- AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Power and energy meter (DIN-rail submeter) · BACnet points list
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The AcuRev 1310 series meters switch from Modbus RTU to BACnet MS/TP on the front-panel settings. In BACnet mode they expose 90 fixed, read-only Analog Inputs: voltage, current, power, power factor, demand and demand prediction, energy by direction and quadrant, chip temperature and demand-reset history. No mapping is needed. BACnet IP is not supported.
This page lists 90 BACnet objects for the Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
- Equipment
- Power and energy meter (DIN-rail submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 90 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- v2.16 or later for protocol switching
- Default device instance
- 1
- Also known as
- AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
On the meter set Protocol Selection to 1 (BACnet), then set MAC, baud, max info frame and device instance and reset the meter to save. Read total kW, imported kWh, demand, power factor, current and voltage.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 18 | Total Active Power | Total real power, kW | Read |
| AI 45 | Import Active Energy | Imported energy total, kWh | Read |
| AI 32 | Active Power Demand | Real power demand, kW | Read |
| AI 26 | Total Apparent Power | Total apparent power, kVA | Read |
| AI 30 | Total Power Factor | Three-phase power factor | Read |
| AI 13 | Total Current | Total current, A | Read |
| AI 5 | Average Phase Voltage | Average phase voltage, V | Read |
| AI 1 | Frequency | Supply frequency, Hz | Read |
Network setup
- Factory default protocol is Modbus RTU; change Protocol Selection to 1 for BACnet MS/TP (default settings password 0000).
- MAC address 0-127, default 0; baud 9600, 19200, 38400 or 76800, default 38400; Max Info Frames 1-250, default 10.
- Device instance default 1, range 1-4,194,302.
- The last settings screen resets the meter; the reset is needed to save the BACnet settings.
Watch out for
- Several printed names repeat (AI 57/58, AI 77-82); map by instance, not by name.
- Units in the source table are shifted on some rows; check scaling against the meter display.
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Frequency | Hz | Read | ||
| AI | 2 | Phase A Voltage | V | Read | ||
| AI | 3 | Phase B Voltage | V | Read | ||
| AI | 4 | Phase C Voltage | V | Read | ||
| AImin | 5 | Average Phase Voltage | V | Read | ||
| AI | 6 | Line Voltage AB | V | Read | ||
| AI | 7 | Line Voltage BC | V | Read | ||
| AI | 8 | Line Voltage CA | V | Read | ||
| AI | 9 | Average Line Voltage | V | Read | ||
| AI | 10 | Phase A Current | A | Read | ||
| AI | 11 | Phase B Current | A | Read | ||
| AI | 12 | Phase C Current | A | Read | ||
| AImin | 13 | Total Current | A | Read | ||
| AI | 14 | Neutral Current | A | Read | ||
| AI | 15 | Phase A Active Power | kW | Read | ||
| AI | 16 | Phase B Active Power | kW | Read | ||
| AI | 17 | Phase C Active Power | kW | Read | ||
| AImin | 18 | Total Active Power | kW | Read | ||
| AI | 19 | Phase A Reactive Power | kvar | Read | ||
| AI | 20 | Phase B Reactive Power | kvar | Read | ||
| AI | 21 | Phase C Reactive Power | kvar | Read | ||
| AI | 22 | Total Reactive Power | kvar | Read | ||
| AI | 23 | Phase A Apparent Power | kVA | Read | ||
| AI | 24 | Phase B Apparent Power | kVA | Read | ||
| AI | 25 | Phase C Apparent Power | kVA | Read | ||
| AImin | 26 | Total Apparent Power | kVA | Read | ||
| AI | 27 | Phase A Power Factor | Read | |||
| AI | 28 | Phase B Power Factor | Read | |||
| AI | 29 | Phase C Power Factor | Read | |||
