Underfloor plenum pressure (VAV) controller · BACnet points list

Price Industries PCU constant pressure controller (PCM plenum pressurization) BACnet points list

Updated 6 November 2026

Short answer

The PCU in its constant pressure sequence modulates a damper to hold underfloor plenum pressure. The points list has 27 objects: pressure sensors and target, occupied/unoccupied pressure setpoints, damper position and override, room temperature/CO2/humidity from the thermostat, and BMS override values for setpoint, room temperature, occupancy and lights.

This page lists 27 BACnet objects for the Price Industries PCU constant pressure controller (PCM plenum pressurization) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Price Industries’s own free documentation, linked below.

Manufacturer
Price Industries
Model
PCU constant pressure controller (PCM plenum pressurization)
Equipment
Underfloor plenum pressure (VAV) controller
Equipment type
VAV boxes & fan coils
BACnet objects
27 (9 writable)
Transport
BACnet MS/TP
Firmware
v1.04
Also known as
PCU, PCU-PP1, PCM, Price PCU constant pressure
Source document
BACnet points list for PCU firmware v1.04 Constant Pressure · rev. Rev 0
Download CSV 27 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Price Industries’s current documentation and the live device before use. Not official Price Industries information. Terms of use.

BMS integration notes: Price Industries PCU constant pressure controller (PCM plenum pressurization)

Integration in brief

Write AV 19 Pressure Setpoint and AV 30 Net Occupancy; read AI 2 Current Pressure, AV 1 Pressure Target and AV 18 damper position.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 30Net OccupancyBMS occupancy: 0 normal, 1 occupied, 2 unoccupiedWrite
AV 19Pressure SetpointPlenum pressure setpoint, inH2OWrite
AV 2OccupancyCurrent occupancy: 0 unocc, 1 occRead
AI 2Current PressureMeasured plenum pressure, inH2ORead
AV 1Pressure TargetPressure target being controlled toRead
AV 18Current Damper PositionDamper position, % (999 = calibrating)Read

Enable & remote start

AV 30 Net Occupancy: 0 = normal operation, 1 = force occupied, 2 = force unoccupied. AV 25 Remote Mode Flag can override the damper (0 = automatic).

Network setup

Price Industries PCU constant pressure controller (PCM plenum pressurization) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

27 of 27 shown
Type
Access
Show
Price Industries PCU constant pressure controller (PCM plenum pressurization) BACnet Points List
DescriptionStates
AI1Room TemperatureCurrent Room Temperature°F/°CRead
AImin2Current PressureCurrent final pressure readinginH2ORead
AI3T1 Temperature SensorCurrent temperature reading from T1 Sensor°F/°CRead
AI4Pressure Sensor 1Current pressure reading on AI4inH2ORead
AI5Pressure Sensor 2Current pressure reading on AI5inH2ORead
AI6Pressure Sensor 3Current pressure reading on AI6inH2ORead
AI70-5VDC Sensor Signal InputVoltage from sensor inputVRead
AI8T2 Temperature SnsorCurrent temperature reading from T2 Sensor°F/°CRead
AI9Humidity ReadingCurrent Relitive Humidity at the T-Stat%RHRead
AI10CO2 ReadingCurrent CO2 Reading from T-StatppmRead
AVmin1Pressure TargetCurrent pressure targetinH2ORead
AVmin2OccupancyRead0=Unoccupied, 1=Occupied
AV3Occupancy SourceRead0=Occupied from VVT (Default Mode), 2=Occupied from Contact Closure, 3=Occupied from T-Stat Button, 4=Occupied from Motion Sensor, 5=Occupied from Network Override, 12=Unoccupied from Contact Closure, 14=Unoccupied from Motion Sensor, 15=Unoccupied from Network Override
AV9Analog Heat Output VoltageCurrent voltage on the Analog Heat output (AO2)VRead
AV10Analog Cool Output VoltageCurrent voltage on the Analog Cool output (AO3)VRead
AV11AO4 Output VoltageCurrent voltage on AO4 outputVRead
AV12Unoccupied Pressure SetpointPressure held during unoccupied periodsinH2OWrite
AV13PINGNumber of times the LCD T-Stat will beepWrite
AV17Binary Output Status CodeBinary outputs as a bit field: bit 0 = BO1 ... bit 4 = BO5Read
AVmin18Current Damper PositionCurrent damper position in percent, 999% indicates the damper is recalibrating itself%Read
AVmin19Pressure SetpointCurrent pressure setpointinH2OWrite
AV25Remote Mode FlagRemote Mode - Damper OverrideWrite0=Automatic control (normal run mode), 1=Target Cool Min, 2=Target Cool Max, 3=Target Heat Min, 4=Target Heat Max, 5=Target Neutral Damper Position, 6=Open Damper 100%, 7=Close Damper (0%)
AV27Reheat TypeNot SupportedWrite
AV28Net SetpointSetpoint override from the network (0 = normal operation)°F/°CWrite
AV29Net Room TempRoom temperature override from the network (0 = normal operation)°F/°CWrite
AVmin30Net OccupancyOccupancy override from BACnet networkWrite0=Normal Operation, 1=Force Occupied, 2=Force Unoccupied
AV31Net LightsRoom Lights override from BACnet networkWrite0=Normal Operation, 1=Force Lights On, 2=Force Lights Off
Object ID lookup: Price Industries PCU constant pressure controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PCU constant pressure controller (PCM plenum pressurization) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Price Industries PCU constant pressure controller (PCM plenum pressurization)

How many BACnet points does the Price Industries PCU constant pressure controller (PCM plenum pressurization) have?

This list has 27 BACnet objects: 10 analog inputs, 17 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Price Industries PCU constant pressure controller (PCM plenum pressurization) BACnet points are writable?

9 of the 27 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Price Industries PCU constant pressure controller (PCM plenum pressurization) BACnet documentation?

The source is BACnet points list for PCU firmware v1.04 Constant Pressure, revision Rev 0, published free by Price Industries at https://priceindustries.com/wp-content/uploads/BACnet-points-list-v1.04-PCU-Constant-Pressure-Rev-0-1.pdf.

What are the minimum BACnet points to integrate the Price Industries PCU constant pressure controller (PCM plenum pressurization)?

Start with AV 30 Net Occupancy (BMS occupancy: 0 normal, 1 occupied, 2 unoccupied); AV 19 Pressure Setpoint (Plenum pressure setpoint, inH2O); AV 2 Occupancy (Current occupancy: 0 unocc, 1 occ); AI 2 Current Pressure (Measured plenum pressure, inH2O); AV 1 Pressure Target (Pressure target being controlled to); AV 18 Current Damper Position (Damper position, % (999 = calibrating)).

How do I enable BMS control of the Price Industries PCU constant pressure controller (PCM plenum pressurization)?

AV 30 Net Occupancy: 0 = normal operation, 1 = force occupied, 2 = force unoccupied. AV 25 Remote Mode Flag can override the damper (0 = automatic).

How do I check these points on the real PCU constant pressure controller (PCM plenum pressurization)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Price Industries BACnet points lists