Commercial water heater controller · BACnet points list

Lochinvar Regent BACnet points list

Updated 28 October 2026

Short answer

The Regent water heater shares the Crest communication manual but has its own BACnet MS/TP object map. It covers DHW thermostat and setpoint commands, safety switch and relay states, temperatures, flow rate, combustion values and status codes.

This page lists 63 BACnet objects for the Lochinvar Regent — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Regent
Equipment
Commercial water heater controller
Equipment type
Boilers & water heaters
BACnet objects
63 (7 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
680000 + MAC address (base can be changed)
Also known as
Regent IWH, IWH500-1000
Source document
Modbus and BACnet Communication Instructions (Crest FB/OF751-6001, FCB1000-6000 & Regent IWH500-1000) · 100161012_2000020084 · rev. Rev X, 04/26
Download CSV 63 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lochinvar Regent

Integration in brief

The Regent water heater uses the same Modbus/BACnet board and configuration approach as the Crest: write AV 0 Configuration to say which values the BAS supplies, then command the DHW thermostat and setpoint. Most integrations simply read status, temperatures and the status, blocking and lockout codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBitmask of BAS-supplied inputs; resend before commandsWrite
BV 4DHW ThermostatDHW call from the BASWrite
AV 3DHW SetpointDHW setpoint from the BASWrite
AI 13Unit Status CodeWhat the heater is doing; 40 = lockoutRead
AI 8Outlet TemperatureHeater outlet water temperature, °CRead
AI 11Firing RateBurner firing rate, %Read
AI 15Unit Lockout CodeLockout cause; valid only when status code is 40Read

Enable & remote start

Set the Demand Configuration under Main Menu > Setup > BMS. ENABLE active / BMS inactive: local setpoints plus an enable (BV 4, packed in AV 1). ENABLE and BMS active: enable plus the AV 2 setpoint command. Set the matching AV 0 bits first.

Heartbeat & communication loss

The Regent communication timer is fixed at 300 s; if communication stops longer than that the unit reverts to its own controls. When the BAS sends a setpoint command it must refresh it at least every 4 seconds or the unit reverts to its own inputs.

Sensors & values from the BMS

With the matching AV 0 bits set, the BAS can write AV 6 System Supply Temperature and AV 7 Building Recirculation Temperature (°C).

