Power and energy meter (BACnet IP module) · BACnet points list

Accuenergy Acuvim II with AXM-BIP BACnet IP module BACnet points list

Updated 28 October 2026

Short answer

The AXM-BIP clips onto an Acuvim II power meter and serves its readings over BACnet IP with no mapping needed. It exposes 71 metering Analog Inputs (voltage, current, power, demand, energy, THD), plus Binary Inputs, analog-input values and pulse counters for any AXM-IO modules fitted. Everything is read-only.

This page lists 135 BACnet objects for the Accuenergy Acuvim II with AXM-BIP BACnet IP module — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.

Manufacturer
Accuenergy
Model
Acuvim II with AXM-BIP BACnet IP module
Equipment
Power and energy meter (BACnet IP module)
Equipment type
Thermostats, sensors & meters
BACnet objects
135 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102
Source document
BACnet for Acuvim II Series Power Meter, User's Manual · 1040E2102 (V2.0.1) · rev. 2023-08
Download CSV 135 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Accuenergy Acuvim II with AXM-BIP BACnet IP module

Integration in brief

Set the meter's second serial port to 38400 baud, 8N1 and protocol 'Other', give the AXM-BIP an IP address from the front panel, then set the device instance and UDP port in its web page. Read total power, imported energy, demand, power factor, current and voltage.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 18Total Active PowerTotal real power, kWRead
AI 40Import Active EnergyImported energy total, kWhRead
AI 34Active Power DemandReal power demand, kWRead
AI 26Total Apparent PowerTotal apparent power, kVARead
AI 30Total Power FactorThree-phase power factorRead
AI 13Average CurrentAverage phase current, ARead
AI 9Average Line VoltageAverage line-to-line voltage, V (see notes)Read
AI 1FrequencySupply frequency, HzRead

Network setup

Watch out for

Accuenergy Acuvim II with AXM-BIP BACnet IP module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

