Electric boiler controller · BACnet points list

Lochinvar Lectrus electric boiler (KEB) BACnet points list

Updated 4 November 2026

Short answer

The Lectrus electric boiler uses the same Lochinvar Modbus/BACnet communication board and object scheme as the SMART TOUCH gas units, with its own names in an 'Electric Object Name' column. Binary values take the boiler and DHW enable commands, binary inputs give flow, pressure, LWCO and limit status plus relay and pump states, analog inputs give setpoints, temperatures, modulation and status codes, and analog values take the BAS configuration bits, rate command and remote temperatures.

This page lists 39 BACnet objects for the Lochinvar Lectrus electric boiler (KEB) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.

Manufacturer
Lochinvar
Model
Lectrus electric boiler (KEB)
Equipment
Electric boiler controller
Equipment type
Boilers & water heaters
BACnet objects
39 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
600000 + MAC address (base is model dependent and can be changed)
Also known as
Lectrus, KEB, KEB0015, KEB0150, MODB-I-O-KEB, Lochinvar electric boiler
Source document
Modbus and BACnet Communication Instructions - Models KEB 0015-0150 · 100389961_2000844370 · rev. Rev A
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.

BMS integration notes: Lochinvar Lectrus electric boiler (KEB)

Integration in brief

At the control (installer code 5309, Control Modes) set BMS / ModBus-BACnet to Active, then write AV 0 Configuration so the boiler knows which values the BAS will supply. The BAS then sends the enable (BV 0, or the packed AV 1), a rate command (AV 2), or both, and keeps rewriting them. Status, temperatures and codes can be read without taking control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0ConfigurationBitmask of BAS-supplied inputs; resend before commandsWrite
BV 0Boiler EnableEnable / call for heat from the BASWrite
AV 20-10V BMS InputRate command: modulation % or setpoint, per BMS TypeWrite
AI 13Boiler Status CodeWhat the boiler is doingRead
AI 8Outlet TemperatureBoiler outlet water temperature, °CRead
AI 11Modulation RateHeating modulation rate, %Read
AI 15Boiler Lockout CodeActive lockout codeRead

Enable & remote start

Control Mode 1: local setpoints plus BAS enable (AV 0 = 0x0001, AV 1 = 0x0001). Control Mode 2: enable plus AV 2 rate command; BMS Type sets whether AV 2 is modulation % (POWER) or a temperature setpoint (SETPOINT, default). Set BMS to ACTIVE in Control Modes for rate control.

Heartbeat & communication loss

The Modbus T/O timer (installer code 5309, Control Modes, Modbus T/O; 5-120 s, default 10 s) is reset by every write with new temperatures or commands; if it runs out the boiler reverts to its own controls. Commands without temperatures must still be refreshed at least every 4 minutes. Lochinvar recommends the shortest timer setting.

Sensors & values from the BMS

Set the AV 0 bits for the values the BAS will supply, then write AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature or AV 7 DHW recirculation temperature, and keep refreshing them.

Network setup

Watch out for

Lochinvar Lectrus electric boiler (KEB) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

