  4. PresSura 8631-HC Hospital Room Pressure Controller

Room pressure controller · BACnet points list

TSI PresSura 8631-HC Hospital Room Pressure Controller BACnet points list

Updated 6 November 2026

Short answer

The 8631-HC controls hospital isolation room pressure by modulating an exhaust damper, switching between negative, positive and no-isolation modes. With the BACnet board it is a BACnet MS/TP device exposing room pressure, active setpoint, flow, damper position, the negative and positive setpoints, alarm limits, a Status Index alarm code, the control mode and an emergency command.

This page lists 22 BACnet objects for the TSI PresSura 8631-HC Hospital Room Pressure Controller — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TSI’s own free documentation, linked below.

Manufacturer
TSI
Model
PresSura 8631-HC Hospital Room Pressure Controller
Equipment
Room pressure controller
Equipment type
Thermostats, sensors & meters
BACnet objects
22 (15 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS)
Default device instance
863001
Also known as
8631-HC, 8631-HC-BAC, PresSura 8631-HC
Source document
PresSura Hospital Room Pressure Monitor/Controller, Models 8631-HM/8631-HC Operation and Service Manual · P/N 1980488 · rev. Revision J
Download CSV 22 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TSI’s current documentation and the live device before use. Not official TSI information. Terms of use.

BMS integration notes: TSI PresSura 8631-HC Hospital Room Pressure Controller

Integration in brief

Set the room mode with Control Mode (MV 2) and use Emergency Mode (MV 4) for purge. Read room pressure, the active setpoint, flow, damper position and the Status Index (MI 1) for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2Control Mode1 = negative, 2 = positive, 3 = no isolationWrite
MV 4Emergency Mode1 = exit, 2 = enter emergency mode, 3 = normalWrite
AV 2Neg Pressure SetpointNegative-mode pressure setpointWrite
AV 3Pos Pressure SetpointPositive-mode pressure setpointWrite
AI 1Room PressureRoom differential pressureRead
AI 4Flow RateMeasured airflowRead
AI 6Damper PositionDamper position, %Read
MI 1Status IndexAlarm state; 1 = normal, 8 = emergencyRead

Enable & remote start

Control Mode (MV 2) selects negative, positive or no isolation; Emergency Mode (MV 4) works like the red EMERGENCY key.

Network setup

Watch out for

TSI PresSura 8631-HC Hospital Room Pressure Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

22 of 22 shown
Type
Access
Show
TSI PresSura 8631-HC Hospital Room Pressure Controller BACnet Points List
DescriptionStates
AImin1Room Pressureft/min, m/s, in. H2O, PaRead
AI2Sec Sens PressureSecond pressure sensorft/min, m/s, in. H2O, PaRead
AI3Current Pressure SetpointActive pressure setpointft/min, m/s, in. H2O, PaRead
AImin4Flow Ratecfm, l/sRead
AI5Air Changes Per HourRead
AImin6Damper Position%Read
AV1MAC AddressRange 1 to 127Write
AVmin2Neg Pressure SetpointRange 0 to -0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AVmin3Pos Pressure SetpointRange 0 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV4Neg Low AlarmRange 0 to -0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV5Neg High AlarmRange 0 to -0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV6Pos Low AlarmRange 0 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV7Pos High AlarmRange 0 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV8Sec Low AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV9Sec High AlarmRange -0.195 to 0.195 in. H2Oft/min, m/s, in. H2O, PaWrite
AV10Min Exhaust SetpointRange 0 to 30,000 cfmcfm, l/sWrite
AV11Min Exhaust AlarmRange 0 to 30,000 cfmcfm, l/sWrite
AV12MAC IDRange 1 to 999; sets the device instanceWrite
MImin1Status IndexRead1=Normal, 2=Low Alarm, 3=High Alarm, 4=Min Exhaust Alarm, 5=Sec Sens Low Alarm, 6=Sec Sens High Alarm, 7=Data Error, 8=Emergency
MVmin2Control ModeWrite1=Negative, 2=Positive, 3=No Isolation
MV3Units ValueWrite1=ft/min, 2=m/s, 3="H2O, 4=Pa
MVmin4Emergency ModeWrite1=Exit Emergency Mode, 2=Enter Emergency Mode, 3=Normal
Object ID lookup: TSI PresSura 8631-HC Hospital Room Pressure Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PresSura 8631-HC Hospital Room Pressure Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TSI PresSura 8631-HC Hospital Room Pressure Controller

How many BACnet points does the TSI PresSura 8631-HC Hospital Room Pressure Controller have?

This list has 22 BACnet objects: 6 analog inputs, 12 analog values, 1 multi-state input, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TSI PresSura 8631-HC Hospital Room Pressure Controller BACnet points are writable?

15 of the 22 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official TSI PresSura 8631-HC Hospital Room Pressure Controller BACnet documentation?

The source is PresSura Hospital Room Pressure Monitor/Controller, Models 8631-HM/8631-HC Operation and Service Manual (P/N 1980488), revision Revision J, published free by TSI at https://tsi.com/getmedia/0d020f91-9602-4aad-bd3e-d587ae6579d4/1980488-8631HM-HC-Pressura-web?ext=.pdf.

What are the minimum BACnet points to integrate the TSI PresSura 8631-HC Hospital Room Pressure Controller?

Start with MV 2 Control Mode (1 = negative, 2 = positive, 3 = no isolation); MV 4 Emergency Mode (1 = exit, 2 = enter emergency mode, 3 = normal); AV 2 Neg Pressure Setpoint (Negative-mode pressure setpoint); AV 3 Pos Pressure Setpoint (Positive-mode pressure setpoint); AI 1 Room Pressure (Room differential pressure); AI 4 Flow Rate (Measured airflow); AI 6 Damper Position (Damper position, %); MI 1 Status Index (Alarm state; 1 = normal, 8 = emergency).

How do I enable BMS control of the TSI PresSura 8631-HC Hospital Room Pressure Controller?

Control Mode (MV 2) selects negative, positive or no isolation; Emergency Mode (MV 4) works like the red EMERGENCY key.

How do I check these points on the real PresSura 8631-HC Hospital Room Pressure Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TSI BACnet points lists

Source: PresSura Hospital Room Pressure Monitor/Controller, Models 8631-HM/8631-HC Operation and Service Manual · P/N 1980488 · rev. Revision J. Object names, instances and units are reproduced as published; descriptions are our own.