Power and energy meter (DIN-rail submeter) · BACnet points list
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet) BACnet points list
Updated 7 November 2026
The AcuRev 1320 exposes the same objects on BACnet IP and BACnet MS/TP: 61 read-only Analog Inputs (voltage, current, power, PF, unbalance, THD, demand, the independent channel 4 and the 'Sum2' summation), 38 Large Analog Value energy totals, three DI pulse counters and three DI status inputs.
This page lists 105 BACnet objects for the Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
- Equipment
- Power and energy meter (DIN-rail submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 105 (0 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- v1.01p21
- Also known as
- AcuRev 1320, AcuRev 1320 BACnet
- Source document
- BACnet Points List AcuRev1320 · rev. 2026-10-10
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
All objects are read-only measurements. Read system power, imported energy, demand, PF, current and voltage; add channel 4 and the DI status inputs if they are wired.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 18 | P_rms | System real power, kW | Read |
| LAV 1 | Active_Energy_Imp | Imported energy, kWh | Read |
| AI 40 | p_dema | System kW demand | Read |
| AI 30 | PF_rms | System power factor | Read |
| AI 13 | Iavg_rms | Average current, A | Read |
| AI 5 | Uavg_rms | Average L-N voltage, V | Read |
| AI 1 | Freq_rms | Frequency, Hz | Read |
| AI 47 | P4_rms | Channel 4 real power, kW | Read |
Network setup
- BACnet IP and BACnet MS/TP expose the same object set.
Watch out for
- Energy totals are Large Analog Value objects; check that the BMS reads LAV.
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Freq_rms | System Frequency | Hz | Read | |
| AI | 2 | Ua_rms | Phase A Line-to-Neutral Voltage | V | Read | |
| AI | 3 | Ub_rms | Phase B Line-to-Neutral Voltage | V | Read | |
| AI | 4 | Uc_rms | Phase C Line-to-Neutral Voltage | V | Read | |
| AImin | 5 | Uavg_rms | Average Line-to-Neutral Voltage | V | Read | |
| AI | 6 | Uab_rms | Phase AB Line-to-Line Voltage | V | Read | |
| AI | 7 | Ubc_rms | Phase BC Line-to-Line Voltage | V | Read | |
| AI | 8 | Uca_rms | Phase CA Line-to-Line Voltage | V | Read | |
| AI | 9 | Ulavg_rms | Average Line-to-Line Voltage | V | Read | |
| AI | 10 | Ia_rms | Phase A Current | A | Read | |
| AI | 11 | Ib_rms | Phase B Current | A | Read | |
| AI | 12 | Ic_rms | Phase C Current | A | Read | |
| AImin | 13 | Iavg_rms | Average Current | A | Read | |
| AI | 14 | In_rms | Phase N Current | A | Read | |
| AI | 15 | Pa_rms | Phase A Active Power | kW | Read | |
| AI | 16 | Pb_rms | Phase B Active Power | kW | Read | |
| AI | 17 | Pc_rms | Phase C Active Power | kW | Read | |
| AImin | 18 | P_rms | System Active Power | kW | Read | |
| AI | 19 | Qa_rms | Phase A Reactive Power | kvar | Read | |
| AI | 20 | Qb_rms | Phase B Reactive Power | kvar | Read | |
| AI | 21 | Qc_rms | Phase C Reactive Power | kvar | Read | |
| AI | 22 | Q_rms | System Reactive Power | kvar | Read | |
