Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) BACnet points list

Updated 6 November 2026

Short answer

Lochinvar's ProtoNode FPC-N54 start-up guide maps the larger Power Fin boilers (2.5-5.0) to 55 BACnet objects (Appendix C.7). Two BVs take the enable and tank demands, BIs give safety switch, flame, pump, valve and fan states, AIs give temperatures, firing rate, pump speed, status/blocking/lockout codes and the lockout codes of up to 7 cascade members, and eight AVs take the Modbus board command and BMS-supplied sensor values.

This page lists 55 BACnet objects for the Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Power Fin 2.5-5.0 (ProtoNode FPC-N54)
Equipment
Commercial boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
55 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Power Fin 2.5-5.0, Power-Fin 2500-5000, PBN/PFN 2.5-5.0, Lochinvar Power Fin, ProtoNode FPC-N54
Source document
ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.7 Power Fin 2.5-5.0 · Document Revision 5.A (Lochinvar 2000594856 Rev A) · rev. 2020-06 (effective date)
Download CSV 55 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.

BMS integration notes: Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)

Integration in brief

Enable the boiler with BV 1 (Boiler Enable/Room Thermostat 1/Stg 1) and, for DHW, BV 2; send a rate or setpoint on AV 50. Read boiler 1 status, outlet temperature, firing rate, flame, alarm contacts and the lockout codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Boiler Enable/Room Thermostat 1/Stg 1Boiler enable / stage 1 demand from the BMSWrite
BV 2Tank Thermostat CmdTank (DHW) demand from the BMSWrite
AV 500-10 Volt Input/Rate Cmd/SP CmdRate or setpoint command from the BMSWrite
AV 48ConfigurationConfiguration register; see the Modbus manualWrite
AI 36Boiler 1 Status CodeWhat boiler 1 is doingRead
AI 31Outlet Temperature 1Boiler 1 outlet water temperatureRead
AI 34Firing Rate 1Boiler 1 firing rateRead
BI 8Flame 1Flame present on burner 1Read
BI 14Alarm Contacts 1Alarm contacts closedRead
AI 38Boiler 1 Lockout CodeBoiler 1 lockout codeRead

Enable & remote start

BV 1 Boiler Enable/Room Thermostat 1/Stg 1 and BV 2 Tank Thermostat Cmd are the demand commands; AV 48 Configuration, AV 49 Coils and AV 50 0-10 Volt Input/Rate Cmd/SP Cmd are the Modbus board command registers. The guide does not give the command sequence.

Sensors & values from the BMS

AV 52-55 (tank, outdoor, system supply and return temperature) are writable so the BMS can supply those values; the guide does not say when they are used.

Network setup

Watch out for

Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

55 of 55 shown
Type
Access
Show
Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) BACnet Points List
DescriptionStates
BVmin1Boiler Enable/Room Thermostat 1/Stg 1Write
BVmin2Tank Thermostat CmdWrite
BI3Manual Reset High Limit 1Read
BI4Flow Switch 1Read
BI5Gas Pressure Switch 1Read
BI6Louver Proving Switch 1Read
BI7Blocked Drain Switch 1Read
BImin8Flame 1Read
BI9Enable/Room Thermostat 1/Stg 1Read
BI10Tank ThermostatRead
BI11Stage 2/Air Pressure SwitchRead
BI12Air Pres Switch 2/Flap Vlv 2/Flue VlvRead
BI13Run-time ContactsRead
BImin14Alarm Contacts 1Read
BI15CH Pump 1Read
BI16DHW Pump 1Read
BI17Louver Relay 1Read
BI18Gas Vlv 1Read
BI19System PumpRead
BI20DHW Pump 2/Flue ValveRead
BI21Mains Fan 1Read
BI22External SparkRead
AI23Discrete Inputs 1 - 16Read
AI24Discrete Inputs 17 - 32Read
AI25Discrete Inputs 33 - 48Read
AI26System/Cascade SetpointRead
AI27System Pump SpeedRead
AI28Cascade Total PowerRead
AI29Cascade Current PowerRead
AI30Outlet Setpoint 1Read
AImin31Outlet Temperature 1Read
AI32Inlet Temperature 1Read
AI33Flue Temperature 1Read
AImin34Firing Rate 1Read
AI35Boiler 1 Pump SpeedRead
AImin36Boiler 1 Status CodeRead
AI37Boiler 1 Blocking CodeRead
AImin38Boiler 1 Lockout CodeRead
AI39Discrete Inputs 49-64Read
AI40Lockout Error LeaderRead
AI41Lockout Error Member 1Read
AI42Lockout Error Member 2Read
AI43Lockout Error Member 3Read
AI44Lockout Error Member 4Read
AI45Lockout Error Member 5Read
AI46Lockout Error Member 6Read
AI47Lockout Error Member 7Read
AVmin48ConfigurationWrite
AV49CoilsWrite
AVmin500-10 Volt Input/Rate Cmd/SP CmdWrite
AV51Tank SetpointWrite
AV52Tank TemperatureWrite
AV53Outdoor TemperatureWrite
AV54System Supply TemperatureWrite
AV55System Return TemperatureWrite
Object ID lookup: Lochinvar Power Fin 2.5-5.0 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Power Fin 2.5-5.0 (ProtoNode FPC-N54) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)

How many BACnet points does the Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) have?

This list has 55 BACnet objects: 25 analog inputs, 8 analog values, 20 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) BACnet points are writable?

10 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54) BACnet documentation?

The source is ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.7 Power Fin 2.5-5.0 (Document Revision 5.A (Lochinvar 2000594856 Rev A)), revision 2020-06 (effective date), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/161357100338377_2000594856_Rev%20A%20(ProtoNode%20FPC-N54%20Start-up%20Guide%20for%20Lochinvar).pdf.

What are the minimum BACnet points to integrate the Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)?

Start with BV 1 Boiler Enable/Room Thermostat 1/Stg 1 (Boiler enable / stage 1 demand from the BMS); BV 2 Tank Thermostat Cmd (Tank (DHW) demand from the BMS); AV 50 0-10 Volt Input/Rate Cmd/SP Cmd (Rate or setpoint command from the BMS); AV 48 Configuration (Configuration register; see the Modbus manual); AI 36 Boiler 1 Status Code (What boiler 1 is doing); AI 31 Outlet Temperature 1 (Boiler 1 outlet water temperature); AI 34 Firing Rate 1 (Boiler 1 firing rate); BI 8 Flame 1 (Flame present on burner 1); BI 14 Alarm Contacts 1 (Alarm contacts closed); AI 38 Boiler 1 Lockout Code (Boiler 1 lockout code).

How do I enable BMS control of the Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)?

BV 1 Boiler Enable/Room Thermostat 1/Stg 1 and BV 2 Tank Thermostat Cmd are the demand commands; AV 48 Configuration, AV 49 Coils and AV 50 0-10 Volt Input/Rate Cmd/SP Cmd are the Modbus board command registers. The guide does not give the command sequence.

Can the BMS supply sensor values to the Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)?

AV 52-55 (tank, outdoor, system supply and return temperature) are writable so the BMS can supply those values; the guide does not say when they are used.

How do I check these points on the real Power Fin 2.5-5.0 (ProtoNode FPC-N54)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.7 Power Fin 2.5-5.0 · Document Revision 5.A (Lochinvar 2000594856 Rev A) · rev. 2020-06 (effective date). Object names, instances and units are reproduced as published; descriptions are our own.