Power and energy meter · BACnet points list
Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39) BACnet points list
Updated 12 November 2026
The Acuvim II V3 meter serves 103 read-only Analog Inputs (real-time values, demand, energy, THD, AXM-IO3 analog inputs and AXM-IO pulse counters) and 44 Binary Inputs (AXM-IO digital inputs and 16 alarm channel status flags). Its object map differs from the AXM-BIP and AXM-WEB2 module lists for the older Acuvim II, for example the pulse counters sit on AI 76-103.
This page lists 147 BACnet objects for the Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- Acuvim II V3 power meter (native BACnet, firmware v6.39)
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 147 (0 writable)
- Transport
- —
- Firmware
- v6.39
- Also known as
- Acuvim II V3, Acuvim-II V3, Acuvim II V3 BACnet, Acuvim-II_BACnet-Obj-List
- Source document
- BACnet Points List Acuvim II V3 · rev. 2026-10-05
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39)
All objects are read-only measurements. Map total power, imported energy, demand, PF, current and voltage; I/O module and alarm channel objects only matter when they are set up.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 18 | P_rms | Total real power, kW | Read |
| AI 40 | Active_Energy_Imp | Imported energy, kWh | Read |
| AI 34 | P_dema | Real power demand, kW | Read |
| AI 30 | PF_rms | Total power factor | Read |
| AI 13 | Iavg_rms | Average current, A | Read |
| AI 5 | Uavg_rms | Average L-N voltage, V | Read |
| AI 1 | Freq_rms | Frequency, Hz | Read |
Watch out for
- AXM-IO objects (AI 72-103, BI 1-28) only read real values when the module is fitted.
Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Freq_rms | Frequency | Hz | Read | |
| AI | 2 | Ua_rms | Phase A Voltage | V | Read | |
| AI | 3 | Ub_rms | Phase B Voltage | V | Read | |
| AI | 4 | Uc_rms | Phase C Voltage | V | Read | |
| AImin | 5 | Uavg_rms | Average Phase Voltage | V | Read | |
| AI | 6 | Uab_rms | Line Voltage AB | V | Read | |
| AI | 7 | Ubc_rms | Line Voltage BC | V | Read | |
| AI | 8 | Uca_rms | Line Voltage CA | V | Read | |
| AI | 9 | Ulavg_rms | Average Line Voltage | V | Read | |
| AI | 10 | Ia_rms | Phase A Current | A | Read | |
| AI | 11 | Ib_rms | Phase B Current | A | Read | |
| AI | 12 | Ic_rms | Phase C Current | A | Read | |
| AImin | 13 | Iavg_rms | Average Current | A | Read | |
| AI | 14 | In_rms | Neutral Current | A | Read | |
| AI | 15 | Pa_rms | Phase A Active Power | kW | Read | |
| AI | 16 | Pb_rms | Phase B Active Power | kW | Read | |
| AI | 17 | Pc_rms | Phase C Active Power | kW | Read | |
| AImin | 18 | P_rms | Total Active Power | kW | Read | |
| AI | 19 | Qa_rms | Phase A Reactive Power | kvar | Read | |
| AI | 20 | Qb_rms | Phase B Reactive Power | kvar | Read | |
| AI | 21 | Qc_rms | Phase C Reactive Power | kvar | Read | |
| AI | 22 | Q_rms | Total Reactive Power | kvar | Read | |
