Underfloor air terminal (VAV) controller · BACnet points list

Price Industries UMC3 underfloor controller BACnet points list

Updated 6 November 2026

Short answer

UMC3 is Price's controller for underfloor air terminals on BACnet MS/TP. The points list has 38 objects: room and supply air temperatures, 0-10 V heat/cool inputs, setpoints and limits, damper and LFGH damper positions, PI load, auxiliary output settings and BMS override values for setpoint, room temperature, occupancy and lights.

This page lists 38 BACnet objects for the Price Industries UMC3 underfloor controller — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.

Manufacturer
Price Industries
Model
UMC3 underfloor controller
Equipment
Underfloor air terminal (VAV) controller
Equipment type
VAV boxes & fan coils
BACnet objects
38 (22 writable)
Transport
BACnet MS/TP
Firmware
v1.19.0
Also known as
UMC3, Price UMC3
Source document
BACnet points list for UMC3 firmware v1.19.0 · rev. Rev 0
Download CSV 38 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Price Industries’s current documentation and the live device before use. Not official Price Industries information. Terms of use.

BMS integration notes: Price Industries UMC3 underfloor controller

Integration in brief

Use AV 30 Net Occupancy, AV 28 Net Setpoint and, if needed, AV 29 to drive the controller from the BMS; read AV 2 Occupancy, AI 1 room temperature, AV 14 room load and AV 18 damper position.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 30Net OccupancyBMS occupancy: 0 normal, 1 occupied, 2 unoccupiedWrite
AV 28Net SetpointBMS setpoint override, 0 = noneWrite
AV 29Net Room TemperatureBMS room temperature, 0 = noneWrite
AV 2OccupancyCurrent occupancy: 0 unocc, 1 occRead
AI 1Room TemperatureRoom temperatureRead
AV 6Room SetpointCurrent room setpointRead
AV 14Controller StatusRoom load: + heating, - cooling, %Read
AV 18Current Damper PositionDamper position, % (999 = calibrating)Read

Enable & remote start

AV 30 Net Occupancy: 0 = normal operation, 1 = force occupied, 2 = force unoccupied. AV 1 selects thermostat/network control or the 0-10 V heat/cool input signals.

Sensors & values from the BMS

AV 28 Net Setpoint and AV 29 Net Room Temp override the thermostat setpoint and room temperature from the BMS (0 = normal operation, no override); AV 30 Net Occupancy forces occupied (1) or unoccupied (2).

Network setup

Price Industries UMC3 underfloor controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

