °F | Write | ||
| AV | 751 | Supply 3 Temp Throttling Range | °F | Write | ||
| AV | 752 | Supply 4 Temp Throttling Range | °F | Write | ||
| AV | 753 | Supply 1 Temp Integral Time | s | Write | ||
| AV | 754 | Supply 2 Temp Integral Time | s | Write | ||
| AV | 755 | Supply 3 Temp Integral Time | s | Write | ||
| AV | 756 | Supply 4 Temp Integral Time | s | Write | ||
| AV | 757 | Supply 1 Flow Speed | % | Write | ||
| AV | 758 | Supply 2 Flow Speed | % | Write | ||
| AV | 759 | Supply 3 Flow Speed | % | Write | ||
| AV | 760 | Supply 4 Flow Speed | % | Write | ||
| AV | 761 | Exhaust 1 Flow Speed | % | Write | ||
| AV | 762 | Exhaust 2 Flow Speed | % | Write | ||
| AV | 763 | Supply 1 Flow Sensitivity | % | Write | ||
| AV | 764 | Supply 2 Flow Sensitivity | % | Write | ||
| AV | 765 | Supply 3 Flow Sensitivity | % | Write | ||
| AV | 766 | Supply 4 Flow Sensitivity | % | Write | ||
| AV | 767 | Exhaust 1 Flow Sensitivity | % | Write | ||
| AV | 768 | Exhaust 2 Flow Sensitivity | % | Write | ||
| AV | 769 | Supply 1 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 770 | Supply 1 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 771 | Supply 2 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 772 | Supply 2 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 773 | Supply 3 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 774 | Supply 3 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 775 | Supply 4 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 776 | Supply 4 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 777 | Exhaust 1 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 778 | Exhaust 1 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 779 | Exhaust 2 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 780 | Exhaust 2 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 781 | Exhaust 1 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 782 | Exhaust 1 Unocc High Flow Alarm | CFM | Write | ||
| AV | 783 | Exhaust 2 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 784 | Exhaust 2 Unocc High Flow Alarm | CFM | Write | ||
| AV | 785 | Current Exhaust 1 Low Flow Alarm | CFM | Write | ||
| AV | 786 | Current Exhaust 1 High Flow Alarm | CFM | Write | ||
| AV | 787 | Current Exhaust 2 Low Flow Alarm | CFM | Write | ||
| AV | 788 | Current Exhaust 2 High Flow Alarm | CFM | Write | ||
| AV | 789 | Hood 8 Flow | CFM | Write | ||
| AV | 790 | Hood 9 Flow | CFM | Write | ||
| AV | 791 | Hood 10 Flow | CFM | Write | ||
| AV | 792 | Hood 11 Flow | CFM | Write | ||
| AV | 793 | Hood 12 Flow | CFM | Write | ||
| AV | 794 | Hood 13 Flow | CFM | Write | ||
| AV | 795 | Hood 14 Flow | CFM | Write | ||
| AV | 796 | Hood 15 Flow | CFM | Write | ||
| AV | 797 | Hood 16 Flow | CFM | Write | ||
| AV | 798 | Hood 17 Flow | CFM | Write | ||
| AV | 799 | Hood 18 Flow | CFM | Write | ||
| AV | 800 | Hood 19 Flow | CFM | Write | ||
| AV | 801 | Hood 20 Flow | CFM | Write | ||
| AV | 802 | Hood 8 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 803 | Hood 9 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 804 | Hood 10 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 805 | Hood 11 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 806 | Hood 12 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 807 | Hood 13 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 808 | Hood 14 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 809 | Hood 15 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 810 | Hood 16 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 811 | Hood 17 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 812 | Hood 18 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 813 | Hood 19 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 814 | Hood 20 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 815 | Hood 8 Venturi Minimum Flow | CFM | Write | ||
| AV | 816 | Hood 8 Venturi Maximum Flow | CFM | Write | ||
| AV | 817 | Hood 8 Venturi LOM ESC Time | s | Write | ||
| AV | 818 | Hood 8 Linear Duct Area | ft² | Write | ||
| AV | 819 | Hood 8 Linear Top Velocity | ft/min | Write | ||
| AV | 820 | Hood 8 Linear Signal Minimum | V | Write | ||
| AV | 821 | Hood 8 Linear Signal Maximum | V | Write | ||
| AV | 822 | Hood 8 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 823 | Hood 8 Transducer Signal Minimum | V | Write | ||
| AV | 824 | Hood 8 Transducer Signal Maximum | V | Write | ||
| AV | 825 | Hood 8 Pitot Duct Area | ft² | Write | ||
| AV | 826 | Hood 8 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 827 | Hood 8 Pitot Low Cal Flow | CFM | Write | ||
| AV | 828 | Hood 8 Pitot High Cal Flow | CFM | Write | ||
| AV | 829 | Hood 8 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 830 | Hood 8 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 831 | Hood 8 TP Min Flow | CFM | Write | ||
| AV | 832 | Hood 8 TP Max Flow | CFM | Write | ||
| AV | 833 | Hood 9 Venturi Minimum Flow | CFM | Write | ||
| AV | 834 | Hood 9 Venturi Maximum Flow | CFM | Write | ||
| AV | 835 | Hood 9 Venturi LOM ESC Time | s | Write | ||
| AV | 836 | Hood 9 Linear Duct Area | ft² | Write | ||
| AV | 837 | Hood 9 Linear Top Velocity | ft/min | Write | ||
| AV | 838 | Hood 9 Linear Signal Minimum | V | Write | ||
| AV | 839 | Hood 9 Linear Signal Maximum | V | Write | ||
| AV | 840 | Hood 9 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 841 | Hood 9 Transducer Signal Minimum | V | Write | ||
| AV | 842 | Hood 9 Transducer Signal Maximum | V | Write | ||
| AV | 843 | Hood 9 Pitot Duct Area | ft² | Write | ||
| AV | 844 | Hood 9 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 845 | Hood 9 Pitot Low Cal Flow | CFM | Write | ||
| AV | 846 | Hood 9 Pitot High Cal Flow | CFM | Write | ||
| AV | 847 | Hood 9 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 848 | Hood 9 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 849 | Hood 9 TP Min Flow | CFM | Write | ||
| AV | 850 | Hood 9 TP Max Flow | CFM | Write | ||
| AV | 851 | Hood 10 Venturi Minimum Flow | CFM | Write | ||
| AV | 852 | Hood 10 Venturi Maximum Flow | CFM | Write | ||
| AV | 853 | Hood 10 Venturi LOM ESC Time | s | Write | ||
| AV | 854 | Hood 10 Linear Duct Area | ft² | Write | ||
| AV | 855 | Hood 10 Linear Top Velocity | ft/min | Write | ||
| AV | 856 | Hood 10 Linear Signal Minimum | V | Write | ||
| AV | 857 | Hood 10 Linear Signal Maximum | V | Write | ||
| AV | 858 | Hood 10 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 859 | Hood 10 Transducer Signal Minimum | V | Write | ||
| AV | 860 | Hood 10 Transducer Signal Maximum | V | Write | ||
| AV | 861 | Hood 10 Pitot Duct Area | ft² | Write | ||
| AV | 862 | Hood 10 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 863 | Hood 10 Pitot Low Cal Flow | CFM | Write | ||
| AV | 864 | Hood 10 Pitot High Cal Flow | CFM | Write | ||
| AV | 865 | Hood 10 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 866 | Hood 10 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 867 | Hood 10 TP Min Flow | CFM | Write | ||
| AV | 868 | Hood 10 TP Max Flow | CFM | Write | ||
| AV | 869 | Hood 11 Venturi Minimum Flow | CFM | Write | ||
| AV | 870 | Hood 11 Venturi Maximum Flow | CFM | Write | ||
| AV | 871 | Hood 11 Venturi LOM ESC Time | s | Write | ||
| AV | 872 | Hood 11 Linear Duct Area | ft² | Write | ||
| AV | 873 | Hood 11 Linear Top Velocity | ft/min | Write | ||
| AV | 874 | Hood 11 Linear Signal Minimum | V | Write | ||
| AV | 875 | Hood 11 Linear Signal Maximum | V | Write | ||
| AV | 876 | Hood 11 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 877 | Hood 11 Transducer Signal Minimum | V | Write | ||
| AV | 878 | Hood 11 Transducer Signal Maximum | V | Write | ||
| AV | 879 | Hood 11 Pitot Duct Area | ft² | Write | ||
| AV | 880 | Hood 11 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 881 | Hood 11 Pitot Low Cal Flow | CFM | Write | ||
| AV | 882 | Hood 11 Pitot High Cal Flow | CFM | Write | ||
| AV | 883 | Hood 11 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 884 | Hood 11 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 885 | Hood 11 TP Min Flow | CFM | Write | ||
| AV | 886 | Hood 11 TP Max Flow | CFM | Write | ||
| AV | 887 | Hood 12 Venturi Minimum Flow | CFM | Write | ||
| AV | 888 | Hood 12 Venturi Maximum Flow | CFM | Write | ||
| AV | 889 | Hood 12 Venturi LOM ESC Time | s | Write | ||
| AV | 890 | Hood 12 Linear Duct Area | ft² | Write | ||
| AV | 891 | Hood 12 Linear Top Velocity | ft/min | Write | ||
| AV | 892 | Hood 12 Linear Signal Minimum | V | Write | ||
| AV | 893 | Hood 12 Linear Signal Maximum | V | Write | ||
| AV | 894 | Hood 12 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 895 | Hood 12 Transducer Signal Minimum | V | Write | ||
| AV | 896 | Hood 12 Transducer Signal Maximum | V | Write | ||
| AV | 897 | Hood 12 Pitot Duct Area | ft² | Write | ||
| AV | 898 | Hood 12 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 899 | Hood 12 Pitot Low Cal Flow | CFM | Write | ||
| AV | 900 | Hood 12 Pitot High Cal Flow | CFM | Write | ||
| AV | 901 | Hood 12 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 902 | Hood 12 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 903 | Hood 12 TP Min Flow | CFM | Write | ||
| AV | 904 | Hood 12 TP Max Flow | CFM | Write | ||
| AV | 905 | Hood 13 Venturi Minimum Flow | CFM | Write | ||
| AV | 906 | Hood 13 Venturi Maximum Flow | CFM | Write | ||
| AV | 907 | Hood 13 Venturi LOM ESC Time | s | Write | ||
| AV | 908 | Hood 13 Linear Duct Area | ft² | Write | ||
| AV | 909 | Hood 13 Linear Top Velocity | ft/min | Write | ||
| AV | 910 | Hood 13 Linear Signal Minimum | V | Write | ||
| AV | 911 | Hood 13 Linear Signal Maximum | V | Write | ||
| AV | 912 | Hood 13 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 913 | Hood 13 Transducer Signal Minimum | V | Write | ||
| AV | 914 | Hood 13 Transducer Signal Maximum | V | Write | ||
| AV | 915 | Hood 13 Pitot Duct Area | ft² | Write | ||
| AV | 916 | Hood 13 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 917 | Hood 13 Pitot Low Cal Flow | CFM | Write | ||
| AV | 918 | Hood 13 Pitot High Cal Flow | CFM | Write | ||
| AV | 919 | Hood 13 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 920 | Hood 13 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 921 | Hood 13 TP Min Flow | CFM | Write | ||
| AV | 922 | Hood 13 TP Max Flow | CFM | Write | ||
| AV | 923 | Hood 14 Venturi Minimum Flow | CFM | Write | ||
| AV | 924 | Hood 14 Venturi Maximum Flow | CFM | Write | ||
| AV | 925 | Hood 14 Venturi LOM ESC Time | s | Write | ||
| AV | 926 | Hood 14 Linear Duct Area | ft² | Write | ||
| AV | 927 | Hood 14 Linear Top Velocity | ft/min | Write | ||
| AV | 928 | Hood 14 Linear Signal Minimum | V | Write | ||
| AV | 929 | Hood 14 Linear Signal Maximum | V | Write | ||
| AV | 930 | Hood 14 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 931 | Hood 14 Transducer Signal Minimum | V | Write | ||
| AV | 932 | Hood 14 Transducer Signal Maximum | V | Write | ||
| AV | 933 | Hood 14 Pitot Duct Area | ft² | Write | ||
| AV | 934 | Hood 14 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 935 | Hood 14 Pitot Low Cal Flow | CFM | Write | ||
| AV | 936 | Hood 14 Pitot High Cal Flow | CFM | Write | ||
| AV | 937 | Hood 14 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 938 | Hood 14 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 939 | Hood 14 TP Min Flow | CFM | Write | ||
| AV | 940 | Hood 14 TP Max Flow | CFM | Write | ||
| AV | 941 | Hood 15 Venturi Minimum Flow | CFM | Write | ||
| AV | 942 | Hood 15 Venturi Maximum Flow | CFM | Write | ||
| AV | 943 | Hood 15 Venturi LOM ESC Time | s | Write | ||
| AV | 944 | Hood 15 Linear Duct Area | ft² | Write | ||
| AV | 945 | Hood 15 Linear Top Velocity | ft/min | Write | ||
| AV | 946 | Hood 15 Linear Signal Minimum | V | Write | ||
| AV | 947 | Hood 15 Linear Signal Maximum | V | Write | ||
| AV | 948 | Hood 15 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 949 | Hood 15 Transducer Signal Minimum | V | Write | ||
| AV | 950 | Hood 15 Transducer Signal Maximum | V | Write | ||
| AV | 951 | Hood 15 Pitot Duct Area | ft² | Write | ||
| AV | 952 | Hood 15 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 953 | Hood 15 Pitot Low Cal Flow | CFM | Write | ||
| AV | 954 | Hood 15 Pitot High Cal Flow | CFM | Write | ||
| AV | 955 | Hood 15 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 956 | Hood 15 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 957 | Hood 15 TP Min Flow | CFM | Write | ||
| AV | 958 | Hood 15 TP Max Flow | CFM | Write | ||
| AV | 959 | Hood 16 Venturi Minimum Flow | CFM | Write | ||
| AV | 960 | Hood 16 Venturi Maximum Flow | CFM | Write | ||
| AV | 961 | Hood 16 Venturi LOM ESC Time | s | Write | ||
| AV | 962 | Hood 16 Linear Duct Area | ft² | Write | ||
| AV | 963 | Hood 16 Linear Top Velocity | ft/min | Write | ||
| AV | 964 | Hood 16 Linear Signal Minimum | V | Write | ||
| AV | 965 | Hood 16 Linear Signal Maximum | V | Write | ||
| AV | 966 | Hood 16 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 967 | Hood 16 Transducer Signal Minimum | V | Write | ||
| AV | 968 | Hood 16 Transducer Signal Maximum | V | Write | ||
| AV | 969 | Hood 16 Pitot Duct Area | ft² | Write | ||
| AV | 970 | Hood 16 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 971 | Hood 16 Pitot Low Cal Flow | CFM | Write | ||
| AV | 972 | Hood 16 Pitot High Cal Flow | CFM | Write | ||
| AV | 973 | Hood 16 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 974 | Hood 16 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 975 | Hood 16 TP Min Flow | CFM | Write | ||
| AV | 976 | Hood 16 TP Max Flow | CFM | Write | ||
| AV | 977 | Hood 17 Venturi Minimum Flow | CFM | Write | ||
| AV | 978 | Hood 17 Venturi Maximum Flow | CFM | Write | ||
| AV | 979 | Hood 17 Venturi LOM ESC Time | s | Write | ||
| AV | 980 | Hood 17 Linear Duct Area | ft² | Write | ||
| AV | 981 | Hood 17 Linear Top Velocity | ft/min | Write | ||
| AV | 982 | Hood 17 Linear Signal Minimum | V | Write | ||
| AV | 983 | Hood 17 Linear Signal Maximum | V | Write | ||
| AV | 984 | Hood 17 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 985 | Hood 17 Transducer Signal Minimum | V | Write | ||
| AV | 986 | Hood 17 Transducer Signal Maximum | V | Write | ||
| AV | 987 | Hood 17 Pitot Duct Area | ft² | Write | ||
| AV | 988 | Hood 17 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 989 | Hood 17 Pitot Low Cal Flow | CFM | Write | ||
| AV | 990 | Hood 17 Pitot High Cal Flow | CFM | Write | ||
| AV | 991 | Hood 17 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 992 | Hood 17 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 993 | Hood 17 TP Min Flow | CFM | Write | ||
| AV | 994 | Hood 17 TP Max Flow | CFM | Write | ||
| AV | 995 | Hood 18 Venturi Minimum Flow | CFM | Write | ||
| AV | 996 | Hood 18 Venturi Maximum Flow | CFM | Write | ||
| AV | 997 | Hood 18 Venturi LOM ESC Time | s | Write | ||
| AV | 998 | Hood 18 Linear Duct Area | ft² | Write | ||
| AV | 999 | Hood 18 Linear Top Velocity | ft/min | Write | ||
| AV | 1000 | Hood 18 Linear Signal Minimum | V | Write | ||
| AV | 1001 | Hood 18 Linear Signal Maximum | V | Write | ||
| AV | 1002 | Hood 18 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 1003 | Hood 18 Transducer Signal Minimum | V | Write | ||
| AV | 1004 | Hood 18 Transducer Signal Maximum | V | Write | ||
| AV | 1005 | Hood 18 Pitot Duct Area | ft² | Write | ||
| AV | 1006 | Hood 18 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 1007 | Hood 18 Pitot Low Cal Flow | CFM | Write | ||
| AV | 1008 | Hood 18 Pitot High Cal Flow | CFM | Write | ||
| AV | 1009 | Hood 18 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1010 | Hood 18 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1011 | Hood 18 TP Min Flow | CFM | Write | ||
| AV | 1012 | Hood 18 TP Max Flow | CFM | Write | ||