| AImin | 30 | Total Power Factor | Read | |||
| AI | 31 | Load Type | Read | |||
| AImin | 32 | Active Power Demand | kW | Read | ||
| AI | 33 | Reactive Power Demand | kvar | Read | ||
| AI | 34 | Apparent Power Demand | kVA | Read | ||
| AI | 35 | Phase A Current Demand | A | Read | ||
| AI | 36 | Phase B Current Demand | A | Read | ||
| AI | 37 | Phase C Current Demand | A | Read | ||
| AI | 38 | System Active Power Demand Prediction | kW | Read | ||
| AI | 39 | System Reactive Power Demand Prediction | kvar | Read | ||
| AI | 40 | System Apparent Power Demand Prediction | kVA | Read | ||
| AI | 41 | Phase A Current Demand Prediction | A | Read | ||
| AI | 42 | Phase B Current Demand Prediction | A | Read | ||
| AI | 43 | Phase C Current Demand Prediction | A | Read | ||
| AI | 44 | Temperature of chips | °C | Read | ||
| AImin | 45 | Import Active Energy | kWh | Read | ||
| AI | 46 | Export Active Energy | kWh | Read | ||
| AI | 47 | Import Reactive Energy | kvarh | Read | ||
| AI | 48 | Export Reactive Energy | kvarh | Read | ||
| AI | 49 | Import Apparent Power | kVAh | Read | ||
| AI | 50 | Export Apparent Power | kVAh | Read | ||
| AI | 51 | Active Energy Total | kWh | Read | ||
| AI | 52 | Active Energy Net | kWh | Read | ||
| AI | 53 | Reactive Energy Total | kvarh | Read | ||
| AI | 54 | Phase B Import Active Energy | kvarh | Read | ||
| AI | 55 | Phase A Import Active Energy | kWh | Read | ||
| AI | 56 | Phase A Export Active Energy | kWh | Read | ||
| AI | 57 | Phase B Export Active Energy | kWh | Read | ||
| AI | 58 | Phase B Export Active Energy | kWh | Read | ||
| AI | 59 | Phase C Import Active Energy | kWh | Read | ||
| AI | 60 | Phase C Export Active Energy | kWh | Read | ||
| AI | 61 | Reactive Imported Q1 | kvarh | Read | ||
| AI | 62 | Reactive Imported Q2 | kvarh | Read | ||
| AI | 63 | Reactive Imported Q3 | kvarh | Read | ||
| AI | 64 | Reactive Imported Q4 | kvarh | Read | ||
| AI | 65 | Phase A Reactive Imported Q1 | kvarh | Read | ||
| AI | 66 | Phase A Reactive Imported Q2 | kvarh | Read | ||
| AI | 67 | Phase A Reactive Imported Q3 | kvarh | Read | ||
| AI | 68 | Phase A Reactive Imported Q4 | kvarh | Read | ||
| AI | 69 | Phase B Reactive Imported Q1 | kvarh | Read | ||
| AI | 70 | Phase B Reactive Imported Q2 | kvarh | Read | ||
| AI | 71 | Phase B Reactive Imported Q3 | kvarh | Read | ||
| AI | 72 | Phase B Reactive Imported Q4 | kvarh | Read | ||
| AI | 73 | Phase C Reactive Imported Q1 | kvarh | Read | ||
| AI | 74 | Phase C Reactive Imported Q2 | kvarh | Read | ||
| AI | 75 | Phase C Reactive Imported Q3 | kvarh | Read | ||
| AI | 76 | Phase C Reactive Imported Q4 | kvarh | Read | ||
| AI | 77 | Phase A Import Apparent Energy | kVAh | Read | ||
| AI | 78 | Phase A Import Apparent Energy | kVAh | Read | ||
| AI | 79 | Phase B Import Apparent Energy | kVAh | Read | ||
| AI | 80 | Phase B Import Apparent Energy | kVAh | Read | ||
| AI | 81 | Phase C Import Apparent Energy | kVAh | Read | ||
| AI | 82 | Phase C Import Apparent Energy | kVAh | Read | ||
| AI | 83 | Current Imported Active Power Demand Peak and Happening Time | kW | Read | ||
| AI | 84 | Current Exported Active Power Demand Peak and Happening Time | kW | Read | ||
| AI | 85 | Last Month Imported Active Power Demand Peak and Happening Time | kW | Read | ||
| AI | 86 | Last Month Exported Active Power Demand Peak and Happening Time | kW | Read | ||
| AI | 87 | Total Times of Demand Reset | Read | |||
| AI | 88 | Last Demand Reset Happening Time | Read | |||
| AI | 89 | 2nd Last Demand Reset Happening Time | Read | |||
| AI | 90 | 3rd Last Demand Reset Happening Time | Read |
No points match these filters.