Network setup

Watch out for

Lochinvar Regent BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

63 of 63 shown
Type
Access
Show
Lochinvar Regent BACnet Points List
DescriptionStates
BVmin4DHW ThermostatTank / DHW thermostat callWrite
BI0Hex Door Temperature Switch / MRHLSafety / proving switch statusRead
BI1Flow SwitchSafety / proving switch statusRead
BI2Gas Pressure Switch 1Safety / proving switch statusRead
BI4Proof of ClosureSafety / proving switch statusRead
BI5Blocked Drain SwitchSafety / proving switch statusRead
BI7Flame 1Flame statusRead
BI10Blocked Vent SwitchSafety / proving switch statusRead
BI18Gas Pressure Switch 2Safety / proving switch statusRead
BI20Flue Damper SwitchSafety / proving switch statusRead
BI22Flame 2Flame statusRead
BI29DHW ThermostatTank / DHW thermostat callRead
BI32Run Time ContactsOutput or relay statusRead
BI33Alarm ContactsOutput or relay statusRead
BI34Internal Circulation PumpOutput or relay statusRead
BI35Cascade Isolation ValveOutput or relay statusRead
BI37Gas ValveOutput or relay statusRead
BI40Building Recirculation PumpOutput or relay statusRead
BI43Flue Damper OutputOutput or relay statusRead
BI48Main FanOutput or relay statusRead
BI50External Spark / HSIOutput or relay statusRead
BI51Air Valve TriggerOutput or relay statusRead
BI52Air Proving SwitchSafety / proving switch statusRead
AI0Binary Inputs 0-15Packed word of binary inputs 0-15Read
AI1Binary Inputs 16-31Packed word of binary inputs 16-31Read
AI2Binary Inputs 32-47Packed word of binary inputs 32-47Read
AI3System / Cascade SetpointSetpoint value°CRead
AI4System Pump SpeedPump speed output%Read
AI5Cascade Total PowerTotal cascade firing capacity%Read
AI6Cascade Current PowerCurrent cascade firing rate%Read
AI7Outlet SetpointSetpoint value°CRead
AImin8Outlet TemperatureTemperature reading°CRead
AI9Inlet TemperatureTemperature reading°CRead
AI10Flue TemperatureTemperature reading°CRead
AImin11Firing RateBurner firing rate%Read
AImin13Unit Status CodeCurrent operating status codeRead
AI14Unit Blocking CodeActive blocking (soft lockout) codeRead
AImin15Unit Lockout CodeActive lockout codeRead
AI18Air Damper Target AngleCombustion / flow valueRead
AI19Gas Damper Target AngleCombustion / flow valueRead
AI20Fan Speed TargetCombustion / flow valueRead
AI22O2 Sensor StatusCombustion / flow valueRead
AI23Current Trim FactorCombustion / flow valueRead
AI24BarometerCombustion / flow valueRead
AI25Binary Inputs 48-63Packed word of binary inputs 48-63Read
AI26Lock-Out Error LeaderLockout flag for this cascade unitRead
AI27Lock-Out Error Member 1Lockout flag for this cascade unitRead
AI28Lock-Out Error Member 2Lockout flag for this cascade unitRead
AI29Lock-Out Error Member 3Lockout flag for this cascade unitRead
AI30Lock-Out Error Member 4Lockout flag for this cascade unitRead
AI31Lock-Out Error Member 5Lockout flag for this cascade unitRead
AI32Lock-Out Error Member 6Lockout flag for this cascade unitRead
AI33Lock-Out Error Member 7Lockout flag for this cascade unitRead
AI35Flame 1Flame statusRead
AI36Flame 2Flame statusRead
AI37Corrected O2 ReadingCombustion / flow valueRead
AI38Flow RateCombustion / flow valueRead
AVmin0ConfigurationBitmask selecting which values the BAS suppliesWrite
AV1CoilsPacked word of the binary value commandsWrite
AV20-10 Volt Input / Setpoint CommandBAS rate or setpoint command (0-100%)%Write
AVmin3DHW SetpointSetpoint value°CWrite
AV6System Supply TemperatureTemperature reading°CWrite
AV7Building Recirculation TemperatureTemperature reading°CWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Regent and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Regent

How many BACnet points does the Lochinvar Regent have?

This list has 63 BACnet objects: 34 analog inputs, 6 analog values, 22 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Regent BACnet points are writable?

7 of the 63 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lochinvar Regent BACnet documentation?

The source is Modbus and BACnet Communication Instructions (Crest FB/OF751-6001, FCB1000-6000 & Regent IWH500-1000) (100161012_2000020084), revision Rev X, 04/26, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/MODB_100161012_2000020084_REV%20X_(71343).pdf.

What are the minimum BACnet points to integrate the Lochinvar Regent?

Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); BV 4 DHW Thermostat (DHW call from the BAS); AV 3 DHW Setpoint (DHW setpoint from the BAS); AI 13 Unit Status Code (What the heater is doing; 40 = lockout); AI 8 Outlet Temperature (Heater outlet water temperature, °C); AI 11 Firing Rate (Burner firing rate, %); AI 15 Unit Lockout Code (Lockout cause; valid only when status code is 40).

How do I enable BMS control of the Lochinvar Regent?

Set the Demand Configuration under Main Menu > Setup > BMS. ENABLE active / BMS inactive: local setpoints plus an enable (BV 4, packed in AV 1). ENABLE and BMS active: enable plus the AV 2 setpoint command. Set the matching AV 0 bits first.

Does the Lochinvar Regent need a BACnet heartbeat or have a communication timeout?

The Regent communication timer is fixed at 300 s; if communication stops longer than that the unit reverts to its own controls. When the BAS sends a setpoint command it must refresh it at least every 4 seconds or the unit reverts to its own inputs.

Can the BMS supply sensor values to the Lochinvar Regent?

With the matching AV 0 bits set, the BAS can write AV 6 System Supply Temperature and AV 7 Building Recirculation Temperature (°C).

How do I check these points on the real Regent?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: Modbus and BACnet Communication Instructions (Crest FB/OF751-6001, FCB1000-6000 & Regent IWH500-1000) · 100161012_2000020084 · rev. Rev X, 04/26. Object names, instances and units are reproduced as published; descriptions are our own.