| AV | 1013 | Hood 19 Venturi Minimum Flow | CFM | Write | ||
| AV | 1014 | Hood 19 Venturi Maximum Flow | CFM | Write | ||
| AV | 1015 | Hood 19 Venturi LOM ESC Time | s | Write | ||
| AV | 1016 | Hood 19 Linear Duct Area | ft² | Write | ||
| AV | 1017 | Hood 19 Linear Top Velocity | ft/min | Write | ||
| AV | 1018 | Hood 19 Linear Signal Minimum | V | Write | ||
| AV | 1019 | Hood 19 Linear Signal Maximum | V | Write | ||
| AV | 1020 | Hood 19 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 1021 | Hood 19 Transducer Signal Minimum | V | Write | ||
| AV | 1022 | Hood 19 Transducer Signal Maximum | V | Write | ||
| AV | 1023 | Hood 19 Pitot Duct Area | ft² | Write | ||
| AV | 1024 | Hood 19 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 1025 | Hood 19 Pitot Low Cal Flow | CFM | Write | ||
| AV | 1026 | Hood 19 Pitot High Cal Flow | CFM | Write | ||
| AV | 1027 | Hood 19 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1028 | Hood 19 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1029 | Hood 19 TP Min Flow | CFM | Write | ||
| AV | 1030 | Hood 19 TP Max Flow | CFM | Write | ||
| AV | 1031 | Hood 20 Venturi Minimum Flow | CFM | Write | ||
| AV | 1032 | Hood 20 Venturi Maximum Flow | CFM | Write | ||
| AV | 1033 | Hood 20 Venturi LOM ESC Time | s | Write | ||
| AV | 1034 | Hood 20 Linear Duct Area | ft² | Write | ||
| AV | 1035 | Hood 20 Linear Top Velocity | ft/min | Write | ||
| AV | 1036 | Hood 20 Linear Signal Minimum | V | Write | ||
| AV | 1037 | Hood 20 Linear Signal Maximum | V | Write | ||
| AV | 1038 | Hood 20 Pitot Sensor Zero | TSI: do not overwrite | V | Read | |
| AV | 1039 | Hood 20 Transducer Signal Minimum | V | Write | ||
| AV | 1040 | Hood 20 Transducer Signal Maximum | V | Write | ||
| AV | 1041 | Hood 20 Pitot Duct Area | ft² | Write | ||
| AV | 1042 | Hood 20 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 1043 | Hood 20 Pitot Low Cal Flow | CFM | Write | ||
| AV | 1044 | Hood 20 Pitot High Cal Flow | CFM | Write | ||
| AV | 1045 | Hood 20 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1046 | Hood 20 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1047 | Hood 20 TP Min Flow | CFM | Write | ||
| AV | 1048 | Hood 20 TP Max Flow | CFM | Write | ||
| AV | 1049 | Hood 8 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1050 | Hood 8 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1051 | Hood 9 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1052 | Hood 9 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1053 | Hood 10 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1054 | Hood 10 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1055 | Hood 11 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1056 | Hood 11 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1057 | Hood 12 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1058 | Hood 12 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1059 | Hood 13 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1060 | Hood 13 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1061 | Hood 14 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1062 | Hood 14 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1063 | Hood 15 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1064 | Hood 15 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1065 | Hood 16 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1066 | Hood 16 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1067 | Hood 17 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1068 | Hood 17 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1069 | Hood 18 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1070 | Hood 18 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1071 | Hood 19 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1072 | Hood 19 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1073 | Hood 20 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1074 | Hood 20 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1075 | Hood 8 Flow K factor | Write | |||
| AV | 1076 | Hood 9 Flow K factor | Write | |||
| AV | 1077 | Hood 10 Flow K factor | Write | |||
| AV | 1078 | Hood 11 Flow K factor | Write | |||
| AV | 1079 | Hood 12 Flow K factor | Write | |||
| AV | 1080 | Hood 13 Flow K factor | Write | |||
| AV | 1081 | Hood 14 Flow K factor | Write | |||
| AV | 1082 | Hood 15 Flow K factor | Write | |||
| AV | 1083 | Hood 16 Flow K factor | Write | |||
| AV | 1084 | Hood 17 Flow K factor | Write | |||
| AV | 1085 | Hood 18 Flow K factor | Write | |||
| AV | 1086 | Hood 19 Flow K factor | Write | |||
| AV | 1087 | Hood 20 Flow K factor | Write | |||
| AV | 1088 | Supply 1 Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1089 | Supply 2 Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1090 | Supply 3 Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1091 | Supply 4 Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1092 | Exhaust 1 Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1093 | Exhaust 2 Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1094 | Supply 5 Flow Proportional Gain | Write | |||
| AV | 1095 | Supply 5 Flow Integral Time | s | Write | ||
| AV | 1096 | Supply 5 Flow Speed | % | Write | ||
| AV | 1097 | Supply 5 Flow Sensitivity | % | Write | ||
| AV | 1098 | Supply 6 Flow Proportional Gain | Write | |||
| AV | 1099 | Supply 6 Flow Integral Time | s | Write | ||
| AV | 1100 | Supply 6 Flow Speed | % | Write | ||
| AV | 1101 | Supply 6 Flow Sensitivity | % | Write | ||
| AV | 1102 | Supply 5 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1103 | Supply 5 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1104 | Supply 5 Venturi Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1105 | Supply 5 Venturi Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1106 | Supply 5 Flow K Factor | Write | |||
| AV | 1107 | Supply 5 Venturi Setup Position | % | Write | ||
| AV | 1108 | Supply 5 Venturi LOM Esc Time | s | Write | ||
| AV | 1109 | Supply 5 Linear Duct Area | ft² | Write | ||
| AV | 1110 | Supply 5 Linear Top Velocity | ft/min | Write | ||
| AV | 1111 | Supply 5 Linear Signal Minimum | V | Write | ||
| AV | 1112 | Supply 5 Linear Signal Maximum | V | Write | ||
| AV | 1113 | Supply 5 Pitot Sensor Zero | V | Write | ||
| AV | 1114 | Supply 5 Pitot Low Cal Pos | % | Write | ||
| AV | 1115 | Supply 5 Transducer Signal Minimum | V | Write | ||
| AV | 1116 | Supply 5 Pitot High Cal Pos | % | Write | ||
| AV | 1117 | Supply 5 Transducer Signal Maximum | V | Write | ||
| AV | 1118 | Supply 5 Pitot Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1119 | Supply 5 Pitot Duct Area | ft² | Write | ||
| AV | 1120 | Supply 5 Pitot High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1121 | Supply 5 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 1122 | Supply 6 Pitot Uncal Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1123 | Supply 6 Pitot Uncal High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1124 | Supply 6 Venturi Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1125 | Supply 6 Venturi Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1126 | Supply 6 Flow K Factor | Write | |||
| AV | 1127 | Supply 6 Venturi Setup Position | % | Write | ||
| AV | 1128 | Supply 6 Venturi LOM Esc Time | s | Write | ||
| AV | 1129 | Supply 6 Linear Duct Area | ft² | Write | ||
| AV | 1130 | Supply 6 Linear Top Velocity | Write | |||
| AV | 1131 | Supply 6 Linear Signal Minimum | V | Write | ||
| AV | 1132 | Supply 6 Linear Signal Maximum | V | Write | ||
| AV | 1133 | Supply 6 Pitot Sensor Zero | V | Write | ||
| AV | 1134 | Supply 6 Pitot Low Cal Pos | % | Write | ||
| AV | 1135 | Supply 6 Transducer Signal Minimum | V | Write | ||
| AV | 1136 | Supply 6 Pitot High Cal Pos | % | Write | ||
| AV | 1137 | Supply 6 Transducer Signal Maximum | V | Write | ||
| AV | 1138 | Supply 6 Pitot Low Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1139 | Supply 6 Pitot Duct Area | ft² | Write | ||
| AV | 1140 | Supply 6 Pitot High Cal Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1141 | Supply 6 Transducer Sensor Maximum | in. W.C. | Write | ||
| AV | 1142 | Supply 5 Room Temp Offset | °F | Write | ||
| AV | 1143 | Supply 6 Room Temp Offset | °F | Write | ||
| AV | 1144 | Supply 5 Room Temp Adj Signal Minimum | V | Write | ||
| AV | 1145 | Supply 5 Room Temp Adj Signal Maximum | V | Write | ||
| AV | 1146 | Supply 5 Room Temp Adj Sensor Minimum | °F | Write | ||
| AV | 1147 | Supply 5 Room Temp Adj Sensor Maximum | °F | Write | ||
| AV | 1148 | Supply 6 Room Temp Adj Signal Minimum | V | Write | ||
| AV | 1149 | Supply 6 Room Temp Adj Signal Maximum | V | Write | ||
| AV | 1150 | Supply 6 Room Temp Adj Sensor Minimum | °F | Write | ||
| AV | 1151 | Supply 6 Room Temp Adj Sensor Maximum | °F | Write | ||
| AV | 1152 | Supply 5 Reheat/Cooling Delay | s | Write | ||
| AV | 1153 | Supply 6 Reheat/Cooling Delay | s | Write | ||
| AV | 1154 | Supply 5 Room Temp Signal Minimum | V | Write | ||
| AV | 1155 | Supply 5 Room Temp Signal Maximum | V | Write | ||
| AV | 1156 | Supply 5 Room Temp Sensor Minimum | °F | Write | ||
| AV | 1157 | Supply 5 Room Temp Sensor Maximum | °F | Write | ||
| AV | 1158 | Supply 6 Room Temp Signal Minimum | V | Write | ||
| AV | 1159 | Supply 6 Room Temp Signal Maximum | V | Write | ||
| AV | 1160 | Supply 6 Room Temp Sensor Minimum | °F | Write | ||
| AV | 1161 | Supply 6 Room Temp Sensor Maximum | °F | Write | ||
| AV | 1162 | Supply 5 Temp Throttling Range | °F | Write | ||
| AV | 1163 | Supply 6 Temp Throttling Range | °F | Write | ||
| AV | 1164 | Supply 5 Temp Integral Time | s | Write | ||
| AV | 1165 | Supply 6 Temp Integral Time | s | Write | ||
| AV | 1166 | Current Supply 5 Minimum Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1167 | Current Supply 5 Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1168 | Current Supply 5 Cooling Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1169 | Current Supply 5 Heating Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1170 | Current Supply 5 Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1171 | Current Supply 6 Minimum Flow Setpoint | TSI: do not overwrite | CFM | Read | |
| AV | 1172 | Current Supply 6 Minimum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1173 | Current Supply 6 Cooling Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1174 | Current Supply 6 Heating Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1175 | Current Supply 6 Maximum Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1176 | Current Supply 5 Heat Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 1177 | Current Supply 5 Cool Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 1178 | Current Supply 6 Heat Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 1179 | Current Supply 6 Cool Setpoint | TSI: do not overwrite | °F | Read | |
| AV | 1180 | Supply 5 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1181 | Supply 6 Flow | TSI: do not overwrite | CFM | Read | |
| AV | 1182 | Current Supply 5 Temperature Control Position | TSI: do not overwrite | % | Read | |
| AV | 1183 | Current Supply 5 Flow Control Position | TSI: do not overwrite | % | Read | |
| AV | 1184 | Current Supply 6 Temperature Control Position | TSI: do not overwrite | % | Read | |
| AV | 1185 | Current Supply 6 Flow Control Position | TSI: do not overwrite | % | Read | |
| AV | 1186 | Supply 5 Room Temp | TSI: do not overwrite | °F | Read | |
| AV | 1187 | Supply 6 Room Temp | TSI: do not overwrite | °F | Read | |
| AV | 1188 | Supply 5 Room Temp Adj | TSI: do not overwrite | °F | Read | |
| AV | 1189 | Supply 6 Room Temp Adj | TSI: do not overwrite | °F | Read | |
| AV | 1190 | Supply 5 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 1191 | Supply 6 Flow Voltage | TSI: do not overwrite | V | Read | |
| AV | 1192 | Supply 5 Room Temp Voltage | TSI: do not overwrite | V | Read | |
| AV | 1193 | Supply 6 Room Temp Voltage | TSI: do not overwrite | V | Read | |
| AV | 1194 | Supply 5 Room Temp Adjustment Voltage | TSI: do not overwrite | V | Read | |
| AV | 1195 | Supply 6 Room Temp Adjustment Voltage | TSI: do not overwrite | V | Read | |
| AV | 1196 | Supply 5 Flow Setpoint | CFM | Write | ||
| AV | 1197 | Supply 6 Flow Setpoint | CFM | Write | ||
| AV | 1198 | Supply 5 Minimum Flow | CFM | Write | ||
| AV | 1199 | Supply 5 Cooling Flow | CFM | Write | ||
| AV | 1200 | Supply 5 Heating Flow | CFM | Write | ||
| AV | 1201 | Supply 5 Maximum Flow | CFM | Write | ||
| AV | 1202 | Supply 5 Minimum Position | % | Write | ||
| AV | 1203 | Supply 5 Maximum Position | % | Write | ||
| AV | 1204 | Supply 5 Emergency Flow | CFM | Write | ||
| AV | 1205 | Supply 5 Shutdown Flow | CFM | Write | ||
| AV | 1206 | Supply 6 Minimum Flow | CFM | Write | ||
| AV | 1207 | Supply 6 Cooling Flow | CFM | Write | ||
| AV | 1208 | Supply 6 Heating Flow | CFM | Write | ||
| AV | 1209 | Supply 6 Maximum Flow | CFM | Write | ||
| AV | 1210 | Supply 6 Minimum Position | % | Write | ||
| AV | 1211 | Supply 6 Maximum Position | % | Write | ||
| AV | 1212 | Supply 6 Emergency Flow | CFM | Write | ||
| AV | 1213 | Supply 6 Shutdown Flow | CFM | Write | ||
| AV | 1214 | Supply 5 Heat Setpoint | °F | Write | ||
| AV | 1215 | Supply 5 Cool Setpoint | °F | Write | ||
| AV | 1216 | Supply 6 Heat Setpoint | °F | Write | ||
| AV | 1217 | Supply 6 Cool Setpoint | °F | Write | ||
| AV | 1218 | Supply 5 Low Flow Alarm | CFM | Write | ||
| AV | 1219 | Supply 5 High Flow Alarm | CFM | Write | ||
| AV | 1220 | Supply 6 Low Flow Alarm | CFM | Write | ||
| AV | 1221 | Supply 6 High Flow Alarm | CFM | Write | ||
| AV | 1222 | Supply 5 Low Temperature Alarm | °F | Write | ||
| AV | 1223 | Supply 5 High Temperature Alarm | °F | Write | ||
| AV | 1224 | Supply 6 Low Temperature Alarm | °F | Write | ||
| AV | 1225 | Supply 6 High Temperature Alarm | °F | Write | ||
| AV | 1226 | Supply 5 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 1227 | Supply 5 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 1228 | Supply 6 Shutdown Low Flow Alarm | CFM | Write | ||
| AV | 1229 | Supply 6 Shutdown High Flow Alarm | CFM | Write | ||
| AV | 1230 | Supply 5 Flow Change | CFM | Write | ||
| AV | 1231 | Supply 6 Flow Change | CFM | Write | ||
| AV | 1232 | Supply 5 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 1233 | Supply 5 Room Temp Input Number | TSI: do not overwrite | Read | ||
| AV | 1234 | Supply 5 Room Temp Adj Input Number | TSI: do not overwrite | Read | ||
| AV | 1235 | Supply 6 Flow Input Number | TSI: do not overwrite | Read | ||
| AV | 1236 | Supply 6 Room Temp Input Number | TSI: do not overwrite | Read | ||
| AV | 1237 | Supply 6 Room Temp Adj Input Number | TSI: do not overwrite | Read | ||
| AV | 1238 | Current Supply 5 Low Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 1239 | Current Supply 5 High Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 1240 | Current Supply 6 Low Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 1241 | Current Supply 6 High Flow Alarm | TSI: do not overwrite | CFM | Read | |
| AV | 1242 | Current Supply 5 Low Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 1243 | Current Supply 5 High Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 1244 | Current Supply 6 Low Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 1245 | Current Supply 6 High Temperature Alarm | TSI: do not overwrite | °F | Read | |
| AV | 1246 | Supply 5 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1247 | Supply 5 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1248 | Supply 6 Pitot Low Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1249 | Supply 6 Pitot High Cal Voltage | TSI: do not overwrite | V | Read | |
| AV | 1250 | Supply 5 DAT Offset | °F | Write | ||
| AV | 1251 | Supply 6 DAT Offset | °F | Write | ||
| AV | 1252 | Supply 5 Unocc Minimum Flow | CFM | Write | ||
| AV | 1253 | Supply 5 Unocc Cooling Flow | CFM | Write | ||
