Room thermostat (Disio display sequence) · BACnet points list

Price Industries Disio Display DX-50 sequence BACnet points list

Updated 6 November 2026

Short answer

Disio Display is Price's room display/controller. In sequence DX-50 it exposes 45 BACnet MS/TP objects (its outputs are named Output 1 - Analog Heat 0-10, Output 2 - Analog Heat 2-10, Output 4 - Stage 2 Heat, Output 3 - Stage 1 Heat), plus setpoints, loop settings, occupancy, units and network settings. The object list changes with the sequence loaded.

This page lists 45 BACnet objects for the Price Industries Disio Display DX-50 sequence — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.

Manufacturer
Price Industries
Model
Disio Display DX-50 sequence
Equipment
Room thermostat (Disio display sequence)
Equipment type
Thermostats, sensors & meters
BACnet objects
45 (40 writable)
Transport
BACnet MS/TP
Firmware
v1.6.14 Revision: E Version: 22
Also known as
Disio DX-50, DX-50, Disio Display, Price Disio
Source document
Disio Display BACnet Object List - DX-50 · Disio Display BACnet Object List (DX-50)
Download CSV 45 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Price Industries’s current documentation and the live device before use. Not official Price Industries information. Terms of use.

BMS integration notes: Price Industries Disio Display DX-50 sequence

Integration in brief

Write MV Occupancy and the room setpoint from the BMS, and read the room temperature, occupancy source and loop loads. AV 1 MAC Address and MV Baud Rate hold the network settings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6OccupancyOccupied / unoccupied commandWrite
AV 6Room Temperature SetpointRoom setpointWrite
AV 10Room TemperatureRoom temperatureWrite
MV 7Occupancy SourceWhat set the occupancyRead
AV 17Heating Loop LoadHeating loop load, %Write

Network setup

Watch out for

Price Industries Disio Display DX-50 sequence BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

45 of 45 shown
Type
BinaryMulti-state
Access
Show
Price Industries Disio Display DX-50 sequence BACnet Points List
DescriptionStates
AO1Output 1 - Analog Heat 0-10VWrite
AO2Output 2 - Analog Heat 2-10VWrite
BO1Output 4 - Stage 2 HeatWrite
BO2Output 3 - Stage 1 HeatWrite
AV1MAC AddressWrite
AV2Sequence VersionRead
AV3Sequence NumberRead
AV4Hardware VersionRead
AV5LED Brightness%Write
AVmin6Room Temperature Setpoint°F/°CWrite
AV7Room Temperature Setpoint Min°F/°CWrite
AV8Room Temperature Setpoint Max°F/°CWrite
AV9Room Temperature Offset°F/°CWrite
AVmin10Room Temperature°F/°CWrite
AV11Heating Loop KpWrite
AV12Heating Loop KiWrite
AV13Heating Loop Pro Band°F/°CWrite
AV14Heating Loop Dead Band°F/°CWrite
AV15Heating Loop Unoccupied Dead Band°F/°CWrite
AV16Heating Loop Service TimesWrite
AVmin17Heating Loop Load%Write
AV18Stage 2 Heat Min On TimeminWrite
AV19Stage 2 Heat Min Off TimeminWrite
AV20Stage 1 Heat Min On TimeminWrite
AV21Stage 1 Heat Min Off TimeminWrite
AV22Analog Heat 0-10 Min VVWrite
AV23Analog Heat 0-10 Max VVWrite
AV24Analog Heat 0-10 Min On TimeminWrite
AV25Analog Heat 0-10 Min Off TimeminWrite
AV26Analog Heat 2-10 Min VVWrite
AV27Analog Heat 2-10 Max VVWrite
AV28Analog Heat 2-10 Min On TimeminWrite
AV29Analog Heat 2-10 Min Off TimeminWrite
AV30Occupancy TimeoutminWrite
AV31Proximity Screen TimeoutsWrite
AV32Diagnostic ModeWrite
MV1Sequence RevisionRead0=A, 1=B, 2=C, 3=D, 4=E, 5=F, 6=G, 7=H, 8=I, 9=J, 10=K, 11=L, 12=M, 13=N, 14=O, 15=P, 16=Q, 17=R, 18=S, 19=T, 20=U, 21=V, 22=W, 23=X, 24=Y, 25=Z
MV2Temperature UnitsWrite0=C, 1=F
MV3Airflow UnitsWrite0=CFM, 1=L/s, 2=CMH
MV4Pressure UnitsWrite0=inches H20, 1=Pascals
MV5Baud RateWrite0=9600, 1=19200, 2=38400, 3=76800
MVmin6OccupancyWrite0=Unoccupied, 1=Occupied
MVmin7Occupancy SourceRead0=Default Occupied, 1=BACnet, 2=Button, 3=Motion
MV8Support Unoccupied ModeWrite0=No, 1=Yes
MV9Proximity Screen ModeWrite0=Dim, 1=Blank, 2=Always On
Object ID lookup: Price Industries Disio Display DX-50 sequence point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Disio Display DX-50 sequence and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Price Industries Disio Display DX-50 sequence

How many BACnet points does the Price Industries Disio Display DX-50 sequence have?

This list has 45 BACnet objects: 2 analog outputs, 32 analog values, 2 binary outputs, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Price Industries Disio Display DX-50 sequence BACnet points are writable?

40 of the 45 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Price Industries Disio Display DX-50 sequence BACnet documentation?

The source is Disio Display BACnet Object List - DX-50 (Disio Display BACnet Object List (DX-50)), published free by Price Industries at https://priceindustries.com/wp-content/uploads/Assets/literature/documents---bacnet/disio-display-bacnet-points-list.pdf.

What are the minimum BACnet points to integrate the Price Industries Disio Display DX-50 sequence?

Start with MV 6 Occupancy (Occupied / unoccupied command); AV 6 Room Temperature Setpoint (Room setpoint); AV 10 Room Temperature (Room temperature); MV 7 Occupancy Source (What set the occupancy); AV 17 Heating Loop Load (Heating loop load, %).

How do I check these points on the real Disio Display DX-50 sequence?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.