135 of 135 shown
Type
AnalogBinary
Show
Accuenergy Acuvim II with AXM-BIP BACnet IP module BACnet Points List
DescriptionStates
AImin1FrequencyHzRead
AI2Phase A VoltageVRead
AI3Phase B VoltageVRead
AI4Phase C VoltageVRead
AI5Average Line VoltageName printed for both AI 5 and AI 9; see notesVRead
AI6Line Voltage ABVRead
AI7Line Voltage BCVRead
AI8Line Voltage CAVRead
AImin9Average Line VoltageName printed for both AI 5 and AI 9; see notesVRead
AI10Phase A CurrentARead
AI11Phase B CurrentARead
AI12Phase C CurrentARead
AImin13Average CurrentARead
AI14Neutral CurrentARead
AI15Phase A Active PowerkWRead
AI16Phase B Active PowerkWRead
AI17Phase C Active PowerkWRead
AImin18Total Active PowerkWRead
AI19Phase A Reactive PowerkvarRead
AI20Phase B Reactive PowerkvarRead
AI21Phase C Reactive PowerkvarRead
AI22Total Reactive PowerkvarRead
AI23Phase A Apparent PowerkVARead
AI24Phase B Apparent PowerkVARead
AI25Phase C Apparent PowerkVARead
AImin26Total Apparent PowerkVARead
AI27Phase A Power FactorNo units givenRead
AI28Phase B Power FactorNo units givenRead
AI29Phase C Power FactorNo units givenRead
AImin30Total Power FactorNo units givenRead
AI31Voltage Unbalance Factor%Read
AI32Current Unbalance Factor%Read
AI33Load TypeLoad characteristic codeRead
AImin34Active Power DemandkWRead
AI35Reactive Power DemandkvarRead
AI36Apparent Power DemandkVARead
AI37Phase A Current DemandARead
AI38Phase B Current DemandARead
AI39Phase C Current DemandARead
AImin40Import Active EnergykWhRead
AI41Export Active EnergykWhRead
AI42Import Reactive EnergykWhRead
AI43Export Reactive EnergykWhRead
AI44Energy TotalkWhRead
AI45Energy NetkWhRead
AI46Reactive Energy TotalkvarhRead
AI47Reactive Energy NetkvarhRead
AI48Apparent EnergykVAhRead
AI49Phase A Import Active EnergykWhRead
AI50Phase A Export Active EnergykWhRead
AI51Phase B Export Active EnergyName printed for both AI 51 and AI 52; see noteskWhRead
AI52Phase B Export Active EnergyName printed for both AI 51 and AI 52; see noteskWhRead
AI53Phase C Import Active EnergykWhRead
AI54Phase C Export Active EnergykWhRead
AI55Phase A Import Reactive EnergykvarhRead
AI56Phase A Export Reactive EnergykvarhRead
AI57Phase B Import Reactive EnergykvarhRead
AI58Phase B Export Reactive EnergykvarhRead
AI59Phase C Import Reactive EnergykvarhRead
AI60Phase C Export Reactive EnergykvarhRead
AI61Phase A Apparent EnergykVAhRead
AI62Phase B Apparent EnergykVAhRead
AI63Phase C Apparent EnergykVAhRead
AI64Phase A Voltage THD%Read
AI65Phase B Voltage THD%Read
AI66Phase C Voltage THD%Read
AI67Average Voltage THD%Read
AI68Phase A Current THD%Read
AI69Phase B Current THD%Read
AI70Phase C Current THD%Read
AI71Average Current THD%Read
BI1IO11-DI1Digital input on I/O module IO11Read
BI2IO11-DI2Digital input on I/O module IO11Read
BI3IO11-DI3Digital input on I/O module IO11Read
BI4IO11-DI4Digital input on I/O module IO11Read
BI5IO11-DI5Digital input on I/O module IO11Read
BI6IO11-DI6Digital input on I/O module IO11Read
BI7IO21-DI1Digital input on I/O module IO21Read
BI8IO21-DI2Digital input on I/O module IO21Read
BI9IO21-DI3Digital input on I/O module IO21Read
BI10IO21-DI4Digital input on I/O module IO21Read
BI11IO31-DI1Digital input on I/O module IO31Read
BI12IO31-DI2Digital input on I/O module IO31Read
BI13IO31-DI3Digital input on I/O module IO31Read
BI14IO31-DI4Digital input on I/O module IO31Read
BI15IO12-DI1Digital input on I/O module IO12Read
BI16IO12-D2Digital input on I/O module IO12Read
BI17IO12-DI3Digital input on I/O module IO12Read
BI18IO12-DI4Digital input on I/O module IO12Read
BI19IO12-DI5Digital input on I/O module IO12Read
BI20IO12-DI6Digital input on I/O module IO12Read
BI21IO22-DI1Digital input on I/O module IO22Read
BI22IO22-DI2Digital input on I/O module IO22Read
BI23IO22-DI3Digital input on I/O module IO22Read
BI24IO22-DI4Digital input on I/O module IO22Read
BI25IO32-DI1Digital input on I/O module IO32Read
BI26IO32-DI2Digital input on I/O module IO32Read
BI27IO32-DI3Digital input on I/O module IO32Read
BI28IO32-DI4Digital input on I/O module IO32Read
AI1001IO21-AI1Analog input on I/O module IO21mA/VoltsRead
AI1002IO21-AI2Analog input on I/O module IO21mA/VoltsRead
AI1003IO22-AI3Analog input on I/O module IO22mA/VoltsRead
AI1004IO22-AI4Analog input on I/O module IO22mA/VoltsRead
AI1005IO31-AI1Analog input on I/O module IO31mA/VoltsRead
AI1006IO31-AI2Analog input on I/O module IO31mA/VoltsRead
AI1007IO32-AI3Analog input on I/O module IO32mA/VoltsRead
AI1008IO32-AI4Analog input on I/O module IO32mA/VoltsRead
AI2001IO11-DI1-CounterPulse count of digital input IO11-DI1Read
AI2002IO11-DI2-CounterPulse count of digital input IO11-DI2Read
AI2003IO11-DI3-CounterPulse count of digital input IO11-DI3Read
AI2004IO11-DI4-CounterPulse count of digital input IO11-DI4Read
AI2005IO11-DI5-CounterPulse count of digital input IO11-DI5Read
AI2006IO11-DI6-CounterPulse count of digital input IO11-DI6Read
AI2007IO21-DI1-CounterPulse count of digital input IO21-DI1Read
AI2008IO21-DI2-CounterPulse count of digital input IO21-DI2Read
AI2009IO21-DI3-CounterPulse count of digital input IO21-DI3Read
AI2010IO21-DI4-CounterPulse count of digital input IO21-DI4Read
AI2011IO31-DI1-CounterPulse count of digital input IO31-DI1Read
AI2012IO31-DI2-CounterPulse count of digital input IO31-DI2Read
AI2013IO31-DI3-CounterPulse count of digital input IO31-DI3Read
AI2014IO31-DI4-CounterPulse count of digital input IO31-DI4Read
AI2015IO12-DI1-CounterPulse count of digital input IO12-DI1Read
AI2016IO12-D2-CounterPulse count of digital input IO12-D2Read
AI2017IO12-DI3-CounterPulse count of digital input IO12-DI3Read
AI2018IO12-DI4-CounterPulse count of digital input IO12-DI4Read
AI2019IO12-DI5-CounterPulse count of digital input IO12-DI5Read
AI2020IO12-DI6-CounterPulse count of digital input IO12-DI6Read
AI2021IO22-DI1-CounterPulse count of digital input IO22-DI1Read
AI2022IO22-DI2-CounterPulse count of digital input IO22-DI2Read
AI2023IO22-DI3-CounterPulse count of digital input IO22-DI3Read
AI2024IO22-DI4-CounterPulse count of digital input IO22-DI4Read
AI2025IO32-DI1-CounterPulse count of digital input IO32-DI1Read
AI2026IO32-DI2-CounterPulse count of digital input IO32-DI2Read
AI2027IO32-DI3-CounterPulse count of digital input IO32-DI3Read
AI2028IO32-DI4-CounterPulse count of digital input IO32-DI4Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acuvim II with AXM-BIP BACnet IP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accuenergy Acuvim II with AXM-BIP BACnet IP module

