Commercial condensing water heater controller · BACnet points list

Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) BACnet points list

Updated 28 October 2026

Short answer

The large Armor water heaters (1250-4000 MBH) talk BACnet MS/TP through Lochinvar's add-on Modbus/BACnet communication board. The fixed object map has two writable binary values (enable and tank thermostat), safety-switch and output status inputs, temperatures, firing rate, status/blocking/lockout codes, cascade totals, and analog values the BAS writes for configuration, rate or setpoint, tank setpoint and tank temperature.

This page lists 44 BACnet objects for the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Armor 1250-4000 water heater (SMART SYSTEM)
Equipment
Commercial condensing water heater controller
Equipment type
Boilers & water heaters
BACnet objects
44 (7 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
640000 + MAC address
Also known as
Armor, Armor 1250, Armor 4000, AWH, Armor Series 100, Armor Series 101, SMART SYSTEM, MTR-01, 100305786
Source document
Modbus and BACnet Communication Instructions, Armor Models 1250-4000, Series 100 & 101 · 100305786_2000558371 Rev C · rev. 2022-09
Download CSV 44 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)

Integration in brief

Set parameter H5 ModBus to Active on the SMART SYSTEM control, then write AV 0 Configuration so the heater knows which values the BAS will supply. After that the BAS sends an enable (BV 0 / AV 1), a rate or setpoint command (AV 2), or both, and keeps rewriting them. Status, temperatures and the status, blocking and lockout codes can be read without taking control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBitmask of BAS-supplied inputs; resend before commandsWrite
AV 1CoilsEnable command: 1 = enable, 0 = disableWrite
AV 20-10 Volt Input / Rate Command / Setpoint CommandRate command: firing % or setpoint, per BMS TypeWrite
AI 13Status CodeWhat the heater is doing; 40 = lockoutRead
AI 8Outlet TemperatureOutlet water temperature, °CRead
AI 11Firing RateBurner firing rate, %Read
AI 15Lockout CodeLockout cause; valid only when status code is 40Read

Enable & remote start

Set H5 ModBus = Active. Enable only (local setpoints): AV 0 = 0x0001 and AV 1 Coils = 1 (0 disables). Enable plus rate: AV 0 = 0x0005, AV 1 = 1 and AV 2 = modulation % or setpoint. Rate only: AV 0 = 0x0004 and AV 2. AV 2 is a firing % or a setpoint depending on the BMS Type setting; as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures set for the low and high analog input.

Heartbeat & communication loss

BAS-written tank temperature and the 0-10 V/rate value must be refreshed every few seconds; parameter H6 ModBus Time sets the timeout (the manual gives 5-120 s with a 10 s default in one place and 1-255 s in another). Other commands such as the enable have a fixed 4-minute timeout. When either timer runs out the heater goes back to its local inputs.

Sensors & values from the BMS

Set the AV 0 bits for the values the BAS will supply, then write AV 3 tank setpoint and/or AV 4 tank temperature (°C). The tank temperature must be rewritten every few seconds or the heater returns to its own sensor.

