Electric boiler controller · BACnet points list
Lochinvar Lectrus electric boiler (KEB) BACnet points list
Updated 4 November 2026
The Lectrus electric boiler uses the same Lochinvar Modbus/BACnet communication board and object scheme as the SMART TOUCH gas units, with its own names in an 'Electric Object Name' column. Binary values take the boiler and DHW enable commands, binary inputs give flow, pressure, LWCO and limit status plus relay and pump states, analog inputs give setpoints, temperatures, modulation and status codes, and analog values take the BAS configuration bits, rate command and remote temperatures.
This page lists 39 BACnet objects for the Lochinvar Lectrus electric boiler (KEB) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lochinvar’s own free documentation, linked below.
- Manufacturer
- Lochinvar
- Model
- Lectrus electric boiler (KEB)
- Equipment
- Electric boiler controller
- Equipment type
- Boilers & water heaters
- BACnet objects
- 39 (10 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 600000 + MAC address (base is model dependent and can be changed)
- Also known as
- Lectrus, KEB, KEB0015, KEB0150, MODB-I-O-KEB, Lochinvar electric boiler
Reference only, provided as-is: verify against Lochinvar’s current documentation and the live device before use. Not official Lochinvar information. Terms of use.
BMS integration notes: Lochinvar Lectrus electric boiler (KEB)
At the control (installer code 5309, Control Modes) set BMS / ModBus-BACnet to Active, then write AV 0 Configuration so the boiler knows which values the BAS will supply. The BAS then sends the enable (BV 0, or the packed AV 1), a rate command (AV 2), or both, and keeps rewriting them. Status, temperatures and codes can be read without taking control.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Configuration | Bitmask of BAS-supplied inputs; resend before commands | Write |
| BV 0 | Boiler Enable | Enable / call for heat from the BAS | Write |
| AV 2 | 0-10V BMS Input | Rate command: modulation % or setpoint, per BMS Type | Write |
| AI 13 | Boiler Status Code | What the boiler is doing | Read |
| AI 8 | Outlet Temperature | Boiler outlet water temperature, °C | Read |
| AI 11 | Modulation Rate | Heating modulation rate, % | Read |
| AI 15 | Boiler Lockout Code | Active lockout code | Read |
Enable & remote start
Control Mode 1: local setpoints plus BAS enable (AV 0 = 0x0001, AV 1 = 0x0001). Control Mode 2: enable plus AV 2 rate command; BMS Type sets whether AV 2 is modulation % (POWER) or a temperature setpoint (SETPOINT, default). Set BMS to ACTIVE in Control Modes for rate control.
Heartbeat & communication loss
The Modbus T/O timer (installer code 5309, Control Modes, Modbus T/O; 5-120 s, default 10 s) is reset by every write with new temperatures or commands; if it runs out the boiler reverts to its own controls. Commands without temperatures must still be refreshed at least every 4 minutes. Lochinvar recommends the shortest timer setting.
Sensors & values from the BMS
Set the AV 0 bits for the values the BAS will supply, then write AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature or AV 7 DHW recirculation temperature, and keep refreshing them.
Network setup
- MAC address from dip switches 1-8 (master, so 0-127); baud from switches 9-10: 9600, 19200, 38400 or 76800.
- Device instance = base 600000 + MAC address; the base can be changed (0-4194048) and reset by powering up with dip switches 1-8 on.
- Default device name is "MTR-01 BACnet".
Watch out for
- The manual says to resend the AV 0 configuration bits before each command.
- In a cascade only the leader needs the board for control; it then reports cascade totals only.
- Without BMS mode active the board is monitor-only.
- The memory map is shared with gas models; ignore gas-only names when reading the PDF.