| AV | 1254 | Supply 5 Unocc Heating Flow | CFM | Write | ||
| AV | 1255 | Supply 5 Unocc Maximum Flow | CFM | Write | ||
| AV | 1256 | Supply 6 Unocc Minimum Flow | CFM | Write | ||
| AV | 1257 | Supply 6 Unocc Cooling Flow | CFM | Write | ||
| AV | 1258 | Supply 6 Unocc Heating Flow | CFM | Write | ||
| AV | 1259 | Supply 6 Unocc Maximum Flow | CFM | Write | ||
| AV | 1260 | Supply 5 Unocc Heat Setpoint | °F | Write | ||
| AV | 1261 | Supply 5 Unocc Cool Setpoint | °F | Write | ||
| AV | 1262 | Supply 5 DAT Delta | °F | Write | ||
| AV | 1263 | Supply 6 Unocc Heat Setpoint | °F | Write | ||
| AV | 1264 | Supply 6 Unocc Cool Setpoint | °F | Write | ||
| AV | 1265 | Supply 6 DAT Delta | °F | Write | ||
| AV | 1266 | Supply 5 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 1267 | Supply 5 Unocc High Flow Alarm | CFM | Write | ||
| AV | 1268 | Supply 6 Unocc Low Flow Alarm | CFM | Write | ||
| AV | 1269 | Supply 6 Unocc High Flow Alarm | CFM | Write | ||
| AV | 1270 | Supply 5 Unocc Low Temperature Alarm | °F | Write | ||
| AV | 1271 | Supply 5 Unocc High Temperature Alarm | °F | Write | ||
| AV | 1272 | Supply 6 Unocc Low Temperature Alarm | °F | Write | ||
| AV | 1273 | Supply 6 Unocc High Temperature Alarm | °F | Write | ||
| AV | 1274 | Supply 5 High DAT Alarm | °F | Write | ||
| AV | 1275 | Supply 6 High DAT Alarm | °F | Write | ||
| AV | 1276 | Supply 5 DAT Signal Minimum | V | Write | ||
| AV | 1277 | Supply 5 DAT Signal Maximum | V | Write | ||
| AV | 1278 | Supply 5 DAT Sensor Minimum | °F | Write | ||
| AV | 1279 | Supply 5 DAT Sensor Maximum | °F | Write | ||
| AV | 1280 | Supply 6 DAT Signal Minimum | V | Write | ||
| AV | 1281 | Supply 6 DAT Signal Maximum | V | Write | ||
| AV | 1282 | Supply 6 DAT Sensor Minimum | °F | Write | ||
| AV | 1283 | Supply 6 DAT Sensor Maximum | °F | Write | ||
| AV | 1284 | Supply 5 DAT Input Number | TSI: do not overwrite | Read | ||
| AV | 1285 | Supply 5 Occupancy Input Number | TSI: do not overwrite | Read | ||
| AV | 1286 | Supply 6 DAT Input Number | TSI: do not overwrite | Read | ||
| AV | 1287 | Supply 6 Occupancy Input Number | TSI: do not overwrite | Read | ||
| AV | 1288 | Supply 5 DAT | TSI: do not overwrite | °F | Read | |
| AV | 1289 | Supply 6 DAT | TSI: do not overwrite | °F | Read | |
| AV | 1290 | Supply 5 DAT Voltage | TSI: do not overwrite | V | Read | |
| AV | 1291 | Supply 6 DAT Voltage | TSI: do not overwrite | V | Read | |
| BV | 1 | Reset Variables | Write | 0=No, 1=Yes | ||
| BV | 2 | Reset Control | Write | 0=No, 1=Yes | ||
| BV | 3 | Supply 1 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 4 | Supply 2 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 5 | Supply 3 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 6 | Supply 4 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 7 | Supply 1 Temp Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 8 | Supply 2 Temp Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 9 | Supply 3 Temp Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 10 | Supply 4 Temp Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 11 | Exhaust 1 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 12 | Exhaust 2 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 15 | Supply 1 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 16 | Supply 2 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 17 | Supply 3 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 18 | Supply 4 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 19 | Exhaust 1 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 20 | Exhaust 2 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 21 | Door Mode | Write | 0=Closed, 1=Open | ||
| BVmin | 22 | Emergency Mode | Write | 0=Inactive, 1=Active | ||
| BV | 23 | Shutdown Mode | Write | 0=Inactive, 1=Active | ||
| BVmin | 24 | Supply 1 Occupancy Mode | Write | 0=Occupied, 1=Unoccupied | ||
| BV | 25 | Supply 2 Occupancy Mode | Write | 0=Occupied, 1=Unoccupied | ||
| BV | 26 | Supply 3 Occupancy Mode | Write | 0=Occupied, 1=Unoccupied | ||
| BV | 27 | Supply 4 Occupancy Mode | Write | 0=Occupied, 1=Unoccupied | ||
| BV | 28 | Supply 1 Venturi Visible | Write | |||
| BV | 29 | Supply 1 Linear Visible | Write | |||
| BV | 30 | Supply 1 Pitot Visible | Write | |||
| BV | 31 | Supply 2 Venturi Visible | Write | |||
| BV | 32 | Supply 2 Linear Visible | Write | |||
| BV | 33 | Supply 2 Pitot Visible | Write | |||
| BV | 34 | Supply 3 Venturi Visible | Write | |||
| BV | 35 | Supply 3 Linear Visible | Write | |||
| BV | 36 | Supply 3 Pitot Visible | Write | |||
| BV | 37 | Supply 4 Venturi Visible | Write | |||
| BV | 38 | Supply 4 Linear Visible | Write | |||
| BV | 39 | Supply 4 Pitot Visible | Write | |||
| BV | 40 | Exhaust 1 Venturi Visible | Write | |||
| BV | 41 | Exhaust 1 Linear Visible | Write | |||
| BV | 42 | Exhaust 1 Pitot Visible | Write | |||
| BV | 43 | Exhaust 2 Venturi Visible | Write | |||
| BV | 44 | Exhaust 2 Linear Visible | Write | |||
| BV | 45 | Exhaust 2 Pitot Visible | Write | |||
| BV | 46 | Supply 1 DAT RTD Visible | Write | |||
| BV | 47 | Supply 1 DAT Voltage Visible | Write | |||
| BV | 48 | Supply 2 DAT RTD Visible | Write | |||
| BV | 49 | Supply 2 DAT Voltage Visible | Write | |||
| BV | 50 | Supply 3 DAT RTD Visible | Write | |||
| BV | 51 | Supply 3 DAT Voltage Visible | Write | |||
| BV | 52 | Supply 4 DAT RTD Visible | Write | |||
| BV | 53 | Supply 4 DAT Voltage Visible | Write | |||
| BV | 54 | Room Pressure TTW Visible | Write | |||
| BV | 55 | Room Pressure Transducer Visible | Write | |||
| BV | 56 | Hood 1 Venturi Visible | Write | |||
| BV | 57 | Hood 1 Linear Visible | Write | |||
| BV | 58 | Hood 1 Pitot Visible | Write | |||
| BV | 59 | Hood 1 Two Position Visible | Write | |||
| BV | 60 | Hood 2 Venturi Visible | Write | |||
| BV | 61 | Hood 2 Linear Visible | Write | |||
| BV | 62 | Hood 2 Pitot Visible | Write | |||
| BV | 63 | Hood 2 Two Position Visible | Write | |||
| BV | 64 | Hood 3 Venturi Visible | Write | |||
| BV | 65 | Hood 3 Linear Visible | Write | |||
| BV | 66 | Hood 3 Pitot Visible | Write | |||
| BV | 67 | Hood 3 Two Position Visible | Write | |||
| BV | 68 | Hood 4 Venturi Visible | Write | |||
| BV | 69 | Hood 4 Linear Visible | Write | |||
| BV | 70 | Hood 4 Pitot Visible | Write | |||
| BV | 71 | Hood 4 Two Position Visible | Write | |||
| BV | 72 | Hood 5 Venturi Visible | Write | |||
| BV | 73 | Hood 5 Linear Visible | Write | |||
| BV | 74 | Hood 5 Pitot Visible | Write | |||
| BV | 75 | Hood 5 Two Position Visible | Write | |||
| BV | 76 | Hood 6 Venturi Visible | Write | |||
| BV | 77 | Hood 6 Linear Visible | Write | |||
| BV | 78 | Hood 6 Pitot Visible | Write | |||
| BV | 79 | Hood 6 Two Position Visible | Write | |||
| BV | 80 | Hood 7 Venturi Visible | Write | |||
| BV | 81 | Hood 7 Linear Visible | Write | |||
| BV | 82 | Hood 7 Pitot Visible | Write | |||
| BV | 83 | Hood 7 Two Position Visible | Write | |||
| BV | 84 | Door Switch Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 85 | Emergency Switch Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 86 | Shutdown Switch Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 87 | Supply 1 Occupancy Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 88 | Supply 2 Occupancy Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 89 | Supply 3 Occupancy Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 90 | Supply 4 Occupancy Direction | Write | 0=Direct, 1=Reverse | ||
| BV | 91 | Supply 1 Reheat Mode | Write | |||
| BV | 92 | Supply 2 Reheat Mode | Write | |||
| BV | 93 | Supply 3 Reheat Mode | Write | |||
| BV | 94 | Supply 1 PID Control Mode | Write | |||
| BV | 95 | Supply 2 PID Control Mode | Write | |||
| BV | 96 | Supply 3 PID Control Mode | Write | |||
| BV | 97 | Supply 4 PID Control Mode | Write | |||
| BV | 98 | Exhaust 1 PID Control Mode | Write | |||
| BV | 99 | Exhaust 2 PID Control Mode | Write | |||
| BV | 100 | Hood 8 Venturi Visible | Write | |||
| BV | 101 | Hood 8 Linear Visible | Write | |||
| BV | 102 | Hood 8 Pitot Visible | Write | |||
| BV | 103 | Hood 8 Two Position Visible | Write | |||
| BV | 104 | Hood 9 Venturi Visible | Write | |||
| BV | 105 | Hood 9 Linear Visible | Write | |||
| BV | 106 | Hood 9 Pitot Visible | Write | |||
| BV | 107 | Hood 9 Two Position Visible | Write | |||
| BV | 108 | Hood 10 Venturi Visible | Write | |||
| BV | 109 | Hood 10 Linear Visible | Write | |||
| BV | 110 | Hood 10 Pitot Visible | Write | |||
| BV | 111 | Hood 10 Two Position Visible | Write | |||
| BV | 112 | Hood 11 Venturi Visible | Write | |||
| BV | 113 | Hood 11 Linear Visible | Write | |||
| BV | 114 | Hood 11 Pitot Visible | Write | |||
| BV | 115 | Hood 11 Two Position Visible | Write | |||
| BV | 116 | Hood 12 Venturi Visible | Write | |||
| BV | 117 | Hood 12 Linear Visible | Write | |||
| BV | 118 | Hood 12 Pitot Visible | Write | |||
| BV | 119 | Hood 12 Two Position Visible | Write | |||
| BV | 120 | Hood 13 Venturi Visible | Write | |||
| BV | 121 | Hood 13 Linear Visible | Write | |||
| BV | 122 | Hood 13 Pitot Visible | Write | |||
| BV | 123 | Hood 13 Two Position Visible | Write | |||
| BV | 124 | Hood 14 Venturi Visible | Write | |||
| BV | 125 | Hood 14 Linear Visible | Write | |||
| BV | 126 | Hood 14 Pitot Visible | Write | |||
| BV | 127 | Hood 14 Two Position Visible | Write | |||
| BV | 128 | Hood 15 Venturi Visible | Write | |||
| BV | 129 | Hood 15 Linear Visible | Write | |||
| BV | 130 | Hood 15 Pitot Visible | Write | |||
| BV | 131 | Hood 15 Two Position Visible | Write | |||
| BV | 132 | Hood 16 Venturi Visible | Write | |||
| BV | 133 | Hood 16 Linear Visible | Write | |||
| BV | 134 | Hood 16 Pitot Visible | Write | |||
| BV | 135 | Hood 16 Two Position Visible | Write | |||
| BV | 136 | Hood 17 Venturi Visible | Write | |||
| BV | 137 | Hood 17 Linear Visible | Write | |||
| BV | 138 | Hood 17 Pitot Visible | Write | |||
| BV | 139 | Hood 17 Two Position Visible | Write | |||
| BV | 140 | Hood 18 Venturi Visible | Write | |||
| BV | 141 | Hood 18 Linear Visible | Write | |||
| BV | 142 | Hood 18 Pitot Visible | Write | |||
| BV | 143 | Hood 18 Two Position Visible | Write | |||
| BV | 144 | Hood 19 Venturi Visible | Write | |||
| BV | 145 | Hood 19 Linear Visible | Write | |||
| BV | 146 | Hood 19 Pitot Visible | Write | |||
| BV | 147 | Hood 19 Two Position Visible | Write | |||
| BV | 148 | Hood 20 Venturi Visible | Write | |||
| BV | 149 | Hood 20 Linear Visible | Write | |||
| BV | 150 | Hood 20 Pitot Visible | Write | |||
| BV | 151 | Hood 20 Two Position Visible | Write | |||
| BV | 152 | Supply 4 Reheat Mode | Write | |||
| BV | 153 | Hood 1 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 154 | Hood 2 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 155 | Hood 3 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 156 | Hood 4 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 157 | Hood 5 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 158 | Hood 6 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 159 | Hood 7 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 160 | Hood 8 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 161 | Hood 9 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 162 | Hood 10 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 163 | Hood 11 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 164 | Hood 12 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 165 | Hood 13 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 166 | Hood 14 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 167 | Hood 15 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 168 | Hood 16 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 169 | Hood 17 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 170 | Hood 18 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 171 | Hood 19 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 172 | Hood 20 TP Max Flow Signal | Write | 0=Open, 1=Closed | ||
| BV | 173 | Supply 1 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 174 | Supply 2 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 175 | Supply 3 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 176 | Supply 4 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 177 | Exhaust 1 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 178 | Exhaust 2 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 179 | Supply 1 Temp Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 180 | Supply 2 Temp Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 181 | Supply 3 Temp Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 182 | Supply 4 Temp Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 183 | Supply 1 Flow Control Active | Write | |||
| BV | 184 | Supply 2 Flow Control Active | Write | |||
| BV | 185 | Supply 3 Flow Control Active | Write | |||
| BV | 186 | Supply 4 Flow Control Active | Write | |||
| BV | 187 | Exhaust 1 Flow Control Active | Write | |||
| BV | 188 | Exhaust 2 Flow Control Active | Write | |||
| BV | 189 | Supply 1 Temp Control Active | Write | |||
| BV | 190 | Supply 2 Temp Control Active | Write | |||
| BV | 191 | Supply 3 Temp Control Active | Write | |||
| BV | 192 | Supply 4 Temp Control Active | Write | |||
| BV | 193 | Reset Output Selection | Write | |||
| BV | 194 | Reconfigure Outputs | Write | |||
| BV | 195 | Supply 1 Flow Input Active | Write | |||
| BV | 196 | Supply 1 DAT Input Active | Write | |||
| BV | 197 | Supply 1 Room Temp Input Active | Write | |||
| BV | 198 | Supply 1 Temp Setp Input Active | Write | |||
| BV | 199 | Supply 1 Occupancy Input Active | Write | |||
| BV | 200 | Supply 2 Flow Input Active | Write | |||
| BV | 201 | Supply 2 DAT Input Active | Write | |||
| BV | 202 | Supply 2 Room Temp Input Active | Write | |||
| BV | 203 | Supply 2 Temp Setp Input Active | Write | |||
| BV | 204 | Supply 2 Occupancy Input Active | Write | |||
| BV | 205 | Supply 3 Flow Input Active | Write | |||
| BV | 206 | Supply 3 DAT Input Active | Write | |||
| BV | 207 | Supply 3 Room Temp Input Active | Write | |||
| BV | 208 | Supply 3 Temp Setp Input Active | Write | |||
| BV | 209 | Supply 3 Occupancy Input Active | Write | |||
| BV | 210 | Supply 4 Flow Input Active | Write | |||
| BV | 211 | Supply 4 DAT Input Active | Write | |||
| BV | 212 | Supply 4 Room Temp Input Active | Write | |||
| BV | 213 | Supply 4 Temp Setp Input Active | Write | |||
| BV | 214 | Supply 4 Occupancy Input Active | Write | |||
| BV | 215 | Exhaust 1 Flow Input Active | Write | |||
| BV | 216 | Exhaust 2 Flow Input Active | Write | |||
| BV | 217 | Hood 1 Flow Input Active | Write | |||
| BV | 218 | Hood 2 Flow Input Active | Write | |||
| BV | 219 | Hood 3 Flow Input Active | Write | |||
| BV | 220 | Hood 4 Flow Input Active | Write | |||
| BV | 221 | Hood 5 Flow Input Active | Write | |||
| BV | 222 | Hood 6 Flow Input Active | Write | |||
| BV | 223 | Hood 7 Flow Input Active | Write | |||
| BV | 224 | Room Pressure Input Active | Write | |||
| BV | 225 | Relative Humidity Input Active | Write | |||
| BV | 226 | Door Switch Input Active | Write | |||
| BV | 227 | Emergency Switch Input Active | Write | |||
| BV | 228 | Shutdown Switch Input Active | Write | |||
| BV | 229 | Hood 8 Flow Input Active | Write | |||
| BV | 230 | Hood 9 Flow Input Active | Write | |||
| BV | 231 | Hood 10 Flow Input Active | Write | |||
| BV | 232 | Hood 11 Flow Input Active | Write | |||
| BV | 233 | Hood 12 Flow Input Active | Write | |||
| BV | 234 | Hood 13 Flow Input Active | Write | |||
| BV | 235 | Hood 14 Flow Input Active | Write | |||
| BV | 236 | Hood 15 Flow Input Active | Write | |||
| BV | 237 | Hood 16 Flow Input Active | Write | |||
| BV | 238 | Hood 17 Flow Input Active | Write | |||
| BV | 239 | Hood 18 Flow Input Active | Write | |||
| BV | 240 | Hood 19 Flow Input Active | Write | |||
| BV | 241 | Hood 20 Flow Input Active | Write | |||