How many BACnet points does the Accuenergy Acuvim II with AXM-BIP BACnet IP module have?

This list has 135 BACnet objects: 107 analog inputs, 28 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accuenergy Acuvim II with AXM-BIP BACnet IP module BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Accuenergy Acuvim II with AXM-BIP BACnet IP module BACnet documentation?

The source is BACnet for Acuvim II Series Power Meter, User's Manual (1040E2102 (V2.0.1)), revision 2023-08, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/Acuvim-II-Power-Meter-BACnet-User-Manual-EN.pdf.

What are the minimum BACnet points to integrate the Accuenergy Acuvim II with AXM-BIP BACnet IP module?

Start with AI 18 Total Active Power (Total real power, kW); AI 40 Import Active Energy (Imported energy total, kWh); AI 34 Active Power Demand (Real power demand, kW); AI 26 Total Apparent Power (Total apparent power, kVA); AI 30 Total Power Factor (Three-phase power factor); AI 13 Average Current (Average phase current, A); AI 9 Average Line Voltage (Average line-to-line voltage, V (see notes)); AI 1 Frequency (Supply frequency, Hz).

How do I check these points on the real Acuvim II with AXM-BIP BACnet IP module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accuenergy BACnet points lists

Source: BACnet for Acuvim II Series Power Meter, User's Manual · 1040E2102 (V2.0.1) · rev. 2023-08. Object names, instances and units are reproduced as published; descriptions are our own.