Lochinvar Lectrus electric boiler (KEB) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | Boiler Enable | Enable command from the BAS | Write | 0=Off, 1=On | |
| BV | 4 | DHW Enable | DHW enable command / status | Write | 0=Off, 1=On | |
| BI | 1 | Flow Switch | Flow switch status | Read | 0=Off, 1=On | |
| BI | 2 | Low Pressure Switch | Low pressure switch status | Read | 0=Off, 1=On | |
| BI | 3 | External Low Water Cut Off | External low water cutoff status | Read | 0=Off, 1=On | |
| BI | 4 | LWCO/ MRHL | Low water cutoff / manual reset high limit status | Read | 0=Off, 1=On | |
| BI | 6 | Auto Reset High Limit | Auto reset high limit status | Read | 0=Off, 1=On | |
| BI | 8 | SH Enable | Space heating enable input status | Read | 0=Off, 1=On | |
| BI | 9 | DHW Enable | DHW enable command / status | Read | 0=Off, 1=On | |
| BI | 32 | Run-time Contacts | Run-time contacts (relay) status | Read | 0=Off, 1=On | |
| BI | 33 | Alarm Contacts | Alarm contacts (relay) status | Read | 0=Off, 1=On | |
| BI | 34 | Boiler Pump | Boiler pump output status | Read | 0=Off, 1=On | |
| BI | 35 | DHW Pump | DHW pump output status | Read | 0=Off, 1=On | |
| BI | 36 | Low Water Cut Off Enable | Low water cutoff enable status | Read | 0=Off, 1=On | |
| BI | 37 | Safety Monitor Relay | Safety monitor relay status | Read | 0=Off, 1=On | |
| BI | 38 | System Pump | System pump output status | Read | 0=Off, 1=On | |
| AI | 0 | Discrete Inputs 0 - 15 | Packed word of binary inputs 0-15 | Read | ||
| AI | 1 | Discrete Inputs 16 - 31 | Packed word of binary inputs 16-31 | Read | ||
| AI | 2 | Discrete Inputs 32 - 47 | Packed word of binary inputs 32-47 | Read | ||
| AI | 3 | System / Cascade Setpoint | System or cascade setpoint in use | °C | Read | |
| AI | 4 | System Pump Speed | System pump speed output | % | Read | |
| AI | 5 | Cascade Total Power | Total cascade firing capacity | % | Read | |
| AI | 6 | Cascade Current Power | Current cascade firing rate | % | Read | |
| AI | 7 | Outlet Setpoint | Outlet setpoint in use | °C | Read | |
| AImin | 8 | Outlet Temperature | Outlet water temperature | °C | Read | |
| AI | 9 | Inlet Temperature | Inlet water temperature | °C | Read | |
| AImin | 11 | Modulation Rate | Heating element modulation rate | % | Read | |
| AI | 12 | Boiler Pump Speed | Boiler pump speed output | % | Read | |
| AImin | 13 | Boiler Status Code | Current operating status code | Read | ||
| AI | 14 | Boiler Blocking Code | Active blocking (soft lockout) code | Read | ||
| AImin | 15 | Boiler Lockout Code | Active lockout code | Read | ||
| AVmin | 0 | Configuration | Bitmask selecting which values the BAS supplies | Write | ||
| AV | 1 | BV 0-4 | Packed word of the binary value commands | Write | ||
| AVmin | 2 | 0-10V BMS Input | BAS rate or setpoint command (0-100%) | % | Write | |
| AV | 3 | Tank Setpoint | Tank setpoint from the BAS | °C | Write | |
| AV | 4 | Tank Temperature | Tank temperature from the BAS | °C | Write | |
| AV | 5 | Outdoor Temperature | Outdoor temperature from the BAS | °C | Write | |
| AV | 6 | System Supply Temperature | System supply temperature from the BAS | °C | Write | |
| AV | 7 | DHW Recirc Temperature | DHW recirculation temperature from the BAS | °C | Write |
No points match these filters.