| BV | 242 | Supply 1 DAT Delta Active | Write | |||
| BV | 243 | Supply 2 DAT Delta Active | Write | |||
| BV | 244 | Supply 3 DAT Delta Active | Write | |||
| BV | 245 | Supply 4 DAT Delta Active | Write | |||
| BV | 246 | Exhaust Configuration | Write | 0=Unganged, 1=Ganged | ||
| BV | 247 | Reset Supply 1 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 248 | Reset Supply 2 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 249 | Reset Supply 3 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 250 | Reset Supply 4 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 251 | Reset Exhaust 1 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 252 | Reset Exhaust 2 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 253 | Supply 1 Room Temp RTD Visible | Write | 0=No, 1=Yes | ||
| BV | 254 | Supply 1 Room Temp Voltage Visible | Write | 0=No, 1=Yes | ||
| BV | 255 | Supply 2 Room Temp RTD Visible | Write | 0=No, 1=Yes | ||
| BV | 256 | Supply 2 Room Temp Voltage Visible | Write | 0=No, 1=Yes | ||
| BV | 257 | Supply 3 Room Temp RTD Visible | Write | 0=No, 1=Yes | ||
| BV | 258 | Supply 3 Room Temp Voltage Visible | Write | 0=No, 1=Yes | ||
| BV | 259 | Supply 4 Room Temp RTD Visible | Write | 0=No, 1=Yes | ||
| BV | 260 | Supply 4 Room Temp Voltage Visible | Write | 0=No, 1=Yes | ||
| BV | 261 | Reset Supply 5 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 262 | Reset Supply 6 Flow Tuning | Write | 0=No, 1=Yes | ||
| BV | 263 | Supply 5 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 264 | Supply 6 Flow Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 265 | Supply 5 Temp Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 266 | Supply 6 Temp Control Mode | Write | 0=Auto, 1=Manual | ||
| BV | 267 | Supply 5 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 268 | Supply 6 Balancer Mode | Write | 0=Off, 1=On | ||
| BV | 269 | Supply 5 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 270 | Supply 6 Flow Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 271 | Supply 5 Temp Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 272 | Supply 6 Temp Control Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 273 | Supply 5 Venturi Visible | Write | |||
| BV | 274 | Supply 5 Linear Visible | Write | |||
| BV | 275 | Supply 5 Pitot Visible | Write | |||
| BV | 276 | Supply 6 Venturi Visible | Write | |||
| BV | 277 | Supply 6 Linear Visible | Write | |||
| BV | 278 | Supply 6 Pitot Visible | Write | |||
| BV | 279 | Supply 5 Room Temp Voltage Visible | Write | |||
| BV | 280 | Supply 6 Room Temp Voltage Visible | Write | |||
| BV | 281 | Supply 5 Flow Control Active | Write | |||
| BV | 282 | Supply 6 Flow Control Active | Write | |||
| BV | 283 | Supply 5 Temp Control Active | Write | |||
| BV | 284 | Supply 6 Temp Control Active | Write | |||
| BV | 285 | Supply 5 Flow Input Active | Write | |||
| BV | 286 | Supply 5 Room Temp Input Active | Write | |||
| BV | 287 | Supply 5 Room Temp Adj Input Active | Write | |||
| BV | 288 | Supply 6 Flow Input Active | Write | |||
| BV | 289 | Supply 6 Room Temp Input Active | Write | |||
| BV | 290 | Supply 6 Room Temp Adj Input Active | Write | |||
| BV | 291 | Supply 5 Room Temp RTD Visible | Write | |||
| BV | 292 | Supply 6 Room Temp RTD Visible | Write | |||
| BV | 293 | Supply 5 Reheat Mode | Write | |||
| BV | 294 | Supply 6 Reheat Mode | Write | |||
| BV | 295 | Supply 5 PID Control Mode | Write | |||
| BV | 296 | Supply 6 PID Control Mode | Write | |||
| BV | 297 | Supply 5 Occupancy Mode | Write | 0=Occupied, 1=Unoccupied | ||
| BV | 298 | Supply 6 Occupancy Mode | Write | 0=Occupied, 1=Unoccupied | ||
| BV | 299 | Supply 5 Occupancy Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 300 | Supply 6 Occupancy Direction | Write | 0=Reverse, 1=Direct | ||
| BV | 301 | Supply 5 DAT Voltage Visible | Write | |||
| BV | 302 | Supply 6 DAT Voltage Visible | Write | |||
| BV | 303 | Supply 5 DAT Input Active | Write | |||
| BV | 304 | Supply 5 Occupancy Input Active | Write | |||
| BV | 305 | Supply 6 DAT Input Active | Write | |||
| BV | 306 | Supply 6 Occupancy Input Active | Write | |||
| BV | 307 | Supply 5 DAT Delta Active | Write | |||
| BV | 308 | Supply 6 DAT Delta Active | Write | |||
| BV | 309 | Supply 5 DAT RTD Visible | Write | |||
| BV | 310 | Supply 6 DAT RTD Visible | Write | |||
| MV | 1 | Input 1 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 2 | Input 2 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 3 | Input 3 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 4 | Input 4 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 5 | Input 5 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 6 | Input 6 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 7 | Input 7 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 8 | Input 8 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 9 | Input 9 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 10 | Input 10 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 11 | Input 11 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 12 | Input 12 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 13 | Input 13 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 14 | Input 14 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 15 | Input 15 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 16 | Input 16 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 17 | Input 17 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 18 | Input 18 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 19 | Input 19 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 20 | Input 20 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 21 | Input 21 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 22 | Input 22 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 23 | Input 23 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 24 | Input 24 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 25 | Input 25 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 26 | Input 26 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 27 | Input 27 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 28 | Input 28 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 29 | Input 29 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 30 | Input 30 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 31 | Input 31 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 32 | Input 32 Input Type | Write | 1=Unconfigured, 2=Supply 1 Flow, 3=Supply 1 DAT, 4=Supply 1 Room Temp, 5=Supply 1 Temp Adjustment, 6=Supply 1 Occupancy, 7=Supply 2 Flow, 8=Supply 2 DAT, 9=Supply 2 Room Temp, 10=Supply 2 Temp Adjustment, 11=Supply 2 Occupancy, 12=Supply 3 Flow, 13=Supply 3 DAT, 14=Supply 3 Room Temp, 15=Supply 3 Temp Adjustment, 16=Supply 3 Occupancy, 17=Supply 4 Flow, 18=Supply 4 DAT, 19=Supply 4 Room Temp, 20=Supply 4 Temp Adjustment, 21=Supply 4 Occupancy, 22=Exhaust 1 Flow, 23=Exhaust 2 Flow, 24=Hood 1 Flow, 25=Hood 2 Flow, 26=Hood 3 Flow, 27=Hood 4 Flow, 28=Hood 5 Flow, 29=Hood 6 Flow, 30=Hood 7 Flow, 31=Room Pressure, 32=Relative Humidity, 33=Door Switch, 34=Emergency Switch, 35=Shutdown Switch, 36=Hood 8 Flow, 37=Hood 9 Flow, 38=Hood 10 Flow, 39=Hood 11 Flow, 40=Hood 12 Flow, 41=Hood 13 Flow, 42=Hood 14 Flow, 43=Hood 15 Flow, 44=Hood 16 Flow, 45=Hood 17 Flow, 46=Hood 18 Flow, 47=Hood 19 Flow, 48=Hood 20 Flow | ||
| MV | 33 | Output 1 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 34 | Output 2 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 35 | Output 3 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 36 | Output 4 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 37 | Output 5 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 38 | Output 6 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 39 | Output 7 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 40 | Output 8 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 41 | Output 9 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 42 | Output 10 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 43 | Output 11 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 44 | Output 12 Output Type | Write | 1=Unconfigured, 2=Supply 1 Temp, 3=Supply 1 Flow, 4=Supply 2 Temp, 5=Supply 2 Flow, 6=Supply 3 Temp, 7=Supply 3 Flow, 8=Supply 4 Temp, 9=Supply 4 Flow, 10=Exhaust 1 Flow, 11=Exhaust 2 Flow | ||
| MV | 45 | Supply 1 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 46 | Supply 2 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 47 | Supply 3 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 48 | Supply 4 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 49 | Exhaust 1 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 50 | Exhaust 2 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 51 | Hood 1 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 52 | Hood 2 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 53 | Hood 3 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 54 | Hood 4 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 55 | Hood 5 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 56 | Hood 6 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 57 | Hood 7 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot, 5=Two Position | ||
| MV | 58 | Supply 1 DAT Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 59 | Supply 2 DAT Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 60 | Supply 3 DAT Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 61 | Supply 4 DAT Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 62 | Room Pressure Type | Write | 1=Unconfigured, 2=TTW Sensor, 3=Pressure Transducer | ||
| MV | 63 | Supply 1 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 64 | Supply 2 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 65 | Supply 3 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 66 | Supply 4 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 67 | Exhaust 1 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 68 | Exhaust 2 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 69 | Hood 1 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 70 | Hood 2 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 71 | Hood 3 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 72 | Hood 4 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 73 | Hood 5 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 74 | Hood 6 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 75 | Hood 7 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MVmin | 76 | Current Supply 1 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 77 | Current Supply 2 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 78 | Current Supply 3 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 79 | Current Supply 4 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 80 | Current Exhaust 1 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 81 | Current Exhaust 2 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 82 | Current Supply 1 Temp Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 83 | Current Supply 2 Temp Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 84 | Current Supply 3 Temp Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 85 | Current Supply 4 Temp Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MVmin | 86 | Current Room Pressure Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 87 | Current Supply 1 DAT Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 88 | Current Supply 2 DAT Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 89 | Current Supply 3 DAT Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 90 | Current Supply 4 DAT Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MVmin | 91 | Current Controller Flow Mode | TSI: do not overwrite | Read | 1=Standard, 2=Emergency, 3=Shutdown, 4=Balancer | |
| MV | 92 | Current Controller Pressure Mode | TSI: do not overwrite | Read | 1=Normal, 2=Door Open | |
| MV | 93 | Current Supply 1 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 94 | Current Supply 2 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 95 | Current Supply 3 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 96 | Current Supply 4 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 97 | Current Supply 1 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 98 | Current Supply 2 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 99 | Current Supply 3 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 100 | Current Supply 4 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 101 | Current Exhaust 1 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 102 | Current Exhaust 2 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 103 | Current Exhaust 1 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 104 | Current Exhaust 2 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 105 | Current Hood 1 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 106 | Current Hood 2 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 107 | Current Hood 3 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 108 | Current Hood 4 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 109 | Current Hood 5 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 110 | Current Hood 6 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 111 | Current Hood 7 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 112 | Current Hood 1 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 113 | Current Hood 2 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 114 | Current Hood 3 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 115 | Current Hood 4 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 116 | Current Hood 5 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 117 | Current Hood 6 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 118 | Current Hood 7 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 119 | Room Pressure Cal Mode | Write | 1=Save, 2=Sensor Zero | ||
| MV | 120 | Current Offset Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Minimum Offset Alarm, 3=Maximum Offset Alarm | |
| MV | 121 | Hood 8 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 122 | Hood 9 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 123 | Hood 10 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 124 | Hood 11 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 125 | Hood 12 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 126 | Hood 13 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 127 | Hood 14 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 128 | Hood 15 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 129 | Hood 16 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 130 | Hood 17 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 131 | Hood 18 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 132 | Hood 19 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 133 | Hood 20 Flow Type | Write | 1=Normal, 2=Feedback Alarm | ||
