Multi-circuit power and energy meter (submeter) · BACnet points list
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet points list
Updated 7 November 2026
The AcuRev 4100 meters up to 24 CT input channels plus 12 user-defined summing channels. Real-time, demand and power quality values are read-only Analog Inputs (1-721) and energy totals are Large Analog Values (1-360). Channel 1 of each channel group is printed in full; the other channels follow the same layout in the ranges given in the notes.
This page lists 175 BACnet objects for the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- AcuRev 4100 multi-circuit power meter (BACnet)
- Equipment
- Multi-circuit power and energy meter (submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 175 (0 writable)
- Transport
- —
- Firmware
- v1.03p06
- Also known as
- AcuRev 4100, AcuRev 4100 BACnet points list
- Source document
- BACnet Points List AcuRev4100 · rev. 2026-05-26
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Everything is read-only. Map the system power, energy and demand objects first, then the channel 1 objects and the matching objects for the other channels using the per-channel offsets in the notes.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 32 | Psys_rms | System real power, kW | Read |
| LAV 28 | PsysImp_eng | System imported energy, kWh | Read |
| AI 296 | PsysImp_dema | System import kW demand | Read |
| AI 36 | PFsys_rms | System power factor | Read |
| AI 31 | Isys_rms | System average current, A | Read |
| AI 2 | Ua_rms | Phase A voltage, V | Read |
| AI 38 | Pchn1_rms | Input channel 1 real power, kW | Read |
| LAV 37 | PChn1Imp_eng | Input channel 1 imported energy, kWh | Read |
| AI 1 | Freq_rms | Frequency, Hz | Read |
Watch out for
- Channel 2-24 and user channel 2-12 objects are not printed by name; work them out from the channel 1 layout and the ranges.
- Energy totals are Large Analog Value objects (double precision); some older BMS front ends cannot read LAV.
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Freq_rms | Frequency | Hz | Read | |
| AImin | 2 | Ua_rms | Phase A Voltage | V | Read | |
| AI | 3 | Ub_rms | Phase B Voltage | V | Read | |
| AI | 4 | Uc_rms | Phase C Voltage | V | Read | |
| AI | 5 | Uavg_rms | Phase Average Voltage | V | Read | |
| AI | 6 | Uab_rms | Line Voltage AB | V | Read | |
| AI | 7 | Ubc_rms | Line Voltage BC | V | Read | |
| AI | 8 | Uca_rms | Line Voltage CA | V | Read | |
| AI | 9 | Ulavg_rms | Average Line Voltage | V | Read | |
| AI | 10 | UaAng_rms | Phase A Voltage Angle | degrees | Read | |
| AI | 11 | UbAng_rms | Phase B Voltage Angle | degrees | Read | |
| AI | 12 | UcAng_rms | Phase C Voltage Angle | degrees | Read | |
| AI | 13 | Ia_rms | Phase A Current | A | Read | |
| AI | 14 | Pa_rms | Phase A Active Power | kW | Read | |
| AI | 15 | Qa_rms | Phase A Reactive Power | kvar | Read | |
| AI | 16 | Sa_rms | Phase A Apparent Power | kVA | Read | |
| AI | 17 | LNa_rms | Phase A Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load) | Read | ||
| AI | 18 | PFa_rms | Phase A Power Factor | PF | Read | |
| AI | 19 | Ib_rms | Phase B Current | A | Read | |
| AI | 20 | Pb_rms | Phase B Active Power | kW | Read | |
| AI | 21 | Qb_rms | Phase B Reactive Power | kvar | Read | |
| AI | 22 | Sb_rms | Phase B Apparent Power | kVA | Read | |
