- Home
- BACnet points lists
- Accuenergy
- AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Multi-circuit power and energy meter (submeter) · BACnet points list
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) BACnet points list
Updated 7 November 2026
The AcuRev 2100 with the WEB2 module serves 1,230 read-only Analog Inputs: system and per-phase values, per-channel current, power, PF and load nature for input channels 1-18, energy, demand, peak demand, power quality, digital input values and individual harmonics. There are no binary objects.
This page lists 1230 BACnet objects for the Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
- Equipment
- Multi-circuit power and energy meter (submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 1230 (0 writable)
- Transport
- BACnet IP
- Firmware
- v1.22
- Also known as
- AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet
- Source document
- BACnet Points List AcuRev2100-WEB2 · rev. 2026-10-06
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
All values are read-only. Map system power, energy, demand and PF, then per-channel power and energy for the tenant or load circuits.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 5 | System Active Power | System real power, kW | Read |
| AI 201 | System Active Energy | System energy, kWh | Read |
| AI 301 | System Active Power Demand | System kW demand | Read |
| AI 8 | System Power Factor | System power factor | Read |
| AI 4 | Average Line Current | Average line current, A | Read |
| AI 10 | Phase A Line-to-Neutral Voltage | Phase A L-N voltage, V | Read |
| AI 35 | Input Channel 1 Active Power | Input channel 1 real power, kW | Read |
| AI 1 | Average Frequency | Frequency, Hz | Read |
Watch out for
- Objects exist for all 18 input channels; only channels on the installed hardware report values.
- Object names are writable, so a site may have renamed them; map by instance.
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Average Frequency | Hz | Read | ||
| AI | 2 | Average Line-to-Neutral Voltage | V | Read | ||
| AI | 3 | Average Line-to-Line Voltage | V | Read | ||
| AImin | 4 | Average Line Current | A | Read | ||
| AImin | 5 | System Active Power | kW | Read | ||
| AI | 6 | System Reactive Power | kvar | Read | ||
| AI | 7 | System Apparent Power | kVA | Read | ||
| AImin | 8 | System Power Factor | PF | Read | ||
| AI | 9 | System Load Nature | Read | |||
| AImin | 10 | Phase A Line-to-Neutral Voltage | V | Read | ||
| AI | 11 | Phase A-B Line-to-Line Voltage | V | Read | ||
| AI | 12 | Phase A Line Current | A | Read | ||
| AI | 13 | Phase A Active Power | kW | Read | ||
| AI | 14 | Phase A Reactive Power | kvar | Read | ||
| AI | 15 | Phase A Apparent Power | kVA | Read | ||
| AI | 16 | Phase A Power Factor | PF | Read | ||
| AI | 17 | Phase A Load Nature | Read | |||
| AI | 18 | Phase B Line-to-Neutral Voltage | V | Read | ||
| AI | 19 | Phase B-C Line-to-Line Voltage | V | Read | ||
| AI | 20 | Phase B Line Current | A | Read | ||
| AI | 21 | Phase B Active Power | kW | Read | ||
| AI | 22 | Phase B Reactive Power | kvar | Read | ||
| AI | 23 | Phase B Apparent Power | kVA | Read | ||
| AI | 24 | Phase B Power Factor | PF | Read | ||
| AI | 25 | Phase B Load Nature | Read | |||
| AI | 26 | Phase C Line-to-Neutral Voltage | V | Read | ||
| AI | 27 | Phase C-A Line-to-Line Voltage | V | Read | ||
| AI | 28 | Phase C Line Current | A | Read | ||
| AI | 29 | Phase C Active Power | kW | Read | ||
| AI | 30 | Phase C Reactive Power | kvar | Read | ||
| AI | 31 | Phase C Apparent Power | kVA | Read | ||
| AI | 32 | Phase C Power Factor | PF | Read | ||
| AI | 33 | Phase C Load Nature | Read | |||
| AI | 34 | Input Channel 1 Line Current | A | Read | ||
| AImin | 35 | Input Channel 1 Active Power | kW | Read | ||
| AI | 36 | Input Channel 1 Reactive Power | kvar | Read | ||
| AI | 37 | Input Channel 1 Apparent Power | kVA | Read | ||
