Laboratory room pressure and airflow offset controller · BACnet points list

TSI SureFlow 8682 Adaptive Offset Controller BACnet points list

Updated 6 November 2026

Short answer

The SureFlow 8682 controls a laboratory room by tracking up to four supply, two general exhaust and seven fume hood flows to hold a flow offset, trimming it to a room pressure setpoint, with reheat temperature control. Over BACnet MS/TP it exposes room pressure, every flow and the totals, the current offset, temperature, damper and valve positions, setpoints and alarm limits, occupancy, remote and emergency commands, and a Status Index alarm code.

This page lists 49 BACnet objects for the TSI SureFlow 8682 Adaptive Offset Controller — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
SureFlow 8682 Adaptive Offset Controller
Equipment
Laboratory room pressure and airflow offset controller
Equipment type
Thermostats, sensors & meters
BACnet objects
49 (22 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS)
Default device instance
868001
Also known as
8682, 8682-BAC, SureFlow 8682
Source document
SureFlow Adaptive Offset Controller Models 8682/8682-BAC Operation and Service Manual · P/N 1980483 · rev. Revision F
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI SureFlow 8682 Adaptive Offset Controller

Integration in brief

Command occupancy with Occ/Unocc Mode (BV 1), switch to the remote pressure setpoint with Remote Mode (BV 2) and use Emergency Mode (MV 2) for purge. Read room pressure, total supply, exhaust and hood flows, the current offset, temperature and the Status Index (MI 1) for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Occ/Unocc Mode0 = occupied, 1 = unoccupiedWrite
MV 2Emergency Mode1 = exit, 2 = enter emergency modeWrite
AV 2Room Pressure Set PointRoom pressure setpointWrite
AV 17Temperature Set PointOccupied room temperature setpointWrite
AI 1Room PressureRoom differential pressureRead
AI 2Total Supply FlowTotal supply airflowRead
AI 5Total Exhaust FlowTotal exhaust airflowRead
AI 21Current Flow OffsetSupply/exhaust offset now in useRead
AI 22TemperatureRoom temperatureRead
MI 1Status IndexAlarm state; 1 = normal, 9 = emergencyRead

Enable & remote start

Occ/Unocc Mode (BV 1) switches between the occupied and unoccupied flow and temperature setpoints; Remote Mode (BV 2) selects the remote pressure setpoint and alarms (AV 3, AV 6, AV 7); Emergency Mode (MV 2) works like the EMERGENCY key.

Network setup

Watch out for

TSI SureFlow 8682 Adaptive Offset Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