| MV | 134 | Hood 8 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 135 | Hood 9 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 136 | Hood 10 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 137 | Hood 11 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 138 | Hood 12 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 139 | Hood 13 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 140 | Hood 14 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 141 | Hood 15 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 142 | Hood 16 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 143 | Hood 17 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 144 | Hood 18 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 145 | Hood 19 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 146 | Hood 20 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 147 | Current Hood 8 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 148 | Current Hood 9 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 149 | Current Hood 10 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 150 | Current Hood 11 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 151 | Current Hood 12 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 152 | Current Hood 13 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 153 | Current Hood 14 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 154 | Current Hood 15 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 155 | Current Hood 16 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 156 | Current Hood 17 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 157 | Current Hood 18 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 158 | Current Hood 19 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 159 | Current Hood 20 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=No Flow Alarm | |
| MV | 160 | Current Hood 8 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 161 | Current Hood 9 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 162 | Current Hood 10 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 163 | Current Hood 11 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 164 | Current Hood 12 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 165 | Current Hood 13 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 166 | Current Hood 14 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 167 | Current Hood 15 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 168 | Current Hood 16 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 169 | Current Hood 17 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 170 | Current Hood 18 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 171 | Current Hood 19 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 172 | Current Hood 20 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Feedback Alarm | |
| MV | 173 | Supply 1 Room Temp Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 174 | Supply 2 Room Temp Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 175 | Supply 3 Room Temp Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 176 | Supply 4 Room Temp Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 177 | Supply 5 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 178 | Supply 6 Flow Type | Write | 1=Unconfigured, 2=Venturi, 3=Linear, 4=Pitot | ||
| MV | 179 | Supply 5 Room Temp Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 180 | Supply 6 Room Temp Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 181 | Supply 5 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 182 | Supply 6 Pitot Cal mode | Write | 1=Save, 2=Low Cal Mode, 3=High Cal Mode, 4=Sensor Zero | ||
| MV | 183 | Current Supply 5 Temp Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 184 | Current Supply 6 Temp Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 185 | Current Supply 5 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 186 | Current Supply 6 Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 187 | Current Supply 5 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 188 | Current Supply 6 No Flow Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 189 | Current Supply 5 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 190 | Current Supply 6 Feedback Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 191 | Supply 5 DAT Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 192 | Supply 6 DAT Type | Write | 1=Unconfigured, 2=0 to 10V, 3=RTD | ||
| MV | 193 | Current Supply 5 DAT Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm | |
| MV | 194 | Current Supply 6 DAT Alarm Status | TSI: do not overwrite | Read | 1=Normal, 2=Low Alarm, 3=High Alarm |
No points match these filters.
Object ID lookup: TSI Laboratory Room Controller point IDs by name
AV1Supply 1 Pitot Uncal Low Cal FlowAV2Supply 1 Pitot Uncal High Cal FlowAV3Supply 1 Venturi Minimum FlowAV4Supply 1 Venturi Maximum FlowAV5Supply 1 Flow K FactorAV6Supply 1 Venturi Setup PositionAV7Supply 1 Venturi LOM Esc TimeAV8Supply 1 Linear Duct AreaAV10Supply 1 Linear Top VelocityAV11Supply 1 Linear Signal MinimumAV12Supply 1 Linear Signal MaximumAV13Supply 1 Pitot Sensor ZeroAV14Supply 1 Transducer Signal MinimumAV15Supply 1 Transducer Signal MaximumAV16Supply 1 Pitot Duct AreaAV17Supply 5 Flow ErrorAV18Supply 1 Transducer Sensor MaximumAV19Supply 1 Pitot Low Cal PosAV20Supply 1 Pitot High Cal PosAV21Supply 1 Pitot Low Cal FlowAV22Supply 1 Pitot High Cal FlowAV23Supply 2 Pitot Uncal High Cal FlowAV24Supply 2 Pitot Uncal Low Cal FlowAV25Supply 2 Venturi Minimum FlowAV26Supply 2 Venturi Maximum FlowAV27Supply 2 Flow K FactorAV28Supply 2 Venturi Setup PositionAV29Supply 2 Venturi LOM Esc TimeAV30Supply 2 Linear Duct AreaAV32Supply 2 Linear Top VelocityAV33Supply 2 Linear Signal MinimumAV34Supply 2 Linear Signal MaximumAV35Supply 2 Pitot Sensor ZeroAV36Supply 2 Pitot Low Cal PosAV37Supply 2 Transducer Signal MinimumAV38Supply 2 Pitot High Cal PosAV39Supply 2 Transducer Signal MaximumAV40Supply 2 Pitot Low Cal FlowAV41Supply 2 Pitot Duct AreaAV42Supply 2 Pitot High Cal FlowAV43Supply 6 Flow ErrorAV44Supply 2 Transducer Sensor MaximumAV45Supply 3 Pitot Uncal Low Cal FlowAV46Supply 3 Pitot Uncal High Cal FlowAV47Supply 3 Venturi Minimum FlowAV48Supply 3 Venturi Maximum FlowAV49Supply 3 Flow K FactorAV50Supply 3 Venturi Setup PositionAV51Supply 3 Venturi LOM Esc TimeAV52Supply 3 Linear Duct AreaAV54Supply 3 Linear Top VelocityAV55Supply 3 Linear Signal MinimumAV56Supply 3 Linear Signal MaximumAV57Supply 3 Pitot Sensor ZeroAV58Supply 3 Pitot Low Cal PosAV59Supply 3 Transducer Signal MinimumAV60Supply 3 Pitot High Cal PosAV61Supply 3 Transducer Signal MaximumAV62Supply 3 Pitot Low Cal FlowAV63Supply 3 Pitot Duct AreaAV64Supply 3 Pitot High Cal FlowAV65Old Supply 5 ErrorAV66Supply 3 Transducer Sensor MaximumAV67Supply 4 Pitot Uncal Low Cal FlowAV68Supply 4 Pitot Uncal High Cal FlowAV69Supply 4 Venturi Minimum FlowAV70Supply 4 Venturi Maximum FlowAV71Supply 4 Flow K FactorAV72Supply 4 Venturi Setup PositionAV73Supply 4 Venturi LOM Esc TimeAV74Supply 4 Linear Duct AreaAV76Supply 4 Linear Top VelocityAV77Supply 4 Linear Signal MinimumAV78Supply 4 Linear Signal MaximumAV79Supply 4 Pitot Sensor ZeroAV80Supply 4 Pitot Low Cal PosAV81Supply 4 Transducer Signal MinimumAV82Supply 4 Pitot High Cal PosAV83Supply 4 Transducer Signal MaximumAV84Supply 4 Pitot Low Cal FlowAV85Supply 4 Pitot Duct AreaAV86Supply 4 Pitot High Cal FlowAV87Old Supply 5 ErrorAV88Supply 4 Transducer Sensor MaximumAV89Exhaust 1 Pitot Uncal Low Cal FlowAV90Exhaust 1 Pitot Uncal High Cal FlowAV91Exhaust 1 Venturi Minimum FlowAV92Exhaust 1 Venturi Maximum FlowAV93Exhaust 1 Flow K FactorAV94Exhaust 1 Venturi Setup PositionAV95Exhaust 1 Venturi LOM Esc TimeAV96Exhaust 1 Linear Duct AreaAV98Exhaust 1 Linear Top VelocityAV99Exhaust 1 Linear Signal MinimumAV100Exhaust 1 Linear Signal MaximumAV101Exhaust 1 Pitot Sensor ZeroAV102Exhaust 1 Pitot Low Cal PosAV103Exhaust 1 Transducer Signal MinimumAV104Exhaust 1 Pitot High Cal PosAV105Exhaust 1 Transducer Signal MaximumAV106Exhaust 1 Pitot Low Cal FlowAV107Exhaust 1 Pitot Duct AreaAV108Exhaust 1 Pitot High Cal FlowAV110Exhaust 1 Transducer Sensor MaximumAV111Exhaust 2 Pitot Uncal Low Cal FlowAV112Exhaust 2 Pitot Uncal High Cal FlowAV113Exhaust 2 Venturi Minimum FlowAV114Exhaust 2 Venturi Maximum FlowAV115Exhaust 2 Flow K FactorAV116Exhaust 2 Venturi Setup PositionAV117Exhaust 2 Venturi LOM Esc TimeAV118Exhaust 2 Linear Duct AreaAV120Exhaust 2 Linear Top VelocityAV121Exhaust 2 Linear Signal MinimumAV122Exhaust 2 Linear Signal MaximumAV123Exhaust 2 Pitot Sensor ZeroAV124Exhaust 2 Pitot Low Cal PosAV125Exhaust 2 Transducer Signal MinimumAV126Exhaust 2 Pitot High Cal PosAV127Exhaust 2 Transducer Signal MaximumAV128Exhaust 2 Pitot Low Cal FlowAV129Exhaust 2 Pitot Duct AreaAV130Exhaust 2 Pitot High Cal FlowAV132Exhaust 2 Transducer Sensor MaximumAV133Supply 1 Room Temp OffsetAV134Supply 2 Room Temp OffsetAV135Supply 3 Room Temp OffsetAV136Supply 4 Room Temp OffsetAV137Supply 1 DAT OffsetAV138Supply 2 DAT OffsetAV139Supply 3 DAT OffsetAV140Supply 4 DAT OffsetAV141Supply 1 DAT Signal MinimumAV142Supply 1 DAT Signal MaximumAV143Supply 1 DAT Sensor MinimumAV144Supply 1 DAT Sensor MaximumAV146Supply 2 DAT Signal MinimumAV147Supply 2 DAT Signal MaximumAV148Supply 2 DAT Sensor MinimumAV149Supply 2 DAT Sensor MaximumAV151Supply 3 DAT Signal MinimumAV152Supply 3 DAT Signal MaximumAV153Supply 3 DAT Sensor MinimumAV154Supply 3 DAT Sensor MaximumAV156Supply 4 DAT Signal MinimumAV157Supply 4 DAT Signal MaximumAV158Supply 4 DAT Sensor MinimumAV159Supply 4 DAT Sensor MaximumAV161Supply 1 Room Temp Adj Signal MinimumAV162Supply 1 Room Temp Adj Signal MaximumAV163Supply 1 Room Temp Adj Sensor MinimumAV164Supply 1 Room Temp Adj Sensor MaximumAV165Supply 2 Room Temp Adj Signal MinimumAV166Supply 2 Room Temp Adj Signal MaximumAV167Supply 2 Room Temp Adj Sensor MinimumAV168Supply 2 Room Temp Adj Sensor MaximumAV169Supply 3 Room Temp Adj Signal MinimumAV170Supply 3 Room Temp Adj Signal MaximumAV171Supply 3 Room Temp Adj Sensor MinimumAV172Supply 3 Room Temp Adj Sensor MaximumAV173Supply 4 Room Temp Adj Signal MinimumAV174Supply 4 Room Temp Adj Signal MaximumAV175Supply 4 Room Temp Adj Sensor MinimumAV176Supply 4 Room Temp Adj Sensor MaximumAV177Relative Humidity Signal MinimumAV178Relative Humidity Signal MaximumAV179Relative Humidity Sensor MinimumAV180Relative Humidity Sensor MaximumAV181Relative Humidity OffsetAV182Pressure Transducer Signal MaximumAV183Pressure Transducer Signal MinimumAV184Pressure Transducer Sensor MinimumAV185Pressure Transducer Sensor MaximumAV186Room Pressure Sensor ZeroAV188TTW Sensor Velocity K-FactorAV189TTW Sensor ElevationAV190Supply 1 Minimum FlowAV191Supply 1 Cooling FlowAV192Supply 1 Heating FlowAV193Supply 1 Maximum FlowAV194Supply 1 Minimum PositionAV195Supply 1 Maximum PositionAV196Supply 1 Unocc Minimum FlowAV197Supply 1 Unocc Cooling FlowAV198Supply 1 Unocc Heating FlowAV199Supply 1 Unocc Maximum FlowAV200Supply 1 Emergency FlowAV201Supply 1 Shutdown FlowAV202Supply 2 Minimum FlowAV203Supply 2 Unocc Minimum FlowAV204Supply 2 Cooling FlowAV205Supply 2 Unocc Cooling FlowAV206Supply 2 Heating FlowAV207Supply 2 Unocc Heating FlowAV208Supply 2 Maximum FlowAV209Supply 2 Unocc Maximum FlowAV210Supply 2 Emergency FlowAV211Supply 2 Minimum PositionAV212Supply 2 Shutdown FlowAV213Supply 2 Maximum PositionAV214Supply 3 Minimum FlowAV215Supply 3 Unocc Minimum FlowAV216Supply 3 Cooling FlowAV217Supply 3 Unocc Cooling FlowAV218Supply 3 Heating FlowAV219Supply 3 Unocc Heating FlowAV220Supply 3 Maximum FlowAV221Supply 3 Unocc Maximum FlowAV222Supply 3 Emergency FlowAV223Supply 3 Minimum PositionAV224Supply 3 Shutdown FlowAV225Supply 3 Maximum PositionAV226Supply 4 Minimum FlowAV227Supply 4 Unocc Minimum FlowAV228Supply 4 Cooling FlowAV229Supply 4 Unocc Cooling FlowAV230Supply 4 Heating FlowAV231Supply 4 Unocc Heating FlowAV232Supply 4 Maximum FlowAV233Supply 4 Unocc Maximum FlowAV234Supply 4 Emergency FlowAV235Supply 4 Minimum PositionAV236Supply 4 Shutdown FlowAV237Supply 4 Maximum PositionAV238Exhaust 1 Minimum FlowAV239Exhaust 1 Maximum FlowAV240Exhaust 1 Minimum PositionAV241Exhaust 1 Maximum PositionAV242Exhaust 1 Emergency FlowAV243Exhaust 2 Minimum FlowAV244Exhaust 2 Maximum FlowAV245Exhaust 2 Minimum PositionAV246Exhaust 2 Maximum PositionAV247Exhaust 2 Emergency FlowAV248Supply 1 Heat SetpointAV249Supply 1 Cool SetpointAV250Supply 1 Unocc Heat SetpointAV251Supply 1 Unocc Cool SetpointAV252Supply 1 DAT DeltaAV253Supply 2 Heat SetpointAV254Supply 2 Cool SetpointAV255Supply 2 Unocc Heat SetpointAV256Supply 2 Unocc Cool SetpointAV257Supply 2 DAT DeltaAV258Supply 3 Heat SetpointAV259Supply 3 Cool SetpointAV260Supply 3 Unocc Heat SetpointAV261Supply 3 Unocc Cool SetpointAV262Supply 3 DAT DeltaAV263Supply 4 Heat SetpointAV264Supply 4 Cool SetpointAV265Supply 4 Unocc Heat SetpointAV266Supply 4 Unocc Cool SetpointAV267Supply 4 DAT DeltaAV268Room Pressure SetpointAV269Door Room Pressure SetpointAV270Minimum OffsetAV271Maximum OffsetAV272Supply 1 Low Flow AlarmAV273Supply 1 High Flow AlarmAV274Supply 1 Unocc Low Flow AlarmAV275Supply 1 Unocc High Flow AlarmAV276Supply 2 Low Flow AlarmAV277Supply 2 High Flow AlarmAV278Supply 2 Unocc Low Flow AlarmAV279Supply 2 Unocc High Flow AlarmAV280Supply 3 Low Flow AlarmAV281Supply 3 High Flow AlarmAV282Supply 3 Unocc Low Flow AlarmAV283Supply 3 Unocc High Flow AlarmAV284Supply 4 Low Flow AlarmAV285Supply 4 High Flow AlarmAV286Supply 4 Unocc Low Flow AlarmAV287Supply 4 Unocc High Flow AlarmAV288Exhaust 1 Low Flow AlarmAV289Exhaust 1 High Flow AlarmAV290Exhaust 2 Low Flow AlarmAV291Exhaust 2 High Flow AlarmAV292Supply 1 Low Temperature AlarmAV293Supply 1 High Temperature AlarmAV294Supply 1 Unocc Low Temperature AlarmAV295Supply 1 Unocc High Temperature AlarmAV296Supply 2 Low Temperature AlarmAV297Supply 2 High Temperature AlarmAV298Supply 2 Unocc Low Temperature AlarmAV299Supply 2 Unocc High Temperature AlarmAV300Supply 3 Low Temperature AlarmAV301Supply 3 High Temperature AlarmAV302Supply 3 Unocc Low Temperature AlarmAV303Supply 3 Unocc High Temperature AlarmAV304Supply 4 Low Temperature AlarmAV305Supply 4 High Temperature AlarmAV306Supply 4 Unocc Low Temperature AlarmAV307Supply 4 Unocc High Temperature AlarmAV308Low Pressure AlarmAV309High Pressure AlarmAV310Door Low Pressure AlarmAV311Door High Pressure AlarmAV312Alarm DelayAV313Door Alarm DelayAV314Supply 1 Flow Manual PositionAV315Supply 2 Flow Manual PositionAV316Supply 3 Flow Manual PositionAV317Supply 4 Flow Manual PositionAV318Supply 1 Temp Manual PositionAV319Supply 2 Temp Manual PositionAV320Supply 3 Temp Manual PositionAV321Supply 4 Temp Manual PositionAV322Exhaust 1 Flow Manual PositionAV323Exhaust 2 Flow Manual PositionAV324Supply 5 Flow Manual PositionAV325Supply 6 Flow Manual PositionAV326Supply 1 Balancer FlowAV327Supply 2 Balancer FlowAV328Supply 3 Balancer FlowAV329Supply 4 Balancer FlowAV330Exhaust 1 Balancer FlowAV331Exhaust 2 Balancer FlowAV332Supply 1 High DAT AlarmAV333Supply 2 High DAT AlarmAV334Supply 3 High DAT AlarmAV335Supply 4 High DAT AlarmAV336Minimum Offset AlarmAV337Maximum Offset AlarmAV338Supply 1 Flow Input NumberAV339Supply 1 DAT Input NumberAV340Supply 1 Room Temp Input NumberAV341Supply 1 Room Temp Adj Input NumberAV342Supply 1 Occupancy Input NumberAV343Supply 2 Flow Input NumberAV344Supply 2 DAT Input NumberAV345Supply 2 Room Temp Input NumberAV346Supply 2 Room Temp Adj Input NumberAV347Supply 2 Occupancy Input NumberAV348Supply 3 Flow Input NumberAV349Supply 3 DAT Input NumberAV350Supply 3 Room Temp Input NumberAV351Supply 3 Room Temp Adj Input NumberAV352Supply 3 Occupancy Input NumberAV353Supply 4 Flow Input NumberAV354Supply 4 DAT Input NumberAV355Supply 4 Room Temp Input NumberAV356Supply 4 Room Temp Adj Input NumberAV357Supply 4 Occupancy Input NumberAV358Exhaust 1 Flow Input NumberAV359Exhaust 2 Flow Input NumberAV360Room Pressure Input NumberAV361Relative Humidity Input NumberAV362Door Switch Input NumberAV363Emergency Input NumberAV364Shutdown Input NumberAV365Hood 1 Flow Input NumberAV366Hood 2 Flow Input NumberAV367Hood 3 Flow Input NumberAV368Hood 4 Flow Input NumberAV369Hood 5 Flow Input NumberAV370Hood 6 Flow Input NumberAV371Hood 7 Flow Input NumberAV372Supply 1 Flow ChangeAV373Supply 2 Flow ChangeAV374Supply 3 Flow ChangeAV375Supply 4 Flow ChangeAV376Supply 1 Reheat/Cooling DelayAV377Supply 2 Reheat/Cooling DelayAV378Supply 3 Reheat/Cooling DelayAV379Supply 4 Reheat/Cooling DelayAV392Supply 5 Temp Manual PositionAV393Supply 6 Temp Manual PositionAV395Current Alarm DelayAV396Current OffsetAV398Current Supply 1 Minimum FlowAV399Current Supply 1 Cooling FlowAV400Current Supply 1 Heating FlowAV401Current Supply 1 Maximum FlowAV402Current Supply 2 Minimum