Room thermostat (Disio display sequence) · BACnet points list

Price Industries Disio Display DX-302 sequence BACnet points list

Updated 6 November 2026

Short answer

Disio Display is Price's room display/controller. In sequence DX-302 it exposes 53 BACnet MS/TP objects (its outputs are named Output 1 - Analog Fan, Output 4 - Binary Fan, Output 2 - Cooling Valve, Output 3 - Heating Valve), plus setpoints, loop settings, occupancy, units and network settings. The object list changes with the sequence loaded.

This page lists 53 BACnet objects for the Price Industries Disio Display DX-302 sequence — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.

Manufacturer
Price Industries
Model
Disio Display DX-302 sequence
Equipment
Room thermostat (Disio display sequence)
Equipment type
Thermostats, sensors & meters
BACnet objects
53 (48 writable)
Transport
BACnet MS/TP
Firmware
v1.6.14 Revision: E Version: 12
Also known as
Disio DX-302, DX-302, Disio Display, Price Disio
Source document
Disio Display BACnet Object List - DX-302 · Disio Display BACnet Object List (DX-302)
Download CSV 53 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Price Industries’s current documentation and the live device before use. Not official Price Industries information. Terms of use.

BMS integration notes: Price Industries Disio Display DX-302 sequence

Integration in brief

Write MV Occupancy and the room setpoint from the BMS, and read the room temperature, occupancy source and loop loads. AV 1 MAC Address and MV Baud Rate hold the network settings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6OccupancyOccupied / unoccupied commandWrite
AV 6Room Temperature SetpointRoom setpointWrite
AV 10Room TemperatureRoom temperatureWrite
MV 7Occupancy SourceWhat set the occupancyRead
AV 17Cooling Loop LoadCooling loop load, %Write
AV 24Heating Loop LoadHeating loop load, %Write

Network setup

Watch out for

Price Industries Disio Display DX-302 sequence BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

53 of 53 shown
Type
BinaryMulti-state
Access
Show
Price Industries Disio Display DX-302 sequence BACnet Points List
DescriptionStates
AI1Thermistive Input 1°F/°CWrite
AO1Output 1 - Analog FanVWrite
BO1Output 4 - Binary FanWrite
BO2Output 2 - Cooling ValveWrite
BO3Output 3 - Heating ValveWrite
AV1MAC AddressWrite
AV2Sequence VersionRead
AV3Sequence NumberRead
AV4Hardware VersionRead
AV5LED Brightness%Write
AVmin6Room Temperature Setpoint°F/°CWrite
AV7Room Temperature Setpoint Min°F/°CWrite
AV8Room Temperature Setpoint Max°F/°CWrite
AV9Room Temperature Offset°F/°CWrite
AVmin10Room Temperature°F/°CWrite
AV11Cooling Loop KpWrite
AV12Cooling Loop KiWrite
AV13Cooling Loop Pro Band°F/°CWrite
AV14Cooling Loop Dead Band°F/°CWrite
AV15Cooling Loop Unoccupied Dead Band°F/°CWrite
AV16Cooling Loop Service TimesWrite
AVmin17Cooling Loop Load%Write
AV18Heating Loop KpWrite
AV19Heating Loop KiWrite
AV20Heating Loop Pro Band°F/°CWrite
AV21Heating Loop Dead Band°F/°CWrite
AV22Heating Loop Unoccupied Dead Band°F/°CWrite
AV23Heating Loop Service TimesWrite
AVmin24Heating Loop Load%Write
AV25Binary Fan Min On TimeminWrite
AV26Binary Fan Min Off TimeminWrite
AV27DAT Offset°F/°CWrite
AV28DAT°F/°CWrite
AV29Analog Fan Min VVWrite
AV30Analog Fan Max VVWrite
AV31Analog Fan Min On TimeminWrite
AV32Analog Fan Min Off TimeminWrite
AV33Cooling Valve Min On TimeminWrite
AV34Cooling Valve Min Off TimeminWrite
AV35Heating Valve Min On TimeminWrite
AV36Heating Valve Min Off TimeminWrite
AV37Occupancy TimeoutminWrite
AV38Proximity Screen TimeoutsWrite
AV39Diagnostic ModeWrite
MV1Sequence RevisionRead0=A, 1=B, 2=C, 3=D, 4=E, 5=F, 6=G, 7=H, 8=I, 9=J, 10=K, 11=L, 12=M, 13=N, 14=O, 15=P, 16=Q, 17=R, 18=S, 19=T, 20=U, 21=V, 22=W, 23=X, 24=Y, 25=Z
MV2Temperature UnitsWrite0=C, 1=F
MV3Airflow UnitsWrite0=CFM, 1=L/s, 2=CMH
MV4Pressure UnitsWrite0=inches H20, 1=Pascals
MV5Baud RateWrite0=9600, 1=19200, 2=38400, 3=76800
MVmin6OccupancyWrite0=Unoccupied, 1=Occupied
MVmin7Occupancy SourceRead0=Default Occupied, 1=BACnet, 2=Button, 3=Motion
MV8Support Unoccupied ModeWrite0=No, 1=Yes
MV9Proximity Screen ModeWrite0=Dim, 1=Blank, 2=Always On
Object ID lookup: Price Industries Disio Display DX-302 sequence point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Disio Display DX-302 sequence and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Price Industries Disio Display DX-302 sequence

How many BACnet points does the Price Industries Disio Display DX-302 sequence have?

This list has 53 BACnet objects: 1 analog input, 1 analog output, 39 analog values, 3 binary outputs, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Price Industries Disio Display DX-302 sequence BACnet points are writable?

48 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Price Industries Disio Display DX-302 sequence BACnet documentation?

The source is Disio Display BACnet Object List - DX-302 (Disio Display BACnet Object List (DX-302)), published free by Price Industries at https://priceindustries.com/wp-content/uploads/Assets/literature/documents---bacnet/disio-display-bacnet-points-list.pdf.

What are the minimum BACnet points to integrate the Price Industries Disio Display DX-302 sequence?

Start with MV 6 Occupancy (Occupied / unoccupied command); AV 6 Room Temperature Setpoint (Room setpoint); AV 10 Room Temperature (Room temperature); MV 7 Occupancy Source (What set the occupancy); AV 17 Cooling Loop Load (Cooling loop load, %); AV 24 Heating Loop Load (Heating loop load, %).

How do I check these points on the real Disio Display DX-302 sequence?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Price Industries BACnet points lists

Source: Disio Display BACnet Object List - DX-302 · Disio Display BACnet Object List (DX-302). Object names, instances and units are reproduced as published; descriptions are our own.