| AI | 23 | Sa_rms | Phase A Apparent Power | kVA | Read | |
| AI | 24 | Sb_rms | Phase B Apparent Power | kVA | Read | |
| AI | 25 | Sc_rms | Phase C Apparent Power | kVA | Read | |
| AI | 26 | S_rms | Total Apparent Power | kVA | Read | |
| AI | 27 | PFa_rms | Phase A Power Factor | Read | ||
| AI | 28 | PFb_rms | Phase B Power Factor | Read | ||
| AI | 29 | PFc_rms | Phase C Power Factor | Read | ||
| AImin | 30 | PF_rms | Total Power Factor | Read | ||
| AI | 31 | U_unbl | Voltage Unbalance Factor | Read | ||
| AI | 32 | I_unbl | Current Unbalance Factor | Read | ||
| AI | 33 | Rlc_val | Load Type (82:Resistive load 76:Inductive load 67:Capacitive load) | Read | ||
| AImin | 34 | P_dema | Active Power Demand | kW | Read | |
| AI | 35 | Q_dema | Reactive Power Demand | kvar | Read | |
| AI | 36 | S_dema | Apparent Power Demand | kVA | Read | |
| AI | 37 | Ia_dema | Phase A Current Demand | A | Read | |
| AI | 38 | Ib_dema | Phase B Current Demand | A | Read | |
| AI | 39 | Ic_dema | Phase C Current Demand | A | Read | |
| AImin | 40 | Active_Energy_Imp | Import Active Energy | kWh | Read | |
| AI | 41 | Active_Energy_Exp | Export Active Energy | kWh | Read | |
| AI | 42 | Reactive_Energy_Imp | Import Reactive Energy | kvarh | Read | |
| AI | 43 | Reactive_Energy_Exp | Export Reactive Energy | kvarh | Read | |
| AI | 44 | Active_Energy_Total | Active Energy Total | kWh | Read | |
| AI | 45 | Active_Energy_Net | Active Energy Net | kWh | Read | |
| AI | 46 | Reactive_Energy_Total | Reactive Energy Total | kvarh | Read | |
| AI | 47 | Reactive_Energy_Net | Reactive Energy Net | kvarh | Read | |
| AI | 48 | Apparent_Energy | Apparent Energy | kVAh | Read | |
| AI | 49 | Active_Energy_Imp_A | Phase A Import Active Energy | kWh | Read | |
| AI | 50 | Active_Energy_Exp_A | Phase A Export Active Energy | kWh | Read | |
| AI | 51 | Active_Energy_Imp_B | Phase B Import Active Energy | kWh | Read | |
| AI | 52 | Active_Energy_Exp_B | Phase B Export Active Energy | kWh | Read | |
| AI | 53 | Active_Energy_Imp_C | Phase C Import Active Energy | kWh | Read | |
| AI | 54 | Active_Energy_Exp_C | Phase C Export Active Energy | kWh | Read | |
| AI | 55 | Reactive_Energy_Imp_A | Phase A Import Reactive Energy | kvarh | Read | |
| AI | 56 | Reactive_Energy_Exp_A | Phase A Export Reactive Energy | kvarh | Read | |
| AI | 57 | Reactive_Energy_Imp_B | Phase B Import Reactive Energy | kvarh | Read | |
| AI | 58 | Reactive_Energy_Exp_B | Phase B Export Reactive Energy | kvarh | Read | |
| AI | 59 | Reactive_Energy_Imp_C | Phase C Import Reactive Energy | kvarh | Read | |
| AI | 60 | Reactive_Energy_Exp_C | Phase C Export Reactive Energy | kvarh | Read | |
| AI | 61 | Apparent_Energy_A | Phase A Apparent Energy | kVAh | Read | |
| AI | 62 | Apparent_Energy_B | Phase B Apparent Energy | kVAh | Read | |
| AI | 63 | Apparent_Energy_C | Phase C Apparent Energy | kVAh | Read | |
| AI | 64 | V1_thd | Voltage 1 THD | V | Read | |
