TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) BACnet points list

Updated 6 November 2026

Short answer

The RPM20-CC is the RPM20 room pressure monitor with two particle-count channels for clean rooms. Over BACnet MS/TP it exposes the room pressure, temperature, humidity and flow readings, the particle counts and particle alarm settings, per-room modes and the Status Index alarm code.

This page lists 81 BACnet objects for the TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) — 53 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
PresSura RPM20-CC Room Pressure Monitor (particle counting)
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
81 (53 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
RPM20-CC, PresSura RPM20-CC, RPM20 CC
Source document
PresSura Room Pressure Monitor Models RPM10 and RPM20 Operation and Service Manual · P/N 6006644 · rev. Revision N, February 2023
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI PresSura RPM20-CC Room Pressure Monitor (particle counting)

Integration in brief

Read room pressure, the flows and the Status Index (MV 16) for alarms; door and occupancy inputs are BIs. The room mode (positive, negative, no isolation) is writable from the BMS. The monitor can also take some readings from the BMS instead of wired sensors.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 11Room 1 Mode1 = positive, 2 = negative, 3 = no isolationWrite
AI 1Room1 PressureRoom differential pressureRead
AI 16Particle Channel A CountsParticle channel A countRead
AI 17Particle Channel B CountsParticle channel B countRead
AI 5Room TemperatureRoom temperatureRead
AI 4Relative HumidityRoom relative humidityRead
AV 19Particle Alarm StatusParticle sensor status; 2 = normalRead
MV 16Status IndexActive alarm code; 1 = normalRead

Sensors & values from the BMS

Supply flow, exhaust flow, relative humidity and room temperature can come from the BMS: enable BV 9 / BV 12 / BV 10 / BV 11 and write AV 55 / AV 58 / AV 56 / AV 57.