| AI | 23 | Sa_rms | Phase A Apparent Power | kVA | Read | |
| AI | 24 | Sb_rms | Phase B Apparent Power | kVA | Read | |
| AI | 25 | Sc_rms | Phase C Apparent Power | kVA | Read | |
| AI | 26 | S_rms | System Apparent Power | kVA | Read | |
| AI | 27 | PFa_rms | Phase A Power Factor | PF | Read | |
| AI | 28 | PFb_rms | Phase B Power Factor | PF | Read | |
| AI | 29 | PFc_rms | Phase C Power Factor | PF | Read | |
| AImin | 30 | PF_rms | System Power Factor | PF | Read | |
| AI | 31 | U_unbl | Voltage Unbalance Negative | % | Read | |
| AI | 32 | I_unbl | Current Unbalance Negative | % | Read | |
| AI | 33 | Rlc_val | System Load Nature(82:Resistive load 76:Inductive load 67:Capacitive load) | Read | ||
| AI | 34 | V1_thd | Phase A Voltage THD | % | Read | |
| AI | 35 | V2_thd | Phase B Voltage THD | % | Read | |
| AI | 36 | V3_thd | Phase C Voltage THD | % | Read | |
| AI | 37 | I1_thd | Phase A Current THD | % | Read | |
| AI | 38 | I2_thd | Phase B Current THD | % | Read | |
| AI | 39 | I3_thd | Phase C Current THD | % | Read | |
| AImin | 40 | p_dema | System Active Power Demand | kW | Read | |
| AI | 41 | q_dema | System Reactive Power Demand | kvar | Read | |
| AI | 42 | s_dema | System Apparent Power Demand | kVA | Read | |
| AI | 43 | Ia_dema | Phase A Current Demand | A | Read | |
| AI | 44 | Ib_dema | Phase B Current Demand | A | Read | |
| AI | 45 | Ic_dema | Phase C Current Demand | A | Read | |
| AI | 46 | I4_rms | Channel 4 Current | A | Read | |
| AImin | 47 | P4_rms | Channel 4 Active Power | kW | Read | |
| AI | 48 | Q4_rms | Channel 4 Reactive Power | kvar | Read | |
| AI | 49 | S4_rms | Channel 4 Apparent Power | kVA | Read | |
| AI | 50 | PF4_rms | Channel 4 Power Factor | PF | Read | |
| AI | 51 | I4_thd | Channel 4 Current THD | % | Read | |
| AI | 52 | I4_dema | Channel 4 Current Demand | A | Read | |
| AI | 53 | Isum2_avg_rms | Summation 2 Average Current | A | Read | |
| AI | 54 | Psum2_rms | Summation 2 Active Power | kW | Read | |
| AI | 55 | Qsum2_rms | Summation 2 Reactive Power | kvar | Read | |
| AI | 56 | Ssum2_rms | Summation 2 Apparent Power | kVA | Read | |
| AI | 57 | PFsum2_rms | Summation 2 Power Factor | PF | Read | |
| AI | 58 | Rlc_sum2_val | Summation 2 Load Nature(82:Resistive load 76:Inductive load 67:Capacitive load) | Read | ||
| AI | 59 | Psum2_dema | Summation 2 Active Power Demand | kW | Read | |
| AI | 60 | Qsum2_dema | Summation 2 Reactive Power Demand | kvar | Read | |
| AI | 61 | Ssum2_dema | Summation 2 Apparent Power Demand | kVA | Read | |
| LAVmin | 1 | Active_Energy_Imp | System active energy import | kWh | Read | |
| LAV | 2 | Active_Energy_Exp | System active energy export | kWh | Read | |
| LAV | 3 | Reactive_Energy_Imp | System reactive energy import | kvarh | Read | |
| LAV | 4 | Reactive_Energy_Exp | System reactive energy export | kvarh | Read | |
| LAV | 5 | Active_Energy_Total | System active energy total | kWh | Read | |
| LAV | 6 | Active_Energy_Net | System active energy net | kWh | Read | |
| LAV | 7 | Reactive_Energy_Total | System reactive energy total | kvarh | Read | |
