Rooftop unit controller (zoning / voting) · BACnet points list

Price Industries PRTU Price Rooftop Unit Controller BACnet points list

Updated 28 October 2026

Short answer

The PRTU is a Price controller that stages a packaged rooftop unit (up to 4 cooling and 4 heating stages plus fan) from its own thermostat or from zone demand. In networked mode it polls up to 30 Price PIC controllers or Prodigy diffusers over BACnet MS/TP every 3 minutes and picks the rooftop mode by voting; if polling fails it drops to standalone. A BMS reaches it on the same BACnet MS/TP trunk as the zone controllers.

This page lists 89 BACnet objects for the Price Industries PRTU Price Rooftop Unit Controller — 55 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.

Manufacturer
Price Industries
Model
PRTU Price Rooftop Unit Controller
Equipment
Rooftop unit controller (zoning / voting)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
89 (55 writable)
Transport
BACnet MS/TP
Firmware
v1.8.0
Default device instance
100
Also known as
PRTU, Price Rooftop Unit Controller, PRTU-STAT
Source document
BACnet Points List - PRTU · rev. REV 0
Download CSV 89 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Price Industries PRTU Price Rooftop Unit Controller

Integration in brief

Give the PRTU a MAC in 101-126 and a unique device instance, keep 76800 baud, and map the rooftop mode command, the standalone setpoints, the rooftop status, discharge/return temperatures and the polling-failed flag. In networked mode the zone controllers drive the rooftop mode by voting, so the BMS mostly monitors.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 5Rooftop ModeMode: 1 Auto, 2 Cool, 3 Heat, 4 Vent, 5 OffWrite
AV 1Standalone Cooling SetpointCooling setpoint in standalone modeWrite
AV 2Standalone Heating SetpointHeating setpoint in standalone modeWrite
MV 3Rooftop StatusCurrent mode: cooling, heating or deadbandWrite
MV 1Occupancy StatusOccupancy and its source (schedule, override, motion)Read
AI 1Discharge Air TemperatureDischarge air temperatureRead
AI 2Return Air TemperatureReturn air temperatureRead
AI 13Thermostat TemperatureTemperature at the PRTU thermostatRead
AV 32Number of Zones UpZones answering polls (max = AV 8)Read
BV 2Polling Failed to StandaloneTrue = polling failed, running standaloneWrite

Enable & remote start

No separate enable point. MV 5 Rooftop Mode sets Auto, Cool, Heat, Ventilation or Off. Occupancy follows the PRTU's internal schedule (default 6am-8pm), the thermostat button or motion; there is no BMS occupancy command in the list. MV 2 Strategy selects standalone or a polling strategy.

Heartbeat & communication loss

None for the BMS. For zone polling: if the PRTU can't poll its zones (bad address or wiring) or more than half are offline, it falls back to standalone on its own thermostat and sets BV 2; it returns to networked mode by itself once polling works.

Network setup

Watch out for

Price Industries PRTU Price Rooftop Unit Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