39 of 39 shown
Type
Access
Show
Lochinvar Lectrus electric boiler (KEB) BACnet Points List
DescriptionStates
BVmin0Boiler EnableEnable command from the BASWrite0=Off, 1=On
BV4DHW EnableDHW enable command / statusWrite0=Off, 1=On
BI1Flow SwitchFlow switch statusRead0=Off, 1=On
BI2Low Pressure SwitchLow pressure switch statusRead0=Off, 1=On
BI3External Low Water Cut OffExternal low water cutoff statusRead0=Off, 1=On
BI4LWCO/ MRHLLow water cutoff / manual reset high limit statusRead0=Off, 1=On
BI6Auto Reset High LimitAuto reset high limit statusRead0=Off, 1=On
BI8SH EnableSpace heating enable input statusRead0=Off, 1=On
BI9DHW EnableDHW enable command / statusRead0=Off, 1=On
BI32Run-time ContactsRun-time contacts (relay) statusRead0=Off, 1=On
BI33Alarm ContactsAlarm contacts (relay) statusRead0=Off, 1=On
BI34Boiler PumpBoiler pump output statusRead0=Off, 1=On
BI35DHW PumpDHW pump output statusRead0=Off, 1=On
BI36Low Water Cut Off EnableLow water cutoff enable statusRead0=Off, 1=On
BI37Safety Monitor RelaySafety monitor relay statusRead0=Off, 1=On
BI38System PumpSystem pump output statusRead0=Off, 1=On
AI0Discrete Inputs 0 - 15Packed word of binary inputs 0-15Read
AI1Discrete Inputs 16 - 31Packed word of binary inputs 16-31Read
AI2Discrete Inputs 32 - 47Packed word of binary inputs 32-47Read
AI3System / Cascade SetpointSystem or cascade setpoint in use°CRead
AI4System Pump SpeedSystem pump speed output%Read
AI5Cascade Total PowerTotal cascade firing capacity%Read
AI6Cascade Current PowerCurrent cascade firing rate%Read
AI7Outlet SetpointOutlet setpoint in use°CRead
AImin8Outlet TemperatureOutlet water temperature°CRead
AI9Inlet TemperatureInlet water temperature°CRead
AImin11Modulation RateHeating element modulation rate%Read
AI12Boiler Pump SpeedBoiler pump speed output%Read
AImin13Boiler Status CodeCurrent operating status codeRead
AI14Boiler Blocking CodeActive blocking (soft lockout) codeRead
AImin15Boiler Lockout CodeActive lockout codeRead
AVmin0ConfigurationBitmask selecting which values the BAS suppliesWrite
AV1BV 0-4Packed word of the binary value commandsWrite
AVmin20-10V BMS InputBAS rate or setpoint command (0-100%)%Write
AV3Tank SetpointTank setpoint from the BAS°CWrite
AV4Tank TemperatureTank temperature from the BAS°CWrite
AV5Outdoor TemperatureOutdoor temperature from the BAS°CWrite
AV6System Supply TemperatureSystem supply temperature from the BAS°CWrite
AV7DHW Recirc TemperatureDHW recirculation temperature from the BAS°CWrite
Object ID lookup: Lochinvar Lectrus electric boiler point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lectrus electric boiler (KEB) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lochinvar Lectrus electric boiler (KEB)

How many BACnet points does the Lochinvar Lectrus electric boiler (KEB) have?

This list has 39 BACnet objects: 15 analog inputs, 8 analog values, 14 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lochinvar Lectrus electric boiler (KEB) BACnet points are writable?

10 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lochinvar Lectrus electric boiler (KEB) BACnet documentation?

The source is Modbus and BACnet Communication Instructions - Models KEB 0015-0150 (100389961_2000844370), revision Rev A, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/MODB-I-O-KEB_100389961_2000844370_Rev_A_(63600).pdf.

What are the minimum BACnet points to integrate the Lochinvar Lectrus electric boiler (KEB)?

Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); BV 0 Boiler Enable (Enable / call for heat from the BAS); AV 2 0-10V BMS Input (Rate command: modulation % or setpoint, per BMS Type); AI 13 Boiler Status Code (What the boiler is doing); AI 8 Outlet Temperature (Boiler outlet water temperature, °C); AI 11 Modulation Rate (Heating modulation rate, %); AI 15 Boiler Lockout Code (Active lockout code).

How do I enable BMS control of the Lochinvar Lectrus electric boiler (KEB)?

Control Mode 1: local setpoints plus BAS enable (AV 0 = 0x0001, AV 1 = 0x0001). Control Mode 2: enable plus AV 2 rate command; BMS Type sets whether AV 2 is modulation % (POWER) or a temperature setpoint (SETPOINT, default). Set BMS to ACTIVE in Control Modes for rate control.

Does the Lochinvar Lectrus electric boiler (KEB) need a BACnet heartbeat or have a communication timeout?

The Modbus T/O timer (installer code 5309, Control Modes, Modbus T/O; 5-120 s, default 10 s) is reset by every write with new temperatures or commands; if it runs out the boiler reverts to its own controls. Commands without temperatures must still be refreshed at least every 4 minutes. Lochinvar recommends the shortest timer setting.

Can the BMS supply sensor values to the Lochinvar Lectrus electric boiler (KEB)?

Set the AV 0 bits for the values the BAS will supply, then write AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature or AV 7 DHW recirculation temperature, and keep refreshing them.

How do I check these points on the real Lectrus electric boiler (KEB)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lochinvar BACnet points lists

Source: Modbus and BACnet Communication Instructions - Models KEB 0015-0150 · 100389961_2000844370 · rev. Rev A. Object names, instances and units are reproduced as published; descriptions are our own.