Commercial boiler / water heater controller · BACnet points list

Lochinvar Power-Fin (SMART SYSTEM) BACnet points list

Updated 4 November 2026

Short answer

Lochinvar's Power-fin talks BACnet MS/TP through an add-on Modbus/BACnet communication board. The object map is small and fixed: binary values for enable and tank thermostat commands, binary inputs for safety switches and relay states, analog inputs for temperatures, firing rate, cascade data and status, blocking and lockout codes, and analog values the BAS can write for setpoints and remote sensor values.

This page lists 51 BACnet objects for the Lochinvar Power-Fin (SMART SYSTEM) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Power-Fin (SMART SYSTEM)
Equipment
Commercial boiler / water heater controller
Equipment type
Boilers & water heaters
BACnet objects
51 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
640000 + MAC address (base is model dependent and can be changed)
Also known as
Power-fin, Powerfin, PBX-PFX-MODB, SMART SYSTEM
Source document
Modbus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 · PBX-PFX-MODB_100161633_2000016132 · rev. Rev D
Download CSV 51 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.

BMS integration notes: Lochinvar Power-Fin (SMART SYSTEM)

Integration in brief

Set parameter H5 ModBus to Active at the boiler, then write AV 0 Configuration so the unit knows which values the BAS will supply. After that the BAS sends an enable (BV 0, or the packed AV 1), a rate command (AV 2), or both, and keeps rewriting them. Status, temperatures and the status, blocking and lockout codes can be read without taking control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBitmask of BAS-supplied inputs; resend before commandsWrite
BV 0Boiler EnableEnable / call for heat from the BASWrite
AV 20-10 Volt Input / Rate Command / Setpoint CommandRate command: firing % or setpoint, per BMS TypeWrite
AI 13Boiler Status CodeWhat the boiler is doingRead
AI 8Outlet TemperatureBoiler outlet water temperature, °CRead
AI 11Firing RateBurner firing rate, %Read
AI 15Boiler Lockout CodeActive lockout codeRead

Enable & remote start

Set parameter H5 ModBus to Active. Then: enable only (local setpoints) = AV 0 0x0001 and AV 1 0x0001; enable plus rate = AV 0 0x0005, AV 1 0x0001 and AV 2 rate; rate alone = AV 0 0x0004 and AV 2. AV 2 means firing % or a temperature setpoint depending on the BMS Type setting; as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures at low and high input.

Heartbeat & communication loss

BAS-written system and tank temperatures must be refreshed within the timeout set in parameter H6 (5-120 s, default 10 s; another section of the manual gives 1-255 s); other commands must be refreshed at least every 4 minutes. If either timer expires the control reverts to its local inputs. Lochinvar recommends the shortest H6 setting.

Sensors & values from the BMS

Set the AV 0 bits for the values the BAS will supply, then write them: AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply and AV 7 system return temperature, all in °C. For remote DHW, AV 0 = 0x004A with AV 1 = 0x0008 (tank thermostat), AV 3 and AV 4.

Network setup

Watch out for

Lochinvar Power-Fin (SMART SYSTEM) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