| LAV | 8 | Reactive_Energy_Net | System reactive energy net | kvarh | Read | |
| LAV | 9 | Apparent_Energy | System apparent energy total | kVAh | Read | |
| LAV | 10 | Active_Energy_Imp_A | Phase A active energy import | kWh | Read | |
| LAV | 11 | Active_Energy_Exp_A | Phase A active energy export | kWh | Read | |
| LAV | 12 | Active_Energy_Imp_B | Phase B active energy import | kWh | Read | |
| LAV | 13 | Active_Energy_Exp_B | Phase B active energy export | kWh | Read | |
| LAV | 14 | Active_Energy_Imp_C | Phase C active energy import | kWh | Read | |
| LAV | 15 | Active_Energy_Exp_C | Phase C active energy export | kWh | Read | |
| LAV | 16 | Reactive_Energy_Imp_A | Phase A reactive energy import | kvarh | Read | |
| LAV | 17 | Reactive_Energy_Exp_A | Phase A reactive energy export | kvarh | Read | |
| LAV | 18 | Reactive_Energy_Imp_B | Phase B reactive energy import | kvarh | Read | |
| LAV | 19 | Reactive_Energy_Exp_B | Phase B reactive energy export | kvarh | Read | |
| LAV | 20 | Reactive_Energy_Imp_C | Phase C reactive energy import | kvarh | Read | |
| LAV | 21 | Reactive_Energy_Exp_C | Phase C reactive energy export | kvarh | Read | |
| LAV | 22 | Apparent_Energy_A | Phase A apparent energy total | kVAh | Read | |
| LAV | 23 | Apparent_Energy_B | Phase B apparent energy total | kVAh | Read | |
| LAV | 24 | Apparent_Energy_C | Phase C apparent energy total | kVAh | Read | |
| LAV | 25 | CH4_Active_Energy_Imp | Channel 4 active energy import | kWh | Read | |
| LAV | 26 | CH4_Active_Energy_Exp | Channel 4 active energy export | kWh | Read | |
| LAV | 27 | CH4_Reactive_Energy_Imp | Channel 4 reactive energy import | kvarh | Read | |
| LAV | 28 | CH4_Reactive_Energy_Exp | Channel 4 reactive energy export | kvarh | Read | |
| LAV | 29 | CH4_Apparent_Energy_Total | Channel 4 apparent energy total | kVAh | Read | |
| LAV | 30 | Sum2_Active_Energy_Imp | Summation 2 active energy import | kWh | Read | |
| LAV | 31 | Sum2_Active_Energy_Exp | Summation 2 active energy export | kWh | Read | |
| LAV | 32 | Sum2_Reactive_Energy_Imp | Summation 2 reactive energy import | kvarh | Read | |
| LAV | 33 | Sum2_Reactive_Energy_Exp | Summation 2 reactive energy export | kvarh | Read | |
| LAV | 34 | Sum2_Active_Energy_Total | Summation 2 active energy total | kWh | Read | |
| LAV | 35 | Sum2_Active_Energy_Net | Summation 2 active energy net | kWh | Read | |
| LAV | 36 | Sum2_Reactive_Energy_Total | Summation 2 reactive energy total | kvarh | Read | |
| LAV | 37 | Sum2_Reactive_Energy_Net | Summation 2 reactive energy net | kvarh | Read | |
| LAV | 38 | Sum2_Apparent_Energy_Total | Summation 2 apparent energy total | kVAh | Read | |
| Other | 1 | DI1_pc | DI1 pulse counter | Read | ||
| Other | 2 | DI2_pc | DI2 pulse counter | Read | ||
| Other | 3 | DI3_pc | DI3 pulse counter | Read | ||
| BI | 1 | DI1_s | Digital Input 1 Status | Read | ||
| BI | 2 | DI2_s | Digital Input 2 Status | Read | ||
| BI | 3 | DI3_s | Digital Input 3 Status | Read |
No points match these filters.