89 of 89 shown
Type
Multi-state
Access
Show
Price Industries PRTU Price Rooftop Unit Controller BACnet Points List
DescriptionStates
AImin1Discharge Air TemperatureAir temperature entering controlled space°F/°CRead
AImin2Return Air TemperatureAir temperature leaving controlled space°F/°CRead
AI3Outside Air TemperatureAir temperature outside of the building°F/°CRead
AI410K Thermistor Spare (AI4)Spare temperature sensor°F/°CRead
AI510K Thermistor Spare (AI5)Spare temperature sensor°F/°CRead
AI610K Thermistor Spare (AI6)Spare temperature sensor°F/°CRead
AI70-10VDC Spare (AI7)Spare analog 0-10 VDC inputRead
AI80-10VDC Spare (AI8)Spare analog 0-10 VDC inputRead
AI90-10VDC Spare (AI9)Spare analog 0-10 VDC inputRead
AI100-10VDC Spare (AI10)Spare analog 0-10 VDC inputRead
AI110-10VDC Spare (AI11)Spare analog 0-10 VDC inputRead
AI120-10VDC Spare (AI12)Spare analog 0-10 VDC inputRead
AImin13Thermostat TemperatureTemperature at the connected thermostat°F/°CRead
BI1Binary Input 1Contact input; function set in the controller Input menuReadOpen/Closed
BI2Binary Input 2Contact input; function set in the controller Input menuReadOpen/Closed
AO1Fan (AO1)Analog controlled fan speedVWrite
AO2Heat (AO2)Analog controlled heatVWrite
AO3Cool (AO3)Analog controlled coolingVWrite
AO4Demand (AO4)Analog controlled demandVWrite
BO1Fan (BO1)Fan on or offWriteOff/On
BO2Cool 1 (BO2)Stage 1 cooling on or offWriteOff/On
BO3Cool 2 (BO3)Stage 2 cooling on or offWriteOff/On
BO4Cool 3 (BO4)Stage 3 cooling on or offWriteOff/On
BO5Cool 4 (BO5)Stage 4 cooling on or offWriteOff/On
BO6Heat 1 (BO6)Stage 1 heating on or offWriteOff/On
BO7Heat 2 (BO7)Stage 2 heating on or offWriteOff/On
BO8Heat 3 (BO8)Stage 3 heating on or offWriteOff/On
BO9Heat 4 (B09)Stage 4 heating on or offWriteOff/On
BO10Cool Enable (BO10)Enables coolingWriteOff/On
AVmin1Standalone Cooling SetpointCooling setpoint when in standalone mode°F/°CWrite
AVmin2Standalone Heating SetpointHeating setpoint when in standalone mode°F/°CWrite
AV3Setpoint DifferenceHeat/cool setpoint separation (standalone only)°F/°CWrite
AV4Day Minimum SetpointLowest user-adjustable setpoint (default 65°F)°F/°CWrite
AV5Day Minimum SetpointHighest user-adjustable setpoint (default 80°F)°F/°CWrite
AV6Night Cool SetpointUnoccupied cooling setpoint°F/°CWrite
AV7Night Heat SetpointUnoccupied heating setpoint°F/°CWrite
AV8Number of ZonesNumber of zones polled by the PRTU (1-30)Write
AV9Standalone PIPI load when in standalone mode%Write
AV10Polled Cooling DemandThe demand for cooling from the polled zones%Write
AV11Polled Heating DemandThe demand for heating from the polled zones%Write
AV12Polled Deadband DemandThe demand for deadband from the polled zones%Write
AV13Stage Activate DelayDelay between stages of heating or cooling when activatingminWrite
AV14Stage Deactivate DelayDelay between stages of heating or cooling when deactivatingminWrite
AV15Mode Switchover DelayDelay between switching between heating and coolingminWrite
AV16Binary Output Minimum ON TimeMinimum amount of time that a binary output can be onsWrite
AV17Binary Output Minimum OFF TimeMinimum amount of time that a binary output can be offsWrite
AV18Standalone Proportional BandPI proportional band in standalone mode°F/°CWrite
AV19Standalone Day DifferentialSatisfied band around the standalone setpoint°F/°CWrite
AV20Polling Proportional BandPI proportional band in polling mode°F/°CWrite
AV21Polling Day DifferentialSatisfied band around the polled setpoint°F/°CWrite
AV22Motion Occupied TimeLength of time that motion will set the space to occupiedsWrite
AV23Non-Majority TripMinority-zone demand that still gets served%Write
AV24DAT Hot Trip 11st Discharge Air Temperature hot trip point°F/°CWrite
AV25DAT Hot Trip 22nd Discharge Air Temperature hot trip point°F/°CWrite
AV26RAT Hot Trip 11st Return Air Temperature hot trip point°F/°CWrite
AV27RAT Hot Trip 22nd Return Air Temperature hot trip point°F/°CWrite
AV28DAT Cold Trip 11st Discharge Air Temperature cold trip point°F/°CWrite
AV29DAT Cold Trip 22nd Discharge Air Temperature cold trip point°F/°CWrite
AV30RAT Cold Trip 11st Return Air Temperature cold trip point°F/°CWrite
AV31RAT Cold Trip 22nd Return Air Temperature cold trip point°F/°CWrite
AVmin32Number of Zones UpZones being polled successfully (max = AV8)Read
AV33PingWrite n to make the thermostat beep n timesWrite
AV34POR ResetsPower out reset count (internal use)Read
AV35BOR ResetsBrown out reset count (internal use)Read
AV36WDT ResetsWatchdog timer reset count (internal use)Read
AV37SWR ResetsSoftware reset count (internal use)Read
AV38EXTR ResetsExternal power reset count (internal use)Read
AV39IOPWR ResetsIllegal opcode reset count (internal use)Read
AV40Trap ResetsTrap reset count (internal use)Read
AV41Total ResetsTotal controller reset count (internal use)Read
AV42Zones Up (0-15) flagBit flags: zones 0-15 up (internal use)Read
AV43Zones Up (16-30) flagBit flags: zones 16-30 up (internal use)Read
AV44Deadband Zones (0-15) flagBit flags: zones 0-15 in deadband (internal use)Read
AV45Deadband Zones (16-30) flagBit flags: zones 16-30 in deadband (internal use)Read
AV46Cooling Zones (0-15) flagBit flags: zones 0-15 in cooling (internal use)Read
AV47Cooling Zones (16-30) flagBit flags: zones 16-30 in cooling (internal use)Read
AV48Heating Zones (0-15) flagBit flags: zones 0-15 in heating (internal use)Read
AV49Heating Zones (16-30) flagBit flags: zones 16-30 in heating (internal use)Read
MVmin1Occupancy StatusCurrent occupancy state and sourceRead1=Schedule Unoccupied, 2=Schedule Occupied, 3=Override Unoccupied, 4=Override Occupied, 5=Motion Occupied
MV2StrategyControl strategy (standalone or a polling method)Write1=Standalone, 2=Average Polling, 3=Non-Majority Polling, 4=Energy Hog
MVmin3Rooftop StatusCurrent rooftop mode: cooling, heating or deadbandWrite1=Cooling, 2=Heating, 3=Deadband
MV4Pending Rooftop StatusPending rooftop mode: cooling, heating or deadbandWrite1=Cooling, 2=Heating, 3=Deadband
MVmin5Rooftop ModeRooftop operating mode commandWrite1=Auto, 2=Cool, 3=Heat, 4=Ventilation, 5=Off
MV6N/AUnlabelled multistate (One-Four)Read1=One, 2=Two, 3=Three, 4=Four
MV7Temperature UnitsDisplay unitsWrite1=Fahrenheit, 2=Celsius
MV8Fan ConfigurationFan operation: day/night, on demand or 24/7Write1=Day/Night, 2=On Demand, 3=24/7
MV9Non-Majority ModeMode favoured in non-majority pollingWrite1=Cooling, 2=Heating, 3=Deadband
BV1Motion EnableLets motion set the space occupiedWrite
BVmin2Polling Failed to StandalonePolling failed; PRTU running standaloneWriteTrue=polling failed, standalone; False=polling OK