| AI | 23 | LNb_rms | Phase B Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load) | Read | ||
| AI | 24 | PFb_rms | Phase B Power Factor | PF | Read | |
| AI | 25 | Ic_rms | Phase C Current | A | Read | |
| AI | 26 | Pc_rms | Phase C Active Power | kW | Read | |
| AI | 27 | Qc_rms | Phase C Reactive Power | kvar | Read | |
| AI | 28 | Sc_rms | Phase C Apparent Power | kVA | Read | |
| AI | 29 | LNc_rms | Phase C Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load) | Read | ||
| AI | 30 | PFc_rms | Phase C Power Factor | PF | Read | |
| AImin | 31 | Isys_rms | System Average Current | A | Read | |
| AImin | 32 | Psys_rms | System Active Power | kW | Read | |
| AI | 33 | Qsys_rms | System Reactive Power | kvar | Read | |
| AI | 34 | Ssys_rms | System Apparent Power | kVA | Read | |
| AI | 35 | LNsys_rms | System Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load) | Read | ||
| AImin | 36 | PFsys_rms | System Power Factor | PF | Read | |
| AI | 37 | Ichn1_rms | Input Channel 1 Current | A | Read | |
| AImin | 38 | Pchn1_rms | Input Channel 1 Active Power | kW | Read | |
| AI | 39 | Qchn1_rms | Input Channel 1 Reactive Power | kvar | Read | |
| AI | 40 | Schn1_rms | Input Channel 1 Apparent Power | kVA | Read | |
| AI | 41 | LNchn1_rms | Input Channel 1 Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load) | Read | ||
| AI | 42 | PFchn1_rms | Input Channel 1 Power Factor | PF | Read | |
| AI | 43 | Angchn1_rms | Input Channel 1 Current Phase Angle | degrees | Read | |
| AI | 205 | Iusr1_rms | User Channel 1 Current | A | Read | |
| AI | 206 | Pusr1_rms | User Channel 1 Active Power | kW | Read | |
| AI | 207 | Qusr1_rms | User Channel 1 Reactive Power | kvar | Read | |
| AI | 208 | Susr1_rms | User Channel 1 Apparent Power | kVA | Read | |
| AI | 209 | LNusr1_rms | User Channel 1 Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load) | Read | ||
| AI | 210 | PFusr1_rms | User Channel 1 Power Factor | PF | Read | |
| AI | 277 | Ia_dema | Phase A Current Demand | A | Read | |
| AI | 278 | PaImp_dema | Phase A Import Active Power Demand | kW | Read | |
| AI | 279 | PaExp_dema | Phase A Export Active Power Demand | kW | Read | |
| AI | 280 | QaImp_dema | Phase A Import Reactive Power Demand | kvar | Read | |
| AI | 281 | QaExp_dema | Phase A Export Reactive Power Demand | kvar | Read | |
| AI | 282 | Sa_dema | Phase A Apparent Power Demand | kVA | Read | |
| AI | 283 | Ib_dema | Phase B Current Demand | A | Read | |
| AI | 284 | PbImp_dema | Phase B Import Active Power Demand | kW | Read | |
| AI | 285 | PbExp_dema | Phase B Export Active Power Demand | kW | Read | |
| AI | 286 | QbImp_dema | Phase B Import Reactive Power Demand | kvar | Read | |
| AI | 287 | QbExp_dema | Phase B Export Reactive Power Demand | kvar | Read | |
| AI | 288 | Sb_dema | Phase B Apparent Power Demand | kVA | Read | |
| AI | 289 | Ic_dema | Phase C Current Demand | A | Read | |
| AI | 290 | PcImp_dema | Phase C Import Active Power Demand | kW | Read | |
| AI | 291 | PcExp_dema | Phase C Export Active Power Demand | kW | Read | |
| AI | 292 | QcImp_dema | Phase C Import Reactive Power Demand | kvar | Read | |
| AI | 293 | QcExp_dema | Phase C Export Reactive Power Demand | kvar | Read | |
| AI | 294 | Sc_dema | Phase C Apparent Power Demand | kVA | Read | |
