Room thermostat (Disio display sequence) · BACnet points list
Price Industries Disio Display DX-150 sequence BACnet points list
Updated 6 November 2026
Disio Display is Price's room display/controller. In sequence DX-150 it exposes 95 BACnet MS/TP objects (its outputs are named Output 3 - Analog Reheat, Output 1 - Binary Actuator Open, Output 2 - Binary Actuator Close, Output 4 - Binary Reheat), plus setpoints, loop settings, occupancy, units and network settings. The object list changes with the sequence loaded.
This page lists 95 BACnet objects for the Price Industries Disio Display DX-150 sequence — 86 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.
- Manufacturer
- Price Industries
- Model
- Disio Display DX-150 sequence
- Equipment
- Room thermostat (Disio display sequence)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 95 (86 writable)
- Transport
- BACnet MS/TP
- Firmware
- v1.6.14 Revision: A Version: 19
- Also known as
- Disio DX-150, DX-150, Disio Display, Price Disio
Reference only, provided as-is: verify against Price Industries’s current documentation and the live device before use. Not official Price Industries information. Terms of use.
BMS integration notes: Price Industries Disio Display DX-150 sequence
Write MV Occupancy and the room setpoint from the BMS, and read the room temperature, occupancy source and loop loads. AV 1 MAC Address and MV Baud Rate hold the network settings.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 14 | Occupancy | Occupied / unoccupied command | Write |
| AV 7 | Room Temperature Setpoint | Room setpoint | Write |
| AV 11 | Room Temperature | Room temperature | Write |
| MV 15 | Occupancy Source | What set the occupancy | Read |
| AV 17 | SAT | Supply air temperature | Write |
| AV 27 | Cooling Loop Load | Cooling loop load, % | Write |
| AV 34 | Heating Loop Load | Heating loop load, % | Write |
| AV 62 | Binary Actuator Damper Position | Damper position, % | Read |
Network setup
- MAC address is AV 1 (default 2); baud rate is the Baud Rate MV (0=9600, 1=19200, 2=38400, 3=76800).
Watch out for
- Many objects are marked as retained on power failure; avoid writing those cyclically.
Price Industries Disio Display DX-150 sequence BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Analog Input 2 | V | Write | ||
| AI | 2 | Thermistive Input 1 | °F/°C | Write | ||
| AO | 1 | Output 3 - Analog Reheat | V | Write | ||
| BO | 1 | Output 1 - Binary Actuator Open | Write | |||
| BO | 2 | Output 2 - Binary Actuator Close | Write | |||
| BO | 3 | Output 4 - Binary Reheat | Write | |||
| AV | 1 | MAC Address | Write | |||
| AV | 2 | Sequence Version | Read | |||
| AV | 3 | Sequence Number | Read | |||
| AV | 4 | Hardware Version | Read | |||
| AV | 5 | LED Brightness | % | Write | ||
| AV | 6 | Analog Input 2 Calibration Offset | V | Write | ||
| AVmin | 7 | Room Temperature Setpoint | °F/°C | Write | ||
| AV | 8 | Room Temperature Setpoint Min | °F/°C | Write | ||
| AV | 9 | Room Temperature Setpoint Max | °F/°C | Write | ||
| AV | 10 | Room Temperature Offset | °F/°C | Write | ||
| AVmin | 11 | Room Temperature | °F/°C | Write | ||
| AV | 12 | CFM K Factor | Write | |||
| AV | 13 | Airflow Scale | Write | |||
| AV | 14 | Airflow Offset | Write | |||
| AV | 15 | Airflow | Write | |||
| AV | 16 | SAT Offset | °F/°C | Write | ||
| AVmin | 17 | SAT | °F/°C | Write | ||
| AV | 18 | Neutral Min Offset | °F/°C | Write | ||
| AV | 19 | Neutral Max Offset | °F/°C | Write | ||
| AV | 20 | Cold Differential Offset | °F/°C | Write | ||
| AV | 21 | Cooling Loop Kp | Write | |||
| AV | 22 | Cooling Loop Ki | Write | |||
| AV | 23 | Cooling Loop Pro Band | °F/°C | Write | ||
| AV | 24 | Cooling Loop Dead Band | °F/°C | Write | ||
| AV | 25 | Cooling Loop Unoccupied Dead Band | °F/°C | Write | ||
| AV | 26 | Cooling Loop Service Time | s | Write | ||
| AVmin | 27 | Cooling Loop Load | % | Write | ||
| AV | 28 | Heating Loop Kp | Write | |||
