 "manufacturer": "TSI",
 "manufacturer_slug": "tsi",
 "model": "SureFlow 8636 Room Pressure Controller",
 "model_slug": "sureflow-8636",
 "aliases": [
  "8636",
  "8636-BAC",
  "SureFlow 8636"
 ],
 "equipment_type": "Room pressure controller",
 "applies_to": "TSI SureFlow Model 8636-BAC room pressure controllers with the BACnet MS/TP board.",
 "summary": "The SureFlow 8636 holds a room at a pressure setpoint by modulating supply and exhaust dampers, with supply flow tracking, temperature control through a reheat valve and occupied/unoccupied flow and temperature setpoints. Over BACnet MS/TP it exposes room pressure, supply flow, temperature, damper and valve positions, all setpoints and alarm limits, occupancy and emergency commands, and a Status Index alarm code.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "1.0 (PICS)",
 "default_device_instance": 863001,
 "access_inferred": true,
 "notes": [
  "From the Model 8636-BAC BACnet MS/TP Object Set table (manual pages 70-71).",
  "The table has no read/write column. Access is inferred from the PICS, which lists Present_Value as writable for Analog, Binary and Multi-state Values only.",
  "Units follow Units Value (MV 3): 1 = ft/min, 2 = m/s, 3 = in. H2O, 4 = Pa; English units (cfm, °F) apply with 1 or 3. English is the default."
 ],
 "source": {
  "title": "SureFlow Room Pressure Controller Models 8636/8636-BAC Operation and Service Manual",
  "doc_number": "P/N 1980441",
  "revision_date": "Revision H, February 2013",
  "url": "https://tsi.com/getmedia/2df9628e-24cc-42f2-8ec5-a0e717143bd8/1980441G-8636?ext=.pdf"
 },
 "integration": {
  "summary": "Command occupancy with Occ/Unocc Mode (BV 2) and use Emergency Mode (MV 2) for purge. Read room pressure, supply flow, temperature, damper positions and the Status Index (MI 1) for alarms.",
  "minimum_points": [
   {
    "ref": "BV 2",
    "name": "Occ/Unocc Mode",
    "why": "0 = occupied, 1 = unoccupied"
   },
   {
    "ref": "MV 2",
    "name": "Emergency Mode",
    "why": "1 = exit, 2 = enter emergency mode, 3 = normal"
   },
   {
    "ref": "AV 2",
    "name": "Room Pressure Setpoint",
    "why": "Room pressure setpoint"
   },
   {
    "ref": "AV 12",
    "name": "Temperature Setpoint",
    "why": "Occupied room temperature setpoint"
   },
   {
    "ref": "AI 1",
    "name": "Room Pressure",
    "why": "Room differential pressure"
   },
   {
    "ref": "AI 2",
    "name": "Supply Flow Rate",
    "why": "Supply airflow"
   },
   {
    "ref": "AI 4",
    "name": "Temperature",
    "why": "Room temperature"
   },
   {
    "ref": "AI 6",
    "name": "Exhaust Damper Position",
    "why": "Exhaust damper position"
   },
   {
    "ref": "MI 1",
    "name": "Status Index",
    "why": "Alarm state; 1 = normal, 6 = emergency"
   }
  ],
  "enable": "Occ/Unocc Mode (BV 2) switches between the occupied and unoccupied flow and temperature setpoints; Emergency Mode (MV 2) works like the EMERGENCY key.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet MS/TP master at 9600, 19.2k, 38.4k or 76.8k baud (PICS).",
   "Set the MS/TP MAC with the MAC ADDRESS menu item (1-127).",
   "The device instance is 863000 plus the MAC address (MAC 1 gives 863001)."
  ],
  "gotchas": [
   "Pressure units change with Units Value (MV 3); check it before scaling pressures in the BMS.",
   "The device instance changes if the MAC address is changed.",
   "Setpoints and alarm limits are stored settings; do not write them cyclically."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Room Pressure",
   "description": "",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Supply Flow Rate",
   "description": "",
   "units": "cfm, l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Supply Flow Setpoint",
   "description": "",
   "units": "cfm, l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Temperature",
   "description": "",
   "units": "°F, °C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Supply Damper Position",
   "description": "",
   "units": "% open",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Exhaust Damper Position",
   "description": "",
   "units": "% open",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Reheat Valve Position",
   "description": "",
   "units": "% open",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "MAC Address",
   "description": "Range 1 to 127",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Room Pressure Setpoint",
   "description": "Range -0.195 to 0.195 in. H2O",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Door Pressure Setpoint",
   "description": "Range -0.195 to 0.195 in. H2O",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Low Pressure Alarm",
   "description": "Range -0.195 to 0.195 in. H2O",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "High Pressure Alarm",
   "description": "Range -0.195 to 0.195 in. H2O",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Door Low Pressure Alarm",
   "description": "Range -0.195 to 0.195 in. H2O",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Door High Pressure Alarm",
   "description": "Range -0.195 to 0.195 in. H2O",
   "units": "ft/min, m/s, in. H2O, Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Vent Min Setpoint",
   "description": "Range 0 to 30,000 cfm",
   "units": "cfm, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Cooling Flow Setpoint",
   "description": "Range 0 to 30,000 cfm",
   "units": "cfm, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Unocc Flow Setpoint",
   "description": "Range 0 to 30,000 cfm",
   "units": "cfm, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Min Supply Alarm",
   "description": "Range 0 to 30,000 cfm",
   "units": "cfm, l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Temperature Setpoint",
   "description": "Range 50 to 85 °F",
   "units": "°F, °C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Unocc Temp Setpoint",
   "description": "Range 50 to 85 °F",
   "units": "°F, °C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Min Sup Damp Setpoint",
   "description": "Range 0 to 100%",
   "units": "% open",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Max Sup Damp Setpoint",
   "description": "Range 0 to 100%",
   "units": "% open",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Min Exh Damp Setpoint",
   "description": "Range 0 to 100%",
   "units": "% open",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Max Exh Damp Setpoint",
   "description": "Range 0 to 100%",
   "units": "% open",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Control Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Door Mode"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Occ/Unocc Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Occupied, 1=Unoccupied"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "Status Index",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Low Press Alarm, 3=High Press Alarm, 4=Min Supply Alarm, 5=Data Error, 6=Emergency"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Emergency Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Exit Emergency Mode, 2=Enter Emergency Mode, 3=Normal"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Units Value",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=ft/min, 2=m/s, 3=in. H2O, 4=Pa"
  },
  {
   "type": "DEV",
   "instance": 863001,
   "name": "TSI8636",
   "description": "Device object; instance = 863000 + MAC address",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/tsi/sureflow-8636",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}