Object ID lookup: Lochinvar Lectrus electric boiler point IDs by name
BV0Boiler EnableBV4DHW EnableBI1Flow SwitchBI2Low Pressure SwitchBI3External Low Water Cut OffBI4LWCO/ MRHLBI6Auto Reset High LimitBI8SH EnableBI9DHW EnableBI32Run-time ContactsBI33Alarm ContactsBI34Boiler PumpBI35DHW PumpBI36Low Water Cut Off EnableBI37Safety Monitor RelayBI38System PumpAI0Discrete Inputs 0 - 15AI1Discrete Inputs 16 - 31AI2Discrete Inputs 32 - 47AI3System / Cascade SetpointAI4System Pump SpeedAI5Cascade Total PowerAI6Cascade Current PowerAI7Outlet SetpointAI8Outlet TemperatureAI9Inlet TemperatureAI11Modulation RateAI12Boiler Pump SpeedAI13Boiler Status CodeAI14Boiler Blocking CodeAI15Boiler Lockout CodeAV0ConfigurationAV1BV 0-4AV20-10V BMS InputAV3Tank SetpointAV4Tank TemperatureAV5Outdoor TemperatureAV6System Supply TemperatureAV7DHW Recirc Temperature
Integration notes
- The manual prints one table for gas and electric units; this list uses the Electric Object Name column.
- Objects marked 'Not Used' for electric units are left out: BV 1, BV 2, BI 5, BI 43.
- AV 0 (Configuration) is a bitmask: bit 0 boiler enable, 1 DHW enable, 2 0-10V BMS input, 3 tank setpoint, 4 system supply, 5 outdoor, 6 tank temperature.
- Setpoints AI 3, AI 7 and AV 3 are printed with both °C and °F ranges; other temperatures are °C.
- Default device name is "MTR-01 BACnet".
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lectrus electric boiler (KEB) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lochinvar Lectrus electric boiler (KEB)
How many BACnet points does the Lochinvar Lectrus electric boiler (KEB) have?
This list has 39 BACnet objects: 15 analog inputs, 8 analog values, 14 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lochinvar Lectrus electric boiler (KEB) BACnet points are writable?
10 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Lochinvar Lectrus electric boiler (KEB) BACnet documentation?
The source is Modbus and BACnet Communication Instructions - Models KEB 0015-0150 (100389961_2000844370), revision Rev A, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/MODB-I-O-KEB_100389961_2000844370_Rev_A_(63600).pdf.
What are the minimum BACnet points to integrate the Lochinvar Lectrus electric boiler (KEB)?
Start with AV 0 Configuration (Bitmask of BAS-supplied inputs; resend before commands); BV 0 Boiler Enable (Enable / call for heat from the BAS); AV 2 0-10V BMS Input (Rate command: modulation % or setpoint, per BMS Type); AI 13 Boiler Status Code (What the boiler is doing); AI 8 Outlet Temperature (Boiler outlet water temperature, °C); AI 11 Modulation Rate (Heating modulation rate, %); AI 15 Boiler Lockout Code (Active lockout code).
How do I enable BMS control of the Lochinvar Lectrus electric boiler (KEB)?
Control Mode 1: local setpoints plus BAS enable (AV 0 = 0x0001, AV 1 = 0x0001). Control Mode 2: enable plus AV 2 rate command; BMS Type sets whether AV 2 is modulation % (POWER) or a temperature setpoint (SETPOINT, default). Set BMS to ACTIVE in Control Modes for rate control.
Does the Lochinvar Lectrus electric boiler (KEB) need a BACnet heartbeat or have a communication timeout?
The Modbus T/O timer (installer code 5309, Control Modes, Modbus T/O; 5-120 s, default 10 s) is reset by every write with new temperatures or commands; if it runs out the boiler reverts to its own controls. Commands without temperatures must still be refreshed at least every 4 minutes. Lochinvar recommends the shortest timer setting.
Can the BMS supply sensor values to the Lochinvar Lectrus electric boiler (KEB)?
Set the AV 0 bits for the values the BAS will supply, then write AV 3 tank setpoint, AV 4 tank temperature, AV 5 outdoor temperature, AV 6 system supply temperature or AV 7 DHW recirculation temperature, and keep refreshing them.