49 of 49 shown
Type
BinaryOther
Access
Show
TSI SureFlow 8682 Adaptive Offset Controller BACnet Points List
DescriptionStates
AImin1Room Pressureft/min, m/s, in. H2O, PaRead
AImin2Total Supply Flowcfm, l/sRead
AI3Total General Exhaust Flowcfm, l/sRead
AI4Total Hood Flowcfm, l/sRead
AImin5Total Exhaust Flowcfm, l/sRead
AI6Supply 1 Flow Ratecfm, l/sRead
AI7Supply 2 Flow Ratecfm, l/sRead
AI8Supply 3 Flow Ratecfm, l/sRead
AI9Supply 4 Flow Ratecfm, l/sRead
AI10Exhaust 1 Flow Ratecfm, l/sRead
AI11Exhaust 2 Flow Ratecfm, l/sRead
AI12Hood 1 Flow Ratecfm, l/sRead
AI13Hood 2 Flow Ratecfm, l/sRead
AI14Hood 3 Flow Ratecfm, l/sRead
AI15Hood 4 Flow Ratecfm, l/sRead
AI16Hood 5 Flow Ratecfm, l/sRead
AI17Hood 6 Flow Ratecfm, l/sRead
AI18Hood 7 Flow Ratecfm, l/sRead
AI19Supply Flow Set Pointcfm, l/sRead
AI20General Exhaust Flow Set Pointcfm, l/sRead
AImin21Current Flow Offsetcfm, l/sRead
AImin22Temperature°F, °CRead
AI23Supply Damper Position% openRead
AI24Exhaust Damper Position% openRead
AI25Reheat Valve Position% openRead
AV1MAC AddressRange 1 to 127Write
AVmin2Room Pressure Set PointRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV3Remote Pressure Set PointRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV4Low Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV5High Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV6Remote Low Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV7Remote High Pressure AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV8Vent Min Set PointRange 0 to 30,000 cfmcfm, l/sWrite
AV9Cooling Flow Set PointRange 0 to 30,000 cfmcfm, l/sWrite
AV10Unocc Flow Set PointRange 0 to 30,000 cfmcfm, l/sWrite
AV11Min OffsetRange 0 to 30,000 cfmcfm, l/sWrite
AV12Max OffsetRange 0 to 30,000 cfmcfm, l/sWrite
AV13Max Supply Set PointRange 0 to 30,000 cfmcfm, l/sWrite
AV14Min Exhaust Set PointRange 0 to 30,000 cfmcfm, l/sWrite
AV15Min Supply AlarmRange 0 to 30,000 cfmcfm, l/sWrite
AV16Max Exhaust AlarmRange 0 to 30,000 cfmcfm, l/sWrite
AVmin17Temperature Set PointRange 50 to 85 °F°F, °CWrite
AV18Unocc Temp Set PointRange 50 to 85 °F°F, °CWrite
BVmin1Occ/Unocc ModeWrite0=Occupied, 1=Unoccupied
BV2Remote ModeWrite0=Normal Mode, 1=Remote Mode
MImin1Status IndexRead1=Normal, 2=Dim Data Error, 3=Low Press Alarm, 4=High Press Alarm, 5=Min Supply Alarm, 6=Max Exhaust Alarm, 7=Data Error, 8=Cal Error, 9=Emergency
MVmin2Emergency ModeWrite1=Exit Emergency Mode, 2=Enter Emergency Mode
MV3Units ValueWrite1=ft/min, 2=m/s, 3=in. H2O, 4=Pa
DEV868001TSI8682Device object; instance = 868000 + MAC addressRead
Object ID lookup: TSI SureFlow 8682 Adaptive Offset Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SureFlow 8682 Adaptive Offset Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI SureFlow 8682 Adaptive Offset Controller

How many BACnet points does the TSI SureFlow 8682 Adaptive Offset Controller have?

This list has 49 BACnet objects: 25 analog inputs, 18 analog values, 2 binary values, 1 device, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI SureFlow 8682 Adaptive Offset Controller BACnet points are writable?

22 of the 49 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official TSI SureFlow 8682 Adaptive Offset Controller BACnet documentation?

The source is SureFlow Adaptive Offset Controller Models 8682/8682-BAC Operation and Service Manual (P/N 1980483), revision Revision F, published free by TSI at https://tsi.com/getmedia/11c587ef-a3fe-44d9-8f24-f90854dae1e9/1980483E-8682-SureFlow?ext=.pdf.

What are the minimum BACnet points to integrate the TSI SureFlow 8682 Adaptive Offset Controller?

Start with BV 1 Occ/Unocc Mode (0 = occupied, 1 = unoccupied); MV 2 Emergency Mode (1 = exit, 2 = enter emergency mode); AV 2 Room Pressure Set Point (Room pressure setpoint); AV 17 Temperature Set Point (Occupied room temperature setpoint); AI 1 Room Pressure (Room differential pressure); AI 2 Total Supply Flow (Total supply airflow); AI 5 Total Exhaust Flow (Total exhaust airflow); AI 21 Current Flow Offset (Supply/exhaust offset now in use); AI 22 Temperature (Room temperature); MI 1 Status Index (Alarm state; 1 = normal, 9 = emergency).

How do I enable BMS control of the TSI SureFlow 8682 Adaptive Offset Controller?

Occ/Unocc Mode (BV 1) switches between the occupied and unoccupied flow and temperature setpoints; Remote Mode (BV 2) selects the remote pressure setpoint and alarms (AV 3, AV 6, AV 7); Emergency Mode (MV 2) works like the EMERGENCY key.

How do I check these points on the real SureFlow 8682 Adaptive Offset Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: SureFlow Adaptive Offset Controller Models 8682/8682-BAC Operation and Service Manual · P/N 1980483 · rev. Revision F. Object names, instances and units are reproduced as published; descriptions are our own.