| AI | 295 | Isys_dema | System Average Current Demand | A | Read | |
| AImin | 296 | PsysImp_dema | System Import Active Power Demand | kW | Read | |
| AI | 297 | PsysExp_dema | System Export Active Power Demand | kW | Read | |
| AI | 298 | QsysImp_dema | System Import Reactive Power Demand | kvar | Read | |
| AI | 299 | QsysExp_dema | System Export Reactive Power Demand | kvar | Read | |
| AI | 300 | Ssys_dema | System Apparent Power Demand | kVA | Read | |
| AI | 301 | Ichn1_dema | Input Channel 1 Current Demand | A | Read | |
| AI | 302 | Pchn1Imp_dema | Input Channel 1 Import Active Power Demand | kW | Read | |
| AI | 303 | Pchn1Exp_dema | Input Channel 1 Export Active Power Demand | kW | Read | |
| AI | 304 | Qchn1Imp_dema | Input Channel 1 Import Reactive Power Demand | kvar | Read | |
| AI | 305 | Qchn1Exp_dema | Input Channel 1 Export Reactive Power Demand | kvar | Read | |
| AI | 306 | Schn1_dema | Input Channel 1 Apparent Power Demand | kVA | Read | |
| AI | 445 | Iusr1_dema | User Channel 1 Current Demand | A | Read | |
| AI | 446 | Pusr1Imp_dema | User Channel 1 Import Active Power Demand | kW | Read | |
| AI | 447 | Pusr1Exp_dema | User Channel 1 Export Active Power Demand | kW | Read | |
| AI | 448 | Qusr1Imp_dema | User Channel 1 Import Reactive Power Demand | kvar | Read | |
| AI | 449 | Qusr1Exp_dema | User Channel 1 Export Reactive Power Demand | kvar | Read | |
| AI | 450 | Susr1_dema | User Channel 1 Apparent Power Demand | kVA | Read | |
| AI | 517 | Vpsm_pq | Voltage Positive Sequence Magnitude | V | Read | |
| AI | 518 | Vzsm_pq | Voltage Zero Sequence Magnitude | V | Read | |
| AI | 519 | Vnsm_pq | Voltage Negative Sequence Magnitude | V | Read | |
| AI | 520 | Vpsa_pq | Voltage Positive Sequence Angle | degrees | Read | |
| AI | 521 | Vzsa_pq | Voltage Zero Sequence Angle | degrees | Read | |
| AI | 522 | Vnsa_pq | Voltage Negative Sequence Angle | degrees | Read | |
| AI | 523 | Vufm_pq | Voltage Unbalance Factor Magnitude | % | Read | |
| AI | 524 | VThd_A_pq | Phase A Voltage THD | % | Read | |
| AI | 525 | VThdO_A_pq | Phase A Voltage THD Odd | % | Read | |
| AI | 526 | VThdE_A_pq | Phase A Voltage THD Even | % | Read | |
| AI | 527 | VCF_A_pq | Phase A Voltage Crest Factor | Read | ||
| AI | 528 | VThff_A_pq | Phase A Voltage THFF Factor | % | Read | |
| AI | 529 | VThd_B_pq | Phase B Voltage THD | % | Read | |
| AI | 530 | VThdO_B_pq | Phase B Voltage THD Odd | % | Read | |
| AI | 531 | VThdE_B_pq | Phase B Voltage THD Even | % | Read | |
| AI | 532 | VCF_B_pq | Phase B Voltage Crest Factor | Read | ||
| AI | 533 | VThff_B_pq | Phase B Voltage THFF Factor | % | Read | |
| AI | 534 | VThd_C_pq | Phase C Voltage THD | % | Read | |
| AI | 535 | VThdO_C_pq | Phase C Voltage THD Odd | % | Read | |
| AI | 536 | VThdE_C_pq | Phase C Voltage THD Even | % | Read | |
| AI | 537 | VCF_C_pq | Phase C Voltage Crest Factor | Read | ||
| AI | 538 | VThff_C_pq | Phase C Voltage THFF Factor | % | Read | |
| AI | 539 | VavgThd_pq | Average Voltage THD | % | Read | |
| AI | 540 | VavgThdO_pq | Average Voltage THD Odd | % | Read | |
| AI | 541 | VavgThdE_pq | Average Voltage THD Even | % | Read | |
| AI | 542 | Ichn1Thd_pq | Input Channel 1 Current THD | % | Read | |
| AI | 543 | Ichn1ThdO_pq | Input Channel 1 Current THD Odd | % | Read | |
| AI | 544 | Ichn1ThdE_pq | Input Channel 1 Current THD Even | % | Read | |
