Power and energy meter (BACnet MS/TP module) · BACnet points list

Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet points list

Updated 28 October 2026

Short answer

The AXM-BMS clips onto an Acuvim II power meter and serves 56 fixed Analog Value objects over BACnet MS/TP: frequency, voltages, currents, power per phase and total, power factor, unbalance, demand, energy totals and THD. No mapping is needed. The manual lists object names and data types but no units.

This page lists 56 BACnet objects for the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.

Manufacturer
Accuenergy
Model
Acuvim II with AXM-BMS BACnet MS/TP module
Equipment
Power and energy meter (BACnet MS/TP module)
Equipment type
Thermostats, sensors & meters
BACnet objects
56 (0 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102
Source document
BACnet for Acuvim II Series Power Meter, User's Manual · 1040E2102 (V2.0.1) · rev. 2023-08
Download CSV 56 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module

Integration in brief

Set the meter's second port protocol to BACNET, then set the module's MS/TP MAC address, baud rate and max info frames from the meter's NET pages and reset the module. Read total power, imported energy, demand, power factor, current and voltage.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 17P_rmsTotal active power, WRead
AV 39Active_Energy_IMPImported active energy totalRead
AV 33P_demaActive power demandRead
AV 25S_rmsTotal apparent powerRead
AV 29PF_rmsTotal power factorRead
AV 12Iavg_rmsAverage phase currentRead
AV 8Ulavg_rmsAverage line-to-line voltageRead
AV 0Freq_rmsSupply frequencyRead

Network setup

Watch out for

Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

56 of 56 shown
Type
Analog
Show
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet Points List
DescriptionStates
AVmin0Freq_rmsFrequency (Float)Read
AV1Ua_rmsVoltage A (Float)Read
AV2Ub_rmsVoltage B (Float)Read
AV3Uc_rmsVoltage C (Float)Read
AV4Uvag_rmsAverage Phase Voltage (Float)Read
AV5Uab_rmsVoltage A-B (Float)Read
AV6Ubc_rmsVoltage B-C (Float)Read
AV7Uca_rmsVoltage C-A (Float)Read
AVmin8Ulavg_rmsAverage Line Voltage (Float)Read
AV9Ia_rmsCurrent A (Float)Read
AV10Ib_rmsCurrent B (Float)Read
AV11Ic_rmsCurrent C (Float)Read
AVmin12Iavg_rmsAverage Current (Float)Read
AV13In_rmsNeutral Current (Float)Read
AV14Pa_rmsPa (Float)Read
AV15Pb_rmsPb (Float)Read
AV16Pc_rmsPc (Float)Read
AVmin17P_rmsTotal Active Power (Float)Read
AV18Qa_rmsQa (Float)Read
AV19Qb_rmsQb (Float)Read
AV20Qc_rmsQc (Float)Read
AV21Q_rmsTotal Reactive Power (Float)Read
AV22Sa_rmsSa (Float)Read
AV23Sb_rmsSb (Float)Read
AV24Sc_rmsSc (Float)Read
AVmin25S_rmsTotal Apparent Power (Float)Read
AV26PFa_rmsPFa (Float)Read
AV27PFb_rmsPFb (Float)Read
AV28PFc_rmsPFc (Float)Read
AVmin29PF_rmsTotal Power Factor (Float)Read
AV30Unbl_u2Voltage Imbalance (Float)Read
AV31Unbl_i2Current Imbalance (Float)Read
AV32Rlc_valLoad Characteristics (Float)Read
AVmin33P_demaP Demand (Float)Read
AV34Q_demaQ Demand (Float)Read
AV35S_demaS Demand (Float)Read
AV36Ia_DemandIa Demand (Float)Read
AV37Ib_DemandIb Demand (Float)Read
AV38Ic_DemandIc Demand (Float)Read
AVmin39Active_Energy_IMPActive_Energy_IMP (UINT32)Read
AV40Active_Energy_EXPActive_Energy_EXP (UINT32)Read
AV41Reactive_Energy_IMPReactive_Energy_IMP (UINT32)Read
AV42Reactive_Energy_EXPReactive_Energy_EXP (UINT32)Read
AV43Active_Energy_TOTALActive_Energy_TOTAL (UINT32)Read
AV44Active_Energy_NETActive_Energy_NET (SINT32)Read
AV45Reactive_Energy_TOTALReactive_Energy_TOTAL (UINT32)Read
AV46Reactive_Energy_NET SReactive_Energy_NET (SINT32)Read
AV47Apparent_EnergyApparent_Energy (UINT32)Read
AV48THD_V1THD_V1 (UINT32)Read
AV49THD_V2THD_V2 (UINT32)Read
AV50THD_V3THD_V3 (UINT32)Read
AV51THD_VTHD_V (UINT32)Read
AV52THD_I1THD_I1 (UINT32)Read
AV53THD_I2THD_I2 (UINT32)Read
AV54THD_I3THD_I3 (UINT32)Read
AV55THD_ITHD_I (UINT32)Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acuvim II with AXM-BMS BACnet MS/TP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module

How many BACnet points does the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module have?

This list has 56 BACnet objects: 56 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet documentation?

The source is BACnet for Acuvim II Series Power Meter, User's Manual (1040E2102 (V2.0.1)), revision 2023-08, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/Acuvim-II-Power-Meter-BACnet-User-Manual-EN.pdf.

What are the minimum BACnet points to integrate the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module?

Start with AV 17 P_rms (Total active power, W); AV 39 Active_Energy_IMP (Imported active energy total); AV 33 P_dema (Active power demand); AV 25 S_rms (Total apparent power); AV 29 PF_rms (Total power factor); AV 12 Iavg_rms (Average phase current); AV 8 Ulavg_rms (Average line-to-line voltage); AV 0 Freq_rms (Supply frequency).

How do I check these points on the real Acuvim II with AXM-BMS BACnet MS/TP module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accuenergy BACnet points lists

Source: BACnet for Acuvim II Series Power Meter, User's Manual · 1040E2102 (V2.0.1) · rev. 2023-08. Object names, instances and units are reproduced as published; descriptions are our own.