Room thermostat (Disio display sequence) · BACnet points list

Price Industries Disio Display DX-600 sequence BACnet points list

Updated 6 November 2026

Short answer

Disio Display is Price's room display/controller. In sequence DX-600 it exposes 56 BACnet MS/TP objects (its outputs are named Output 1 - Damper, Output 3 - Analog Heat, Output 2 - Binary Heat), plus setpoints, loop settings, occupancy, units and network settings. The object list changes with the sequence loaded.

This page lists 56 BACnet objects for the Price Industries Disio Display DX-600 sequence — 51 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.

Manufacturer
Price Industries
Model
Disio Display DX-600 sequence
Equipment
Room thermostat (Disio display sequence)
Equipment type
Thermostats, sensors & meters
BACnet objects
56 (51 writable)
Transport
BACnet MS/TP
Firmware
v1.6.14 Revision: F Version: 14
Also known as
Disio DX-600, DX-600, Disio Display, Price Disio
Source document
Disio Display BACnet Object List - DX-600 · Disio Display BACnet Object List (DX-600)
Download CSV 56 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Price Industries’s current documentation and the live device before use. Not official Price Industries information. Terms of use.

BMS integration notes: Price Industries Disio Display DX-600 sequence

Integration in brief

Write MV Occupancy and the room setpoint from the BMS, and read the room temperature, occupancy source and loop loads. AV 1 MAC Address and MV Baud Rate hold the network settings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 7OccupancyOccupied / unoccupied commandWrite
AV 6Room Temperature SetpointRoom setpointWrite
AV 11Room TemperatureRoom temperatureWrite
MV 8Occupancy SourceWhat set the occupancyRead
AV 13SATSupply air temperatureWrite
AV 20Cooling Loop LoadCooling loop load, %Write
AV 27Heating Loop LoadHeating loop load, %Write

Network setup

Watch out for

Price Industries Disio Display DX-600 sequence BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

56 of 56 shown
Type
BinaryMulti-state
Access
Show
Price Industries Disio Display DX-600 sequence BACnet Points List
DescriptionStates
AI1Thermistive Input 1°F/°CWrite
AO1Output 1 - DamperVWrite
AO2Output 3 - Analog HeatVWrite
BO1Output 2 - Binary HeatWrite
AV1MAC AddressWrite
AV2Sequence VersionRead
AV3Sequence NumberRead
AV4Hardware VersionRead
AV5LED Brightness%Write
AVmin6Room Temperature Setpoint°F/°CWrite
AV7Room Temperature Setpoint Min°F/°CWrite
AV8Room Temperature Setpoint Max°F/°CWrite
AV9Deadband Damper%Write
AV10Room Temperature Offset°F/°CWrite
AVmin11Room Temperature°F/°CWrite
AV12SAT Offset°F/°CWrite
AVmin13SAT°F/°CWrite
AV14Cooling Loop KpWrite
AV15Cooling Loop KiWrite
AV16Cooling Loop Pro Band°F/°CWrite
AV17Cooling Loop Dead Band°F/°CWrite
AV18Cooling Loop Unoccupied Dead Band°F/°CWrite
AV19Cooling Loop Service TimesWrite
AVmin20Cooling Loop Load%Write
AV21Heating Loop KpWrite
AV22Heating Loop KiWrite
AV23Heating Loop Pro Band°F/°CWrite
AV24Heating Loop Dead Band°F/°CWrite
AV25Heating Loop Unoccupied Dead Band°F/°CWrite
AV26Heating Loop Service TimesWrite
AVmin27Heating Loop Load%Write
AV28Inlet Temperature Delta°F/°CWrite
AV29Damper Min VVWrite
AV30Damper Max VVWrite
AV31Damper Min On TimeminWrite
AV32Damper Min Off TimeminWrite
AV33Binary Heat Min On TimeminWrite
AV34Binary Heat Min Off TimeminWrite
AV35Analog Heat Min VVWrite
AV36Analog Heat Max VVWrite
AV37Analog Heat Min On TimeminWrite
AV38Analog Heat Min Off TimeminWrite
AV39Occupancy TimeoutminWrite
AV40Proximity Screen TimeoutsWrite
AV41Diagnostic ModeWrite
MV1Sequence RevisionRead0=A, 1=B, 2=C, 3=D, 4=E, 5=F, 6=G, 7=H, 8=I, 9=J, 10=K, 11=L, 12=M, 13=N, 14=O, 15=P, 16=Q, 17=R, 18=S, 19=T, 20=U, 21=V, 22=W, 23=X, 24=Y, 25=Z
MV2Inlet HCCO StateWrite0=Neutral, 1=Hot, 2=Cold
MV3Temperature UnitsWrite0=C, 1=F
MV4Airflow UnitsWrite0=CFM, 1=L/s, 2=CMH
MV5Pressure UnitsWrite0=inches H20, 1=Pascals
MV6Baud RateWrite0=9600, 1=19200, 2=38400, 3=76800
MVmin7OccupancyWrite0=Unoccupied, 1=Occupied
MVmin8Occupancy SourceRead0=Default Occupied, 1=BACnet, 2=Button, 3=Motion
MV9Support Unoccupied ModeWrite0=No, 1=Yes
MV10Proximity Screen ModeWrite0=Dim, 1=Blank, 2=Always On
MV11Device ModeWrite0=Standard, 1=Balancing
Object ID lookup: Price Industries Disio Display DX-600 sequence point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Disio Display DX-600 sequence and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Price Industries Disio Display DX-600 sequence

How many BACnet points does the Price Industries Disio Display DX-600 sequence have?

This list has 56 BACnet objects: 1 analog input, 2 analog outputs, 41 analog values, 1 binary output, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Price Industries Disio Display DX-600 sequence BACnet points are writable?

51 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Price Industries Disio Display DX-600 sequence BACnet documentation?

The source is Disio Display BACnet Object List - DX-600 (Disio Display BACnet Object List (DX-600)), published free by Price Industries at https://priceindustries.com/wp-content/uploads/Assets/literature/documents---bacnet/disio-display-bacnet-points-list.pdf.

What are the minimum BACnet points to integrate the Price Industries Disio Display DX-600 sequence?

Start with MV 7 Occupancy (Occupied / unoccupied command); AV 6 Room Temperature Setpoint (Room setpoint); AV 11 Room Temperature (Room temperature); MV 8 Occupancy Source (What set the occupancy); AV 13 SAT (Supply air temperature); AV 20 Cooling Loop Load (Cooling loop load, %); AV 27 Heating Loop Load (Heating loop load, %).

How do I check these points on the real Disio Display DX-600 sequence?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Price Industries BACnet points lists

Source: Disio Display BACnet Object List - DX-600 · Disio Display BACnet Object List (DX-600). Object names, instances and units are reproduced as published; descriptions are our own.