Lochinvar Crest BACnet points list

Updated 28 October 2026

Short answer

The Crest boiler exposes BACnet MS/TP through Lochinvar's Modbus/BACnet communication board. Besides the usual enable, temperature, firing rate and status/blocking/lockout codes, larger and FCB models add dual-burner, damper, O2 trim and cascade member lockout points.

This page lists 77 BACnet objects for the Lochinvar Crest — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Crest
Equipment
Condensing boiler controller
Equipment type
Boilers & water heaters
BACnet objects
77 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Base + MAC address: 610000 for FB 751-2001, 670000 for FB 2501-6001, 680000 for FCB1000-6000 (base can be changed)
Also known as
Crest FB, Crest OF, Crest FCB, Hellcat
Source document
Modbus and BACnet Communication Instructions (Crest FB/OF751-6001, FCB1000-6000 & Regent IWH500-1000) · 100161012_2000020084 · rev. Rev X, 04/26
Download CSV 77 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lochinvar Crest

Integration in brief

Pick the BMS control mode at the boiler, then write AV 0 Configuration so the unit knows which values the BAS will supply. After that the BAS sends an enable, a rate command (AV 2), or both, and keeps rewriting them. Status, temperatures and the status, blocking and lockout codes can be read without taking control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBitmask of BAS-supplied inputs; resend before commandsWrite
BV 0Boiler EnableEnable / call for heat from the BASWrite
AV 20-10 Volt Input / Rate Command / Setpoint CommandRate command: firing % or setpoint, per BMS TypeWrite
AI 13Boiler Status CodeWhat the boiler is doing; 40 = lockoutRead
AI 8Outlet TemperatureBoiler outlet water temperature, °CRead
AI 11Firing RateBurner firing rate, %Read
AI 15Boiler Lockout CodeLockout cause; valid only when status code is 40Read

Enable & remote start

Set the Demand Configuration under Main Menu > Setup > BMS. ENABLE active / BMS inactive: local setpoints plus BV 0 enable. ENABLE and BMS active: BV 0 enable plus AV 2 rate or setpoint command. ENABLE inactive / BMS active: AV 2 modulation % or setpoint alone. Always set the matching AV 0 bits first. AV 2 means firing % or temperature setpoint depending on the BMS Type setting (Power or Setpoint); as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures at low and high input.

Heartbeat & communication loss

If BAS-written temperatures stop arriving within the timeout, the unit reverts to its own sensor inputs. On Crest the timeout is programmable from 5 to 120 s (Main Menu > Setup > BAS); Lochinvar recommends the shortest value. On Hellcat and Regent it is fixed at 300 s. Other commands must be refreshed at least every 4 minutes or the boiler runs on its own inputs.

Sensors & values from the BMS

Set the AV 0 bits for the values the BAS will supply, then write them to the analog values: AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature, AV 7 system return temperature. Values are in °C. Temperatures must be rewritten every few seconds or the unit returns to its own sensors.