38 of 38 shown
Type
Access
Show
Price Industries UMC3 underfloor controller BACnet Points List
DescriptionStates
AImin1Room TemperatureAnalog Output can be tied to several signals°F/°CRead
AI3Supply Air TemperatureCurrent Supply Air Temperature°F/°CRead
AI4Cooling Signal InputVoltage on Cooling Signal Input terminal (0-10V input #1)VRead
AI5Heating Signal InputVoltage on Heating Signal Input terminal (0-10 input #2)VRead
AI8CO2 ReadingCurrent CO2 at the T-StatppmRead
AV1Use 0-10V Heat-Cool SignalsConfigures the controller to control using T-Stat or network setpoint and temperatureWrite0=Control from Price Thermostat, 1=Control from 0-10V input signals
AVmin2OccupancyOccupancy StatusRead0=Unoccupied, 1=Occupied
AV3Occupancy SourceRead0=VVT mode On, 3=ON from T-Stat button press, 4=ON from Motion Sensor, 5=ON from Network Override, 14=OFF from Motion Sensor, 15=OFF from Network Override
AV4Room Setpoint - low limitHighest user-adjustable setpoint°F/°CWrite
AV5Room Setpoint - high limitLowest user-adjustable setpoint°F/°CWrite
AVmin6Room SetpointCurrent Room Setpoint°F/°CRead
AV7Night Heat SetpointUnoccupied heating setpoint (at least 1 degree below AV 8)°F/°CWrite
AV8Night Cool SetpointUnoccupied cooling setpoint (at least 1 degree above AV 7)°F/°CWrite
AV9Aux Binary Output ApplicationConfiguration of the spare binary outputWrite0=ON during Heat, 1=ON during Cooling, 2=ON during Heating & Cooling, 3=ON during Deadband (satisfied), 4=Room Lights control (Motion T-Stat), 5=Output OFF, 6=Output ON
AV10Aux Binary Output StatusStatus of spare binary outputRead0=Output currently OFF, 1=Output currently ON
AV11Aux Analog Output VoltageCurrent voltage on the AUX Analog outputVRead
AV12Unoccupied (Night) Damper PositionDamper position held while unoccupied%Write
AV13PINGNumber of times the LCD T-Stat will beepWrite
AVmin14Controller StatusRoom load (PI): +1 to +100 % heating, 0 deadband, negative cooling%Read
AV15Proportional BandTemperature band through which the PI controller travels through 1% to 100%°F/°CWrite
AV16Day DifferentialDeadband either side of the setpoint°F/°CWrite
AV17Analog Heat Output VoltageCurrent Voltage at AI17VRead
AVmin18Current Damper PositionCurrent damper position in percent, 999% indicates the damper is recalibrating itself%Read
AV19Damper TargetCurrent Damper Target (damper value the controller is chasing) in percent%Read
AV20Damper Neutral Supply PositionSee flow response chart for UMC3%Write
AV21Damper Cool Min PositionSee flow response chart for UMC3, Upper Limit is AV22%Write
AV22Damper Colol Max PositionSee flow response chart for UMC3, Lower Limit is AV21%Write
AV23Damper Heat Min PositionSee flow response chart for UMC3, Upper Limit is AV24%Write
AV24Damper Heat Max PositionSee flow response chart for UMC3, Lower Limit is AV23%Write
AV25Remote Mode FlagRemote Mode - Damper OverrideWrite0=Automatic control (normal run mode), 1=Target Cool Min, 2=Target Cool Max, 3=Target Heat Min, 4=Target Heat Max, 5=Target Neutral Damper Position, 6=Open Damper 100%, 7=Close Damper (0%)
AV26LFGH Damper PositionCurrent LFGH Damper PositionRead
AV27LFGH Damper TargetLFGH damper target in percentRead
AVmin28Net SetpointSetpoint override from the network (0 = normal operation)°F/°CWrite
AVmin29Net Room TemperatureRoom temperature override from the network (0 = normal operation)°F/°CWrite
AVmin30Net OccupancyOccupancy ocerride from BACnet networkWrite0=Normal Operation, 1=Force Occupied, 2=Force Unoccupied
AV31Net LightsRoom Lights override from BACnet networkWrite0=Normal Operation, 1=Force Lights On, 2=Force Lights Off
AV32CO2 Min SetpointLowest user-adjustable CO2 setpointWrite
AV33CO2 Max SetpointHighest user-adjustable CO2 setpointWrite
Object ID lookup: Price Industries UMC3 underfloor controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UMC3 underfloor controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Price Industries UMC3 underfloor controller

How many BACnet points does the Price Industries UMC3 underfloor controller have?

This list has 38 BACnet objects: 5 analog inputs, 33 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Price Industries UMC3 underfloor controller BACnet points are writable?

22 of the 38 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Price Industries UMC3 underfloor controller BACnet documentation?

The source is BACnet points list for UMC3 firmware v1.19.0, revision Rev 0, published free by Price Industries at https://priceindustries.com/wp-content/uploads/BACnet-points-list-v1.19.0-UMC3-Rev-0.pdf.

What are the minimum BACnet points to integrate the Price Industries UMC3 underfloor controller?

Start with AV 30 Net Occupancy (BMS occupancy: 0 normal, 1 occupied, 2 unoccupied); AV 28 Net Setpoint (BMS setpoint override, 0 = none); AV 29 Net Room Temperature (BMS room temperature, 0 = none); AV 2 Occupancy (Current occupancy: 0 unocc, 1 occ); AI 1 Room Temperature (Room temperature); AV 6 Room Setpoint (Current room setpoint); AV 14 Controller Status (Room load: + heating, - cooling, %); AV 18 Current Damper Position (Damper position, % (999 = calibrating)).

How do I enable BMS control of the Price Industries UMC3 underfloor controller?

AV 30 Net Occupancy: 0 = normal operation, 1 = force occupied, 2 = force unoccupied. AV 1 selects thermostat/network control or the 0-10 V heat/cool input signals.

Can the BMS supply sensor values to the Price Industries UMC3 underfloor controller?

AV 28 Net Setpoint and AV 29 Net Room Temp override the thermostat setpoint and room temperature from the BMS (0 = normal operation, no override); AV 30 Net Occupancy forces occupied (1) or unoccupied (2).

How do I check these points on the real UMC3 underfloor controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Price Industries BACnet points lists

Source: BACnet points list for UMC3 firmware v1.19.0 · rev. Rev 0. Object names, instances and units are reproduced as published; descriptions are our own.