FlowAV403Current Supply 2 Cooling FlowAV404Current Supply 2 Heating FlowAV405Current Supply 2 Maximum FlowAV406Current Supply 3 Minimum FlowAV407Current Supply 3 Cooling FlowAV408Current Supply 3 Heating FlowAV409Current Supply 3 Maximum FlowAV410Current Supply 4 Minimum FlowAV411Current Supply 4 Cooling FlowAV412Current Supply 4 Heating FlowAV413Current Supply 4 Maximum FlowAV414Current Supply 1 Heat SetpointAV415Current Supply 1 Cool SetpointAV416Current Supply 2 Heat SetpointAV417Current Supply 2 Cool SetpointAV418Current Supply 3 Heat SetpointAV419Current Supply 3 Cool SetpointAV420Current Supply 4 Heat SetpointAV421Current Supply 4 Cool SetpointAV422Current Room Pressure SetpointAV423Current Supply 1 Low Flow AlarmAV424Current Supply 1 High Flow AlarmAV425Current Supply 2 Low Flow AlarmAV426Current Supply 2 High Flow AlarmAV427Current Supply 3 Low Flow AlarmAV428Current Supply 3 High Flow AlarmAV429Current Supply 4 Low Flow AlarmAV430Current Supply 4 High Flow AlarmAV431Current Low Pressure AlarmAV432Current High Pressure AlarmAV433Current Supply 1 Low Temperature AlarmAV434Current Supply 1 High Temperature AlarmAV435Current Supply 2 Low Temperature AlarmAV436Current Supply 2 High Temperature AlarmAV437Current Supply 3 Low Temperature AlarmAV438Current Supply 3 High Temperature AlarmAV439Current Supply 4 Low Temperature AlarmAV440Current Supply 4 High Temperature AlarmAV441Hood 1 Venturi Minimum FlowAV442Hood 1 Venturi Maximum FlowAV443Hood 1 Flow K factorAV445Hood 1 Venturi LOM ESC TimeAV446Hood 1 Linear Duct AreaAV448Hood 1 Linear Top VelocityAV449Hood 1 Linear Signal MinimumAV450Hood 1 Linear Signal MaximumAV451Hood 1 Pitot Sensor ZeroAV452Hood 1 Transducer Signal MinimumAV453Hood 1 Transducer Signal MaximumAV454Hood 1 Pitot Duct AreaAV456Hood 1 Transducer Sensor MaximumAV459Hood 1 Pitot Low Cal FlowAV460Hood 1 Pitot High Cal FlowAV461Hood 1 Pitot Low Cal VoltageAV462Hood 1 Pitot High Cal VoltageAV463Hood 1 TP Min FlowAV464Hood 1 TP Max FlowAV465Hood 2 Venturi Minimum FlowAV466Hood 2 Venturi Maximum FlowAV467Hood 2 Flow K factorAV469Hood 2 Venturi LOM ESC TimeAV470Hood 2 Linear Duct AreaAV472Hood 2 Linear Top VelocityAV473Hood 2 Linear Signal MinimumAV474Hood 2 Linear Signal MaximumAV475Hood 2 Pitot Sensor ZeroAV476Hood 2 Transducer Signal MinimumAV477Hood 2 Transducer Signal MaximumAV478Hood 2 Pitot Duct AreaAV480Hood 2 Transducer Sensor MaximumAV483Hood 2 Pitot Low Cal FlowAV484Hood 2 Pitot High Cal FlowAV485Hood 2 Pitot Low Cal VoltageAV486Hood 2 Pitot High Cal VoltageAV487Hood 2 TP Min FlowAV488Hood 2 TP Max FlowAV489Hood 3 Venturi Minimum FlowAV490Hood 3 Venturi Maximum FlowAV491Hood 3 Flow K factorAV493Hood 3 Venturi LOM ESC TimeAV494Hood 3 Linear Duct AreaAV496Hood 3 Linear Top VelocityAV497Hood 3 Linear Signal MinimumAV498Hood 3 Linear Signal MaximumAV499Hood 3 Pitot Sensor ZeroAV500Hood 3 Transducer Signal MinimumAV501Hood 3 Transducer Signal MaximumAV502Hood 3 Pitot Duct AreaAV504Hood 3 Transducer Sensor MaximumAV507Hood 3 Pitot Low Cal FlowAV508Hood 3 Pitot High Cal FlowAV509Hood 3 Pitot Low Cal VoltageAV510Hood 3 Pitot High Cal VoltageAV511Hood 3 TP Min FlowAV512Hood 3 TP Max FlowAV513Hood 4 Venturi Minimum FlowAV514Hood 4 Venturi Maximum FlowAV515Hood 4 Flow K factorAV517Hood 4 Venturi LOM ESC TimeAV518Hood 4 Linear Duct AreaAV520Hood 4 Linear Top VelocityAV521Hood 4 Linear Signal MinimumAV522Hood 4 Linear Signal MaximumAV523Hood 4 Pitot Sensor ZeroAV524Hood 4 Transducer Signal MinimumAV525Hood 4 Transducer Signal MaximumAV526Hood 4 Pitot Duct AreaAV528Hood 4 Transducer Sensor MaximumAV531Hood 4 Pitot Low Cal FlowAV532Hood 4 Pitot High Cal FlowAV533Hood 4 Pitot Low Cal VoltageAV534Hood 4 Pitot High Cal VoltageAV535Hood 4 TP Min FlowAV536Hood 4 TP Max FlowAV537Hood 5 Venturi Minimum FlowAV538Hood 5 Venturi Maximum FlowAV539Hood 5 Flow K factorAV541Hood 5 Venturi LOM ESC TimeAV542Hood 5 Linear Duct AreaAV544Hood 5 Linear Top VelocityAV545Hood 5 Linear Signal MinimumAV546Hood 5 Linear Signal MaximumAV547Hood 5 Pitot Sensor ZeroAV548Hood 5 Transducer Signal MinimumAV549Hood 5 Transducer Signal MaximumAV550Hood 5 Pitot Duct AreaAV552Hood 5 Transducer Sensor MaximumAV555Hood 5 Pitot Low Cal FlowAV556Hood 5 Pitot High Cal FlowAV557Hood 5 Pitot Low Cal VoltageAV558Hood 5 Pitot High Cal VoltageAV559Hood 5 TP Min FlowAV560Hood 5 TP Max FlowAV561Hood 6 Venturi Minimum FlowAV562Hood 6 Venturi Maximum FlowAV563Hood 6 Flow K factorAV565Hood 6 Venturi LOM ESC TimeAV566Hood 6 Linear Duct AreaAV568Hood 6 Linear Top VelocityAV569Hood 6 Linear Signal MinimumAV570Hood 6 Linear Signal MaximumAV571Hood 6 Pitot Sensor ZeroAV572Hood 6 Transducer Signal MinimumAV573Hood 6 Transducer Signal MaximumAV574Hood 6 Pitot Duct AreaAV576Hood 6 Transducer Sensor MaximumAV579Hood 6 Pitot Low Cal FlowAV580Hood 6 Pitot High Cal FlowAV581Hood 6 Pitot Low Cal VoltageAV582Hood 6 Pitot High Cal VoltageAV583Hood 6 TP Min FlowAV584Hood 6 TP Max FlowAV585Hood 7 Venturi Minimum FlowAV586Hood 7 Venturi Maximum FlowAV587Hood 7 Flow K factorAV589Hood 7 Venturi LOM ESC TimeAV590Hood 7 Linear Duct AreaAV592Hood 7 Linear Top VelocityAV593Hood 7 Linear Signal MinimumAV594Hood 7 Linear Signal MaximumAV595Hood 7 Pitot Sensor ZeroAV596Hood 7 Transducer Signal MinimumAV597Hood 7 Transducer Signal MaximumAV598Hood 7 Pitot Duct AreaAV600Hood 7 Transducer Sensor MaximumAV603Hood 7 Pitot Low Cal FlowAV604Hood 7 Pitot High Cal FlowAV605Hood 7 Pitot Low Cal VoltageAV606Hood 7 Pitot High Cal VoltageAV607Hood 7 TP Min FlowAV608Hood 7 TP Max FlowAV609Hood 1 Pitot Uncal Low Cal FlowAV610Hood 1 Pitot Uncal High Cal FlowAV611Hood 2 Pitot Uncal Low Cal FlowAV612Hood 2 Pitot Uncal High Cal FlowAV613Hood 3 Pitot Uncal Low Cal FlowAV614Hood 3 Pitot Uncal High Cal FlowAV615Hood 4 Pitot Uncal Low Cal FlowAV616Hood 4 Pitot Uncal High Cal FlowAV617Hood 5 Pitot Uncal Low Cal FlowAV618Hood 5 Pitot Uncal High Cal FlowAV619Hood 6 Pitot Uncal Low Cal FlowAV620Hood 6 Pitot Uncal High Cal FlowAV621Hood 7 Pitot Uncal Low Cal FlowAV622Hood 7 Pitot Uncal High Cal FlowAV623TTW Sensor UnSpanned VelocityAV624TTW Sensor Spanned VelocityAV625Supply 1 Pitot Low Cal VoltageAV626Supply 1 Pitot High Cal VoltageAV627Supply 2 Pitot Low Cal VoltageAV628Supply 2 Pitot High Cal VoltageAV629Supply 3 Pitot Low Cal VoltageAV630Supply 3 Pitot High Cal VoltageAV631Supply 4 Pitot Low Cal VoltageAV632Supply 4 Pitot High Cal VoltageAV633Exhaust 1 Pitot Low Cal VoltageAV634Exhaust 1 Pitot High Cal VoltageAV635Exhaust 2 Pitot Low Cal VoltageAV636Exhaust 2 Pitot High Cal VoltageAV653Supply 5 Balancer FlowAV654Supply 6 Balancer FlowAV655Current Supply 1 Minimum Flow SetpointAV656Current Supply 2 Minimum Flow SetpointAV657Current Supply 3 Minimum Flow SetpointAV658Current Supply 4 Minimum Flow SetpointAV659Offset SetpointAV660Current Total Supply FlowAV661Current Total Exhaust FlowAV662Supply 1 FlowAV663Supply 2 FlowAV664Supply 3 FlowAV665Supply 4 FlowAV666Exhaust 1 FlowAV667Exhaust 2 FlowAV668Hood 1 FlowAV669Hood 2 FlowAV670Hood 3 FlowAV671Hood 4 FlowAV672Hood 5 FlowAV673Hood 6 FlowAV674Hood 7 FlowAV675Current Supply 1 Temperature Control PositionAV676Current Supply 1 Flow Control PositionAV677Current Supply 2 Temperature Control PositionAV678Current Supply 2 Flow Control PositionAV679Current Supply 3 Temperature Control PositionAV680Current Supply 3 Flow Control PositionAV681Current Supply 4 Temperature Control PositionAV682Current Supply 4 Flow Control PositionAV683Current Exhaust 1 Flow Control PositionAV684Current Exhaust 2 Flow Control PositionAV685Supply 1 DATAV686Supply 2 DATAV687Supply 3 DATAV688Supply 4 DATAV689Supply 1 Room TempAV690Supply 2 Room TempAV691Supply 3 Room TempAV692Supply 4 Room TempAV693Supply 1 Room Temp AdjAV694Supply 2 Room Temp AdjAV695Supply 3 Room Temp AdjAV696Supply 4 Room Temp AdjAV697Room PressureAV698Relative HumidityAV699Hood 8 Flow Input NumberAV700Hood 9 Flow Input NumberAV701Hood 10 Flow Input NumberAV702Hood 11 Flow Input NumberAV703Hood 12 Flow Input NumberAV704Hood 13 Flow Input NumberAV705Hood 14 Flow Input NumberAV706Hood 15 Flow Input NumberAV707Hood 16 Flow Input NumberAV708Hood 17 Flow Input NumberAV709Hood 18 Flow Input NumberAV710Hood 19 Flow Input NumberAV711Hood 20 Flow Input NumberAV713Supply 1 Flow VoltageAV714Supply 2 Flow VoltageAV715Supply 3 Flow VoltageAV716Supply 4 Flow VoltageAV717Exhaust 1 Flow VoltageAV718Exhaust 2 Flow VoltageAV719Hood 1 Flow VoltageAV720Hood 2 Flow VoltageAV721Hood 3 Flow VoltageAV722Hood 4 Flow VoltageAV723Hood 5 Flow VoltageAV724Hood 6 Flow VoltageAV725Hood 7 Flow VoltageAV726Supply 1 DAT VoltageAV727Supply 2 DAT VoltageAV728Supply 3 DAT VoltageAV729Supply 4 DAT VoltageAV730Room Pressure VoltageAV731Relative Humidity VoltageAV732Supply 1 Room Temp Adjustment VoltageAV733Supply 2 Room Temp Adjustment VoltageAV734Supply 3 Room Temp Adjustment VoltageAV735Supply 4 Room Temp Adjustment VoltageAV736Supply 1 Flow Proportional GainAV737Supply 2 Flow Proportional GainAV738Supply 3 Flow Proportional GainAV739Supply 4 Flow Proportional GainAV740Exhaust 1 Flow Proportional GainAV741Exhaust 2 Flow Proportional GainAV742Supply 1 Flow Integral TimeAV743Supply 2 Flow Integral TimeAV744Supply 3 Flow Integral TimeAV745Supply 4 Flow Integral TimeAV746Exhaust 1 Flow Integral TimeAV747Exhaust 2 Flow Integral TimeAV748Pressure Control GainAV749Supply 1 Temp Throttling RangeAV750Supply 2 Temp Throttling RangeAV751Supply 3 Temp Throttling RangeAV752Supply 4 Temp Throttling RangeAV753Supply 1 Temp Integral TimeAV754Supply 2 Temp Integral TimeAV755Supply 3 Temp Integral TimeAV756Supply 4 Temp Integral TimeAV757Supply 1 Flow SpeedAV758Supply 2 Flow SpeedAV759Supply 3 Flow SpeedAV760Supply 4 Flow SpeedAV761Exhaust 1 Flow SpeedAV762Exhaust 2 Flow SpeedAV763Supply 1 Flow SensitivityAV764Supply 2 Flow SensitivityAV765Supply 3 Flow SensitivityAV766Supply 4 Flow SensitivityAV767Exhaust 1 Flow SensitivityAV768Exhaust 2 Flow SensitivityAV769Supply 1 Shutdown Low Flow AlarmAV770Supply 1 Shutdown High Flow AlarmAV771Supply 2 Shutdown Low Flow AlarmAV772Supply 2 Shutdown High Flow AlarmAV773Supply 3 Shutdown Low Flow AlarmAV774Supply 3 Shutdown High Flow AlarmAV775Supply 4 Shutdown Low Flow AlarmAV776Supply 4 Shutdown High Flow AlarmAV777Exhaust 1 Shutdown Low Flow AlarmAV778Exhaust 1 Shutdown High Flow AlarmAV779Exhaust 2 Shutdown Low Flow AlarmAV780Exhaust 2 Shutdown High Flow AlarmAV781Exhaust 1 Unocc Low Flow AlarmAV782Exhaust 1 Unocc High Flow AlarmAV783Exhaust 2 Unocc Low Flow AlarmAV784Exhaust 2 Unocc High Flow AlarmAV785Current Exhaust 1 Low Flow AlarmAV786Current Exhaust 1 High Flow AlarmAV787Current Exhaust 2 Low Flow AlarmAV788Current Exhaust 2 High Flow AlarmAV789Hood 8 FlowAV790Hood 9 FlowAV791Hood 10 FlowAV792Hood 11 FlowAV793Hood 12 FlowAV794Hood 13 FlowAV795Hood 14 FlowAV796Hood 15 FlowAV797Hood 16 FlowAV798Hood 17 FlowAV799Hood 18 FlowAV800Hood 19 FlowAV801Hood 20 FlowAV802Hood 8 Flow VoltageAV803Hood 9 Flow VoltageAV804Hood 10 Flow VoltageAV805Hood 11 Flow VoltageAV806Hood 12 Flow VoltageAV807Hood 13 Flow VoltageAV808Hood 14 Flow VoltageAV809Hood 15 Flow VoltageAV810Hood 16 Flow VoltageAV811Hood 17 Flow VoltageAV812Hood 18 Flow VoltageAV813Hood 19 Flow VoltageAV814Hood 20 Flow VoltageAV815Hood 8 Venturi Minimum FlowAV816Hood 8 Venturi Maximum FlowAV817Hood 8 Venturi LOM ESC TimeAV818Hood 8 Linear Duct AreaAV819Hood 8 Linear Top VelocityAV820Hood 8 Linear Signal MinimumAV821Hood 8 Linear Signal MaximumAV822Hood 8 Pitot Sensor ZeroAV823Hood 8 Transducer Signal MinimumAV824Hood 8 Transducer Signal MaximumAV825Hood 8 Pitot Duct AreaAV826Hood 8 Transducer Sensor MaximumAV827Hood 8 Pitot Low Cal FlowAV828Hood 8 Pitot High Cal FlowAV829Hood 8 Pitot Low Cal VoltageAV830Hood 8 Pitot High Cal VoltageAV831Hood 8 TP Min FlowAV832Hood 8 TP Max FlowAV833Hood 9 Venturi Minimum FlowAV834Hood 9 Venturi Maximum FlowAV835Hood 9 Venturi LOM ESC TimeAV836Hood 9 Linear Duct AreaAV837Hood 9 Linear Top VelocityAV838Hood 9 Linear Signal MinimumAV839Hood 9 Linear Signal MaximumAV840Hood 9 Pitot Sensor ZeroAV841Hood 9 Transducer Signal MinimumAV842Hood 9 Transducer Signal MaximumAV843Hood 9 Pitot Duct AreaAV844Hood 9 Transducer Sensor MaximumAV845Hood 9 Pitot Low Cal FlowAV846Hood 9 Pitot High Cal FlowAV847Hood 9 Pitot Low Cal VoltageAV848Hood 9 Pitot High Cal VoltageAV849Hood 9 TP Min FlowAV850Hood 9 TP Max FlowAV851Hood 10 Venturi Minimum FlowAV852Hood 10 Venturi Maximum FlowAV853Hood 10 Venturi LOM ESC TimeAV854Hood 10 Linear Duct AreaAV855Hood 10 Linear Top VelocityAV856Hood 10 Linear Signal MinimumAV857Hood 10 Linear Signal MaximumAV858Hood 10 Pitot Sensor ZeroAV859Hood 10 Transducer Signal MinimumAV860Hood 10 Transducer Signal MaximumAV861Hood 10 Pitot Duct AreaAV862Hood 10 Transducer Sensor MaximumAV863Hood 10 Pitot Low Cal FlowAV864Hood 10 Pitot High Cal FlowAV865Hood 10 Pitot Low Cal VoltageAV866Hood 10 Pitot High Cal VoltageAV867Hood 10 TP Min FlowAV868Hood 10 TP Max FlowAV869Hood 11 Venturi Minimum FlowAV870Hood 11 Venturi Maximum FlowAV871Hood 11 Venturi LOM ESC TimeAV872Hood 11 Linear Duct AreaAV873Hood 11 Linear Top VelocityAV874Hood 11 Linear Signal MinimumAV875Hood 11 Linear Signal MaximumAV876Hood 11 Pitot Sensor ZeroAV877Hood 11 Transducer Signal MinimumAV878Hood 11 Transducer Signal MaximumAV879Hood 11 Pitot Duct AreaAV880Hood 11 Transducer Sensor MaximumAV881Hood 11 Pitot Low Cal FlowAV882Hood 11 Pitot High Cal FlowAV883Hood 11 Pitot Low Cal VoltageAV884Hood 11 Pitot High Cal VoltageAV885Hood 11 TP Min FlowAV886Hood 11 TP Max FlowAV887Hood 12 Venturi Minimum FlowAV888Hood 12 Venturi Maximum FlowAV889Hood 12 Venturi LOM ESC TimeAV890Hood 12 Linear Duct AreaAV891Hood 12 Linear Top VelocityAV892Hood 12 Linear Signal MinimumAV893Hood 12 Linear Signal MaximumAV894Hood 12 Pitot Sensor ZeroAV895Hood 12 Transducer Signal MinimumAV896Hood 12 Transducer Signal MaximumAV897Hood 12 Pitot Duct AreaAV898Hood 12 Transducer Sensor MaximumAV899Hood 12 Pitot Low Cal FlowAV900Hood 12 Pitot High Cal FlowAV901Hood 12 Pitot Low Cal VoltageAV902Hood 12 Pitot High Cal VoltageAV903Hood 12 TP Min FlowAV904Hood 12 TP Max FlowAV905Hood 13 Venturi Minimum FlowAV906Hood 13 Venturi Maximum FlowAV907Hood 13 Venturi LOM ESC TimeAV908Hood 13 Linear Duct AreaAV909Hood 13 Linear Top VelocityAV910Hood 13 Linear Signal MinimumAV911Hood 13 Linear Signal MaximumAV912Hood 13 Pitot Sensor ZeroAV913Hood 13 Transducer Signal MinimumAV914Hood 13 Transducer Signal MaximumAV915Hood 13 Pitot Duct AreaAV916Hood 13 Transducer Sensor MaximumAV917Hood 13 Pitot Low Cal FlowAV918Hood 13 Pitot High Cal FlowAV919Hood 13 Pitot Low Cal VoltageAV920Hood 13 Pitot High Cal VoltageAV921Hood 13 TP Min FlowAV922Hood 13 TP Max FlowAV923Hood 14 Venturi Minimum FlowAV924Hood 14 Venturi Maximum FlowAV925Hood 14 Venturi LOM ESC TimeAV926Hood 14 Linear Duct AreaAV927Hood 14 Linear Top VelocityAV928Hood 14 Linear Signal MinimumAV929Hood 14 Linear Signal MaximumAV930Hood 14 Pitot Sensor ZeroAV931Hood 14 Transducer Signal MinimumAV932Hood 14 Transducer Signal MaximumAV933Hood 14 Pitot Duct AreaAV934Hood 14 Transducer Sensor MaximumAV935Hood 14 Pitot Low Cal FlowAV936Hood 14 Pitot High Cal FlowAV937Hood 14 Pitot Low Cal VoltageAV938Hood 14 Pitot High Cal VoltageAV939Hood 14 TP Min FlowAV940Hood 14 TP Max FlowAV941Hood 15 Venturi Minimum FlowAV942Hood 15 Venturi Maximum FlowAV943Hood 15 Venturi LOM ESC TimeAV944Hood 15 Linear Duct AreaAV945Hood 15 Linear Top VelocityAV946Hood 15 Linear Signal MinimumAV947Hood 15 Linear Signal MaximumAV948Hood 15 Pitot Sensor ZeroAV949Hood 15 Transducer Signal MinimumAV950Hood 15 Transducer Signal MaximumAV951Hood 15 Pitot Duct AreaAV952Hood 15 Transducer Sensor MaximumAV953Hood 15 Pitot Low Cal FlowAV954Hood 15 Pitot High Cal FlowAV955Hood 15 Pitot Low Cal VoltageAV956Hood 15 Pitot High Cal VoltageAV957Hood 15 TP Min FlowAV958Hood 15 TP Max FlowAV959Hood 16 Venturi Minimum FlowAV960Hood 16 Venturi Maximum FlowAV961Hood 16 Venturi LOM ESC TimeAV962Hood 16 Linear Duct AreaAV963Hood 16 Linear Top VelocityAV964Hood 