Dual-heat-exchanger condensing boiler controller · BACnet points list

Lochinvar SYNC BACnet points list

Updated 28 October 2026

Short answer

The SYNC boiler has two heat exchangers in one cabinet, so its BACnet MS/TP map repeats the flame, switch, temperature and status points for unit 1 and unit 2. Access is through Lochinvar's Modbus/BACnet communication board.

This page lists 62 BACnet objects for the Lochinvar SYNC — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
SYNC
Equipment
Dual-heat-exchanger condensing boiler controller
Equipment type
Boilers & water heaters
BACnet objects
62 (9 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
630000 + MAC address (base is model dependent and can be changed)
Also known as
SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC-MODB
Source document
Modbus and BACnet Communication Instructions (SYNC 1.0 - 1.3 - 1.5) · SYNC-MODB_100161723_2000017706 · rev. Rev L, 05/17
Download CSV 62 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lochinvar SYNC

Integration in brief

Pick the BMS control mode at the boiler, then write AV 0 Configuration so the unit knows which values the BAS will supply. After that the BAS sends an enable, a rate command (AV 2), or both, and keeps rewriting them. Status, temperatures and the status, blocking and lockout codes can be read without taking control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBitmask of BAS-supplied inputs; resend before commandsWrite
BV 0Boiler EnableEnable / call for heat from the BASWrite
AV 20-10 Volt Input / Rate Command / Setpoint CommandRate command: firing % or setpoint, per BMS TypeWrite
AI 13Unit 1 Status CodeWhat heat exchanger 1 is doing; 40 = lockoutRead
AI 22Unit 2 Status CodeWhat heat exchanger 2 is doing; 40 = lockoutRead
AI 8Outlet Temperature 1Outlet temperature, heat exchanger 1Read
AI 17Outlet Temperature 2Outlet temperature, heat exchanger 2Read
AI 15Unit 1 Lockout CodeLockout cause, heat exchanger 1; valid only at status 40Read
AI 24Unit 2 Lockout CodeLockout cause, heat exchanger 2; valid only at status 40Read

Enable & remote start

Set Demand Configuration 4, 5 or 6 under Main > Setup > Service/Setup > Demand Config. 4: local setpoints plus BV 0 enable. 5: enable plus AV 2 rate command. 6: AV 2 modulation % alone. Set the matching AV 0 bits first. AV 2 means firing % or temperature setpoint depending on the BMS Type setting (Power or Setpoint); as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures at low and high input.

Heartbeat & communication loss

If BAS-written temperatures or commands stop arriving, the unit reverts to its own readings and controls. The timeout is set under Main > Setup > BMS > Modbus / BACnet Timeout; the manual gives 5-120 s with a 10 s default in one place and 0-120 s in another. Every write resets it, and Lochinvar recommends the shortest value. Commands without temperatures must be refreshed at least every 4 minutes.

Sensors & values from the BMS

Set the AV 0 bits for the values the BAS will supply, then write them to the analog values: AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature. Values are in °C. Temperatures must be rewritten every few seconds or the unit returns to its own sensors.