Object ID lookup: Accuenergy AcuRev 1320 series DIN-rail multi-channel meter point IDs by name
AI1Freq_rmsAI2Ua_rmsAI3Ub_rmsAI4Uc_rmsAI5Uavg_rmsAI6Uab_rmsAI7Ubc_rmsAI8Uca_rmsAI9Ulavg_rmsAI10Ia_rmsAI11Ib_rmsAI12Ic_rmsAI13Iavg_rmsAI14In_rmsAI15Pa_rmsAI16Pb_rmsAI17Pc_rmsAI18P_rmsAI19Qa_rmsAI20Qb_rmsAI21Qc_rmsAI22Q_rmsAI23Sa_rmsAI24Sb_rmsAI25Sc_rmsAI26S_rmsAI27PFa_rmsAI28PFb_rmsAI29PFc_rmsAI30PF_rmsAI31U_unblAI32I_unblAI33Rlc_valAI34V1_thdAI35V2_thdAI36V3_thdAI37I1_thdAI38I2_thdAI39I3_thdAI40p_demaAI41q_demaAI42s_demaAI43Ia_demaAI44Ib_demaAI45Ic_demaAI46I4_rmsAI47P4_rmsAI48Q4_rmsAI49S4_rmsAI50PF4_rmsAI51I4_thdAI52I4_demaAI53Isum2_avg_rmsAI54Psum2_rmsAI55Qsum2_rmsAI56Ssum2_rmsAI57PFsum2_rmsAI58Rlc_sum2_valAI59Psum2_demaAI60Qsum2_demaAI61Ssum2_demaLAV1Active_Energy_ImpLAV2Active_Energy_ExpLAV3Reactive_Energy_ImpLAV4Reactive_Energy_ExpLAV5Active_Energy_TotalLAV6Active_Energy_NetLAV7Reactive_Energy_TotalLAV8Reactive_Energy_NetLAV9Apparent_EnergyLAV10Active_Energy_Imp_ALAV11Active_Energy_Exp_ALAV12Active_Energy_Imp_BLAV13Active_Energy_Exp_BLAV14Active_Energy_Imp_CLAV15Active_Energy_Exp_CLAV16Reactive_Energy_Imp_ALAV17Reactive_Energy_Exp_ALAV18Reactive_Energy_Imp_BLAV19Reactive_Energy_Exp_BLAV20Reactive_Energy_Imp_CLAV21Reactive_Energy_Exp_CLAV22Apparent_Energy_ALAV23Apparent_Energy_BLAV24Apparent_Energy_CLAV25CH4_Active_Energy_ImpLAV26CH4_Active_Energy_ExpLAV27CH4_Reactive_Energy_ImpLAV28CH4_Reactive_Energy_ExpLAV29CH4_Apparent_Energy_TotalLAV30Sum2_Active_Energy_ImpLAV31Sum2_Active_Energy_ExpLAV32Sum2_Reactive_Energy_ImpLAV33Sum2_Reactive_Energy_ExpLAV34Sum2_Active_Energy_TotalLAV35Sum2_Active_Energy_NetLAV36Sum2_Reactive_Energy_TotalLAV37Sum2_Reactive_Energy_NetLAV38Sum2_Apparent_Energy_TotalBI1DI1_sBI2DI2_sBI3DI3_s
Integration notes
- DI pulse counters are Pulse Converter objects (listed as type Other).
- AI 33 / AI 58 load nature: 82 resistive, 76 inductive, 67 capacitive.
- Sum2 objects are a summation channel; channel 4 is the independent current input.
- Source: Accuenergy 'BACnet Points List AcuRev1320' spreadsheet, firmware v1.01p21, generated 2026-10-10.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AcuRev 1320 series DIN-rail multi-channel meter (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
How many BACnet points does the Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet) have?
This list has 105 BACnet objects: 61 analog inputs, 3 binary inputs, 38 large analog values, 3 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet) BACnet documentation?
The source is BACnet Points List AcuRev1320, revision 2026-10-10, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev-1320_BACnet-Object-List.xlsx.
What are the minimum BACnet points to integrate the Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)?
Start with AI 18 P_rms (System real power, kW); LAV 1 Active_Energy_Imp (Imported energy, kWh); AI 40 p_dema (System kW demand); AI 30 PF_rms (System power factor); AI 13 Iavg_rms (Average current, A); AI 5 Uavg_rms (Average L-N voltage, V); AI 1 Freq_rms (Frequency, Hz); AI 47 P4_rms (Channel 4 real power, kW).
How do I check these points on the real AcuRev 1320 series DIN-rail multi-channel meter (BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet - Power and energy meter (communication module)
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Accuenergy AXM-WEB2 Ethernet / web module fitted to Acuvim II series meters, with optional IO11/12, IO21/22 and IO31/32 modules.
Also known as: AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
Source: BACnet Points List AcuRev1320 · rev. 2026-10-10. Object names, instances and units are reproduced as published; descriptions are our own.