- AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Power and energy meter (communication module) · BACnet points list
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) BACnet points list
Updated 7 November 2026
The AXM-WEB2 module adds BACnet IP to an Acuvim II meter. It serves 119 read-only Analog Inputs (metering, demand, energy, THD, per-channel demand, I/O module analog values at 1001-1008 and DI pulse counters at 2001-2028) and 44 Binary Inputs (DI status 1-28, alarm channel status 29-44).
This page lists 163 BACnet objects for the Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
- Equipment
- Power and energy meter (communication module)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 163 (0 writable)
- Transport
- BACnet IP
- Firmware
- v1.39c
- Also known as
- AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
- Source document
- BACnet Points List AXM-WEB2 · rev. 2026-10-06
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
All objects are read-only. Map total power, imported energy, demand, PF, current and voltage; I/O objects appear only when the modules are enabled.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 18 | Total Active Power | Total real power, kW | Read |
| AI 40 | Import Active Energy | Imported energy, kWh | Read |
| AI 34 | Active Power Demand | Real power demand, kW | Read |
| AI 30 | Total Power Factor | Total power factor | Read |
| AI 13 | Average Current | Average current, A | Read |
| AI 5 | Average Voltage | Average L-N voltage, V | Read |
| AI 1 | Frequency | Frequency, Hz | Read |
Watch out for
- I/O and alarm-channel objects are created only when the hardware or option is present, so the object list changes with the module fit.
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Frequency | Hz | Read | ||
| AI | 2 | Phase A Voltage | V | Read | ||
| AI | 3 | Phase B Voltage | V | Read | ||
| AI | 4 | Phase C Voltage | V | Read | ||
| AImin | 5 | Average Voltage | V | Read | ||
| AI | 6 | Line Voltage AB | V | Read | ||
| AI | 7 | Line Voltage BC | V | Read | ||
| AI | 8 | Line Voltage CA | V | Read | ||
| AI | 9 | Average Line Voltage | V | Read | ||
| AI | 10 | Phase A Current | A | Read | ||
| AI | 11 | Phase B Current | A | Read | ||
| AI | 12 | Phase C Current | A | Read | ||
| AImin | 13 | Average Current | A | Read | ||
| AI | 14 | Neutral Current | A | Read | ||
| AI | 15 | Phase A Active Power | kW | Read | ||
| AI | 16 | Phase B Active Power | kW | Read | ||
| AI | 17 | Phase C Active Power | kW | Read | ||
| AImin | 18 | Total Active Power | kW | Read | ||
| AI | 19 | Phase A Reactive Power | kvar | Read | ||
| AI | 20 | Phase B Reactive Power | kvar | Read | ||
| AI | 21 | Phase C Reactive Power | kvar | Read | ||
| AI | 22 | Total Reactive Power | kvar | Read | ||
| AI | 23 | Phase A Apparent Power | kVA | Read | ||
| AI | 24 | Phase B Apparent Power | kVA | Read | ||
| AI | 25 | Phase C Apparent Power | kVA | Read | ||
| AI | 26 | Total Apparent Power | kVA | Read | ||
| AI | 27 | Phase A Power Factor | PF | Read | ||
| AI | 28 | Phase B Power Factor | PF | Read | ||
| AI | 29 | Phase C Power Factor | PF | Read | ||
| AImin | 30 | Total Power Factor | PF | Read | ||
| AI | 31 | Voltage Unbalance Factor | % | Read | ||
| AI | 32 | Current Unbalance Factor | % | Read | ||