| AI | 65 | V2_thd | Voltage 2 THD | V | Read | |
| AI | 66 | V3_thd | Voltage 3 THD | V | Read | |
| AI | 67 | V_thd | Average Voltage THD | V | Read | |
| AI | 68 | I1_thd | Current 1 THD | A | Read | |
| AI | 69 | I2_thd | Current 2 THD | A | Read | |
| AI | 70 | I3_thd | Current 3 THD | A | Read | |
| AI | 71 | I_thd | Average Current THD | A | Read | |
| AI | 72 | IO31_ai1 | IO31 Analog Input 1 | Read | ||
| AI | 73 | IO31_ai2 | IO31 Analog Input 2 | Read | ||
| AI | 74 | IO32_ai1 | IO32 Analog Input 1 | Read | ||
| AI | 75 | IO32_ai2 | IO32 Analog Input 2 | Read | ||
| AI | 76 | IO11_pc1 | IO11 Pulse Counter 1 | Read | ||
| AI | 77 | IO11_pc2 | IO11 Pulse Counter 2 | Read | ||
| AI | 78 | IO11_pc3 | IO11 Pulse Counter 3 | Read | ||
| AI | 79 | IO11_pc4 | IO11 Pulse Counter 4 | Read | ||
| AI | 80 | IO11_pc5 | IO11 Pulse Counter 5 | Read | ||
| AI | 81 | IO11_pc6 | IO11 Pulse Counter 6 | Read | ||
| AI | 82 | IO21_pc1 | IO21 Pulse Counter 1 | Read | ||
| AI | 83 | IO21_pc2 | IO21 Pulse Counter 2 | Read | ||
| AI | 84 | IO21_pc3 | IO21 Pulse Counter 3 | Read | ||
| AI | 85 | IO21_pc4 | IO21 Pulse Counter 4 | Read | ||
| AI | 86 | IO31_pc1 | IO31 Pulse Counter 1 | Read | ||
| AI | 87 | IO31_pc2 | IO31 Pulse Counter 2 | Read | ||
| AI | 88 | IO31_pc3 | IO31 Pulse Counter 3 | Read | ||
| AI | 89 | IO31_pc4 | IO31 Pulse Counter 4 | Read | ||
| AI | 90 | IO12_pc1 | IO12 Pulse Counter 1 | Read | ||
| AI | 91 | IO12_pc2 | IO12 Pulse Counter 2 | Read | ||
| AI | 92 | IO12_pc3 | IO12 Pulse Counter 3 | Read | ||
| AI | 93 | IO12_pc4 | IO12 Pulse Counter 4 | Read | ||
| AI | 94 | IO12_pc5 | IO12 Pulse Counter 5 | Read | ||
| AI | 95 | IO12_pc6 | IO12 Pulse Counter 6 | Read | ||
| AI | 96 | IO22_pc1 | IO22 Pulse Counter 1 | Read | ||
| AI | 97 | IO22_pc2 | IO22 Pulse Counter 2 | Read | ||
| AI | 98 | IO22_pc3 | IO22 Pulse Counter 3 | Read | ||
| AI | 99 | IO22_pc4 | IO22 Pulse Counter 4 | Read | ||
| AI | 100 | IO32_pc1 | IO32 Pulse Counter 1 | Read | ||
| AI | 101 | IO32_pc2 | IO32 Pulse Counter 2 | Read | ||
| AI | 102 | IO32_pc3 | IO32 Pulse Counter 3 | Read | ||
| AI | 103 | IO32_pc4 | IO32 Pulse Counter 4 | Read | ||
| BI | 1 | IO11_di1 | IO11 Digital Input 1 | Read | ||
| BI | 2 | IO11_di2 | IO11 Digital Input 2 | Read | ||
| BI | 3 | IO11_di3 | IO11 Digital Input 3 | Read | ||
| BI | 4 | IO11_di4 | IO11 Digital Input 4 | Read | ||
| BI | 5 | IO11_di5 | IO11 Digital Input 5 | Read | ||
| BI | 6 | IO11_di6 | IO11 Digital Input 6 | Read | ||
| BI | 7 | IO21_di1 | IO21 Digital Input 1 | Read | ||
| BI | 8 | IO21_di2 | IO21 Digital Input 2 | Read | ||
| BI | 9 | IO21_di3 | IO21 Digital Input 3 | Read | ||
| BI | 10 | IO21_di4 | IO21 Digital Input 4 | Read | ||
| BI | 11 | IO31_di1 | IO31 Digital Input 1 | Read | ||
| BI | 12 | IO31_di2 | IO31 Digital Input 2 | Read | ||
| BI | 13 | IO31_di3 | IO31 Digital Input 3 | Read | ||
| BI | 14 | IO31_di4 | IO31 Digital Input 4 | Read | ||