16 Linear Signal MinimumAV965Hood 16 Linear Signal MaximumAV966Hood 16 Pitot Sensor ZeroAV967Hood 16 Transducer Signal MinimumAV968Hood 16 Transducer Signal MaximumAV969Hood 16 Pitot Duct AreaAV970Hood 16 Transducer Sensor MaximumAV971Hood 16 Pitot Low Cal FlowAV972Hood 16 Pitot High Cal FlowAV973Hood 16 Pitot Low Cal VoltageAV974Hood 16 Pitot High Cal VoltageAV975Hood 16 TP Min FlowAV976Hood 16 TP Max FlowAV977Hood 17 Venturi Minimum FlowAV978Hood 17 Venturi Maximum FlowAV979Hood 17 Venturi LOM ESC TimeAV980Hood 17 Linear Duct AreaAV981Hood 17 Linear Top VelocityAV982Hood 17 Linear Signal MinimumAV983Hood 17 Linear Signal MaximumAV984Hood 17 Pitot Sensor ZeroAV985Hood 17 Transducer Signal MinimumAV986Hood 17 Transducer Signal MaximumAV987Hood 17 Pitot Duct AreaAV988Hood 17 Transducer Sensor MaximumAV989Hood 17 Pitot Low Cal FlowAV990Hood 17 Pitot High Cal FlowAV991Hood 17 Pitot Low Cal VoltageAV992Hood 17 Pitot High Cal VoltageAV993Hood 17 TP Min FlowAV994Hood 17 TP Max FlowAV995Hood 18 Venturi Minimum FlowAV996Hood 18 Venturi Maximum FlowAV997Hood 18 Venturi LOM ESC TimeAV998Hood 18 Linear Duct AreaAV999Hood 18 Linear Top VelocityAV1000Hood 18 Linear Signal MinimumAV1001Hood 18 Linear Signal MaximumAV1002Hood 18 Pitot Sensor ZeroAV1003Hood 18 Transducer Signal MinimumAV1004Hood 18 Transducer Signal MaximumAV1005Hood 18 Pitot Duct AreaAV1006Hood 18 Transducer Sensor MaximumAV1007Hood 18 Pitot Low Cal FlowAV1008Hood 18 Pitot High Cal FlowAV1009Hood 18 Pitot Low Cal VoltageAV1010Hood 18 Pitot High Cal VoltageAV1011Hood 18 TP Min FlowAV1012Hood 18 TP Max FlowAV1013Hood 19 Venturi Minimum FlowAV1014Hood 19 Venturi Maximum FlowAV1015Hood 19 Venturi LOM ESC TimeAV1016Hood 19 Linear Duct AreaAV1017Hood 19 Linear Top VelocityAV1018Hood 19 Linear Signal MinimumAV1019Hood 19 Linear Signal MaximumAV1020Hood 19 Pitot Sensor ZeroAV1021Hood 19 Transducer Signal MinimumAV1022Hood 19 Transducer Signal MaximumAV1023Hood 19 Pitot Duct AreaAV1024Hood 19 Transducer Sensor MaximumAV1025Hood 19 Pitot Low Cal FlowAV1026Hood 19 Pitot High Cal FlowAV1027Hood 19 Pitot Low Cal VoltageAV1028Hood 19 Pitot High Cal VoltageAV1029Hood 19 TP Min FlowAV1030Hood 19 TP Max FlowAV1031Hood 20 Venturi Minimum FlowAV1032Hood 20 Venturi Maximum FlowAV1033Hood 20 Venturi LOM ESC TimeAV1034Hood 20 Linear Duct AreaAV1035Hood 20 Linear Top VelocityAV1036Hood 20 Linear Signal MinimumAV1037Hood 20 Linear Signal MaximumAV1038Hood 20 Pitot Sensor ZeroAV1039Hood 20 Transducer Signal MinimumAV1040Hood 20 Transducer Signal MaximumAV1041Hood 20 Pitot Duct AreaAV1042Hood 20 Transducer Sensor MaximumAV1043Hood 20 Pitot Low Cal FlowAV1044Hood 20 Pitot High Cal FlowAV1045Hood 20 Pitot Low Cal VoltageAV1046Hood 20 Pitot High Cal VoltageAV1047Hood 20 TP Min FlowAV1048Hood 20 TP Max FlowAV1049Hood 8 Pitot Uncal Low Cal FlowAV1050Hood 8 Pitot Uncal High Cal FlowAV1051Hood 9 Pitot Uncal Low Cal FlowAV1052Hood 9 Pitot Uncal High Cal FlowAV1053Hood 10 Pitot Uncal Low Cal FlowAV1054Hood 10 Pitot Uncal High Cal FlowAV1055Hood 11 Pitot Uncal Low Cal FlowAV1056Hood 11 Pitot Uncal High Cal FlowAV1057Hood 12 Pitot Uncal Low Cal FlowAV1058Hood 12 Pitot Uncal High Cal FlowAV1059Hood 13 Pitot Uncal Low Cal FlowAV1060Hood 13 Pitot Uncal High Cal FlowAV1061Hood 14 Pitot Uncal Low Cal FlowAV1062Hood 14 Pitot Uncal High Cal FlowAV1063Hood 15 Pitot Uncal Low Cal FlowAV1064Hood 15 Pitot Uncal High Cal FlowAV1065Hood 16 Pitot Uncal Low Cal FlowAV1066Hood 16 Pitot Uncal High Cal FlowAV1067Hood 17 Pitot Uncal Low Cal FlowAV1068Hood 17 Pitot Uncal High Cal FlowAV1069Hood 18 Pitot Uncal Low Cal FlowAV1070Hood 18 Pitot Uncal High Cal FlowAV1071Hood 19 Pitot Uncal Low Cal FlowAV1072Hood 19 Pitot Uncal High Cal FlowAV1073Hood 20 Pitot Uncal Low Cal FlowAV1074Hood 20 Pitot Uncal High Cal FlowAV1075Hood 8 Flow K factorAV1076Hood 9 Flow K factorAV1077Hood 10 Flow K factorAV1078Hood 11 Flow K factorAV1079Hood 12 Flow K factorAV1080Hood 13 Flow K factorAV1081Hood 14 Flow K factorAV1082Hood 15 Flow K factorAV1083Hood 16 Flow K factorAV1084Hood 17 Flow K factorAV1085Hood 18 Flow K factorAV1086Hood 19 Flow K factorAV1087Hood 20 Flow K factorAV1088Supply 1 Flow SetpointAV1089Supply 2 Flow SetpointAV1090Supply 3 Flow SetpointAV1091Supply 4 Flow SetpointAV1092Exhaust 1 Flow SetpointAV1093Exhaust 2 Flow SetpointAV1094Supply 5 Flow Proportional GainAV1095Supply 5 Flow Integral TimeAV1096Supply 5 Flow SpeedAV1097Supply 5 Flow SensitivityAV1098Supply 6 Flow Proportional GainAV1099Supply 6 Flow Integral TimeAV1100Supply 6 Flow SpeedAV1101Supply 6 Flow SensitivityAV1102Supply 5 Pitot Uncal Low Cal FlowAV1103Supply 5 Pitot Uncal High Cal FlowAV1104Supply 5 Venturi Minimum FlowAV1105Supply 5 Venturi Minimum FlowAV1106Supply 5 Flow K FactorAV1107Supply 5 Venturi Setup PositionAV1108Supply 5 Venturi LOM Esc TimeAV1109Supply 5 Linear Duct AreaAV1110Supply 5 Linear Top VelocityAV1111Supply 5 Linear Signal MinimumAV1112Supply 5 Linear Signal MaximumAV1113Supply 5 Pitot Sensor ZeroAV1114Supply 5 Pitot Low Cal PosAV1115Supply 5 Transducer Signal MinimumAV1116Supply 5 Pitot High Cal PosAV1117Supply 5 Transducer Signal MaximumAV1118Supply 5 Pitot Low Cal FlowAV1119Supply 5 Pitot Duct AreaAV1120Supply 5 Pitot High Cal FlowAV1121Supply 5 Transducer Sensor MaximumAV1122Supply 6 Pitot Uncal Low Cal FlowAV1123Supply 6 Pitot Uncal High Cal FlowAV1124Supply 6 Venturi Minimum FlowAV1125Supply 6 Venturi Maximum FlowAV1126Supply 6 Flow K FactorAV1127Supply 6 Venturi Setup PositionAV1128Supply 6 Venturi LOM Esc TimeAV1129Supply 6 Linear Duct AreaAV1130Supply 6 Linear Top VelocityAV1131Supply 6 Linear Signal MinimumAV1132Supply 6 Linear Signal MaximumAV1133Supply 6 Pitot Sensor ZeroAV1134Supply 6 Pitot Low Cal PosAV1135Supply 6 Transducer Signal MinimumAV1136Supply 6 Pitot High Cal PosAV1137Supply 6 Transducer Signal MaximumAV1138Supply 6 Pitot Low Cal FlowAV1139Supply 6 Pitot Duct AreaAV1140Supply 6 Pitot High Cal FlowAV1141Supply 6 Transducer Sensor MaximumAV1142Supply 5 Room Temp OffsetAV1143Supply 6 Room Temp OffsetAV1144Supply 5 Room Temp Adj Signal MinimumAV1145Supply 5 Room Temp Adj Signal MaximumAV1146Supply 5 Room Temp Adj Sensor MinimumAV1147Supply 5 Room Temp Adj Sensor MaximumAV1148Supply 6 Room Temp Adj Signal MinimumAV1149Supply 6 Room Temp Adj Signal MaximumAV1150Supply 6 Room Temp Adj Sensor MinimumAV1151Supply 6 Room Temp Adj Sensor MaximumAV1152Supply 5 Reheat/Cooling DelayAV1153Supply 6 Reheat/Cooling DelayAV1154Supply 5 Room Temp Signal MinimumAV1155Supply 5 Room Temp Signal MaximumAV1156Supply 5 Room Temp Sensor MinimumAV1157Supply 5 Room Temp Sensor MaximumAV1158Supply 6 Room Temp Signal MinimumAV1159Supply 6 Room Temp Signal MaximumAV1160Supply 6 Room Temp Sensor MinimumAV1161Supply 6 Room Temp Sensor MaximumAV1162Supply 5 Temp Throttling RangeAV1163Supply 6 Temp Throttling RangeAV1164Supply 5 Temp Integral TimeAV1165Supply 6 Temp Integral TimeAV1166Current Supply 5 Minimum Flow SetpointAV1167Current Supply 5 Minimum FlowAV1168Current Supply 5 Cooling FlowAV1169Current Supply 5 Heating FlowAV1170Current Supply 5 Maximum FlowAV1171Current Supply 6 Minimum Flow SetpointAV1172Current Supply 6 Minimum FlowAV1173Current Supply 6 Cooling FlowAV1174Current Supply 6 Heating FlowAV1175Current Supply 6 Maximum FlowAV1176Current Supply 5 Heat SetpointAV1177Current Supply 5 Cool SetpointAV1178Current Supply 6 Heat SetpointAV1179Current Supply 6 Cool SetpointAV1180Supply 5 FlowAV1181Supply 6 FlowAV1182Current Supply 5 Temperature Control PositionAV1183Current Supply 5 Flow Control PositionAV1184Current Supply 6 Temperature Control PositionAV1185Current Supply 6 Flow Control PositionAV1186Supply 5 Room TempAV1187Supply 6 Room TempAV1188Supply 5 Room Temp AdjAV1189Supply 6 Room Temp AdjAV1190Supply 5 Flow VoltageAV1191Supply 6 Flow VoltageAV1192Supply 5 Room Temp VoltageAV1193Supply 6 Room Temp VoltageAV1194Supply 5 Room Temp Adjustment VoltageAV1195Supply 6 Room Temp Adjustment VoltageAV1196Supply 5 Flow SetpointAV1197Supply 6 Flow SetpointAV1198Supply 5 Minimum FlowAV1199Supply 5 Cooling FlowAV1200Supply 5 Heating FlowAV1201Supply 5 Maximum FlowAV1202Supply 5 Minimum PositionAV1203Supply 5 Maximum PositionAV1204Supply 5 Emergency FlowAV1205Supply 5 Shutdown FlowAV1206Supply 6 Minimum FlowAV1207Supply 6 Cooling FlowAV1208Supply 6 Heating FlowAV1209Supply 6 Maximum FlowAV1210Supply 6 Minimum PositionAV1211Supply 6 Maximum PositionAV1212Supply 6 Emergency FlowAV1213Supply 6 Shutdown FlowAV1214Supply 5 Heat SetpointAV1215Supply 5 Cool SetpointAV1216Supply 6 Heat SetpointAV1217Supply 6 Cool SetpointAV1218Supply 5 Low Flow AlarmAV1219Supply 5 High Flow AlarmAV1220Supply 6 Low Flow AlarmAV1221Supply 6 High Flow AlarmAV1222Supply 5 Low Temperature AlarmAV1223Supply 5 High Temperature AlarmAV1224Supply 6 Low Temperature AlarmAV1225Supply 6 High Temperature AlarmAV1226Supply 5 Shutdown Low Flow AlarmAV1227Supply 5 Shutdown High Flow AlarmAV1228Supply 6 Shutdown Low Flow AlarmAV1229Supply 6 Shutdown High Flow AlarmAV1230Supply 5 Flow ChangeAV1231Supply 6 Flow ChangeAV1232Supply 5 Flow Input NumberAV1233Supply 5 Room Temp Input NumberAV1234Supply 5 Room Temp Adj Input NumberAV1235Supply 6 Flow Input NumberAV1236Supply 6 Room Temp Input NumberAV1237Supply 6 Room Temp Adj Input NumberAV1238Current Supply 5 Low Flow AlarmAV1239Current Supply 5 High Flow AlarmAV1240Current Supply 6 Low Flow AlarmAV1241Current Supply 6 High Flow AlarmAV1242Current Supply 5 Low Temperature AlarmAV1243Current Supply 5 High Temperature AlarmAV1244Current Supply 6 Low Temperature AlarmAV1245Current Supply 6 High Temperature AlarmAV1246Supply 5 Pitot Low Cal VoltageAV1247Supply 5 Pitot High Cal VoltageAV1248Supply 6 Pitot Low Cal VoltageAV1249Supply 6 Pitot High Cal VoltageAV1250Supply 5 DAT OffsetAV1251Supply 6 DAT OffsetAV1252Supply 5 Unocc Minimum FlowAV1253Supply 5 Unocc Cooling FlowAV1254Supply 5 Unocc Heating FlowAV1255Supply 5 Unocc Maximum FlowAV1256Supply 6 Unocc Minimum FlowAV1257Supply 6 Unocc Cooling FlowAV1258Supply 6 Unocc Heating FlowAV1259Supply 6 Unocc Maximum FlowAV1260Supply 5 Unocc Heat SetpointAV1261Supply 5 Unocc Cool SetpointAV1262Supply 5 DAT DeltaAV1263Supply 6 Unocc Heat SetpointAV1264Supply 6 Unocc Cool SetpointAV1265Supply 6 DAT DeltaAV1266Supply 5 Unocc Low Flow AlarmAV1267Supply 5 Unocc High Flow AlarmAV1268Supply 6 Unocc Low Flow AlarmAV1269Supply 6 Unocc High Flow AlarmAV1270Supply 5 Unocc Low Temperature AlarmAV1271Supply 5 Unocc High Temperature AlarmAV1272Supply 6 Unocc Low Temperature AlarmAV1273Supply 6 Unocc High Temperature AlarmAV1274Supply 5 High DAT AlarmAV1275Supply 6 High DAT AlarmAV1276Supply 5 DAT Signal MinimumAV1277Supply 5 DAT Signal MaximumAV1278Supply 5 DAT Sensor MinimumAV1279Supply 5 DAT Sensor MaximumAV1280Supply 6 DAT Signal MinimumAV1281Supply 6 DAT Signal MaximumAV1282Supply 6 DAT Sensor MinimumAV1283Supply 6 DAT Sensor MaximumAV1284Supply 5 DAT Input NumberAV1285Supply 5 Occupancy Input NumberAV1286Supply 6 DAT Input NumberAV1287Supply 6 Occupancy Input NumberAV1288Supply 5 DATAV1289Supply 6 DATAV1290Supply 5 DAT VoltageAV1291Supply 6 DAT VoltageBV1Reset VariablesBV2Reset ControlBV3Supply 1 Flow Control ModeBV4Supply 2 Flow Control ModeBV5Supply 3 Flow Control ModeBV6Supply 4 Flow Control ModeBV7Supply 1 Temp Control ModeBV8Supply 2 Temp Control ModeBV9Supply 3 Temp Control ModeBV10Supply 4 Temp Control ModeBV11Exhaust 1 Flow Control ModeBV12Exhaust 2 Flow Control ModeBV15Supply 1 Balancer ModeBV16Supply 2 Balancer ModeBV17Supply 3 Balancer ModeBV18Supply 4 Balancer ModeBV19Exhaust 1 Balancer ModeBV20Exhaust 2 Balancer ModeBV21Door ModeBV22Emergency ModeBV23Shutdown ModeBV24Supply 1 Occupancy ModeBV25Supply 2 Occupancy ModeBV26Supply 3 Occupancy ModeBV27Supply 4 Occupancy ModeBV28Supply 1 Venturi VisibleBV29Supply 1 Linear VisibleBV30Supply 1 Pitot VisibleBV31Supply 2 Venturi VisibleBV32Supply 2 Linear VisibleBV33Supply 2 Pitot VisibleBV34Supply 3 Venturi VisibleBV35Supply 3 Linear VisibleBV36Supply 3 Pitot VisibleBV37Supply 4 Venturi VisibleBV38Supply 4 Linear VisibleBV39Supply 4 Pitot VisibleBV40Exhaust 1 Venturi VisibleBV41Exhaust 1 Linear VisibleBV42Exhaust 1 Pitot VisibleBV43Exhaust 2 Venturi VisibleBV44Exhaust 2 Linear VisibleBV45Exhaust 2 Pitot VisibleBV46Supply 1 DAT RTD VisibleBV47Supply 1 DAT Voltage VisibleBV48Supply 2 DAT RTD VisibleBV49Supply 2 DAT Voltage VisibleBV50Supply 3 DAT RTD VisibleBV51Supply 3 DAT Voltage VisibleBV52Supply 4 DAT RTD VisibleBV53Supply 4 DAT Voltage VisibleBV54Room Pressure TTW VisibleBV55Room Pressure Transducer VisibleBV56Hood 1 Venturi VisibleBV57Hood 1 Linear VisibleBV58Hood 1 Pitot VisibleBV59Hood 1 Two Position VisibleBV60Hood 2 Venturi VisibleBV61Hood 2 Linear VisibleBV62Hood 2 Pitot VisibleBV63Hood 2 Two Position VisibleBV64Hood 3 Venturi VisibleBV65Hood 3 Linear VisibleBV66Hood 3 Pitot VisibleBV67Hood 3 Two Position VisibleBV68Hood 4 Venturi VisibleBV69Hood 4 Linear VisibleBV70Hood 4 Pitot VisibleBV71Hood 4 Two Position VisibleBV72Hood 5 Venturi VisibleBV73Hood 5 Linear VisibleBV74Hood 5 Pitot VisibleBV75Hood 5 Two Position VisibleBV76Hood 6 Venturi VisibleBV77Hood 6 Linear VisibleBV78Hood 6 Pitot VisibleBV79Hood 6 Two Position VisibleBV80Hood 7 Venturi VisibleBV81Hood 7 Linear VisibleBV82Hood 7 Pitot VisibleBV83Hood 7 Two Position VisibleBV84Door Switch DirectionBV85Emergency Switch DirectionBV86Shutdown Switch DirectionBV87Supply 1 Occupancy DirectionBV88Supply 2 Occupancy DirectionBV89Supply 3 Occupancy DirectionBV90Supply 4 Occupancy DirectionBV91Supply 1 Reheat ModeBV92Supply 2 Reheat ModeBV93Supply 3 Reheat ModeBV94Supply 1 PID Control ModeBV95Supply 2 PID Control ModeBV96Supply 3 PID Control ModeBV97Supply 4 PID Control ModeBV98Exhaust 1 PID Control ModeBV99Exhaust 2 PID Control ModeBV100Hood 8 Venturi VisibleBV101Hood 8 Linear VisibleBV102Hood 8 Pitot VisibleBV103Hood 8 Two Position VisibleBV104Hood 9 Venturi VisibleBV105Hood 9 Linear VisibleBV106Hood 9 Pitot VisibleBV107Hood 9 Two Position VisibleBV108Hood 10 Venturi VisibleBV109Hood 10 Linear VisibleBV110Hood 10 Pitot VisibleBV111Hood 10 Two Position VisibleBV112Hood 11 Venturi VisibleBV113Hood 11 Linear VisibleBV114Hood 11 Pitot VisibleBV115Hood 11 Two Position VisibleBV116Hood 12 Venturi VisibleBV117Hood 12 Linear VisibleBV118Hood 12 Pitot VisibleBV119Hood 12 Two Position VisibleBV120Hood 13 Venturi VisibleBV121Hood 13 Linear VisibleBV122Hood 13 Pitot VisibleBV123Hood 13 Two Position VisibleBV124Hood 14 Venturi VisibleBV125Hood 14 Linear VisibleBV126Hood 14 Pitot VisibleBV127Hood 14 Two Position VisibleBV128Hood 15 Venturi VisibleBV129Hood 15 Linear VisibleBV130Hood 15 Pitot VisibleBV131Hood 15 Two Position VisibleBV132Hood 16 Venturi VisibleBV133Hood 16 Linear VisibleBV134Hood 16 Pitot VisibleBV135Hood 16 Two Position VisibleBV136Hood 17 Venturi VisibleBV137Hood 17 Linear VisibleBV138Hood 17 Pitot VisibleBV139Hood 17 Two Position VisibleBV140Hood 18 Venturi VisibleBV141Hood 18 Linear VisibleBV142Hood 18 Pitot VisibleBV143Hood 18 Two Position VisibleBV144Hood 19 Venturi VisibleBV145Hood 19 Linear VisibleBV146Hood 19 Pitot VisibleBV147Hood 19 Two Position VisibleBV148Hood 20 Venturi VisibleBV149Hood 20 Linear VisibleBV150Hood 20 Pitot VisibleBV151Hood 20 Two Position VisibleBV152Supply 4 Reheat ModeBV153Hood 1 TP Max Flow SignalBV154Hood 2 TP Max Flow SignalBV155Hood 3 TP Max Flow SignalBV156Hood 4 TP Max Flow SignalBV157Hood 5 TP Max Flow SignalBV158Hood 6 TP Max Flow SignalBV159Hood 7 TP Max Flow SignalBV160Hood 8 TP Max Flow SignalBV161Hood 9 TP Max Flow SignalBV162Hood 10 TP Max Flow SignalBV163Hood 11 TP Max Flow SignalBV164Hood 12 TP Max Flow SignalBV165Hood 13 TP Max Flow SignalBV166Hood 14 TP Max Flow SignalBV167Hood 15 TP Max Flow SignalBV168Hood 16 TP Max Flow SignalBV169Hood 17 TP Max Flow SignalBV170Hood 18 TP Max Flow SignalBV171Hood 19 TP Max Flow SignalBV172Hood 20 TP Max Flow SignalBV173Supply 1 Flow Control DirectionBV174Supply 2 Flow Control DirectionBV175Supply 3 Flow Control DirectionBV176Supply 4 