| AI | 545 | Ichn1KF_pq | Input Channel 1 Current K Factor | Read | ||
| AI | 638 | Iuser1psm_pq | User Channel 1 Current Positive Sequence Magnitude | A | Read | |
| AI | 639 | Iuser1zsm_pq | User Channel 1 Current Zero Sequence Magnitude | A | Read | |
| AI | 640 | Iuser1nsm_pq | User Channel 1 Current Negative Sequence Magnitude | A | Read | |
| AI | 641 | Iuser1psa_pq | User Channel 1 Current Positive Sequence Angle | degrees | Read | |
| AI | 642 | Iuser1zsa_pq | User Channel 1 Current Zero Sequence Angle | degrees | Read | |
| AI | 643 | Iuser1nsa_pq | User Channel 1 Current Negative Sequence Angle | degrees | Read | |
| AI | 644 | Iuser1ufm_pq | User Channel 1 Current Unbalance Factor Magnitude | % | Read | |
| LAV | 1 | PaImp_eng | Phase A active energy import | kWh | Read | |
| LAV | 2 | PaExp_eng | Phase A active energy export | kWh | Read | |
| LAV | 3 | PaNet_eng | Phase A active energy net | kWh | Read | |
| LAV | 4 | PaTotal_eng | Phase A active energy total | kWh | Read | |
| LAV | 5 | QaImp_eng | Phase A reactive energy import | kvarh | Read | |
| LAV | 6 | QaExp_eng | Phase A reactive energy export | kvarh | Read | |
| LAV | 7 | QaNet_eng | Phase A reactive energy net | kvarh | Read | |
| LAV | 8 | QaTotal_eng | Phase A reactive energy total | kvarh | Read | |
| LAV | 9 | Sa_eng | Phase A apparent energy | kVAh | Read | |
| LAV | 10 | PbImp_eng | Phase B active energy import | kWh | Read | |
| LAV | 11 | PbExp_eng | Phase B active energy export | kWh | Read | |
| LAV | 12 | PbNet_eng | Phase B active energy net | kWh | Read | |
| LAV | 13 | PbTotal_eng | Phase B active energy total | kWh | Read | |
| LAV | 14 | QbImp_eng | Phase B reactive energy import | kvarh | Read | |
| LAV | 15 | QbExp_eng | Phase B reactive energy export | kvarh | Read | |
| LAV | 16 | QbNet_eng | Phase B reactive energy net | kvarh | Read | |
| LAV | 17 | QbTotal_eng | Phase B reactive energy total | kvarh | Read | |
| LAV | 18 | Sb_eng | Phase B apparent energy | kVAh | Read | |
| LAV | 19 | PcImp_eng | Phase C active energy import | kWh | Read | |
| LAV | 20 | PcExp_eng | Phase C active energy export | kWh | Read | |
| LAV | 21 | PcNet_eng | Phase C active energy net | kWh | Read | |
| LAV | 22 | PcTotal_eng | Phase C active energy total | kWh | Read | |
| LAV | 23 | QcImp_eng | Phase C reactive energy import | kvarh | Read | |
| LAV | 24 | QcExp_eng | Phase C reactive energy export | kvarh | Read | |
| LAV | 25 | QcNet_eng | Phase C reactive energy net | kvarh | Read | |
| LAV | 26 | QcTotal_eng | Phase C reactive energy total | kvarh | Read | |
| LAV | 27 | Sc_eng | Phase C apparent energy | kVAh | Read | |
| LAVmin | 28 | PsysImp_eng | System active energy import | kWh | Read | |
| LAV | 29 | PsysExp_eng | System active energy export | kWh | Read | |
| LAV | 30 | PsysNet_eng | System active energy net | kWh | Read | |
| LAV | 31 | PsysTotal_eng | System active energy total | kWh | Read | |
| LAV | 32 | QsysImp_eng | System reactive energy import | kvarh | Read | |
| LAV | 33 | QsysExp_eng | System reactive energy export | kvarh | Read | |
| LAV | 34 | QsysNet_eng | System reactive energy net | kvarh | Read | |
| LAV | 35 | QsysTotal_eng | System reactive energy total | kvarh | Read | |
| LAV | 36 | Ssys_eng | System apparent energy | kVAh | Read | |