| AV | 29 | Heating Loop Ki | Write | |||
| AV | 30 | Heating Loop Pro Band | °F/°C | Write | ||
| AV | 31 | Heating Loop Dead Band | °F/°C | Write | ||
| AV | 32 | Heating Loop Unoccupied Dead Band | °F/°C | Write | ||
| AV | 33 | Heating Loop Service Time | s | Write | ||
| AVmin | 34 | Heating Loop Load | % | Write | ||
| AV | 35 | Airflow Target Temperature Delta | °F/°C | Write | ||
| AV | 36 | Airflow Target Cool Min | Write | |||
| AV | 37 | Airflow Target Cool Max | Write | |||
| AV | 38 | Airflow Target Heat Min | Write | |||
| AV | 39 | Airflow Target Heat Max | Write | |||
| AV | 40 | Airflow Target Neutral | Write | |||
| AV | 41 | Airflow Target Output Value | Write | |||
| AV | 42 | Airflow Control Hold Time | s | Write | ||
| AV | 43 | Airflow Control Min Step | % | Write | ||
| AV | 44 | Airflow Control Max Step | % | Write | ||
| AV | 45 | Airflow Control Percent Dead Band | % | Write | ||
| AV | 46 | Airflow Control Dead Band | Write | |||
| AV | 47 | Airflow Control Unoccupied Percent Dead Band | % | Write | ||
| AV | 48 | Airflow Control Unoccupied Dead Band | Write | |||
| AV | 49 | Airflow Control Output Value | % | Write | ||
| AV | 50 | Pres Dep Temperature Delta | °F/°C | Write | ||
| AV | 51 | Pres Dep Cool Min | % | Write | ||
| AV | 52 | Pres Dep Cool Max | % | Write | ||
| AV | 53 | Pres Dep Heat Min | % | Write | ||
| AV | 54 | Pres Dep Heat Max | % | Write | ||
| AV | 55 | Pres Dep Neutral | % | Write | ||
| AV | 56 | Pres Dep Output Value | % | Write | ||
| AV | 57 | Binary Actuator Runtime | s | Write | ||
| AV | 58 | Binary Actuator Calibration Time | s | Write | ||
| AV | 59 | Binary Actuator Min On Time | min | Write | ||
| AV | 60 | Binary Actuator Min Off Time | min | Write | ||
| AV | 61 | Binary Actuator Target Value | % | Write | ||
| AVmin | 62 | Binary Actuator Damper Position | % | Read | ||
| AV | 63 | Analog Reheat Min V | V | Write | ||
| AV | 64 | Analog Reheat Max V | V | Write | ||
| AV | 65 | Analog Reheat Min On Time | min | Write | ||
| AV | 66 | Analog Reheat Min Off Time | min | Write | ||
| AV | 67 | Binary Reheat Min On Time | min | Write | ||
| AV | 68 | Binary Reheat Min Off Time | min | Write | ||
| AV | 69 | Occupancy Timeout | min | Write | ||
| AV | 70 | Proximity Screen Timeout | s | Write | ||
| AV | 71 | Diagnostic Mode | Write | |||
| MV | 1 | Sequence Revision | Read | 0=A, 1=B, 2=C, 3=D, 4=E, 5=F, 6=G, 7=H, 8=I, 9=J, 10=K, 11=L, 12=M, 13=N, 14=O, 15=P, 16=Q, 17=R, 18=S, 19=T, 20=U, 21=V, 22=W, 23=X, 24=Y, 25=Z | ||
| MV | 2 | CFM Duct Inlet Size | Write | 0=4, 1=5, 2=6, 3=7, 4=8, 5=9, 6=10, 7=12, 8=14, 9=16, 10=24x16, 11=9 lp, 12=10 lp, 13=12 lp, 14=14 lp, 15=16 lp | ||
| MV | 3 | Airflow Target HCCO State | Write | 0=Neutral, 1=Hot, 2=Cold | ||
| MV | 4 | Airflow Target Flow Units | Read | 0=Airflow, 1=Percent | ||
| MV | 5 | Pres Dep HCCO State | Write | 0=Neutral, 1=Hot, 2=Cold | ||
| MV | 6 | Pres Dep Flow Units | Read | 0=Airflow, 1=Percent | ||
| MV | 7 | Binary Actuator Calibration Direction | Write | 0=Open, 1=Close | ||
| MV | 8 | Calibrating Sensor | Write | 0=Not Calibrating, 1=Input 2, 2=Clear Calibration | ||
| MV | 9 | Calibrated Sensors | Read | 0=1, 1=2, 2=3, 3=4, 4=1&2, 5=1&3, 6=1&4, 7=1&2&3, 8=1&2&4, 9=1&3&4, 10=All, 11=2&3, 12=2&4, 13=2&3&4, 14=3&4, 15=No | ||
| MV | 10 | Temperature Units | Write | 0=C, 1=F | ||
| MV | 11 | Airflow Units | Write | 0=CFM, 1=L/s, 2=CMH | ||
| MV | 12 | Pressure Units | Write | 0=inches H20, 1=Pascals | ||
| MV | 13 | Baud Rate | Write | 0=9600, 1=19200, 2=38400, 3=76800 | ||
| MVmin | 14 | Occupancy | Write | 0=Unoccupied, 1=Occupied | ||
| MVmin | 15 | Occupancy Source | Read | 0=Default Occupied, 1=BACnet, 2=Button, 3=Motion | ||
| MV | 16 | Support Unoccupied Mode | Write | 0=No, 1=Yes | ||
| MV | 17 | Proximity Screen Mode | Write | 0=Dim, 1=Blank, 2=Always On | ||
| MV | 18 | Device Mode | Write | 0=Standard, 1=Balancing |
No points match these filters.