Network setup

Watch out for

Lochinvar Crest BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

77 of 77 shown
Type
Access
Show
Lochinvar Crest BACnet Points List
DescriptionStates
BVmin0Boiler EnableBAS enable command for the applianceWrite
BV4Tank ThermostatTank / DHW thermostat callWrite
BI0Manual Reset High LimitSafety / proving switch statusRead
BI1Flow SwitchSafety / proving switch statusRead
BI2Gas Pressure SwitchSafety / proving switch statusRead
BI3Louver Proving SwitchSafety / proving switch statusRead
BI4Proof of ClosureGas valve proof of closure (FCB1000-6001 only; usable on FB/OF4001-6001)Read
BI5Blocked Drain SwitchSafety / proving switch statusRead
BI7Flame 1Flame statusRead
BI8EnableEnable input status (Crest 751-6001 only)Read
BI9Tank ThermostatTank / DHW thermostat call (Crest 751-6001 only)Read
BI10Blocked Vent SwitchSafety / proving switch statusRead
BI12Fan 2 Proving SwitchSecond fan proving switch (751-6001 only; older dual-fan models)Read
BI17Internal LWCOSafety / proving switch status (Crest FCB1000-6001 only)Read
BI18Gas Pressure Switch 2Safety / proving switch status (Crest FCB1000-6001 only)Read
BI20Flue Damper SwitchSafety / proving switch statusRead
BI22Flame 2Flame statusRead
BI25EnableEnable input status (Crest FCB1000-6001 only)Read
BI29Tank ThermostatTank / DHW thermostat call (Crest FCB1000-6001 only)Read
BI32Run Time ContactsOutput or relay statusRead
BI33Alarm ContactsOutput or relay statusRead
BI34Boiler PumpOutput or relay statusRead
BI35DHW PumpOutput or relay statusRead
BI36Louver RelayOutput or relay statusRead
BI37Gas Valve 1Output or relay statusRead
BI38System PumpOutput or relay statusRead
BI40DHW Recirc PumpOutput or relay status (Crest FCB1000-6001 only)Read
BI43Flue Damper OutputOutput or relay statusRead
BI45Gas Valve 2Output or relay statusRead
BI46Transition Gas ValveOutput or relay status (Crest 751-1501 only)Read
BI48Main Fan 1Output or relay statusRead
BI49Main Fan 2Output or relay status (Crest 2501-6001 only; Dual fan models only)Read
BI50External Spark / HSIOutput or relay statusRead
BI51Air Valve TriggerOutput or relay statusRead
BI52Air Valve ProvingSafety / proving switch statusRead
AI0Binary Inputs 0-15Packed word of binary inputs 0-15Read
AI1Binary Inputs 16-31Packed word of binary inputs 16-31Read
AI2Binary Inputs 32-47Packed word of binary inputs 32-47Read
AI3System / Cascade SetpointSetpoint value°CRead
AI4System Pump SpeedPump speed output%Read
AI5Cascade Total PowerTotal cascade firing capacity%Read
AI6Cascade Current PowerCurrent cascade firing rate%Read
AI7Outlet SetpointSetpoint value°CRead
AImin8Outlet TemperatureTemperature reading°CRead
AI9Inlet TemperatureTemperature reading°CRead
AI10Flue TemperatureTemperature reading°CRead
AImin11Firing RateBurner firing rate%Read
AI12Boiler Pump SpeedPump speed output%Read
AImin13Boiler Status CodeCurrent operating status codeRead
AI14Boiler Blocking CodeActive blocking (soft lockout) codeRead
AImin15Boiler Lockout CodeActive lockout codeRead
AI18Air Damper Target AngleCombustion / flow value (Crest FCB1000-6001 only)Read
AI19Gas Damper Target AngleCombustion / flow value (Crest FCB1000-6001 only)Read
AI20Fan Speed TargetCombustion / flow value (Crest FCB1000-6001 only)Read
AI22O2 Sensor StatusCombustion / flow value (Crest FCB1000-6001 only)Read
AI23Current Trim FactorCombustion / flow value (Crest FCB1000-6001 only)Read
AI24BarometerCombustion / flow value (Crest FCB1000-6001 only)Read
AI25Binary Inputs 48-63Packed word of binary inputs 48-63Read
AI26Lock-Out Error LeaderLockout flag for this cascade unitRead
AI27Lock-Out Error Member 1Lockout flag for this cascade unitRead
AI28Lock-Out Error Member 2Lockout flag for this cascade unitRead
AI29Lock-Out Error Member 3Lockout flag for this cascade unitRead
AI30Lock-Out Error Member 4Lockout flag for this cascade unitRead
AI31Lock-Out Error Member 5Lockout flag for this cascade unitRead
AI32Lock-Out Error Member 6Lockout flag for this cascade unitRead
AI33Lock-Out Error Member 7Lockout flag for this cascade unitRead
AI35Flame 1Flame status (Crest FCB1000-6001 only)Read
AI36Flame 2Flame status (Crest FCB1000-6001 only)Read
AI37Corrected O2 ReadingCombustion / flow value (Crest FCB1000-6001 only)Read
AVmin0ConfigurationBitmask selecting which values the BAS suppliesWrite
AV1CoilsPacked word of the binary value commandsWrite
AVmin20-10 Volt Input / Rate Command / Setpoint CommandBAS rate or setpoint command (0-100%)%Write
AV3Tank SetpointSetpoint value°CWrite
AV4Tank TemperatureTemperature reading°CWrite
AV5Outdoor TemperatureTemperature reading°CWrite
AV6System Supply TemperatureTemperature reading°CWrite
AV7System Return TemperatureTemperature reading°CWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Crest and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Crest

How many BACnet points does the Lochinvar Crest have?

This list has 77 BACnet objects: 34 analog inputs, 8 analog values, 33 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Crest BACnet points are writable?

10 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lochinvar Crest BACnet documentation?

The source is Modbus and BACnet Communication Instructions (Crest FB/OF751-6001, FCB1000-6000 & Regent IWH500-1000) (100161012_2000020084), revision Rev X, 04/26, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/MODB_100161012_2000020084_REV%20X_(71343).pdf.

What are the minimum BACnet points to integrate the Lochinvar Crest?

Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); BV 0 Boiler Enable (Enable / call for heat from the BAS); AV 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate command: firing % or setpoint, per BMS Type); AI 13 Boiler Status Code (What the boiler is doing; 40 = lockout); AI 8 Outlet Temperature (Boiler outlet water temperature, °C); AI 11 Firing Rate (Burner firing rate, %); AI 15 Boiler Lockout Code (Lockout cause; valid only when status code is 40).

How do I enable BMS control of the Lochinvar Crest?

Set the Demand Configuration under Main Menu > Setup > BMS. ENABLE active / BMS inactive: local setpoints plus BV 0 enable. ENABLE and BMS active: BV 0 enable plus AV 2 rate or setpoint command. ENABLE inactive / BMS active: AV 2 modulation % or setpoint alone. Always set the matching AV 0 bits first. AV 2 means firing % or temperature setpoint depending on the BMS Type setting (Power or Setpoint); as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures at low and high input.

Does the Lochinvar Crest need a BACnet heartbeat or have a communication timeout?

If BAS-written temperatures stop arriving within the timeout, the unit reverts to its own sensor inputs. On Crest the timeout is programmable from 5 to 120 s (Main Menu > Setup > BAS); Lochinvar recommends the shortest value. On Hellcat and Regent it is fixed at 300 s. Other commands must be refreshed at least every 4 minutes or the boiler runs on its own inputs.

Can the BMS supply sensor values to the Lochinvar Crest?

Set the AV 0 bits for the values the BAS will supply, then write them to the analog values: AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature, AV 7 system return temperature. Values are in °C. Temperatures must be rewritten every few seconds or the unit returns to its own sensors.

How do I check these points on the real Crest?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.