| LAVmin | 37 | PChn1Imp_eng | Input Channel 1 active energy import | kWh | Read | |
| LAV | 38 | PChn1Exp_eng | Input Channel 1 active energy export | kWh | Read | |
| LAV | 39 | PChn1Net_eng | Input Channel 1 active energy net | kWh | Read | |
| LAV | 40 | PChn1Total_eng | Input Channel 1 active energy total | kWh | Read | |
| LAV | 41 | QChn1Imp_eng | Input Channel 1 reactive energy import | kvarh | Read | |
| LAV | 42 | QChn1Exp_eng | Input Channel 1 reactive energy export | kvarh | Read | |
| LAV | 43 | QChn1Net_eng | Input Channel 1 reactive energy net | kvarh | Read | |
| LAV | 44 | QChn1Total_eng | Input Channel 1 reactive energy total | kvarh | Read | |
| LAV | 45 | SChn1_eng | Input Channel 1 apparent energy | kVAh | Read | |
| LAV | 253 | PUser1Imp_eng | User Channel 1 active energy import | kWh | Read | |
| LAV | 254 | PUser1Exp_eng | User Channel 1 active energy export | kWh | Read | |
| LAV | 255 | PUser1Net_eng | User Channel 1 active energy net | kWh | Read | |
| LAV | 256 | PUser1Total_eng | User Channel 1 active energy total | kWh | Read | |
| LAV | 257 | QUser1Imp_eng | User Channel 1 reactive energy import | kvarh | Read | |
| LAV | 258 | QUser1Exp_eng | User Channel 1 reactive energy export | kvarh | Read | |
| LAV | 259 | QUser1Net_eng | User Channel 1 reactive energy net | kvarh | Read | |
| LAV | 260 | QUser1Total_eng | User Channel 1 reactive energy total | kvarh | Read | |
| LAV | 261 | SUser1_eng | User Channel 1 apparent energy | kVAh | Read |
No points match these filters.
Object ID lookup: Accuenergy AcuRev 4100 multi-circuit power meter point IDs by name
AI1Freq_rmsAI2Ua_rmsAI3Ub_rmsAI4Uc_rmsAI5Uavg_rmsAI6Uab_rmsAI7Ubc_rmsAI8Uca_rmsAI9Ulavg_rmsAI10UaAng_rmsAI11UbAng_rmsAI12UcAng_rmsAI13Ia_rmsAI14Pa_rmsAI15Qa_rmsAI16Sa_rmsAI17LNa_rmsAI18PFa_rmsAI19Ib_rmsAI20Pb_rmsAI21Qb_rmsAI22Sb_rmsAI23LNb_rmsAI24PFb_rmsAI25Ic_rmsAI26Pc_rmsAI27Qc_rmsAI28Sc_rmsAI29LNc_rmsAI30PFc_rmsAI31Isys_rmsAI32Psys_rmsAI33Qsys_rmsAI34Ssys_rmsAI35LNsys_rmsAI36PFsys_rmsAI37Ichn1_rmsAI38Pchn1_rmsAI39Qchn1_rmsAI40Schn1_rmsAI41LNchn1_rmsAI42PFchn1_rmsAI43Angchn1_rmsAI205Iusr1_rmsAI206Pusr1_rmsAI207Qusr1_rmsAI208Susr1_rmsAI209LNusr1_rmsAI210PFusr1_rmsAI277Ia_demaAI278PaImp_demaAI279PaExp_demaAI280QaImp_demaAI281QaExp_demaAI282Sa_demaAI283Ib_demaAI284PbImp_demaAI285PbExp_demaAI286QbImp_demaAI287QbExp_demaAI288Sb_demaAI289Ic_demaAI290PcImp_demaAI291PcExp_demaAI292QcImp_demaAI293QcExp_demaAI294Sc_demaAI295Isys_demaAI296PsysImp_demaAI297PsysExp_demaAI298QsysImp_demaAI299QsysExp_demaAI300Ssys_demaAI301Ichn1_demaAI302Pchn1Imp_demaAI303Pchn1Exp_demaAI304Qchn1Imp_demaAI305Qchn1Exp_demaAI306Schn1_demaAI445Iusr1_demaAI446Pusr1Imp_demaAI447Pusr1Exp_demaAI448Qusr1Imp_demaAI449Qusr1Exp_demaAI450Susr1_demaAI517Vpsm_pqAI518Vzsm_pqAI519Vnsm_pqAI520Vpsa_pqAI521Vzsa_pqAI522Vnsa_pqAI523Vufm_pqAI524VThd_A_pqAI525VThdO_A_pqAI526VThdE_A_pqAI527VCF_A_pqAI528VThff_A_pqAI529VThd_B_pqAI530VThdO_B_pqAI531VThdE_B_pqAI532VCF_B_pqAI533VThff_B_pqAI534VThd_C_pqAI535VThdO_C_pqAI536VThdE_C_pqAI537VCF_C_pqAI538VThff_C_pqAI539VavgThd_pqAI540VavgThdO_pqAI541VavgThdE_pqAI542Ichn1Thd_pqAI543Ichn1ThdO_pqAI544Ichn1ThdE_pqAI545Ichn1KF_pqAI638Iuser1psm_pqAI639Iuser1zsm_pqAI640Iuser1nsm_pqAI641Iuser1psa_pqAI642Iuser1zsa_pqAI643Iuser1nsa_pqAI644Iuser1ufm_pqLAV1PaImp_engLAV2PaExp_engLAV3PaNet_engLAV4PaTotal_engLAV5QaImp_engLAV6