| AI | 33 | Load Type | Read | |||
| AImin | 34 | Active Power Demand | kW | Read | ||
| AI | 35 | Reactive Power Demand | kvar | Read | ||
| AI | 36 | Apparent Power Demand | kVA | Read | ||
| AI | 37 | Phase A Current Demand | A | Read | ||
| AI | 38 | Phase B Current Demand | A | Read | ||
| AI | 39 | Phase C Current Demand | A | Read | ||
| AImin | 40 | Import Active Energy | kWh | Read | ||
| AI | 41 | Export Active Energy | kWh | Read | ||
| AI | 42 | Import Reactive Energy | kvarh | Read | ||
| AI | 43 | Export Reactive Energy | kvarh | Read | ||
| AI | 44 | Energy Total | kWh | Read | ||
| AI | 45 | Energy Net | kWh | Read | ||
| AI | 46 | Reactive Energy Total | kvarh | Read | ||
| AI | 47 | Reactive Energy Net | kvarh | Read | ||
| AI | 48 | Apparent Energy | kVAh | Read | ||
| AI | 49 | Phase A Import Active Energy | kWh | Read | ||
| AI | 50 | Phase A Export Active Energy | kWh | Read | ||
| AI | 51 | Phase B Import Active Energy | kWh | Read | ||
| AI | 52 | Phase B Export Active Energy | kWh | Read | ||
| AI | 53 | Phase C Import Active Energy | kWh | Read | ||
| AI | 54 | Phase C Export Active Energy | kWh | Read | ||
| AI | 55 | Phase A Import Reactive Energy | kvarh | Read | ||
| AI | 56 | Phase A Export Reactive Energy | kvarh | Read | ||
| AI | 57 | Phase B Import Reactive Energy | kvarh | Read | ||
| AI | 58 | Phase B Export Reactive Energy | kvarh | Read | ||
| AI | 59 | Phase C Import Reactive Energy | kvarh | Read | ||
| AI | 60 | Phase C Export Reactive Energy | kvarh | Read | ||
| AI | 61 | Phase A Apparent Energy | kVAh | Read | ||
| AI | 62 | Phase B Apparent Energy | kVAh | Read | ||
| AI | 63 | Phase C Apparent Energy | kVAh | Read | ||
| AI | 64 | Phase A Voltage THD | % | Read | ||
| AI | 65 | Phase B Voltage THD | % | Read | ||
| AI | 66 | Phase C Voltage THD | % | Read | ||
| AI | 67 | Average Voltage THD | % | Read | ||
| AI | 68 | Phase A Current THD | % | Read | ||
| AI | 69 | Phase B Current THD | % | Read | ||
| AI | 70 | Phase C Current THD | % | Read | ||
| AI | 71 | Average Current THD | % | Read | ||
| AI | 72 | Input Channel 1 Active Power Demand kW | Max Phase A Active Power demand | kW | Read | |
| AI | 73 | Input Channel 2 Active Power Demand kW | Max Phase B Active Power demand | kW | Read | |
| AI | 74 | Input Channel 3 Active Power Demand kW | Max Phase C Active Power demand | kW | Read | |
| AI | 75 | Input Channel 1 Reactive Power Demand kvar | Max Phase A Reactive Power demand | kvar | Read | |
| AI | 76 | Input Channel 2 Reactive Power Demand kvar | Max Phase B Reactive Power demand | kvar | Read | |
| AI | 77 | Input Channel 3 Reactive Power Demand kvar | Max Phase C Reactive Power demand | kvar | Read | |
| AI | 78 | Input Channel 1 Apparent Power Demand kVA | Max Phase A Apparent Power Demand | kVA | Read | |
| AI | 79 | Input Channel 2 Apparent Power Demand kVA | Max Phase B Apparent Power Demand | kVA | Read | |
| AI | 80 | Input Channel 3 Apparent Power Demand kVA | Max Phase C Apparent Power Demand | kVA | Read | |
| AI | 81 | Active Power Demand kW | Max System Active Power demand | kW | Read | |
| AI | 82 | Reactive Power Demand kvar | Max System Reactive Power Demand | kvar | Read | |
| AI | 83 | Apparent Power Demand kVA | Max System Apparent Power Demand | kVA | Read | |