Object ID lookup: Accuenergy AcuRev 1310 series DIN-rail power meter point IDs by name
AI1FrequencyAI2Phase A VoltageAI3Phase B VoltageAI4Phase C VoltageAI5Average Phase VoltageAI6Line Voltage ABAI7Line Voltage BCAI8Line Voltage CAAI9Average Line VoltageAI10Phase A CurrentAI11Phase B CurrentAI12Phase C CurrentAI13Total CurrentAI14Neutral CurrentAI15Phase A Active PowerAI16Phase B Active PowerAI17Phase C Active PowerAI18Total Active PowerAI19Phase A Reactive PowerAI20Phase B Reactive PowerAI21Phase C Reactive PowerAI22Total Reactive PowerAI23Phase A Apparent PowerAI24Phase B Apparent PowerAI25Phase C Apparent PowerAI26Total Apparent PowerAI27Phase A Power FactorAI28Phase B Power FactorAI29Phase C Power FactorAI30Total Power FactorAI31Load TypeAI32Active Power DemandAI33Reactive Power DemandAI34Apparent Power DemandAI35Phase A Current DemandAI36Phase B Current DemandAI37Phase C Current DemandAI38System Active Power Demand PredictionAI39System Reactive Power Demand PredictionAI40System Apparent Power Demand PredictionAI41Phase A Current Demand PredictionAI42Phase B Current Demand PredictionAI43Phase C Current Demand PredictionAI44Temperature of chipsAI45Import Active EnergyAI46Export Active EnergyAI47Import Reactive EnergyAI48Export Reactive EnergyAI49Import Apparent PowerAI50Export Apparent PowerAI51Active Energy TotalAI52Active Energy NetAI53Reactive Energy TotalAI54Phase B Import Active EnergyAI55Phase A Import Active EnergyAI56Phase A Export Active EnergyAI57Phase B Export Active EnergyAI58Phase B Export Active EnergyAI59Phase C Import Active EnergyAI60Phase C Export Active EnergyAI61Reactive Imported Q1AI62Reactive Imported Q2AI63Reactive Imported Q3AI64Reactive Imported Q4AI65Phase A Reactive Imported Q1AI66Phase A Reactive Imported Q2AI67Phase A Reactive Imported Q3AI68Phase A Reactive Imported Q4AI69Phase B Reactive Imported Q1AI70Phase B Reactive Imported Q2AI71Phase B Reactive Imported Q3AI72Phase B Reactive Imported Q4AI73Phase C Reactive Imported Q1AI74Phase C Reactive Imported Q2AI75Phase C Reactive Imported Q3AI76Phase C Reactive Imported Q4AI77Phase A Import Apparent EnergyAI78Phase A Import Apparent EnergyAI79Phase B Import Apparent EnergyAI80Phase B Import Apparent EnergyAI81Phase C Import Apparent EnergyAI82Phase C Import Apparent EnergyAI83Current Imported Active Power Demand Peak and Happening TimeAI84Current Exported Active Power Demand Peak and Happening TimeAI85Last Month Imported Active Power Demand Peak and Happening TimeAI86Last Month Exported Active Power Demand Peak and Happening TimeAI87Total Times of Demand ResetAI88Last Demand Reset Happening TimeAI892nd Last Demand Reset Happening TimeAI903rd Last Demand Reset Happening Time
Integration notes
- The table has no access column; all objects are measurements and are listed as read-only.
- The units column of the printed table is shifted on several rows (e.g. AI 23 shows kVAR, AI 27 kVA, AI 57 kVA). Units here are set from each object's name.
- Printed names repeat: AI 54 and AI 57 both read like 'Phase B ... Active Energy' (AI 54 is printed with kVARh), AI 57 and AI 58 are both 'Phase B Export Active Energy', and AI 77-82 print 'Import Apparent Energy' twice per phase. By position AI 54 is probably net reactive energy, AI 57 phase B import, and the second of each 77-82 pair export; check on site.
- AI 49 and AI 50 are named 'Apparent Power' but sit with the energy totals; they are listed in kVAh.
- AI 83-86 hold the peak demand value; the 'happening time' in the name is not a separate object.
- Source: AcuRev 1310 User Manual v1.2.11 (October 2026), Table 5-32.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
How many BACnet points does the Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) have?
This list has 90 BACnet objects: 90 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP) BACnet documentation?
The source is AcuRev 1310 Series DIN-Rail Power Meter User Manual (Version 1.2.11), revision 2026-10, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev-1310-User-Manual.pdf.
What are the minimum BACnet points to integrate the Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)?
Start with AI 18 Total Active Power (Total real power, kW); AI 45 Import Active Energy (Imported energy total, kWh); AI 32 Active Power Demand (Real power demand, kW); AI 26 Total Apparent Power (Total apparent power, kVA); AI 30 Total Power Factor (Three-phase power factor); AI 13 Total Current (Total current, A); AI 5 Average Phase Voltage (Average phase voltage, V); AI 1 Frequency (Supply frequency, Hz).
How do I check these points on the real AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet - Power and energy meter (communication module)