QaExp_engLAV7QaNet_engLAV8QaTotal_engLAV9Sa_engLAV10PbImp_engLAV11PbExp_engLAV12PbNet_engLAV13PbTotal_engLAV14QbImp_engLAV15QbExp_engLAV16QbNet_engLAV17QbTotal_engLAV18Sb_engLAV19PcImp_engLAV20PcExp_engLAV21PcNet_engLAV22PcTotal_engLAV23QcImp_engLAV24QcExp_engLAV25QcNet_engLAV26QcTotal_engLAV27Sc_engLAV28PsysImp_engLAV29PsysExp_engLAV30PsysNet_engLAV31PsysTotal_engLAV32QsysImp_engLAV33QsysExp_engLAV34QsysNet_engLAV35QsysTotal_engLAV36Ssys_engLAV37PChn1Imp_engLAV38PChn1Exp_engLAV39PChn1Net_engLAV40PChn1Total_engLAV41QChn1Imp_engLAV42QChn1Exp_engLAV43QChn1Net_engLAV44QChn1Total_engLAV45SChn1_engLAV253PUser1Imp_engLAV254PUser1Exp_engLAV255PUser1Net_engLAV256PUser1Total_engLAV257QUser1Imp_engLAV258QUser1Exp_engLAV259QUser1Net_engLAV260QUser1Total_engLAV261SUser1_eng
Integration notes
- Per-channel blocks: the list prints channel 1 and then a range for the rest - input channel basics AI 44-204 (7 per channel), user channel basics AI 211-276 (6 per channel; printed as 205-276), input channel demand AI 307-444, user channel demand AI 451-516, input channel power quality AI 546-637 (4 per channel), user channel power quality AI 645-721 (7 per channel), input channel energy LAV 46-252 and user channel energy LAV 262-360 (9 per channel). Only printed objects are listed here.
- AI 208 (Susr1_rms) is printed with 'S' in the ID column; it sits between AI 207 and AI 209 and is listed as 208.
- Load nature values: 0 resistive, 1 capacitive, 2 inductive.
- The list does not say which BACnet transport the meter uses; check the meter manual.
- Source: Accuenergy 'BACnet Points List AcuRev4100' spreadsheet, firmware v1.03p06, generated 2026-05-26.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AcuRev 4100 multi-circuit power meter (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
How many BACnet points does the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) have?
This list has 175 BACnet objects: 121 analog inputs, 54 large analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Accuenergy AcuRev 4100 multi-circuit power meter (BACnet) BACnet documentation?
The source is BACnet Points List AcuRev4100, revision 2026-05-26, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev-4100_BACnet-Object-List.xlsx.
What are the minimum BACnet points to integrate the Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)?
Start with AI 32 Psys_rms (System real power, kW); LAV 28 PsysImp_eng (System imported energy, kWh); AI 296 PsysImp_dema (System import kW demand); AI 36 PFsys_rms (System power factor); AI 31 Isys_rms (System average current, A); AI 2 Ua_rms (Phase A voltage, V); AI 38 Pchn1_rms (Input channel 1 real power, kW); LAV 37 PChn1Imp_eng (Input channel 1 imported energy, kWh); AI 1 Freq_rms (Frequency, Hz).
How do I check these points on the real AcuRev 4100 multi-circuit power meter (BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet - Power and energy meter (communication module)
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Accuenergy AXM-WEB2 Ethernet / web module fitted to Acuvim II series meters, with optional IO11/12, IO21/22 and IO31/32 modules.
Also known as: AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
Source: BACnet Points List AcuRev4100 · rev. 2026-05-26. Object names, instances and units are reproduced as published; descriptions are our own.