Object ID lookup: Price Industries Disio Display DX-150 sequence point IDs by name
AI1Analog Input 2AI2Thermistive Input 1AO1Output 3 - Analog ReheatBO1Output 1 - Binary Actuator OpenBO2Output 2 - Binary Actuator CloseBO3Output 4 - Binary ReheatAV1MAC AddressAV2Sequence VersionAV3Sequence NumberAV4Hardware VersionAV5LED BrightnessAV6Analog Input 2 Calibration OffsetAV7Room Temperature SetpointAV8Room Temperature Setpoint MinAV9Room Temperature Setpoint MaxAV10Room Temperature OffsetAV11Room TemperatureAV12CFM K FactorAV13Airflow ScaleAV14Airflow OffsetAV15AirflowAV16SAT OffsetAV17SATAV18Neutral Min OffsetAV19Neutral Max OffsetAV20Cold Differential OffsetAV21Cooling Loop KpAV22Cooling Loop KiAV23Cooling Loop Pro BandAV24Cooling Loop Dead BandAV25Cooling Loop Unoccupied Dead BandAV26Cooling Loop Service TimeAV27Cooling Loop LoadAV28Heating Loop KpAV29Heating Loop KiAV30Heating Loop Pro BandAV31Heating Loop Dead BandAV32Heating Loop Unoccupied Dead BandAV33Heating Loop Service TimeAV34Heating Loop LoadAV35Airflow Target Temperature DeltaAV36Airflow Target Cool MinAV37Airflow Target Cool MaxAV38Airflow Target Heat MinAV39Airflow Target Heat MaxAV40Airflow Target NeutralAV41Airflow Target Output ValueAV42Airflow Control Hold TimeAV43Airflow Control Min StepAV44Airflow Control Max StepAV45Airflow Control Percent Dead BandAV46Airflow Control Dead BandAV47Airflow Control Unoccupied Percent Dead BandAV48Airflow Control Unoccupied Dead BandAV49Airflow Control Output ValueAV50Pres Dep Temperature DeltaAV51Pres Dep Cool MinAV52Pres Dep Cool MaxAV53Pres Dep Heat MinAV54Pres Dep Heat MaxAV55Pres Dep NeutralAV56Pres Dep Output ValueAV57Binary Actuator RuntimeAV58Binary Actuator Calibration TimeAV59Binary Actuator Min On TimeAV60Binary Actuator Min Off TimeAV61Binary Actuator Target ValueAV62Binary Actuator Damper PositionAV63Analog Reheat Min VAV64Analog Reheat Max VAV65Analog Reheat Min On TimeAV66Analog Reheat Min Off TimeAV67Binary Reheat Min On TimeAV68Binary Reheat Min Off TimeAV69Occupancy TimeoutAV70Proximity Screen TimeoutAV71Diagnostic ModeMV1Sequence RevisionMV2CFM Duct Inlet SizeMV3Airflow Target HCCO StateMV4Airflow Target Flow UnitsMV5Pres Dep HCCO StateMV6Pres Dep Flow UnitsMV7Binary Actuator Calibration DirectionMV8Calibrating SensorMV9Calibrated SensorsMV10Temperature UnitsMV11Airflow UnitsMV12Pressure UnitsMV13Baud RateMV14OccupancyMV15Occupancy SourceMV16Support Unoccupied ModeMV17Proximity Screen ModeMV18Device Mode
Integration notes
- Table for Disio sequence DX-150, pages 9-12 of the Disio Display BACnet Object List (v1.6.14 Revision: A Version: 19).
- The list names the outputs by terminal (for example "Output 1 - Analog Fan"); which outputs exist depends on the sequence.
- Multistate states are printed 0-based (for example 0-Unoccupied, 1-Occupied) and are listed that way.
- The document has no description column; descriptions are empty.