Network setup

Watch out for

Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

44 of 44 shown
Type
Access
Show
Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) BACnet Points List
DescriptionStates
BV0EnableBAS enable command (also packed in AV 1)Write
BV4Tank ThermostatBAS tank thermostat callWrite
BI0Manual Reset High LimitManual reset high limit inputRead
BI1Flow SwitchFlow switch inputRead
BI2Gas Pressure SwitchGas pressure switch inputRead
BI3Louver Proving SwitchLouver proving switch inputRead
BI5Blocked Drain SwitchBlocked drain switch inputRead
BI6Auto Reset High LimitAuto reset high limit inputRead
BI7FlameFlame detectedRead
BI8EnableEnable input statusRead
BI9Tank ThermostatTank thermostat input statusRead
BI32Run Time ContactsRun-time contacts closedRead
BI33Alarm ContactsAlarm contacts closedRead
BI35DHW PumpDHW pump outputRead
BI37Gas ValveGas valve outputRead
BI38Recirculation PumpRecirculation pump outputRead
BI48Power FanBlower (fan) power outputRead
AI0Binary Inputs 0-15Packed copy of binary inputs 0-15Read
AI1Binary Inputs 16-31Packed copy of binary inputs 16-31Read
AI2Binary Inputs 32-47Packed copy of binary inputs 32-47Read
AI3System / Cascade SetpointActive system or cascade setpoint°CRead
AI5Cascade Total PowerTotal cascade capacity, 100-800 %%Read
AI6Cascade Current PowerCascade firing rate now, 0-800 %%Read
AImin8Outlet TemperatureOutlet water temperature°CRead
AI9Inlet TemperatureInlet water temperature°CRead
AI10Flue TemperatureFlue gas temperature°CRead
AImin11Firing RateBurner firing rate%Read
AImin13Status CodeAppliance status code; 40 = lockoutRead
AI14Blocking CodeBlocking reason code; 0 = noneRead
AImin15Lockout CodeLockout cause; valid when status code is 40Read
AI25Binary Inputs 48-63Packed copy of binary inputs 48-63Read
AI26Lock-Out Error LeaderCascade leader lockout flag (0-1)Read
AI27Lock-Out Error Member 1Cascade member 1 lockout flag (0-1)Read
AI28Lock-Out Error Member 2Cascade member 2 lockout flag (0-1)Read
AI29Lock-Out Error Member 3Cascade member 3 lockout flag (0-1)Read
AI30Lock-Out Error Member 4Cascade member 4 lockout flag (0-1)Read
AI31Lock-Out Error Member 5Cascade member 5 lockout flag (0-1)Read
AI32Lock-Out Error Member 6Cascade member 6 lockout flag (0-1)Read
AI33Lock-Out Error Member 7Cascade member 7 lockout flag (0-1)Read
AVmin0ConfigurationBitmask of values the BAS will supplyWriteBit 0 Enable, bit 1 Tank Thermostat, bit 2 Rate/0-10 V/Setpoint Command, bit 3 Tank Setpoint, bit 6 Tank Temperature
AVmin1CoilsPacked BAS commands (enable, tank thermostat)Write
AVmin20-10 Volt Input / Rate Command / Setpoint CommandRate (modulation %) or setpoint command, per BMS Type%Write
AV3Tank SetpointTank setpoint from the BAS, 0-87.5 °C°CWrite
AV4Tank TemperatureTank temperature from the BAS°CWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Armor 1250-4000 water heater (SMART SYSTEM) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)

How many BACnet points does the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) have?

This list has 44 BACnet objects: 22 analog inputs, 5 analog values, 15 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) BACnet points are writable?

7 of the 44 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) BACnet documentation?

The source is Modbus and BACnet Communication Instructions, Armor Models 1250-4000, Series 100 & 101 (100305786_2000558371 Rev C), revision 2022-09, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/100305786_2000558371_Rev%20C_AWH%20Modbus%20Bacnet%20Manual%20(52880).pdf.

What are the minimum BACnet points to integrate the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)?

Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); AV 1 Coils (Enable command: 1 = enable, 0 = disable); AV 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate command: firing % or setpoint, per BMS Type); AI 13 Status Code (What the heater is doing; 40 = lockout); AI 8 Outlet Temperature (Outlet water temperature, °C); AI 11 Firing Rate (Burner firing rate, %); AI 15 Lockout Code (Lockout cause; valid only when status code is 40).

How do I enable BMS control of the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)?

Set H5 ModBus = Active. Enable only (local setpoints): AV 0 = 0x0001 and AV 1 Coils = 1 (0 disables). Enable plus rate: AV 0 = 0x0005, AV 1 = 1 and AV 2 = modulation % or setpoint. Rate only: AV 0 = 0x0004 and AV 2. AV 2 is a firing % or a setpoint depending on the BMS Type setting; as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures set for the low and high analog input.

Does the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM) need a BACnet heartbeat or have a communication timeout?

BAS-written tank temperature and the 0-10 V/rate value must be refreshed every few seconds; parameter H6 ModBus Time sets the timeout (the manual gives 5-120 s with a 10 s default in one place and 1-255 s in another). Other commands such as the enable have a fixed 4-minute timeout. When either timer runs out the heater goes back to its local inputs.

Can the BMS supply sensor values to the Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)?

Set the AV 0 bits for the values the BAS will supply, then write AV 3 tank setpoint and/or AV 4 tank temperature (°C). The tank temperature must be rewritten every few seconds or the heater returns to its own sensor.

How do I check these points on the real Armor 1250-4000 water heater (SMART SYSTEM)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: Modbus and BACnet Communication Instructions, Armor Models 1250-4000, Series 100 & 101 · 100305786_2000558371 Rev C · rev. 2022-09. Object names, instances and units are reproduced as published; descriptions are our own.