Short answer

The AcuRev 4100 meters up to 24 CT input channels plus 12 user-defined summing channels. Real-time, demand and power quality values are read-only Analog Inputs (1-721) and energy totals are Large Analog Values (1-360). Channel 1 of each channel group is printed in full; the other channels follow the same layout in the ranges given in the notes.

This page lists 175 BACnet objects for the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.

Manufacturer
Accuenergy
Model
AcuRev 4100 multi-circuit power meter (BACnet)
Equipment
Multi-circuit power and energy meter (submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
175 (0 writable)
Transport
—
Firmware
v1.03p06
Also known as
AcuRev 4100, AcuRev 4100 BACnet points list
Source document
BACnet Points List AcuRev4100 · rev. 2026-05-26
Download CSV 175 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.

BMS integration notes: Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)

Integration in brief

Everything is read-only. Map the system power, energy and demand objects first, then the channel 1 objects and the matching objects for the other channels using the per-channel offsets in the notes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 32Psys_rmsSystem real power, kWRead
LAV 28PsysImp_engSystem imported energy, kWhRead
AI 296PsysImp_demaSystem import kW demandRead
AI 36PFsys_rmsSystem power factorRead
AI 31Isys_rmsSystem average current, ARead
AI 2Ua_rmsPhase A voltage, VRead
AI 38Pchn1_rmsInput channel 1 real power, kWRead
LAV 37PChn1Imp_engInput channel 1 imported energy, kWhRead
AI 1Freq_rmsFrequency, HzRead

