Commercial boiler controller gateway · BACnet points list

Lochinvar Knight FTXL (ProtoNode FPC-N54) BACnet points list

Updated 6 November 2026

Short answer

Lochinvar's ProtoNode FPC-N54 start-up guide maps the Knight FTXL boiler's Modbus registers to 46 BACnet objects (Appendix C.6). Four BVs carry room and tank thermostat demands, BIs give safety switch, flame, pump and relay states, AIs give temperatures, firing rate, pump speeds and the status, blocking and lockout codes, and eight AVs take the Modbus board command and BMS-supplied sensor values.

This page lists 46 BACnet objects for the Lochinvar Knight FTXL (ProtoNode FPC-N54) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Knight FTXL (ProtoNode FPC-N54)
Equipment
Commercial boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
46 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Knight FTXL, FTXL, Lochinvar FTXL, ProtoNode FPC-N54
Source document
ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.6 Knight FTXL · Document Revision 5.A (Lochinvar 2000594856 Rev A) · rev. 2020-06 (effective date)
Download CSV 46 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.

BMS integration notes: Lochinvar Knight FTXL (ProtoNode FPC-N54)

Integration in brief

Call for heat with the Room Thermostat 1 BV (and Tank Thermostat for DHW), or use the 0-10 Volt Input/Rate Cmd/SP Cmd AV for a rate or setpoint. Read boiler status, outlet temperature, firing rate, flame, alarm contacts and the lockout code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Room Thermostat 1Heat demand (room thermostat 1) from the BMSWrite
BV 4Tank ThermostatTank (DHW) demand from the BMSWrite
AV 410-10 Volt Input/Rate Cmd/SP CmdRate or setpoint command from the BMSWrite
AV 39ConfigurationConfiguration register; see the Modbus manualWrite
AI 36Boiler Status CodeWhat the boiler is doingRead
AI 31Outlet TemperatureBoiler outlet water temperatureRead
AI 34Firing RateBurner firing rateRead
BI 11FlameFlame presentRead
BI 16Alarm ContactsAlarm contacts closedRead
AI 38Boiler Lockout CodeActive lockout codeRead

Enable & remote start

BV 1-3 (Room Thermostat 1-3) and BV 4 (Tank Thermostat) are the demand commands; AV 39 Configuration, AV 40 Coils and AV 41 0-10 Volt Input/Rate Cmd/SP Cmd are the Modbus board command registers. The guide does not give the command sequence.

Sensors & values from the BMS

AV 43-46 (tank, outdoor, system supply and return temperature) are writable so the BMS can supply those values; the guide does not say when they are used.

Network setup

Watch out for

Lochinvar Knight FTXL (ProtoNode FPC-N54) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

46 of 46 shown
Type
Access
Show
Lochinvar Knight FTXL (ProtoNode FPC-N54) BACnet Points List
DescriptionStates
BVmin1Room Thermostat 1Write
BV2Room Thermostat 2Write
BV3Room Thermostat 3Write
BVmin4Tank ThermostatWrite
BI5Flow SwitchRead
BI6Gas Pressure SwitchRead
BI7Louver Proving SwitchRead
BI8Air Pressure SwitchRead
BI9Blocked Drain SwitchRead
BI10Auto Reset High LimitRead
BImin11FlameRead
BI12Room Thermostat 1Read
BI13Tank ThermostatRead
BI14Room Thermostat 2Read
BI15Run-time ContactsRead
BImin16Alarm ContactsRead
BI17CH PumpRead
BI18DHW Pump 1Read
BI19Louver RelayRead
BI20Gas ValveRead
BI21System PumpRead
BI22DHW Pump 2Read
AI23Discrete Inputs 1 - 16Read
AI24Discrete Inputs 17 - 32Read
AI25Discrete Inputs 33 - 48Read
AI26System Cascade SetpointRead
AI27System Pump SpeedRead
AI28Cascade Total PowerRead
AI29Cascade Current PowerRead
AI30Outlet SetpointRead
AImin31Outlet TemperatureRead
AI32Inlet TemperatureRead
AI33Flue TemperatureRead
AImin34Firing RateRead
AI35Boiler Pump SpeedRead
AImin36Boiler Status CodeRead
AI37Boiler Blocking CodeRead
AImin38Boiler Lockout CodeRead
AVmin39ConfigurationWrite
AV40CoilsWrite
AVmin410-10 Volt Input/Rate Cmd/SP CmdWrite
AV42Tank SetpointWrite
AV43Tank TemperatureWrite
AV44Outdoor TemperatureWrite
AV45System Supply TemperatureWrite
AV46System Return TemperatureWrite
Object ID lookup: Lochinvar Knight FTXL point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Knight FTXL (ProtoNode FPC-N54) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Knight FTXL (ProtoNode FPC-N54)

How many BACnet points does the Lochinvar Knight FTXL (ProtoNode FPC-N54) have?

This list has 46 BACnet objects: 16 analog inputs, 8 analog values, 18 binary inputs, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Knight FTXL (ProtoNode FPC-N54) BACnet points are writable?

12 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Lochinvar Knight FTXL (ProtoNode FPC-N54) BACnet documentation?

The source is ProtoNode FPC-N54 Start-up Guide For Interfacing Lochinvar Products, Appendix C.6 Knight FTXL (Document Revision 5.A (Lochinvar 2000594856 Rev A)), revision 2020-06 (effective date), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/161357100338377_2000594856_Rev%20A%20(ProtoNode%20FPC-N54%20Start-up%20Guide%20for%20Lochinvar).pdf.

What are the minimum BACnet points to integrate the Lochinvar Knight FTXL (ProtoNode FPC-N54)?

Start with BV 1 Room Thermostat 1 (Heat demand (room thermostat 1) from the BMS); BV 4 Tank Thermostat (Tank (DHW) demand from the BMS); AV 41 0-10 Volt Input/Rate Cmd/SP Cmd (Rate or setpoint command from the BMS); AV 39 Configuration (Configuration register; see the Modbus manual); AI 36 Boiler Status Code (What the boiler is doing); AI 31 Outlet Temperature (Boiler outlet water temperature); AI 34 Firing Rate (Burner firing rate); BI 11 Flame (Flame present); BI 16 Alarm Contacts (Alarm contacts closed); AI 38 Boiler Lockout Code (Active lockout code).

How do I enable BMS control of the Lochinvar Knight FTXL (ProtoNode FPC-N54)?

BV 1-3 (Room Thermostat 1-3) and BV 4 (Tank Thermostat) are the demand commands; AV 39 Configuration, AV 40 Coils and AV 41 0-10 Volt Input/Rate Cmd/SP Cmd are the Modbus board command registers. The guide does not give the command sequence.

Can the BMS supply sensor values to the Lochinvar Knight FTXL (ProtoNode FPC-N54)?

AV 43-46 (tank, outdoor, system supply and return temperature) are writable so the BMS can supply those values; the guide does not say when they are used.

How do I check these points on the real Knight FTXL (ProtoNode FPC-N54)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.