Heat pump water heater plant controller · BACnet points list

Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) BACnet points list

Updated 6 November 2026

Short answer

Lochinvar's ProtoNode FPC-N54 maps the Veritus / Emerge_X heat pump water heater controller to 54 BACnet objects. Binary inputs give thermostat, BMS enable, louver, recirculation pump, runtime, alarm and backup heat relay states; analog inputs give system and tank temperatures, packed per-unit status words, error codes and flow; eight analog values take BMS commands such as demand enable and tank setpoint.

This page lists 54 BACnet objects for the Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)
Equipment
Heat pump water heater plant controller
Equipment type
Heat pumps
BACnet objects
54 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Veritus, Emerge_X, Emerge X, Lochinvar Veritus, ProtoNode FPC-N54
Source document
Operating Manual - ProtoNode FPC-N54 for Interfacing Lochinvar Products, section 9.1 Veritus and Emerge_X · CN1998 Rev 7.C (Lochinvar 100377812_2000809463 Rev B)
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.

BMS integration notes: Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)

Integration in brief

Map the Demand Enable and Tank Setpoint AVs for control, then read system setpoint and temperatures, tank temperatures, the runtime and alarm relays, the packed units-in-run/lockout words and the SCB error and warning codes. The guide gives no command sequence, so check the Veritus/Emerge_X manual before writing Configuration or the backup heat objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 47Demand EnableDemand enable command from the BMSWrite
AV 48Tank SetpointTank (DHW) setpoint commandWrite
AI 14System SetpointActive system setpointRead
AI 15System Supply TemperatureSystem supply water temperatureRead
AI 19Tank 1 TemperatureTank 1 temperatureRead
BI 6Runtime RelayRuntime relay state (plant running)Read
AI 29Units In Run (1-16)Packed run status, units 1-16Read
BI 7Alarm RelayAlarm relay stateRead
AI 41SCB Error CodeActive system control board error codeRead

Enable & remote start

AV 47 Demand Enable and AV 48 Tank Setpoint are the writable objects for control; BI 2 BMS Enable reads back the BMS enable input. The guide does not describe the values or the order to write them.

Sensors & values from the BMS

AV 49 0-10V BMS Input lets the BMS supply the analog input value; the guide does not say how it is scaled.

Network setup

Watch out for

Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

54 of 54 shown
Type
Binary
Access
Show
Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) BACnet Points List
DescriptionStates
BI1TSTATThermostat input stateRead
BI2BMS EnableBMS enable input stateRead
BI3Louver ProvingRead
BI4Louver RelayRead
BI5Recirc PumpRead
BImin6Runtime RelayRead
BImin7Alarm RelayRead
BI8Backup Heat 1Read
BI9Backup Heat 2Read
AI10Discrete Inputs 0-8Packed discrete inputs 0-8Read
AI1130001Raw Modbus input register 30001Read
AI1230002Raw Modbus input register 30002Read
AI1330003Raw Modbus input register 30003Read
AImin14System SetpointRead
AImin15System Supply TemperatureRead
AI16System Return TemperatureRead
AI17System Recirc TemperatureRead
AI18System Outdoor TemperatureRead
AImin19Tank 1 TemperatureRead
AI20Tank 2 TemperatureRead
AI21Tank 3 TemperatureRead
AI22Tank 4 TemperatureRead
AI23Tank 5 TemperatureRead
AI24Tank 6 TemperatureRead
AI25Units Present (1-16)Units present, units 1-16 (packed)Read
AI26Units Present (17-32)Read
AI27Units Present (33-48)Read
AI28Units Present (49-64)Read
AImin29Units In Run (1-16)Units running, units 1-16 (packed)Read
AI30Units In Run (17-32)Read
AI31Units In Run (33-48)Read
AI32Units In Run (49-64)Read
AI33Units In Blocking (1-16)Units in blocking, units 1-16 (packed)Read
AI34Units In Blocking (17-32)Read
AI35Units In Blocking (33-48)Read
AI36Units In Blocking (49-64)Read
AI37Units In Lockout (1-16)Units in lockout, units 1-16 (packed)Read
AI38Units In Lockout (17-32)Read
AI39Units In Lockout (33-48)Read
AI40Units In Lockout (49-64)Read
AImin41SCB Error CodeSystem control board error codeRead
AI42SCB Warning CodeSystem control board warning codeRead
AI43Backup Heat 1 RateRead
AI44Backup Heat 2 RateRead
AI45Total Heat Pump FlowRead
AV46ConfigurationConfiguration registerWrite
AVmin47Demand EnableDemand enable commandWrite
AVmin48Tank SetpointTank setpoint commandWrite
AV490-10V BMS InputBMS 0-10 V input valueWrite
AV50Active Tank SensorSelects the active tank sensorWrite
AV51Backup Heat 1Write
AV52Backup Heat 2Write
AV53Backup Heat 1 RateWrite
AV54Backup Heat 2 RateWrite
Object ID lookup: Lochinvar Veritus / Emerge_X heat pump water heater point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)

How many BACnet points does the Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) have?

This list has 54 BACnet objects: 36 analog inputs, 9 analog values, 9 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) BACnet points are writable?

9 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54) BACnet documentation?

The source is Operating Manual - ProtoNode FPC-N54 for Interfacing Lochinvar Products, section 9.1 Veritus and Emerge_X (CN1998 Rev 7.C (Lochinvar 100377812_2000809463 Rev B)), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/100377812_2000809463_Rev%20B%20(60567)%20ProtoNode%20Operating%20Manual.pdf.

What are the minimum BACnet points to integrate the Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)?

Start with AV 47 Demand Enable (Demand enable command from the BMS); AV 48 Tank Setpoint (Tank (DHW) setpoint command); AI 14 System Setpoint (Active system setpoint); AI 15 System Supply Temperature (System supply water temperature); AI 19 Tank 1 Temperature (Tank 1 temperature); BI 6 Runtime Relay (Runtime relay state (plant running)); AI 29 Units In Run (1-16) (Packed run status, units 1-16); BI 7 Alarm Relay (Alarm relay state); AI 41 SCB Error Code (Active system control board error code).

How do I enable BMS control of the Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)?

AV 47 Demand Enable and AV 48 Tank Setpoint are the writable objects for control; BI 2 BMS Enable reads back the BMS enable input. The guide does not describe the values or the order to write them.

Can the BMS supply sensor values to the Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)?

AV 49 0-10V BMS Input lets the BMS supply the analog input value; the guide does not say how it is scaled.

How do I check these points on the real Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: Operating Manual - ProtoNode FPC-N54 for Interfacing Lochinvar Products, section 9.1 Veritus and Emerge_X · CN1998 Rev 7.C (Lochinvar 100377812_2000809463 Rev B). Object names, instances and units are reproduced as published; descriptions are our own.