51 of 51 shown
Type
Access
Show
Lochinvar Power-Fin (SMART SYSTEM) BACnet Points List
DescriptionStates
BVmin0Boiler EnableEnable command from the BASWrite0=Off, 1=On
BV4Tank ThermostatTank (DHW) thermostat callWrite0=Off, 1=On
BI0Manual Reset High LimitManual reset high limit statusRead0=Off, 1=On
BI1Flow SwitchFlow switch statusRead0=Off, 1=On
BI2Gas Pressure SwitchGas pressure switch statusRead0=Off, 1=On
BI3Louver Proving SwitchLouver proving switch statusRead0=Off, 1=On
BI4Air Pressure SwitchAir pressure switch statusRead0=Off, 1=On
BI5Blocked Drain SwitchBlocked drain switch statusRead0=Off, 1=On
BI6Auto Reset High LimitAuto reset high limit statusRead0=Off, 1=On
BI7Flame 1Flame detectedRead0=Off, 1=On
BI8EnableEnable input statusRead0=Off, 1=On
BI9Tank ThermostatTank (DHW) thermostat callRead0=Off, 1=On
BI32Run Time ContactsRun-time contacts (relay) statusRead0=Off, 1=On
BI33Alarm ContactsAlarm contacts (relay) statusRead0=Off, 1=On
BI34Boiler PumpBoiler pump output statusRead0=Off, 1=On
BI35DHW PumpDHW pump output statusRead0=Off, 1=On
BI37Gas ValveGas valve output statusRead0=Off, 1=On
BI38System PumpSystem pump output statusRead0=Off, 1=On
BI48Power FanBlower power statusRead0=Off, 1=On
BI50HSIHot surface igniter statusRead0=Off, 1=On
AI0Binary Inputs 0-15Packed word of binary inputs 0-15Read
AI1Binary Inputs 16-31Packed word of binary inputs 16-31Read
AI2Binary Inputs 32-47Packed word of binary inputs 32-47Read
AI3System / Cascade SetpointSystem or cascade setpoint in use°CRead
AI5Cascade Total PowerTotal cascade firing capacity%Read
AI6Cascade Current PowerCurrent cascade firing rate%Read
AI7Outlet SetpointOutlet setpoint in use°CRead
AImin8Outlet TemperatureOutlet water temperature°CRead
AI9Inlet TemperatureInlet water temperature°CRead
AI10Flue TemperatureFlue temperature°CRead
AImin11Firing RateBurner firing rate%Read
AImin13Boiler Status CodeCurrent operating status codeRead
AI14Boiler Blocking CodeActive blocking (soft lockout) codeRead
AImin15Boiler Lockout CodeActive lockout codeRead
AI25Binary Inputs 48-63Packed word of binary inputs 48-63Read
AI26Lock-Out Error LeaderLockout flag, cascade leaderRead
AI27Lock-Out Error Member 1Lockout flag, cascade member 1Read
AI28Lock-Out Error Member 2Lockout flag, cascade member 2Read
AI29Lock-Out Error Member 3Lockout flag, cascade member 3Read
AI30Lock-Out Error Member 4Lockout flag, cascade member 4Read
AI31Lock-Out Error Member 5Lockout flag, cascade member 5Read
AI32Lock-Out Error Member 6Lockout flag, cascade member 6Read
AI33Lock-Out Error Member 7Lockout flag, cascade member 7Read
AVmin0ConfigurationBitmask selecting which values the BAS suppliesWrite
AV1CoilsPacked word of the binary value commandsWrite
AVmin20-10 Volt Input / Rate Command / Setpoint CommandBAS rate or setpoint command (0-100%)%Write
AV3Tank SetpointTank setpoint from the BAS°CWrite
AV4Tank TemperatureTank temperature from the BAS°CWrite
AV5Outdoor TemperatureOutdoor temperature from the BAS°CWrite
AV6System Supply TemperatureSystem supply temperature from the BAS°CWrite
AV7System Return TemperatureSystem return temperature from the BAS°CWrite
Object ID lookup: Lochinvar Power-Fin point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Power-Fin (SMART SYSTEM) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Power-Fin (SMART SYSTEM)

How many BACnet points does the Lochinvar Power-Fin (SMART SYSTEM) have?

This list has 51 BACnet objects: 23 analog inputs, 8 analog values, 18 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Power-Fin (SMART SYSTEM) BACnet points are writable?

10 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lochinvar Power-Fin (SMART SYSTEM) BACnet documentation?

The source is Modbus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 (PBX-PFX-MODB_100161633_2000016132), revision Rev D, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/PBX-PFX-MODB_100161633_2000016132_REV%20D_BACNET(56304).pdf.

What are the minimum BACnet points to integrate the Lochinvar Power-Fin (SMART SYSTEM)?

Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); BV 0 Boiler Enable (Enable / call for heat from the BAS); AV 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate command: firing % or setpoint, per BMS Type); AI 13 Boiler Status Code (What the boiler is doing); AI 8 Outlet Temperature (Boiler outlet water temperature, °C); AI 11 Firing Rate (Burner firing rate, %); AI 15 Boiler Lockout Code (Active lockout code).

How do I enable BMS control of the Lochinvar Power-Fin (SMART SYSTEM)?

Set parameter H5 ModBus to Active. Then: enable only (local setpoints) = AV 0 0x0001 and AV 1 0x0001; enable plus rate = AV 0 0x0005, AV 1 0x0001 and AV 2 rate; rate alone = AV 0 0x0004 and AV 2. AV 2 means firing % or a temperature setpoint depending on the BMS Type setting; as a setpoint it is scaled like a 0-10 V signal between the BMS temperatures at low and high input.

Does the Lochinvar Power-Fin (SMART SYSTEM) need a BACnet heartbeat or have a communication timeout?

BAS-written system and tank temperatures must be refreshed within the timeout set in parameter H6 (5-120 s, default 10 s; another section of the manual gives 1-255 s); other commands must be refreshed at least every 4 minutes. If either timer expires the control reverts to its local inputs. Lochinvar recommends the shortest H6 setting.

Can the BMS supply sensor values to the Lochinvar Power-Fin (SMART SYSTEM)?

Set the AV 0 bits for the values the BAS will supply, then write them: AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply and AV 7 system return temperature, all in °C. For remote DHW, AV 0 = 0x004A with AV 1 = 0x0008 (tank thermostat), AV 3 and AV 4.

How do I check these points on the real Power-Fin (SMART SYSTEM)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: Modbus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 · PBX-PFX-MODB_100161633_2000016132 · rev. Rev D. Object names, instances and units are reproduced as published; descriptions are our own.