- The document does not say which equipment each sequence is for; only the output names hint at it.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Disio Display DX-150 sequence and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Price Industries Disio Display DX-150 sequence
How many BACnet points does the Price Industries Disio Display DX-150 sequence have?
This list has 95 BACnet objects: 2 analog inputs, 1 analog output, 71 analog values, 3 binary outputs, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Price Industries Disio Display DX-150 sequence BACnet points are writable?
86 of the 95 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Price Industries Disio Display DX-150 sequence BACnet documentation?
The source is Disio Display BACnet Object List - DX-150 (Disio Display BACnet Object List (DX-150)), published free by Price Industries at https://priceindustries.com/wp-content/uploads/Assets/literature/documents---bacnet/disio-display-bacnet-points-list.pdf.
What are the minimum BACnet points to integrate the Price Industries Disio Display DX-150 sequence?
Start with MV 14 Occupancy (Occupied / unoccupied command); AV 7 Room Temperature Setpoint (Room setpoint); AV 11 Room Temperature (Room temperature); MV 15 Occupancy Source (What set the occupancy); AV 17 SAT (Supply air temperature); AV 27 Cooling Loop Load (Cooling loop load, %); AV 34 Heating Loop Load (Heating loop load, %); AV 62 Binary Actuator Damper Position (Damper position, %).
How do I check these points on the real Disio Display DX-150 sequence?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Price Industries BACnet points lists
- Fan filter unit (FFU) controller
Price Industries BFC BACnet flow controller for fan filter units
Price fan filter units (FFU / UFFU) with the BFC BACnet Flow Controller, firmware v3.2.0.
Also known as: BFC, BACnet Flow Controller, Price BFC, FFU controller, UFFU - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-100 sequence
Price Disio Display room controllers running sequence DX-100 or DX-101.
Also known as: Disio DX-100, DX-100, Disio Display, Price Disio, Disio DX-101 - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-200 sequence
Price Disio Display room controllers running sequence DX-200 or DX-201.
Also known as: Disio DX-200, DX-200, Disio Display, Price Disio, Disio DX-201 - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-300 sequence
Price Disio Display room controllers running sequence DX-300.
Also known as: Disio DX-300, DX-300, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-301 sequence
Price Disio Display room controllers running sequence DX-301.
Also known as: Disio DX-301, DX-301, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-302 sequence
Price Disio Display room controllers running sequence DX-302.
Also known as: Disio DX-302, DX-302, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-303 sequence
Price Disio Display room controllers running sequence DX-303.
Also known as: Disio DX-303, DX-303, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-304 sequence
Price Disio Display room controllers running sequence DX-304.
Also known as: Disio DX-304, DX-304, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-305 sequence
Price Disio Display room controllers running sequence DX-305.
Also known as: Disio DX-305, DX-305, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-50 sequence
Price Disio Display room controllers running sequence DX-50.
Also known as: Disio DX-50, DX-50, Disio Display, Price Disio - Room thermostat (Disio display sequence)
Price Industries Disio Display DX-600 sequence
Price Disio Display room controllers running sequence DX-600.
Also known as: Disio DX-600, DX-600, Disio Display, Price Disio - Underfloor plenum pressure (VAV) controller
Price Industries PCU constant pressure controller (PCM plenum pressurization)
Price PCU controllers running the constant pressure sequence for underfloor plenum pressurization (PCM).
Also known as: PCU, PCU-PP1, PCM, Price PCU constant pressure - VAV / fan-powered terminal controller
Price Industries PIC Price Intelligent Controller
Price PIC DDC controllers on single-duct, fan-powered, dual-duct and exhaust terminals and on fan coils.
Also known as: PIC, Price Intelligent Controller, PIC-BAC, PIC-VAV - Single-duct VAV terminal controller
Price Industries PIC-SD Price Intelligent Controller - SD
Price PIC-SD controllers on single-duct VAV terminals.
Also known as: PIC-SD, PIC SD, Price Intelligent Controller SD - Rooftop unit controller (zoning / voting)
Price Industries PRTU Price Rooftop Unit Controller
Packaged single- and multi-stage rooftop units (about 2-30 tons) run by a Price PRTU, alone or polling Price zone controllers.
Also known as: PRTU, Price Rooftop Unit Controller, PRTU-STAT - Underfloor air terminal (VAV) controller
Price Industries UMC3 underfloor controller
Price UMC3 controllers for underfloor air distribution terminals.
Also known as: UMC3, Price UMC3 - Underfloor air terminal (VAV) controller
Price Industries UMCB underfloor modulating controller
Price UMCB controllers for underfloor air distribution terminals.
Also known as: UMCB, Price UMCB
Source: Disio Display BACnet Object List - DX-150 · Disio Display BACnet Object List (DX-150). Object names, instances and units are reproduced as published; descriptions are our own.