Network setup

Watch out for

TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

81 of 81 shown
Type
Multi-state
Access
Show
TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) BACnet Points List
DescriptionStates
AImin1Room1 PressureObject name is writablein. W.C.Read
AI2Supply Flow RatecfmRead
AI3Air Changes Per HourRead
AImin4Relative Humidity%RHRead
AImin5Room Temperature°FRead
AI6Exhaust Flow RatecfmRead
AI7Anteroom PressureAnteroom configs onlyin. W.C.Read
AI8Room 2 PressureTwo rooms + anteroom onlyin. W.C.Read
AI10Room 1 LabelObject name holds the room label; write the name to change itRead
AI11Anteroom LabelObject name holds the room label; write the name to change itRead
AI12Room 2 LabelObject name holds the room label; write the name to change itRead
AImin16Particle Channel A CountsRange 0 to 1E+09ft³Read
AImin17Particle Channel B CountsRange 0 to 1E+09ft³Read
AV1Room 1 Neg Low AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV2Room 1 Neg High AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV3Room 1 Pos Low AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV4Room 1 Pos High AlarmRange ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV5Room 1 Low Exhaust AlarmRange 0 to 30,000 cfmcfmWrite
AV6Room 1 Low Supply AlarmRange 0 to 30,000 cfmcfmWrite
AV7Room 1 Low Temperature AlarmRange 50 to 100 °F°FWrite
AV8Room 1 High Temperature AlarmRange 50 to 100 °F°FWrite
AV9Room 1 Low RH AlarmRange 0 to 100%RHWrite
AV10Room 1 High RH AlarmRange 0 to 100%RHWrite
AV11Room 1 VolumeRange 0 to 20,000ft³Write
AVmin19Particle Alarm StatusRead1=No Signal, 2=Normal, 3=Laser Alarm, 4=Flow Alarm, 5=Flow and Laser Alarm
AV20Particle Alarm StrategyWrite1=Consecutive, 2=SPC
AV31Anteroom Neg Low AlarmAnteroom configs only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV32Anteroom Neg High AlarmAnteroom configs only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV33Anteroom Pos Low AlarmAnteroom configs only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV34Anteroom Pos High AlarmAnteroom configs only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV35Room 2 Neg Low AlarmTwo rooms + anteroom only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV36Room 2 Neg High AlarmTwo rooms + anteroom only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV37Room 2 Pos Low AlarmTwo rooms + anteroom only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV38Room 2 Pos High AlarmTwo rooms + anteroom only; range ±0.195 (TSI sensor) or ±1.0 in. W.C. (transducer)in. W.C.Write
AV39Alarm DelayRange 20 to 600 secondsWrite
AV40Mute TimeoutRange 1 to 60 minutesWrite
AV41Door DelayRange 20 to 600 secondsWrite
AV42AddressRange 1 to 127Write
AV43MAC ID (Device ID)Range 0 to 4,194,302Write
AV46Particle Alarm Consecutive ReadingsRange 1 to 60Write
AV47Particle Alarm Exit ReadingsRange 1 to 10Write
AV48Particle Alarm FrequencyRange 1 to 60Write
AV49Particle Alarm PeriodRange 1 to 60Write
AV52Particle A High Alarm SetpointRange 0 to 1E+09ft³Write
AV54Particle B High Alarm SetpointRange 0 to 1E+09ft³Write
AV55Supply Flow over BACnetRange 0 to 10,000 cfmcfmWrite
AV56Relative Humidity over BACnetRange 0 to 100%%RHWrite
AV57Room 1 Temperature over BACnetRange 50 to 85 °F°FWrite
AV58Exhaust Flow over BACnetRange 0 to 10,000 cfmcfmWrite
BI1Room 1 Door SwitchRead0=Door Closed (Normal), 1=Door Open
BI3Room 2 Door SwitchRead0=Door Closed (Normal), 1=Door Open
BI4Room 1 OccupancyRead0=Occupied (Normal), 1=Unoccupied
BI6Room 2 OccupancyRead0=Occupied (Normal), 1=Unoccupied
BV1Room 1 High AlarmWrite0=Disable, 1=Enable
BV2Room 1 Low AlarmWrite0=Disable, 1=Enable
BV3Anteroom High AlarmWrite0=Disable, 1=Enable
BV4Anteroom Low AlarmWrite0=Disable, 1=Enable
BV5Room 2 High AlarmWrite0=Disable, 1=Enable
BV6Room 2 Low AlarmWrite0=Disable, 1=Enable
BV7Particle A High AlarmWrite0=Disable, 1=Enable
BV8Particle B High AlarmWrite0=Disable, 1=Enable
BV9Supply Flow over BACnet EnableWrite0=Disable, 1=Enable
BV10Relative Humidity over BACnet EnableWrite0=Disable, 1=Enable
BV11Room 1 Temperature over BACnet EnableWrite0=Disable, 1=Enable
BV12Exhaust Flow over BACnet EnableWrite0=Disable, 1=Enable
MV1Number of RoomsRead1=1 Room, 2=1 Room with Anteroom, 3=2 Rooms with Anteroom
MV3Passcode EnableWrite1=No Password, 2=Room Mode Password, 3=Menu Password, 4=Menu & Room Mode Passwords
MV4Input 1 ConfigurationRead1=TSI Sensor, 2=Pressure Transducer
MV5Input 2 ConfigurationRead1=TSI Sensor, 2=Pressure Transducer, 4=Particle Channel A, 5=None
MV6Input 3 ConfigurationRead1=Supply Pressure Flow, 2=Supply Linear Flow, 3=Supply Venturi Flow, 4=Supply Switch, 5=TSI Sensor, 6=Pressure Transducer, 7=None
MV7Input 4 ConfigurationRead1=Room 1 Door Switch, 2=Room 1 Occupancy Sensor, 3=Particle Channel B, 4=None
MV8Input 5 ConfigurationRead1=Room 1 Key Switch, 2=Room 1 Relative Humidity, 3=None
MV9Input 6 ConfigurationRead1=Room 1 Temp Sensor, 3=Room 2 Occupancy Sensor, 4=Room 2 Door Switch, 6=None
MV10Input 7 ConfigurationRead2=Exhaust Pressure Flow, 3=Exhaust Linear Flow, 4=Exhaust Venturi Flow, 5=Exhaust Switch, 6=Room 2 Key Switch, 8=Particle Status, 9=None
MVmin11Room 1 ModeWrite1=Positive, 2=Negative, 3=No Isolation
MV12ACH DuctWrite1=Supply, 2=Exhaust, 3=Off
MV14Anteroom ModeWrite1=Positive, 2=Negative, 3=No Isolation
MV15Room 2 ModeWrite1=Positive, 2=Negative, 3=No Isolation
MVmin16Status IndexRead1=Normal, 2=Room 1 Negative Low Alarm, 3=Room 1 Negative High Alarm, 4=Room 1 Positive Low Alarm, 5=Room 1 Positive Low Alarm, 6=Low Exhaust Flow Alarm, 7=Low Supply Flow Alarm, 8=Low Temperature Alarm, 9=High Temperature Alarm, 10=Low RH Alarm, 11=High RH Alarm, 12=Anteroom Negative Low Alarm, 13=Anteroom Negative High Alarm, 14=Anteroom Positive Low Alarm, 15=Anteroom Positive High Alarm, 16=Room 2 Negative Low Alarm, 17=Room 2 Negative High Alarm, 18=Room 2 Positive Low Alarm, 19=Room 2 Positive High Alarm, 20=Data Error
MV17Device TypeRead2=RPM20
MV18Units ValueWrite1=in. W.C., cfm, F, 2=Pa, lps, C, 3=Pa, m3/hr, C
Object ID lookup: TSI PresSura RPM20-CC Room Pressure Monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura RPM20-CC Room Pressure Monitor (particle counting) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI PresSura RPM20-CC Room Pressure Monitor (particle counting)

