Heating appliance controller gateway (IPW) · BACnet points list
Lochinvar IPW (ProtoNode FPC-N54) BACnet points list
Updated 6 November 2026
Lochinvar's ProtoNode FPC-N54 start-up guide lists only four BACnet objects for the IPW: outlet temperature, inlet temperature and outlet voltage as analog inputs, and a writable setpoint. The IPW talks to the ProtoNode at 19200 baud, unlike the other Lochinvar products in the guide.
This page lists 4 BACnet objects for the Lochinvar IPW (ProtoNode FPC-N54) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.
- Manufacturer
- Lochinvar
- Model
- IPW (ProtoNode FPC-N54)
- Equipment
- Heating appliance controller gateway (IPW)
- Equipment type
- Other equipment
- BACnet objects
- 4 (1 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IPW, Lochinvar IPW, ProtoNode FPC-N54
Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.
BMS integration notes: Lochinvar IPW (ProtoNode FPC-N54)
Write the setpoint to AV 4 and read outlet temperature, inlet temperature and outlet voltage.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 4 | Setpoint | Setpoint command from the BMS | Write |
| AI 1 | Outlet Temperature | Outlet water temperature | Read |
| AI 2 | Inlet Temperature | Inlet water temperature | Read |
| AI 3 | Outlet Voltage | Outlet voltage reading (not described in the guide) | Read |
Enable & remote start
AV 4 Setpoint is the only writable object. The guide gives no enable object.
Network setup
- ProtoNode FPC-N54 to the IPW: Modbus RTU, 19200 baud, no parity, 8 data bits, 1 stop bit.
- Give each unit a unique Node-ID (1-255). BACnet device instance = Node_Offset (default 50,000) + Node-ID.
- BACnet IP or BACnet MS/TP is chosen in the ProtoNode web configurator.
Watch out for
- Access is inferred: the table has no read/write column.
- The guide gives no units or ranges for these four objects.
Lochinvar IPW (ProtoNode FPC-N54) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Outlet Temperature | Read | |||
| AImin | 2 | Inlet Temperature | Read | |||
| AImin | 3 | Outlet Voltage | Read | |||
| AVmin | 4 | Setpoint | Write |
No points match these filters.
Object ID lookup: Lochinvar IPW point IDs by name
Integration notes
- Appendix C.8 of the guide (page 53).
- The guide does not describe the IPW product itself; the equipment type is taken from the object list.
- The table has no read/write column, units or states; access is inferred from the N2 type (AO = writable).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IPW (ProtoNode FPC-N54) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lochinvar IPW (ProtoNode FPC-N54)
How many BACnet points does the Lochinvar IPW (ProtoNode FPC-N54) have?
This list has 4 BACnet objects: 3 analog inputs, 1 analog value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lochinvar IPW (ProtoNode FPC-N54) BACnet points are writable?
1 of the 4 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Lochinvar IPW (ProtoNode FPC-N54) BACnet documentation?
The source is ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.8 IPW (Document Revision 5.A (Lochinvar 2000594856 Rev A)), revision 2020-06 (effective date), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/161357100338377_2000594856_Rev%20A%20(ProtoNode%20FPC-N54%20Start-up%20Guide%20for%20Lochinvar).pdf.
What are the minimum BACnet points to integrate the Lochinvar IPW (ProtoNode FPC-N54)?
Start with AV 4 Setpoint (Setpoint command from the BMS); AI 1 Outlet Temperature (Outlet water temperature); AI 2 Inlet Temperature (Inlet water temperature); AI 3 Outlet Voltage (Outlet voltage reading (not described in the guide)).
How do I enable BMS control of the Lochinvar IPW (ProtoNode FPC-N54)?
AV 4 Setpoint is the only writable object. The guide gives no enable object.
How do I check these points on the real IPW (ProtoNode FPC-N54)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lochinvar BACnet points lists
- Commercial condensing water heater controller
Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)
Lochinvar Armor volume water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and the Modbus/BACnet communication board.
Also known as: Armor, Armor 1250, Armor 4000, AWH, Armor Series 100, Armor Series 101, SMART SYSTEM, MTR-01, 100305786 - Commercial boiler / water heater / pool heater controller
Lochinvar Copper-fin II / IIE (CFX, CHX, CPX)
Lochinvar Copper-fin II/IIE boilers and water heaters (models 402-2072) and pool heaters (502-2072) with the SMART SYSTEM control.
Also known as: Copper-fin, Copper-Fin II, Copper-fin IIE, CFX, CHX, CPX, C(F,H,P)X-MODB, CB 402-2072, CW 402-2072 - Condensing boiler controller
Lochinvar Crest
Crest FB/OF 751-6001 and FCB 1000-6000 condensing boilers (the manual uses the same map for Hellcat).
Also known as: Crest FB, Crest OF, Crest FCB, Hellcat - Condensing boiler / water heater controller
Lochinvar Knight / Armor (SMART TOUCH)
Knight, Knight XL, Armor, Wall Mount, Wall Hung, AQUAS, FTXL and Shield boilers and water heaters with the SMART TOUCH control.
Also known as: Knight XL, Outdoor Knight, Armor, Wall Mount, Wall Hung, AQUAS, FTXL, Shield, MODB-I-O - Commercial boiler controller gateway
Lochinvar Knight FTXL (ProtoNode FPC-N54)
Lochinvar Knight FTXL fire-tube boilers, read through the ProtoNode FPC-N54 gateway.
Also known as: Knight FTXL, FTXL, Lochinvar FTXL, ProtoNode FPC-N54 - Electric boiler controller
Lochinvar Lectrus electric boiler (KEB)
Lochinvar Lectrus electric boilers, models KEB 0015-0150, with the Modbus/BACnet communication board.
Also known as: Lectrus, KEB, KEB0015, KEB0150, MODB-I-O-KEB, Lochinvar electric boiler - Commercial boiler controller gateway
Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)
Lochinvar Power Fin boilers in the 2.5-5.0 size range (the guide's "Powerfin_2.5_5.0" profile), read through the ProtoNode FPC-N54 gateway.
Also known as: Power Fin 2.5-5.0, Power-Fin 2500-5000, PBN/PFN 2.5-5.0, Lochinvar Power Fin, ProtoNode FPC-N54 - Commercial boiler / water heater controller
Lochinvar Power-Fin (SMART SYSTEM)
Lochinvar Power-fin models 502-1302 and 1501-2001, with the SMART SYSTEM control and the Modbus/BACnet communication board.
Also known as: Power-fin, Powerfin, PBX-PFX-MODB, SMART SYSTEM - Commercial water heater controller
Lochinvar Regent
Regent IWH 500-1000 commercial gas water heaters.
Also known as: Regent IWH, IWH500-1000 - Dual-heat-exchanger condensing boiler controller
Lochinvar SYNC
SYNC 1.0, 1.3 and 1.5 condensing boilers (two heat exchangers, reported as unit 1 and unit 2).
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC-MODB - Heat pump water heater plant controller
Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)
Lochinvar Veritus and Emerge_X heat pump water heater systems (up to 64 units), read through the ProtoNode FPC-N54.
Also known as: Veritus, Emerge_X, Emerge X, Lochinvar Veritus, ProtoNode FPC-N54
Source: ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.8 IPW · Document Revision 5.A (Lochinvar 2000594856 Rev A) · rev. 2020-06 (effective date). Object names, instances and units are reproduced as published; descriptions are our own.