Watch out for

Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

175 of 175 shown
Type
AnalogOther
Show
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet Points List
DescriptionStates
AImin1Freq_rmsFrequencyHzRead
AImin2Ua_rmsPhase A VoltageVRead
AI3Ub_rmsPhase B VoltageVRead
AI4Uc_rmsPhase C VoltageVRead
AI5Uavg_rmsPhase Average VoltageVRead
AI6Uab_rmsLine Voltage ABVRead
AI7Ubc_rmsLine Voltage BCVRead
AI8Uca_rmsLine Voltage CAVRead
AI9Ulavg_rmsAverage Line VoltageVRead
AI10UaAng_rmsPhase A Voltage AngledegreesRead
AI11UbAng_rmsPhase B Voltage AngledegreesRead
AI12UcAng_rmsPhase C Voltage AngledegreesRead
AI13Ia_rmsPhase A CurrentARead
AI14Pa_rmsPhase A Active PowerkWRead
AI15Qa_rmsPhase A Reactive PowerkvarRead
AI16Sa_rmsPhase A Apparent PowerkVARead
AI17LNa_rmsPhase A Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load)Read
AI18PFa_rmsPhase A Power FactorPFRead
AI19Ib_rmsPhase B CurrentARead
AI20Pb_rmsPhase B Active PowerkWRead
AI21Qb_rmsPhase B Reactive PowerkvarRead
AI22Sb_rmsPhase B Apparent PowerkVARead
AI23LNb_rmsPhase B Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load)Read
AI24PFb_rmsPhase B Power FactorPFRead
AI25Ic_rmsPhase C CurrentARead
AI26Pc_rmsPhase C Active PowerkWRead
AI27Qc_rmsPhase C Reactive PowerkvarRead
AI28Sc_rmsPhase C Apparent PowerkVARead
AI29LNc_rmsPhase C Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load)Read
AI30PFc_rmsPhase C Power FactorPFRead
AImin31Isys_rmsSystem Average CurrentARead
AImin32Psys_rmsSystem Active PowerkWRead
AI33Qsys_rmsSystem Reactive PowerkvarRead
AI34Ssys_rmsSystem Apparent PowerkVARead
AI35LNsys_rmsSystem Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load)Read
AImin36PFsys_rmsSystem Power FactorPFRead
AI37Ichn1_rmsInput Channel 1 CurrentARead
AImin38Pchn1_rmsInput Channel 1 Active PowerkWRead
AI39Qchn1_rmsInput Channel 1 Reactive PowerkvarRead
AI40Schn1_rmsInput Channel 1 Apparent PowerkVARead
AI41LNchn1_rmsInput Channel 1 Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load)Read
AI42PFchn1_rmsInput Channel 1 Power FactorPFRead
AI43Angchn1_rmsInput Channel 1 Current Phase AngledegreesRead
AI205Iusr1_rmsUser Channel 1 CurrentARead
AI206Pusr1_rmsUser Channel 1 Active PowerkWRead
AI207Qusr1_rmsUser Channel 1 Reactive PowerkvarRead
AI208Susr1_rmsUser Channel 1 Apparent PowerkVARead
AI209LNusr1_rmsUser Channel 1 Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load)Read
AI210PFusr1_rmsUser Channel 1 Power FactorPFRead
AI277Ia_demaPhase A Current DemandARead
AI278PaImp_demaPhase A Import Active Power DemandkWRead
AI279PaExp_demaPhase A Export Active Power DemandkWRead
AI280QaImp_demaPhase A Import Reactive Power DemandkvarRead
AI281QaExp_demaPhase A Export Reactive Power DemandkvarRead
AI282Sa_demaPhase A Apparent Power DemandkVARead
AI283Ib_demaPhase B Current DemandARead
AI284PbImp_demaPhase B Import Active Power DemandkWRead
AI285PbExp_demaPhase B Export Active Power DemandkWRead
AI286QbImp_demaPhase B Import Reactive Power DemandkvarRead
AI287QbExp_demaPhase B Export Reactive Power DemandkvarRead
AI288Sb_demaPhase B Apparent Power DemandkVARead
AI289Ic_demaPhase C Current DemandARead
AI290PcImp_demaPhase C Import Active Power DemandkWRead
AI291PcExp_demaPhase C Export Active Power DemandkWRead
AI292QcImp_demaPhase C Import Reactive Power DemandkvarRead
AI293QcExp_demaPhase C Export Reactive Power DemandkvarRead
AI294Sc_demaPhase C Apparent Power DemandkVARead
AI295Isys_demaSystem Average Current DemandARead
AImin296PsysImp_demaSystem Import Active Power DemandkWRead
AI297PsysExp_demaSystem Export Active Power DemandkWRead
AI298QsysImp_demaSystem Import Reactive Power DemandkvarRead
AI299QsysExp_demaSystem Export Reactive Power DemandkvarRead
AI300Ssys_demaSystem Apparent Power DemandkVARead
AI301Ichn1_demaInput Channel 1 Current DemandARead
AI302Pchn1Imp_demaInput Channel 1 Import Active Power DemandkWRead
AI303Pchn1Exp_demaInput Channel 1 Export Active Power DemandkWRead
AI304Qchn1Imp_demaInput Channel 1 Import Reactive Power DemandkvarRead
AI305Qchn1Exp_demaInput Channel 1 Export Reactive Power DemandkvarRead
AI306Schn1_demaInput Channel 1 Apparent Power DemandkVARead
AI445Iusr1_demaUser Channel 1 Current DemandARead
AI446Pusr1Imp_demaUser Channel 1 Import Active Power DemandkWRead
AI447Pusr1Exp_demaUser Channel 1 Export Active Power DemandkWRead
AI448Qusr1Imp_demaUser Channel 1 Import Reactive Power DemandkvarRead
AI449Qusr1Exp_demaUser Channel 1 Export Reactive Power DemandkvarRead
AI450Susr1_demaUser Channel 1 Apparent Power DemandkVARead
AI517Vpsm_pqVoltage Positive Sequence MagnitudeVRead
AI518Vzsm_pqVoltage Zero Sequence MagnitudeVRead
AI519Vnsm_pqVoltage Negative Sequence MagnitudeVRead
AI520Vpsa_pqVoltage Positive Sequence AngledegreesRead
AI521Vzsa_pqVoltage Zero Sequence AngledegreesRead
AI522Vnsa_pqVoltage Negative Sequence AngledegreesRead
AI523Vufm_pqVoltage Unbalance Factor Magnitude%Read
AI524VThd_A_pqPhase A Voltage THD%Read
AI525VThdO_A_pqPhase A Voltage THD Odd%Read
AI526VThdE_A_pqPhase A Voltage THD Even%Read
AI527VCF_A_pqPhase A Voltage Crest FactorRead
AI528VThff_A_pqPhase A Voltage THFF Factor%Read
AI529VThd_B_pqPhase B Voltage THD%Read
AI530VThdO_B_pqPhase B Voltage THD Odd%Read
AI531VThdE_B_pqPhase B Voltage THD Even%Read
AI532VCF_B_pqPhase B Voltage Crest FactorRead
AI533VThff_B_pqPhase B Voltage THFF Factor%Read
AI534VThd_C_pqPhase C Voltage THD%Read