How many BACnet points does the TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) have?

This list has 81 BACnet objects: 13 analog inputs, 36 analog values, 4 binary inputs, 12 binary values, 16 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) BACnet points are writable?

53 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TSI PresSura RPM20-CC Room Pressure Monitor (particle counting) BACnet documentation?

The source is PresSura Room Pressure Monitor Models RPM10 and RPM20 Operation and Service Manual (P/N 6006644), revision Revision N, February 2023, published free by TSI at https://tsi.com/getmedia/8220cb07-6f38-4cec-9e7a-900fecd113e9/RPM10-RPM20_PresSura_Monitor_6006644J-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI PresSura RPM20-CC Room Pressure Monitor (particle counting)?

Start with MV 11 Room 1 Mode (1 = positive, 2 = negative, 3 = no isolation); AI 1 Room1 Pressure (Room differential pressure); AI 16 Particle Channel A Counts (Particle channel A count); AI 17 Particle Channel B Counts (Particle channel B count); AI 5 Room Temperature (Room temperature); AI 4 Relative Humidity (Room relative humidity); AV 19 Particle Alarm Status (Particle sensor status; 2 = normal); MV 16 Status Index (Active alarm code; 1 = normal).

Can the BMS supply sensor values to the TSI PresSura RPM20-CC Room Pressure Monitor (particle counting)?

Supply flow, exhaust flow, relative humidity and room temperature can come from the BMS: enable BV 9 / BV 12 / BV 10 / BV 11 and write AV 55 / AV 58 / AV 56 / AV 57.

How do I check these points on the real PresSura RPM20-CC Room Pressure Monitor (particle counting)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: PresSura Room Pressure Monitor Models RPM10 and RPM20 Operation and Service Manual · P/N 6006644 · rev. Revision N, February 2023. Object names, instances and units are reproduced as published; descriptions are our own.