Network setup

Watch out for

Lochinvar SYNC BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

62 of 62 shown
Type
Access
Show
Lochinvar SYNC BACnet Points List
DescriptionStates
BVmin0Boiler EnableBAS enable command for the applianceWrite
BV4Tank ThermostatTank / DHW thermostat callWrite
BI0Manual Reset High Limit 1Safety / proving switch statusRead
BI1Flow Switch 1Safety / proving switch statusRead
BI2Gas Pressure Switch 1Safety / proving switch statusRead
BI3Louver Proving Switch 1Safety / proving switch statusRead
BI4Flap Valve 1Safety / proving switch statusRead
BI5Blocked Drain Switch 1Safety / proving switch statusRead
BI6Auto Reset High Limit 1Safety / proving switch statusRead
BI7Flame 1Flame statusRead
BI8EnableEnable input statusRead
BI9Tank ThermostatTank / DHW thermostat callRead
BI16Manual Reset High Limit 2Safety / proving switch statusRead
BI17Flow Switch 2Safety / proving switch statusRead
BI18Gas Pressure Switch 2Safety / proving switch statusRead
BI19Louver Proving Switch 2Safety / proving switch statusRead
BI20Flap Valve 2Safety / proving switch statusRead
BI21Blocked Drain Switch 2Safety / proving switch statusRead
BI22Flame 2Flame statusRead
BI32Run-time Contacts 1Output or relay statusRead
BI33Alarm Contacts 1Output or relay statusRead
BI34Boiler Pump 1Output or relay statusRead
BI35DHW Pump 1Output or relay statusRead
BI37Gas Valve 1Output or relay statusRead
BI38System PumpOutput or relay statusRead
BI40Run-time Contacts 2Output or relay statusRead
BI41Alarm Contacts 2Output or relay statusRead
BI42Boiler Pump 2Output or relay statusRead
BI43DHW Pump 2Output or relay statusRead
BI45Gas Valve 2Output or relay statusRead
BI48Fan 1 PowerOutput or relay statusRead
BI49Fan 2 PowerOutput or relay statusRead
AI0Binary Inputs 0 - 15Packed word of binary inputs 0-15Read
AI1Binary Inputs 16 - 31Packed word of binary inputs 16-31Read
AI2Binary Inputs 32 - 47Packed word of binary inputs 32-47Read
AI3System / Cascade SetpointSetpoint value°CRead
AI5Cascade Total PowerTotal cascade firing capacity%Read
AI6Cascade Current PowerCurrent cascade firing rate%Read
AI7Outlet Setpoint 1Setpoint value°CRead
AImin8Outlet Temperature 1Temperature reading°CRead
AI9Inlet Temperature 1Temperature reading°CRead
AI10Flue Temperature 1Temperature reading°CRead
AI11Firing Rate 1Burner firing rate%Read
AImin13Unit 1 Status CodeCurrent operating status codeRead
AI14Unit 1 Blocking CodeActive blocking (soft lockout) codeRead
AImin15Unit 1 Lockout CodeActive lockout codeRead
AI16Outlet Setpoint 2Setpoint value°CRead
AImin17Outlet Temperature 2Temperature reading°CRead
AI18Inlet Temperature 2Temperature reading°CRead
AI19Flue Temperature 2Temperature reading°CRead
AI20Firing Rate 2Burner firing rate%Read
AImin22Unit 2 Status CodeCurrent operating status codeRead
AI23Unit 2 Blocking CodeActive blocking (soft lockout) codeRead
AImin24Unit 2 Lockout CodeActive lockout codeRead
AI25Binary Inputs 48 - 63Packed word of binary inputs 48-63Read
AVmin0ConfigurationBitmask selecting which values the BAS suppliesWrite
AV1Binary ValuesPacked word of the binary value commandsWrite
AVmin20-10 Volt Input / Rate Command / Setpoint CommandBAS rate or setpoint command (0-100%)%Write
AV3Tank SetpointSetpoint value°CWrite
AV4Tank TemperatureTemperature reading°CWrite
AV5Outdoor TemperatureTemperature reading°CWrite
AV6System Supply TemperatureTemperature reading°CWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SYNC and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar SYNC

How many BACnet points does the Lochinvar SYNC have?

This list has 62 BACnet objects: 23 analog inputs, 7 analog values, 30 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar SYNC BACnet points are writable?

9 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lochinvar SYNC BACnet documentation?

The source is Modbus and BACnet Communication Instructions (SYNC 1.0 - 1.3 - 1.5) (SYNC-MODB_100161723_2000017706), revision Rev L, 05/17, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/594260SYNC-MODB_100161723_2000017706__REV%20L_BACNET.pdf.

What are the minimum BACnet points to integrate the Lochinvar SYNC?

Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); BV 0 Boiler Enable (Enable / call for heat from the BAS); AV 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate command: firing % or setpoint, per BMS Type); AI 13 Unit 1 Status Code (What heat exchanger 1 is doing; 40 = lockout); AI 22 Unit 2 Status Code (What heat exchanger 2 is doing; 40 = lockout); AI 8 Outlet Temperature 1 (Outlet temperature, heat exchanger 1); AI 17 Outlet Temperature 2 (Outlet temperature, heat exchanger 2); AI 15 Unit 1 Lockout Code (Lockout cause, heat exchanger 1; valid only at status 40); AI 24 Unit 2 Lockout Code (Lockout cause, heat exchanger 2; valid only at status 40).

How do I enable BMS control of the Lochinvar SYNC?

Set Demand Configuration 4, 5 or 6 under Main > Setup > Service/Setup > Demand Config. 4: local setpoints plus BV 0 enable. 5: enable plus AV 2 rate command. 6: AV 2 modulation % alone. Set the matching AV 0 bits first. AV 2 means firing % or temperature setpoint depending on the BMS Type setting (Power or Setpoint); as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures at low and high input.

Does the Lochinvar SYNC need a BACnet heartbeat or have a communication timeout?

If BAS-written temperatures or commands stop arriving, the unit reverts to its own readings and controls. The timeout is set under Main > Setup > BMS > Modbus / BACnet Timeout; the manual gives 5-120 s with a 10 s default in one place and 0-120 s in another. Every write resets it, and Lochinvar recommends the shortest value. Commands without temperatures must be refreshed at least every 4 minutes.

Can the BMS supply sensor values to the Lochinvar SYNC?

Set the AV 0 bits for the values the BAS will supply, then write them to the analog values: AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature. Values are in °C. Temperatures must be rewritten every few seconds or the unit returns to its own sensors.

How do I check these points on the real SYNC?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: Modbus and BACnet Communication Instructions (SYNC 1.0 - 1.3 - 1.5) · SYNC-MODB_100161723_2000017706 · rev. Rev L, 05/17. Object names, instances and units are reproduced as published; descriptions are our own.