| AI | 1001 | IO21-AO1 | mA or V | Read | ||
| AI | 1002 | IO21-AO2 | mA or V | Read | ||
| AI | 1003 | IO22-AO1 | mA or V | Read | ||
| AI | 1004 | IO22-AO2 | mA or V | Read | ||
| AI | 1005 | IO31-AI1 | mA or V | Read | ||
| AI | 1006 | IO31-AI2 | mA or V | Read | ||
| AI | 1007 | IO32-AI1 | mA or V | Read | ||
| AI | 1008 | IO32-AI2 | mA or V | Read | ||
| AI | 2001 | IO11-DI1-COUNTER | Read | |||
| AI | 2002 | IO11-DI2-COUNTER | Read | |||
| AI | 2003 | IO11-DI3-COUNTER | Read | |||
| AI | 2004 | IO11-DI4-COUNTER | Read | |||
| AI | 2005 | IO11-DI5-COUNTER | Read | |||
| AI | 2006 | IO11-DI6-COUNTER | Read | |||
| AI | 2007 | IO21-DI1-COUNTER | Read | |||
| AI | 2008 | IO21-DI2-COUNTER | Read | |||
| AI | 2009 | IO21-DI3-COUNTER | Read | |||
| AI | 2010 | IO21-DI4-COUNTER | Read | |||
| AI | 2011 | IO31-DI1-COUNTER | Read | |||
| AI | 2012 | IO31-DI2-COUNTER | Read | |||
| AI | 2013 | IO31-DI3-COUNTER | Read | |||
| AI | 2014 | IO31-DI4-COUNTER | Read | |||
| AI | 2015 | IO12-DI1-COUNTER | Read | |||
| AI | 2016 | IO12-DI2-COUNTER | Read | |||
| AI | 2017 | IO12-DI3-COUNTER | Read | |||
| AI | 2018 | IO12-DI4-COUNTER | Read | |||
| AI | 2019 | IO12-DI5-COUNTER | Read | |||
| AI | 2020 | IO12-DI6-COUNTER | Read | |||
| AI | 2021 | IO22-DI1-COUNTER | Read | |||
| AI | 2022 | IO22-DI2-COUNTER | Read | |||
| AI | 2023 | IO22-DI3-COUNTER | Read | |||
| AI | 2024 | IO22-DI4-COUNTER | Read | |||
| AI | 2025 | IO32-DI1-COUNTER | Read | |||
| AI | 2026 | IO32-DI2-COUNTER | Read | |||
| AI | 2027 | IO32-DI3-COUNTER | Read | |||
| AI | 2028 | IO32-DI4-COUNTER | Read | |||
| BI | 1 | IO11-DI1 | Read | |||
| BI | 2 | IO11-DI2 | Read | |||
| BI | 3 | IO11-DI3 | Read | |||
| BI | 4 | IO11-DI4 | Read | |||
| BI | 5 | IO11-DI5 | Read | |||
| BI | 6 | IO11-DI6 | Read | |||
| BI | 7 | IO21-DI1 | Read | |||
| BI | 8 | IO21-DI2 | Read | |||
| BI | 9 | IO21-DI3 | Read | |||
| BI | 10 | IO21-DI4 | Read | |||
| BI | 11 | IO31-DI1 | Read | |||
| BI | 12 | IO31-DI2 | Read | |||
| BI | 13 | IO31-DI3 | Read | |||
| BI | 14 | IO31-DI4 | Read | |||
| BI | 15 | IO12-DI1 | Read | |||
| BI | 16 | IO12-DI2 | Read | |||
| BI | 17 | IO12-DI3 | Read | |||
| BI | 18 | IO12-DI4 | Read | |||
| BI | 19 | IO12-DI5 | Read | |||
| BI | 20 | IO12-DI6 | Read | |||
| BI | 21 | IO22-DI1 | Read | |||
| BI | 22 | IO22-DI2 | Read | |||
| BI | 23 | IO22-DI3 | Read | |||
| BI | 24 | IO22-DI4 | Read | |||
| BI | 25 | IO32-DI1 | Read | |||
| BI | 26 | IO32-DI2 | Read | |||
| BI | 27 | IO32-DI3 | Read | |||
| BI | 28 | IO32-DI4 | Read | |||
| BI | 29 | Alarm Channel 1 Status | Read | |||
| BI | 30 | Alarm Channel 2 Status | Read | |||
| BI | 31 | Alarm Channel 3 Status | Read | |||
| BI | 32 | Alarm Channel 4 Status | Read | |||
| BI | 33 | Alarm Channel 5 Status | Read | |||
| BI | 34 | Alarm Channel 6 Status | Read | |||
| BI | 35 | Alarm Channel 7 Status | Read | |||
| BI | 36 | Alarm Channel 8 Status | Read | |||
| BI | 37 | Alarm Channel 9 Status | Read | |||
| BI | 38 | Alarm Channel 10 Status | Read | |||
| BI | 39 | Alarm Channel 11 Status | Read | |||
| BI | 40 | Alarm Channel 12 Status | Read | |||
| BI | 41 | Alarm Channel 13 Status | Read | |||
| BI | 42 | Alarm Channel 14 Status | Read | |||
| BI | 43 | Alarm Channel 15 Status | Read | |||
| BI | 44 | Alarm Channel 16 Status | Read |
No points match these filters.