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PRTU Price Rooftop Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Price Industries PRTU Price Rooftop Unit Controller

How many BACnet points does the Price Industries PRTU Price Rooftop Unit Controller have?

This list has 89 BACnet objects: 13 analog inputs, 4 analog outputs, 49 analog values, 2 binary inputs, 10 binary outputs, 2 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Price Industries PRTU Price Rooftop Unit Controller BACnet points are writable?

55 of the 89 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Price Industries PRTU Price Rooftop Unit Controller BACnet documentation?

The source is BACnet Points List - PRTU, revision REV 0, published free by Price Industries at https://legacy.priceindustries.com/content/uploads/assets/literature/documents---bacnet/prtu---bacnet-points-list.pdf.

What are the minimum BACnet points to integrate the Price Industries PRTU Price Rooftop Unit Controller?

Start with MV 5 Rooftop Mode (Mode: 1 Auto, 2 Cool, 3 Heat, 4 Vent, 5 Off); AV 1 Standalone Cooling Setpoint (Cooling setpoint in standalone mode); AV 2 Standalone Heating Setpoint (Heating setpoint in standalone mode); MV 3 Rooftop Status (Current mode: cooling, heating or deadband); MV 1 Occupancy Status (Occupancy and its source (schedule, override, motion)); AI 1 Discharge Air Temperature (Discharge air temperature); AI 2 Return Air Temperature (Return air temperature); AI 13 Thermostat Temperature (Temperature at the PRTU thermostat); AV 32 Number of Zones Up (Zones answering polls (max = AV 8)); BV 2 Polling Failed to Standalone (True = polling failed, running standalone).

How do I enable BMS control of the Price Industries PRTU Price Rooftop Unit Controller?

No separate enable point. MV 5 Rooftop Mode sets Auto, Cool, Heat, Ventilation or Off. Occupancy follows the PRTU's internal schedule (default 6am-8pm), the thermostat button or motion; there is no BMS occupancy command in the list. MV 2 Strategy selects standalone or a polling strategy.

Does the Price Industries PRTU Price Rooftop Unit Controller need a BACnet heartbeat or have a communication timeout?

None for the BMS. For zone polling: if the PRTU can't poll its zones (bad address or wiring) or more than half are offline, it falls back to standalone on its own thermostat and sets BV 2; it returns to networked mode by itself once polling works.

How do I check these points on the real PRTU Price Rooftop Unit Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Price Industries BACnet points lists

Source: BACnet Points List - PRTU · rev. REV 0. Object names, instances and units are reproduced as published; descriptions are our own.