Flow Control DirectionBV177Exhaust 1 Flow Control DirectionBV178Exhaust 2 Flow Control DirectionBV179Supply 1 Temp Control DirectionBV180Supply 2 Temp Control DirectionBV181Supply 3 Temp Control DirectionBV182Supply 4 Temp Control DirectionBV183Supply 1 Flow Control ActiveBV184Supply 2 Flow Control ActiveBV185Supply 3 Flow Control ActiveBV186Supply 4 Flow Control ActiveBV187Exhaust 1 Flow Control ActiveBV188Exhaust 2 Flow Control ActiveBV189Supply 1 Temp Control ActiveBV190Supply 2 Temp Control ActiveBV191Supply 3 Temp Control ActiveBV192Supply 4 Temp Control ActiveBV193Reset Output SelectionBV194Reconfigure OutputsBV195Supply 1 Flow Input ActiveBV196Supply 1 DAT Input ActiveBV197Supply 1 Room Temp Input ActiveBV198Supply 1 Temp Setp Input ActiveBV199Supply 1 Occupancy Input ActiveBV200Supply 2 Flow Input ActiveBV201Supply 2 DAT Input ActiveBV202Supply 2 Room Temp Input ActiveBV203Supply 2 Temp Setp Input ActiveBV204Supply 2 Occupancy Input ActiveBV205Supply 3 Flow Input ActiveBV206Supply 3 DAT Input ActiveBV207Supply 3 Room Temp Input ActiveBV208Supply 3 Temp Setp Input ActiveBV209Supply 3 Occupancy Input ActiveBV210Supply 4 Flow Input ActiveBV211Supply 4 DAT Input ActiveBV212Supply 4 Room Temp Input ActiveBV213Supply 4 Temp Setp Input ActiveBV214Supply 4 Occupancy Input ActiveBV215Exhaust 1 Flow Input ActiveBV216Exhaust 2 Flow Input ActiveBV217Hood 1 Flow Input ActiveBV218Hood 2 Flow Input ActiveBV219Hood 3 Flow Input ActiveBV220Hood 4 Flow Input ActiveBV221Hood 5 Flow Input ActiveBV222Hood 6 Flow Input ActiveBV223Hood 7 Flow Input ActiveBV224Room Pressure Input ActiveBV225Relative Humidity Input ActiveBV226Door Switch Input ActiveBV227Emergency Switch Input ActiveBV228Shutdown Switch Input ActiveBV229Hood 8 Flow Input ActiveBV230Hood 9 Flow Input ActiveBV231Hood 10 Flow Input ActiveBV232Hood 11 Flow Input ActiveBV233Hood 12 Flow Input ActiveBV234Hood 13 Flow Input ActiveBV235Hood 14 Flow Input ActiveBV236Hood 15 Flow Input ActiveBV237Hood 16 Flow Input ActiveBV238Hood 17 Flow Input ActiveBV239Hood 18 Flow Input ActiveBV240Hood 19 Flow Input ActiveBV241Hood 20 Flow Input ActiveBV242Supply 1 DAT Delta ActiveBV243Supply 2 DAT Delta ActiveBV244Supply 3 DAT Delta ActiveBV245Supply 4 DAT Delta ActiveBV246Exhaust ConfigurationBV247Reset Supply 1 Flow TuningBV248Reset Supply 2 Flow TuningBV249Reset Supply 3 Flow TuningBV250Reset Supply 4 Flow TuningBV251Reset Exhaust 1 Flow TuningBV252Reset Exhaust 2 Flow TuningBV253Supply 1 Room Temp RTD VisibleBV254Supply 1 Room Temp Voltage VisibleBV255Supply 2 Room Temp RTD VisibleBV256Supply 2 Room Temp Voltage VisibleBV257Supply 3 Room Temp RTD VisibleBV258Supply 3 Room Temp Voltage VisibleBV259Supply 4 Room Temp RTD VisibleBV260Supply 4 Room Temp Voltage VisibleBV261Reset Supply 5 Flow TuningBV262Reset Supply 6 Flow TuningBV263Supply 5 Flow Control ModeBV264Supply 6 Flow Control ModeBV265Supply 5 Temp Control ModeBV266Supply 6 Temp Control ModeBV267Supply 5 Balancer ModeBV268Supply 6 Balancer ModeBV269Supply 5 Flow Control DirectionBV270Supply 6 Flow Control DirectionBV271Supply 5 Temp Control DirectionBV272Supply 6 Temp Control DirectionBV273Supply 5 Venturi VisibleBV274Supply 5 Linear VisibleBV275Supply 5 Pitot VisibleBV276Supply 6 Venturi VisibleBV277Supply 6 Linear VisibleBV278Supply 6 Pitot VisibleBV279Supply 5 Room Temp Voltage VisibleBV280Supply 6 Room Temp Voltage VisibleBV281Supply 5 Flow Control ActiveBV282Supply 6 Flow Control ActiveBV283Supply 5 Temp Control ActiveBV284Supply 6 Temp Control ActiveBV285Supply 5 Flow Input ActiveBV286Supply 5 Room Temp Input ActiveBV287Supply 5 Room Temp Adj Input ActiveBV288Supply 6 Flow Input ActiveBV289Supply 6 Room Temp Input ActiveBV290Supply 6 Room Temp Adj Input ActiveBV291Supply 5 Room Temp RTD VisibleBV292Supply 6 Room Temp RTD VisibleBV293Supply 5 Reheat ModeBV294Supply 6 Reheat ModeBV295Supply 5 PID Control ModeBV296Supply 6 PID Control ModeBV297Supply 5 Occupancy ModeBV298Supply 6 Occupancy ModeBV299Supply 5 Occupancy DirectionBV300Supply 6 Occupancy DirectionBV301Supply 5 DAT Voltage VisibleBV302Supply 6 DAT Voltage VisibleBV303Supply 5 DAT Input ActiveBV304Supply 5 Occupancy Input ActiveBV305Supply 6 DAT Input ActiveBV306Supply 6 Occupancy Input ActiveBV307Supply 5 DAT Delta ActiveBV308Supply 6 DAT Delta ActiveBV309Supply 5 DAT RTD VisibleBV310Supply 6 DAT RTD VisibleMV1Input 1 Input TypeMV2Input 2 Input TypeMV3Input 3 Input TypeMV4Input 4 Input TypeMV5Input 5 Input TypeMV6Input 6 Input TypeMV7Input 7 Input TypeMV8Input 8 Input TypeMV9Input 9 Input TypeMV10Input 10 Input TypeMV11Input 11 Input TypeMV12Input 12 Input TypeMV13Input 13 Input TypeMV14Input 14 Input TypeMV15Input 15 Input TypeMV16Input 16 Input TypeMV17Input 17 Input TypeMV18Input 18 Input TypeMV19Input 19 Input TypeMV20Input 20 Input TypeMV21Input 21 Input TypeMV22Input 22 Input TypeMV23Input 23 Input TypeMV24Input 24 Input TypeMV25Input 25 Input TypeMV26Input 26 Input TypeMV27Input 27 Input TypeMV28Input 28 Input TypeMV29Input 29 Input TypeMV30Input 30 Input TypeMV31Input 31 Input TypeMV32Input 32 Input TypeMV33Output 1 Output TypeMV34Output 2 Output TypeMV35Output 3 Output TypeMV36Output 4 Output TypeMV37Output 5 Output TypeMV38Output 6 Output TypeMV39Output 7 Output TypeMV40Output 8 Output TypeMV41Output 9 Output TypeMV42Output 10 Output TypeMV43Output 11 Output TypeMV44Output 12 Output TypeMV45Supply 1 Flow TypeMV46Supply 2 Flow TypeMV47Supply 3 Flow TypeMV48Supply 4 Flow TypeMV49Exhaust 1 Flow TypeMV50Exhaust 2 Flow TypeMV51Hood 1 Flow TypeMV52Hood 2 Flow TypeMV53Hood 3 Flow TypeMV54Hood 4 Flow TypeMV55Hood 5 Flow TypeMV56Hood 6 Flow TypeMV57Hood 7 Flow TypeMV58Supply 1 DAT TypeMV59Supply 2 DAT TypeMV60Supply 3 DAT TypeMV61Supply 4 DAT TypeMV62Room Pressure TypeMV63Supply 1 Pitot Cal modeMV64Supply 2 Pitot Cal modeMV65Supply 3 Pitot Cal modeMV66Supply 4 Pitot Cal modeMV67Exhaust 1 Pitot Cal modeMV68Exhaust 2 Pitot Cal modeMV69Hood 1 Pitot Cal modeMV70Hood 2 Pitot Cal modeMV71Hood 3 Pitot Cal modeMV72Hood 4 Pitot Cal modeMV73Hood 5 Pitot Cal modeMV74Hood 6 Pitot Cal modeMV75Hood 7 Pitot Cal modeMV76Current Supply 1 Flow Alarm StatusMV77Current Supply 2 Flow Alarm StatusMV78Current Supply 3 Flow Alarm StatusMV79Current Supply 4 Flow Alarm StatusMV80Current Exhaust 1 Flow Alarm StatusMV81Current Exhaust 2 Flow Alarm StatusMV82Current Supply 1 Temp Alarm StatusMV83Current Supply 2 Temp Alarm StatusMV84Current Supply 3 Temp Alarm StatusMV85Current Supply 4 Temp Alarm StatusMV86Current Room Pressure Alarm StatusMV87Current Supply 1 DAT Alarm StatusMV88Current Supply 2 DAT Alarm StatusMV89Current Supply 3 DAT Alarm StatusMV90Current Supply 4 DAT Alarm StatusMV91Current Controller Flow ModeMV92Current Controller Pressure ModeMV93Current Supply 1 No Flow Alarm StatusMV94Current Supply 2 No Flow Alarm StatusMV95Current Supply 3 No Flow Alarm StatusMV96Current Supply 4 No Flow Alarm StatusMV97Current Supply 1 Feedback Alarm StatusMV98Current Supply 2 Feedback Alarm StatusMV99Current Supply 3 Feedback Alarm StatusMV100Current Supply 4 Feedback Alarm StatusMV101Current Exhaust 1 No Flow Alarm StatusMV102Current Exhaust 2 No Flow Alarm StatusMV103Current Exhaust 1 Feedback Alarm StatusMV104Current Exhaust 2 Feedback Alarm StatusMV105Current Hood 1 No Flow Alarm StatusMV106Current Hood 2 No Flow Alarm StatusMV107Current Hood 3 No Flow Alarm StatusMV108Current Hood 4 No Flow Alarm StatusMV109Current Hood 5 No Flow Alarm StatusMV110Current Hood 6 No Flow Alarm StatusMV111Current Hood 7 No Flow Alarm StatusMV112Current Hood 1 Feedback Alarm StatusMV113Current Hood 2 Feedback Alarm StatusMV114Current Hood 3 Feedback Alarm StatusMV115Current Hood 4 Feedback Alarm StatusMV116Current Hood 5 Feedback Alarm StatusMV117Current Hood 6 Feedback Alarm StatusMV118Current Hood 7 Feedback Alarm StatusMV119Room Pressure Cal ModeMV120Current Offset Alarm StatusMV121Hood 8 Flow TypeMV122Hood 9 Flow TypeMV123Hood 10 Flow TypeMV124Hood 11 Flow TypeMV125Hood 12 Flow TypeMV126Hood 13 Flow TypeMV127Hood 14 Flow TypeMV128Hood 15 Flow TypeMV129Hood 16 Flow TypeMV130Hood 17 Flow TypeMV131Hood 18 Flow TypeMV132Hood 19 Flow TypeMV133Hood 20 Flow TypeMV134Hood 8 Pitot Cal modeMV135Hood 9 Pitot Cal modeMV136Hood 10 Pitot Cal modeMV137Hood 11 Pitot Cal modeMV138Hood 12 Pitot Cal modeMV139Hood 13 Pitot Cal modeMV140Hood 14 Pitot Cal modeMV141Hood 15 Pitot Cal modeMV142Hood 16 Pitot Cal modeMV143Hood 17 Pitot Cal modeMV144Hood 18 Pitot Cal modeMV145Hood 19 Pitot Cal modeMV146Hood 20 Pitot Cal modeMV147Current Hood 8 No Flow Alarm StatusMV148Current Hood 9 No Flow Alarm StatusMV149Current Hood 10 No Flow Alarm StatusMV150Current Hood 11 No Flow Alarm StatusMV151Current Hood 12 No Flow Alarm StatusMV152Current Hood 13 No Flow Alarm StatusMV153Current Hood 14 No Flow Alarm StatusMV154Current Hood 15 No Flow Alarm StatusMV155Current Hood 16 No Flow Alarm StatusMV156Current Hood 17 No Flow Alarm StatusMV157Current Hood 18 No Flow Alarm StatusMV158Current Hood 19 No Flow Alarm StatusMV159Current Hood 20 No Flow Alarm StatusMV160Current Hood 8 Feedback Alarm StatusMV161Current Hood 9 Feedback Alarm StatusMV162Current Hood 10 Feedback Alarm StatusMV163Current Hood 11 Feedback Alarm StatusMV164Current Hood 12 Feedback Alarm StatusMV165Current Hood 13 Feedback Alarm StatusMV166Current Hood 14 Feedback Alarm StatusMV167Current Hood 15 Feedback Alarm StatusMV168Current Hood 16 Feedback Alarm StatusMV169Current Hood 17 Feedback Alarm StatusMV170Current Hood 18 Feedback Alarm StatusMV171Current Hood 19 Feedback Alarm StatusMV172Current Hood 20 Feedback Alarm StatusMV173Supply 1 Room Temp TypeMV174Supply 2 Room Temp TypeMV175Supply 3 Room Temp TypeMV176Supply 4 Room Temp TypeMV177Supply 5 Flow TypeMV178Supply 6 Flow TypeMV179Supply 5 Room Temp TypeMV180Supply 6 Room Temp TypeMV181Supply 5 Pitot Cal modeMV182Supply 6 Pitot Cal modeMV183Current Supply 5 Temp Alarm StatusMV184Current Supply 6 Temp Alarm StatusMV185Current Supply 5 Flow Alarm StatusMV186Current Supply 6 Flow Alarm StatusMV187Current Supply 5 No Flow Alarm StatusMV188Current Supply 6 No Flow Alarm StatusMV189Current Supply 5 Feedback Alarm StatusMV190Current Supply 6 Feedback Alarm StatusMV191Supply 5 DAT TypeMV192Supply 6 DAT TypeMV193Current Supply 5 DAT Alarm StatusMV194Current Supply 6 DAT Alarm Status
Integration notes
- Taken from the BACnet Object Set appendix (manual pages 110-149). TSI states every object is readable and writable; objects TSI marks "DO NOT OVERWRITE" are listed here as read-only.
- Units are from the LRC00 column (CFM, in. W.C., °F). The LRC00-LPS and LRC00-CMH versions use LPS or CMH for flow, Pa for pressure, m² for area and °C for temperature.
- Rows printed as "Not applicable" (16 reserved objects) are left out. Some instance numbers are skipped in the table (for example AV 109, AV 380-383, AV 637-652).
- A few names are printed out of sequence in the table (for example AV 17 "Supply 5 Flow Error" inside the Supply 1 block) and are kept as printed.
- Binary and multi-state state texts printed once for a group of rows are applied to every row in that group.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Laboratory Room Controller (LRC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the TSI Laboratory Room Controller (LRC)
How many BACnet points does the TSI Laboratory Room Controller (LRC) have?
This list has 1714 BACnet objects: 1212 analog values, 308 binary values, 194 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which TSI Laboratory Room Controller (LRC) BACnet points are writable?
1251 of the 1714 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official TSI Laboratory Room Controller (LRC) BACnet documentation?
The source is Laboratory Room Controller Model LRC Operation and Service Manual (P/N 6013156), revision Revision E, December 2021, published free by TSI at https://tsi.com/getmedia/76e6ed5c-8c9c-407c-a413-5aa72c00268b/LRC_Lab_Room_Controller_Op_Svc_Mnl_6013156E-web?ext=.pdf.
What are the minimum BACnet points to integrate the TSI Laboratory Room Controller (LRC)?
Start with BV 24 Supply 1 Occupancy Mode (Supply 1 occupancy: 0 = occupied, 1 = unoccupied); BV 22 Emergency Mode (Emergency mode: 1 = active); AV 268 Room Pressure Setpoint (Room pressure setpoint, in. W.C); MV 91 Current Controller Flow Mode (Standard, Emergency, Shutdown or Balancer); AV 697 Room Pressure (Measured room pressure, in. W.C); AV 660 Current Total Supply Flow (Total supply airflow, CFM); AV 661 Current Total Exhaust Flow (Total exhaust airflow, CFM); AV 689 Supply 1 Room Temp (Supply 1 zone room temperature); MV 86 Current Room Pressure Alarm Status (1 = normal, 2 = low alarm, 3 = high alarm); MV 76 Current Supply 1 Flow Alarm Status (Supply 1 flow: 1 = normal, 2 = low, 3 = high alarm).
How do I enable BMS control of the TSI Laboratory Room Controller (LRC)?
No separate BMS enable is described. Occupancy per supply (BV 24-27, BV 297/298 for supplies 5-6), Emergency Mode (BV 22) and Shutdown Mode (BV 23) are writable and switch the controller between its occupied, unoccupied, emergency and shutdown flow setpoints.
How do I check these points on the real Laboratory Room Controller (LRC)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More TSI BACnet points lists
- Room pressure controller
TSI PresSura 8631-CRC Clean Room Pressure Controller
TSI PresSura Model 8631-CRC-BAC clean room pressure controllers with the BACnet board.
Also known as: 8631-CRC, 8631-CRC-BAC, PresSura 8631-CRC - Room pressure monitor
TSI PresSura 8631-CRM Clean Room Pressure Monitor
TSI PresSura Model 8631-CRM-BAC clean room pressure monitors with the BACnet board.
Also known as: 8631-CRM, 8631-CRM-BAC, PresSura 8631-CRM - Room pressure controller
TSI PresSura 8631-HC Hospital Room Pressure Controller
TSI PresSura Model 8631-HC hospital isolation room pressure controllers with the BACnet board.
Also known as: 8631-HC, 8631-HC-BAC, PresSura 8631-HC - Room pressure monitor
TSI PresSura 8631-HM Hospital Room Pressure Monitor
TSI PresSura Model 8631-HM hospital isolation room pressure monitors with the BACnet board.
Also known as: 8631-HM, 8631-HM-BAC, PresSura 8631-HM - Room pressure controller
TSI PresSura RPC30 Room Pressure Controller
TSI PresSura RPC30 controllers that hold one room (optionally with an anteroom) at a set pressure by driving exhaust, supply and reheat outputs.
Also known as: RPC30, PresSura RPC30, RPC30 PresSura - Room pressure monitor
TSI PresSura RPM10 Room Pressure Monitor
TSI PresSura RPM10 single-room pressure monitors.
Also known as: RPM10, PresSura RPM10, RPM10 PresSura - Room pressure monitor
TSI PresSura RPM20 Room Pressure Monitor
TSI PresSura RPM20 room pressure monitors for one room, a room with anteroom, or two rooms with an anteroom.
Also known as: RPM20, PresSura RPM20, RPM20 PresSura - Room pressure monitor
TSI PresSura RPM20-CC Room Pressure Monitor (particle counting)
TSI PresSura RPM20-CC room pressure monitors with particle counter channels, for clean rooms.
Also known as: RPM20-CC, PresSura RPM20-CC, RPM20 CC - Room pressure controller
TSI SureFlow 8636 Room Pressure Controller
TSI SureFlow Model 8636-BAC room pressure controllers with the BACnet MS/TP board.
Also known as: 8636, 8636-BAC, SureFlow 8636 - Laboratory room pressure and airflow offset controller
TSI SureFlow 8681 Adaptive Offset Controller
TSI SureFlow Model 8681-BAC adaptive offset (lab room) controllers with the BACnet MS/TP board.
Also known as: 8681, 8681-BAC, SureFlow 8681 - Laboratory room pressure and airflow offset controller
TSI SureFlow 8682 Adaptive Offset Controller
TSI SureFlow Model 8682-BAC adaptive offset controllers (up to 4 supplies, 2 general exhausts and 7 hoods) with the BACnet MS/TP board.
Also known as: 8682, 8682-BAC, SureFlow 8682
Source: Laboratory Room Controller Model LRC Operation and Service Manual · P/N 6013156 · rev. Revision E, December 2021. Object names, instances and units are reproduced as published; descriptions are our own.