AI535VThdO_C_pqPhase C Voltage THD Odd%Read
AI536VThdE_C_pqPhase C Voltage THD Even%Read
AI537VCF_C_pqPhase C Voltage Crest FactorRead
AI538VThff_C_pqPhase C Voltage THFF Factor%Read
AI539VavgThd_pqAverage Voltage THD%Read
AI540VavgThdO_pqAverage Voltage THD Odd%Read
AI541VavgThdE_pqAverage Voltage THD Even%Read
AI542Ichn1Thd_pqInput Channel 1 Current THD%Read
AI543Ichn1ThdO_pqInput Channel 1 Current THD Odd%Read
AI544Ichn1ThdE_pqInput Channel 1 Current THD Even%Read
AI545Ichn1KF_pqInput Channel 1 Current K FactorRead
AI638Iuser1psm_pqUser Channel 1 Current Positive Sequence MagnitudeARead
AI639Iuser1zsm_pqUser Channel 1 Current Zero Sequence MagnitudeARead
AI640Iuser1nsm_pqUser Channel 1 Current Negative Sequence MagnitudeARead
AI641Iuser1psa_pqUser Channel 1 Current Positive Sequence AngledegreesRead
AI642Iuser1zsa_pqUser Channel 1 Current Zero Sequence AngledegreesRead
AI643Iuser1nsa_pqUser Channel 1 Current Negative Sequence AngledegreesRead
AI644Iuser1ufm_pqUser Channel 1 Current Unbalance Factor Magnitude%Read
LAV1PaImp_engPhase A active energy importkWhRead
LAV2PaExp_engPhase A active energy exportkWhRead
LAV3PaNet_engPhase A active energy netkWhRead
LAV4PaTotal_engPhase A active energy totalkWhRead
LAV5QaImp_engPhase A reactive energy importkvarhRead
LAV6QaExp_engPhase A reactive energy exportkvarhRead
LAV7QaNet_engPhase A reactive energy netkvarhRead
LAV8QaTotal_engPhase A reactive energy totalkvarhRead
LAV9Sa_engPhase A apparent energykVAhRead
LAV10PbImp_engPhase B active energy importkWhRead
LAV11PbExp_engPhase B active energy exportkWhRead
LAV12PbNet_engPhase B active energy netkWhRead
LAV13PbTotal_engPhase B active energy totalkWhRead
LAV14QbImp_engPhase B reactive energy importkvarhRead
LAV15QbExp_engPhase B reactive energy exportkvarhRead
LAV16QbNet_engPhase B reactive energy netkvarhRead
LAV17QbTotal_engPhase B reactive energy totalkvarhRead
LAV18Sb_engPhase B apparent energykVAhRead
LAV19PcImp_engPhase C active energy importkWhRead
LAV20PcExp_engPhase C active energy exportkWhRead
LAV21PcNet_engPhase C active energy netkWhRead
LAV22PcTotal_engPhase C active energy totalkWhRead
LAV23QcImp_engPhase C reactive energy importkvarhRead
LAV24QcExp_engPhase C reactive energy exportkvarhRead
LAV25QcNet_engPhase C reactive energy netkvarhRead
LAV26QcTotal_engPhase C reactive energy totalkvarhRead
LAV27Sc_engPhase C apparent energykVAhRead
LAVmin28PsysImp_engSystem active energy importkWhRead
LAV29PsysExp_engSystem active energy exportkWhRead
LAV30PsysNet_engSystem active energy netkWhRead
LAV31PsysTotal_engSystem active energy totalkWhRead
LAV32QsysImp_engSystem reactive energy importkvarhRead
LAV33QsysExp_engSystem reactive energy exportkvarhRead
LAV34QsysNet_engSystem reactive energy netkvarhRead
LAV35QsysTotal_engSystem reactive energy totalkvarhRead
LAV36Ssys_engSystem apparent energykVAhRead
LAVmin37PChn1Imp_engInput Channel 1 active energy importkWhRead
LAV38PChn1Exp_engInput Channel 1 active energy exportkWhRead
LAV39PChn1Net_engInput Channel 1 active energy netkWhRead
LAV40PChn1Total_engInput Channel 1 active energy totalkWhRead
LAV41QChn1Imp_engInput Channel 1 reactive energy importkvarhRead
LAV42QChn1Exp_engInput Channel 1 reactive energy exportkvarhRead
LAV43QChn1Net_engInput Channel 1 reactive energy netkvarhRead
LAV44QChn1Total_engInput Channel 1 reactive energy totalkvarhRead
LAV45SChn1_engInput Channel 1 apparent energykVAhRead
LAV253PUser1Imp_engUser Channel 1 active energy importkWhRead
LAV254PUser1Exp_engUser Channel 1 active energy exportkWhRead
LAV255PUser1Net_engUser Channel 1 active energy netkWhRead
LAV256PUser1Total_engUser Channel 1 active energy totalkWhRead
LAV257QUser1Imp_engUser Channel 1 reactive energy importkvarhRead
LAV258QUser1Exp_engUser Channel 1 reactive energy exportkvarhRead
LAV259QUser1Net_engUser Channel 1 reactive energy netkvarhRead
LAV260QUser1Total_engUser Channel 1 reactive energy totalkvarhRead
LAV261SUser1_engUser Channel 1 apparent energykVAhRead
Object ID lookup: Accuenergy AcuRev 4100 multi-circuit power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AcuRev 4100 multi-circuit power meter (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)

How many BACnet points does the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) have?

This list has 175 BACnet objects: 121 analog inputs, 54 large analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet documentation?

The source is BACnet Points List AcuRev4100, revision 2026-05-26, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev-4100_BACnet-Object-List.xlsx.

What are the minimum BACnet points to integrate the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)?

Start with AI 32 Psys_rms (System real power, kW); LAV 28 PsysImp_eng (System imported energy, kWh); AI 296 PsysImp_dema (System import kW demand); AI 36 PFsys_rms (System power factor); AI 31 Isys_rms (System average current, A); AI 2 Ua_rms (Phase A voltage, V); AI 38 Pchn1_rms (Input channel 1 real power, kW); LAV 37 PChn1Imp_eng (Input channel 1 imported energy, kWh); AI 1 Freq_rms (Frequency, Hz).

How do I check these points on the real AcuRev 4100 multi-circuit power meter (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accuenergy BACnet points lists

Source: BACnet Points List AcuRev4100 · rev. 2026-05-26. Object names, instances and units are reproduced as published; descriptions are our own.