| BI | 15 | IO12_di1 | IO12 Digital Input 1 | Read | ||
| BI | 16 | IO12_di2 | IO12 Digital Input 2 | Read | ||
| BI | 17 | IO12_di3 | IO12 Digital Input 3 | Read | ||
| BI | 18 | IO12_di4 | IO12 Digital Input 4 | Read | ||
| BI | 19 | IO12_di5 | IO12 Digital Input 5 | Read | ||
| BI | 20 | IO12_di6 | IO12 Digital Input 6 | Read | ||
| BI | 21 | IO22_di1 | IO22 Digital Input 1 | Read | ||
| BI | 22 | IO22_di2 | IO22 Digital Input 2 | Read | ||
| BI | 23 | IO22_di3 | IO22 Digital Input 3 | Read | ||
| BI | 24 | IO22_di4 | IO22 Digital Input 4 | Read | ||
| BI | 25 | IO32_di1 | IO32 Digital Input 1 | Read | ||
| BI | 26 | IO32_di2 | IO32 Digital Input 2 | Read | ||
| BI | 27 | IO32_di3 | IO32 Digital Input 3 | Read | ||
| BI | 28 | IO32_di4 | IO32 Digital Input 4 | Read | ||
| BI | 29 | AlarmStatus1 | Alarm Channel 1 Status | Read | ||
| BI | 30 | AlarmStatus2 | Alarm Channel 2 Status | Read | ||
| BI | 31 | AlarmStatus3 | Alarm Channel 3 Status | Read | ||
| BI | 32 | AlarmStatus4 | Alarm Channel 4 Status | Read | ||
| BI | 33 | AlarmStatus5 | Alarm Channel 5 Status | Read | ||
| BI | 34 | AlarmStatus6 | Alarm Channel 6 Status | Read | ||
| BI | 35 | AlarmStatus7 | Alarm Channel 7 Status | Read | ||
| BI | 36 | AlarmStatus8 | Alarm Channel 8 Status | Read | ||
| BI | 37 | AlarmStatus9 | Alarm Channel 9 Status | Read | ||
| BI | 38 | AlarmStatus10 | Alarm Channel 10 Status | Read | ||
| BI | 39 | AlarmStatus11 | Alarm Channel 11 Status | Read | ||
| BI | 40 | AlarmStatus12 | Alarm Channel 12 Status | Read | ||
| BI | 41 | AlarmStatus13 | Alarm Channel 13 Status | Read | ||
| BI | 42 | AlarmStatus14 | Alarm Channel 14 Status | Read | ||
| BI | 43 | AlarmStatus15 | Alarm Channel 15 Status | Read | ||
| BI | 44 | AlarmStatus16 | Alarm Channel 16 Status | Read |
No points match these filters.
Object ID lookup: Accuenergy Acuvim II V3 power meter point IDs by name
AI1Freq_rmsAI2Ua_rmsAI3Ub_rmsAI4Uc_rmsAI5Uavg_rmsAI6Uab_rmsAI7Ubc_rmsAI8Uca_rmsAI9Ulavg_rmsAI10Ia_rmsAI11Ib_rmsAI12Ic_rmsAI13Iavg_rmsAI14In_rmsAI15Pa_rmsAI16Pb_rmsAI17Pc_rmsAI18P_rmsAI19Qa_rmsAI20Qb_rmsAI21Qc_rmsAI22Q_rmsAI23Sa_rmsAI24Sb_rmsAI25Sc_rmsAI26S_rmsAI27PFa_rmsAI28PFb_rmsAI29PFc_rmsAI30PF_rmsAI31U_unblAI32I_unblAI33Rlc_valAI34P_demaAI35Q_demaAI36S_demaAI37Ia_demaAI38Ib_demaAI39Ic_demaAI40Active_Energy_ImpAI41Active_Energy_ExpAI42Reactive_Energy_ImpAI43Reactive_Energy_ExpAI44Active_Energy_TotalAI45Active_Energy_NetAI46Reactive_Energy_TotalAI47Reactive_Energy_NetAI48Apparent_EnergyAI49Active_Energy_Imp_AAI50Active_Energy_Exp_AAI51Active_Energy_Imp_BAI52Active_Energy_Exp_BAI53Active_Energy_Imp_CAI54Active_Energy_Exp_CAI55Reactive_Energy_Imp_AAI56Reactive_Energy_Exp_AAI57Reactive_Energy_Imp_BAI58Reactive_Energy_Exp_BAI59Reactive_Energy_Imp_CAI60Reactive_Energy_Exp_CAI61Apparent_Energy_AAI62Apparent_Energy_BAI63Apparent_Energy_CAI64V1_thdAI65V2_thdAI66V3_thdAI67V_thdAI68I1_thdAI69I2_thdAI70I3_thdAI71I_thdAI72IO31_ai1AI73IO31_ai2AI74IO32_ai1AI75IO32_ai2AI76IO11_pc1AI77IO11_pc2AI78IO11_pc3AI79IO11_pc4AI80IO11_pc5AI81IO11_pc6AI82IO21_pc1AI83IO21_pc2AI84IO21_pc3AI85IO21_pc4AI86IO31_pc1AI87IO31_pc2AI88IO31_pc3AI89IO31_pc4AI90IO12_pc1AI91IO12_pc2AI92IO12_pc3AI93IO12_pc4AI94IO12_pc5AI95IO12_pc6AI96IO22_pc1AI97IO22_pc2AI98IO22_pc3AI99IO22_pc4AI100IO32_pc1AI101IO32_pc2AI102IO32_pc3AI103IO32_pc4BI1IO11_di1BI2IO11_di2BI3IO11_di3BI4IO11_di4BI5IO11_di5BI6IO11_di6BI7IO21_di1BI8IO21_di2BI9IO21_di3BI10IO21_di4BI11IO31_di1BI12IO31_di2BI13IO31_di3BI14IO31_di4BI15IO12_di1BI16IO12_di2BI17IO12_di3BI18IO12_di4BI19IO12_di5BI20IO12_di6BI21IO22_di1BI22IO22_di2BI23IO22_di3BI24IO22_di4BI25IO32_di1BI26IO32_di2BI27IO32_di3BI28IO32_di4BI29AlarmStatus1BI30AlarmStatus2BI31AlarmStatus3BI32AlarmStatus4BI33AlarmStatus5BI34AlarmStatus6BI35AlarmStatus7BI36AlarmStatus8BI37AlarmStatus9BI38AlarmStatus10BI39AlarmStatus11BI40AlarmStatus12BI41AlarmStatus13BI42AlarmStatus14BI43AlarmStatus15BI44AlarmStatus16
Integration notes
- AI 72-103 and BI 1-28 carry data only when the matching AXM-IO module is fitted.
- AI 33 load type: 82 resistive, 76 inductive, 67 capacitive.
- THD objects AI 64-71 are listed with volts / amperes as units in the spreadsheet.
- The spreadsheet does not say which BACnet transport the V3 uses.
- Source: Accuenergy 'BACnet Points List Acuvim II V3' spreadsheet, firmware v6.39, generated 2026-10-05; alarm channel status BI 29-44 were added 2026-07-17.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acuvim II V3 power meter (native BACnet, firmware v6.39) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39)
How many BACnet points does the Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39) have?
This list has 147 BACnet objects: 103 analog inputs, 44 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39) BACnet documentation?
The source is BACnet Points List Acuvim II V3, revision 2026-10-05, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/Acuvim-II_BACnet-Obj-List.xlsx.
What are the minimum BACnet points to integrate the Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39)?
Start with AI 18 P_rms (Total real power, kW); AI 40 Active_Energy_Imp (Imported energy, kWh); AI 34 P_dema (Real power demand, kW); AI 30 PF_rms (Total power factor); AI 13 Iavg_rms (Average current, A); AI 5 Uavg_rms (Average L-N voltage, V); AI 1 Freq_rms (Frequency, Hz).
How do I check these points on the real Acuvim II V3 power meter (native BACnet, firmware v6.39)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet - Power and energy meter (communication module)
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Accuenergy AXM-WEB2 Ethernet / web module fitted to Acuvim II series meters, with optional IO11/12, IO21/22 and IO31/32 modules.
Also known as: AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
Source: BACnet Points List Acuvim II V3 · rev. 2026-10-05. Object names, instances and units are reproduced as published; descriptions are our own.