Object ID lookup: Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters point IDs by name
AI1FrequencyAI2Phase A VoltageAI3Phase B VoltageAI4Phase C VoltageAI5Average VoltageAI6Line Voltage ABAI7Line Voltage BCAI8Line Voltage CAAI9Average Line VoltageAI10Phase A CurrentAI11Phase B CurrentAI12Phase C CurrentAI13Average CurrentAI14Neutral CurrentAI15Phase A Active PowerAI16Phase B Active PowerAI17Phase C Active PowerAI18Total Active PowerAI19Phase A Reactive PowerAI20Phase B Reactive PowerAI21Phase C Reactive PowerAI22Total Reactive PowerAI23Phase A Apparent PowerAI24Phase B Apparent PowerAI25Phase C Apparent PowerAI26Total Apparent PowerAI27Phase A Power FactorAI28Phase B Power FactorAI29Phase C Power FactorAI30Total Power FactorAI31Voltage Unbalance FactorAI32Current Unbalance FactorAI33Load TypeAI34Active Power DemandAI35Reactive Power DemandAI36Apparent Power DemandAI37Phase A Current DemandAI38Phase B Current DemandAI39Phase C Current DemandAI40Import Active EnergyAI41Export Active EnergyAI42Import Reactive EnergyAI43Export Reactive EnergyAI44Energy TotalAI45Energy NetAI46Reactive Energy TotalAI47Reactive Energy NetAI48Apparent EnergyAI49Phase A Import Active EnergyAI50Phase A Export Active EnergyAI51Phase B Import Active EnergyAI52Phase B Export Active EnergyAI53Phase C Import Active EnergyAI54Phase C Export Active EnergyAI55Phase A Import Reactive EnergyAI56Phase A Export Reactive EnergyAI57Phase B Import Reactive EnergyAI58Phase B Export Reactive EnergyAI59Phase C Import Reactive EnergyAI60Phase C Export Reactive EnergyAI61Phase A Apparent EnergyAI62Phase B Apparent EnergyAI63Phase C Apparent EnergyAI64Phase A Voltage THDAI65Phase B Voltage THDAI66Phase C Voltage THDAI67Average Voltage THDAI68Phase A Current THDAI69Phase B Current THDAI70Phase C Current THDAI71Average Current THDAI72Input Channel 1 Active Power Demand kWAI73Input Channel 2 Active Power Demand kWAI74Input Channel 3 Active Power Demand kWAI75Input Channel 1 Reactive Power Demand kvarAI76Input Channel 2 Reactive Power Demand kvarAI77Input Channel 3 Reactive Power Demand kvarAI78Input Channel 1 Apparent Power Demand kVAAI79Input Channel 2 Apparent Power Demand kVAAI80Input Channel 3 Apparent Power Demand kVAAI81Active Power Demand kWAI82Reactive Power Demand kvarAI83Apparent Power Demand kVAAI1001IO21-AO1AI1002IO21-AO2AI1003IO22-AO1AI1004IO22-AO2AI1005IO31-AI1AI1006IO31-AI2AI1007IO32-AI1AI1008IO32-AI2AI2001IO11-DI1-COUNTERAI2002IO11-DI2-COUNTERAI2003IO11-DI3-COUNTERAI2004IO11-DI4-COUNTERAI2005IO11-DI5-COUNTERAI2006IO11-DI6-COUNTERAI2007IO21-DI1-COUNTERAI2008IO21-DI2-COUNTERAI2009IO21-DI3-COUNTERAI2010IO21-DI4-COUNTERAI2011IO31-DI1-COUNTERAI2012IO31-DI2-COUNTERAI2013IO31-DI3-COUNTERAI2014IO31-DI4-COUNTERAI2015IO12-DI1-COUNTERAI2016IO12-DI2-COUNTERAI2017IO12-DI3-COUNTERAI2018IO12-DI4-COUNTERAI2019IO12-DI5-COUNTERAI2020IO12-DI6-COUNTERAI2021IO22-DI1-COUNTERAI2022IO22-DI2-COUNTERAI2023IO22-DI3-COUNTERAI2024IO22-DI4-COUNTERAI2025IO32-DI1-COUNTERAI2026IO32-DI2-COUNTERAI2027IO32-DI3-COUNTERAI2028IO32-DI4-COUNTERBI1IO11-DI1BI2IO11-DI2BI3IO11-DI3BI4IO11-DI4BI5IO11-DI5BI6IO11-DI6BI7IO21-DI1BI8IO21-DI2BI9IO21-DI3BI10IO21-DI4BI11IO31-DI1BI12IO31-DI2BI13IO31-DI3BI14IO31-DI4BI15IO12-DI1BI16IO12-DI2BI17IO12-DI3BI18IO12-DI4BI19IO12-DI5BI20IO12-DI6BI21IO22-DI1BI22IO22-DI2BI23IO22-DI3BI24IO22-DI4BI25IO32-DI1BI26IO32-DI2BI27IO32-DI3BI28IO32-DI4BI29Alarm Channel 1 StatusBI30Alarm Channel 2 StatusBI31Alarm Channel 3 StatusBI32Alarm Channel 4 StatusBI33Alarm Channel 5 StatusBI34Alarm Channel 6 StatusBI35Alarm Channel 7 StatusBI36Alarm Channel 8 StatusBI37Alarm Channel 9 StatusBI38Alarm Channel 10 StatusBI39Alarm Channel 11 StatusBI40Alarm Channel 12 StatusBI41Alarm Channel 13 StatusBI42Alarm Channel 14 StatusBI43Alarm Channel 15 StatusBI44Alarm Channel 16 Status
Integration notes
- AI 1001-1008 exist only with the IO21/IO22 (AO) or IO31/IO32 (AI) modules; their units follow the module mode (mA or V).
- AI 2001-2028 exist only when the DI is configured as a pulse counter; BI 1-28 need a DI module.
- BI 29-44 (alarm channel status) exist only when the meter supports alarm channel status.
- Shares the Acuvim II metering objects (AI 1-71) with the older AXM-BIP module list, with corrected names at AI 5 and AI 51; it adds max-demand objects AI 72-83 and alarm channel status BI 29-44, and AI 1001-1004 are the IO21/IO22 analog outputs.
- Source: Accuenergy 'BACnet Points List AXM-WEB2' spreadsheet, firmware v1.39c, generated 2026-10-06.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
How many BACnet points does the Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) have?
This list has 163 BACnet objects: 119 analog inputs, 44 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP) BACnet documentation?
The source is BACnet Points List AXM-WEB2, revision 2026-10-06, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AXM-WEB2_BACnet-Object-List.xlsx.
What are the minimum BACnet points to integrate the Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)?
Start with AI 18 Total Active Power (Total real power, kW); AI 40 Import Active Energy (Imported energy, kWh); AI 34 Active Power Demand (Real power demand, kW); AI 30 Total Power Factor (Total power factor); AI 13 Average Current (Average current, A); AI 5 Average Voltage (Average L-N voltage, V); AI 1 Frequency (Frequency, Hz).
How do I check these points on the real AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet
Source: BACnet Points List AXM-WEB2 · rev. 2026-10-06. Object names, instances and units are reproduced as published; descriptions are our own.