How do I check these points on the real Lectrus electric boiler (KEB)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lochinvar BACnet points lists
- Commercial condensing water heater controller
Lochinvar Armor 1250-4000 water heater (SMART SYSTEM)
Lochinvar Armor volume water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and the Modbus/BACnet communication board.
Also known as: Armor, Armor 1250, Armor 4000, AWH, Armor Series 100, Armor Series 101, SMART SYSTEM, MTR-01, 100305786 - Commercial boiler / water heater / pool heater controller
Lochinvar Copper-fin II / IIE (CFX, CHX, CPX)
Lochinvar Copper-fin II/IIE boilers and water heaters (models 402-2072) and pool heaters (502-2072) with the SMART SYSTEM control.
Also known as: Copper-fin, Copper-Fin II, Copper-fin IIE, CFX, CHX, CPX, C(F,H,P)X-MODB, CB 402-2072, CW 402-2072 - Condensing boiler controller
Lochinvar Crest
Crest FB/OF 751-6001 and FCB 1000-6000 condensing boilers (the manual uses the same map for Hellcat).
Also known as: Crest FB, Crest OF, Crest FCB, Hellcat - Heating appliance controller gateway (IPW)
Lochinvar IPW (ProtoNode FPC-N54)
Lochinvar IPW units, read through the ProtoNode FPC-N54 gateway (Appendix C.8).
Also known as: IPW, Lochinvar IPW, ProtoNode FPC-N54 - Condensing boiler / water heater controller
Lochinvar Knight / Armor (SMART TOUCH)
Knight, Knight XL, Armor, Wall Mount, Wall Hung, AQUAS, FTXL and Shield boilers and water heaters with the SMART TOUCH control.
Also known as: Knight XL, Outdoor Knight, Armor, Wall Mount, Wall Hung, AQUAS, FTXL, Shield, MODB-I-O - Commercial boiler controller gateway
Lochinvar Knight FTXL (ProtoNode FPC-N54)
Lochinvar Knight FTXL fire-tube boilers, read through the ProtoNode FPC-N54 gateway.
Also known as: Knight FTXL, FTXL, Lochinvar FTXL, ProtoNode FPC-N54 - Commercial boiler controller gateway
Lochinvar Power Fin 2.5-5.0 (ProtoNode FPC-N54)
Lochinvar Power Fin boilers in the 2.5-5.0 size range (the guide's "Powerfin_2.5_5.0" profile), read through the ProtoNode FPC-N54 gateway.
Also known as: Power Fin 2.5-5.0, Power-Fin 2500-5000, PBN/PFN 2.5-5.0, Lochinvar Power Fin, ProtoNode FPC-N54 - Commercial boiler / water heater controller
Lochinvar Power-Fin (SMART SYSTEM)
Lochinvar Power-fin models 502-1302 and 1501-2001, with the SMART SYSTEM control and the Modbus/BACnet communication board.
Also known as: Power-fin, Powerfin, PBX-PFX-MODB, SMART SYSTEM - Commercial water heater controller
Lochinvar Regent
Regent IWH 500-1000 commercial gas water heaters.
Also known as: Regent IWH, IWH500-1000 - Dual-heat-exchanger condensing boiler controller
Lochinvar SYNC
SYNC 1.0, 1.3 and 1.5 condensing boilers (two heat exchangers, reported as unit 1 and unit 2).
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC-MODB - Heat pump water heater plant controller
Lochinvar Veritus / Emerge_X heat pump water heater (ProtoNode FPC-N54)
Lochinvar Veritus and Emerge_X heat pump water heater systems (up to 64 units), read through the ProtoNode FPC-N54.
Also known as: Veritus, Emerge_X, Emerge X, Lochinvar Veritus, ProtoNode FPC-N54
Source: Modbus and BACnet Communication Instructions - Models KEB 0015-0150 · 100389961_2000844370 · rev. Rev A. Object names, instances and units are reproduced as published; descriptions are our own.