| AI | 38 | Input Channel 1 Power Factor | PF | Read | ||
| AI | 39 | Input Channel 1 Load Nature | Read | |||
| AI | 40 | Input Channel 2 Line Current | A | Read | ||
| AI | 41 | Input Channel 2 Active Power | kW | Read | ||
| AI | 42 | Input Channel 2 Reactive Power | kvar | Read | ||
| AI | 43 | Input Channel 2 Apparent Power | kVA | Read | ||
| AI | 44 | Input Channel 2 Power Factor | PF | Read | ||
| AI | 45 | Input Channel 2 Load Nature | Read | |||
| AI | 46 | Input Channel 3 Line Current | A | Read | ||
| AI | 47 | Input Channel 3 Active Power | kW | Read | ||
| AI | 48 | Input Channel 3 Reactive Power | kvar | Read | ||
| AI | 49 | Input Channel 3 Apparent Power | kVA | Read | ||
| AI | 50 | Input Channel 3 Power Factor | PF | Read | ||
| AI | 51 | Input Channel 3 Load Nature | Read | |||
| AI | 52 | Input Channel 4 Line Current | A | Read | ||
| AI | 53 | Input Channel 4 Active Power | kW | Read | ||
| AI | 54 | Input Channel 4 Reactive Power | kvar | Read | ||
| AI | 55 | Input Channel 4 Apparent Power | kVA | Read | ||
| AI | 56 | Input Channel 4 Power Factor | PF | Read | ||
| AI | 57 | Input Channel 4 Load Nature | Read | |||
| AI | 58 | Input Channel 5 Line Current | A | Read | ||
| AI | 59 | Input Channel 5 Active Power | kW | Read | ||
| AI | 60 | Input Channel 5 Reactive Power | kvar | Read | ||
| AI | 61 | Input Channel 5 Apparent Power | kVA | Read | ||
| AI | 62 | Input Channel 5 Power Factor | PF | Read | ||
| AI | 63 | Input Channel 5 Load Nature | Read | |||
| AI | 64 | Input Channel 6 Line Current | A | Read | ||
| AI | 65 | Input Channel 6 Active Power | kW | Read | ||
| AI | 66 | Input Channel 6 Reactive Power | kvar | Read | ||
| AI | 67 | Input Channel 6 Apparent Power | kVA | Read | ||
| AI | 68 | Input Channel 6 Power Factor | PF | Read | ||
| AI | 69 | Input Channel 6 Load Nature | Read | |||
| AI | 70 | Input Channel 7 Line Current | A | Read | ||
| AI | 71 | Input Channel 7 Active Power | kW | Read | ||
| AI | 72 | Input Channel 7 Reactive Power | kvar | Read | ||
| AI | 73 | Input Channel 7 Apparent Power | kVA | Read | ||
| AI | 74 | Input Channel 7 Power Factor | PF | Read | ||
| AI | 75 | Input Channel 7 Load Nature | Read | |||
| AI | 76 | Input Channel 8 Line Current | A | Read | ||
| AI | 77 | Input Channel 8 Active Power | kW | Read | ||
| AI | 78 | Input Channel 8 Reactive Power | kvar | Read | ||
| AI | 79 | Input Channel 8 Apparent Power | kVA | Read | ||
| AI | 80 | Input Channel 8 Power Factor | PF | Read | ||
| AI | 81 | Input Channel 8 Load Nature | Read | |||
| AI | 82 | Input Channel 9 Line Current | A | Read | ||
| AI | 83 | Input Channel 9 Active Power | kW | Read | ||
| AI | 84 | Input Channel 9 Reactive Power | kvar | Read | ||
| AI | 85 | Input Channel 9 Apparent Power | kVA | Read | ||
| AI | 86 | Input Channel 9 Power Factor | PF | Read | ||
| AI | 87 | Input Channel 9 Load Nature | Read | |||
| AI | 88 | Input Channel 10 Line Current | A | Read | ||
| AI | 89 | Input Channel 10 Active Power | kW | Read | ||
| AI | 90 | Input Channel 10 Reactive Power | kvar | Read | ||
| AI | 91 | Input Channel 10 Apparent Power | kVA | Read | ||
| AI | 92 | Input Channel 10 Power Factor | PF | Read | ||
| AI | 93 | Input Channel 10 Load Nature | Read | |||
| AI | 94 | Input Channel 11 Line Current | A | Read | ||
| AI | 95 | Input Channel 11 Active Power | kW | Read | ||
| AI | 96 | Input Channel 11 Reactive Power | kvar | Read | ||
| AI | 97 | Input Channel 11 Apparent Power | kVA | Read | ||
| AI | 98 | Input Channel 11 Power Factor | PF | Read | ||
| AI | 99 | Input Channel 11 Load Nature | Read | |||
| AI | 100 | Input Channel 12 Line Current | A | Read | ||
| AI | 101 | Input Channel 12 Active Power | kW | Read | ||
| AI | 102 | Input Channel 12 Reactive Power | kvar | Read | ||
| AI | 103 | Input Channel 12 Apparent Power | kVA | Read | ||
| AI | 104 | Input Channel 12 Power Factor | PF | Read | ||
| AI | 105 | Input Channel 12 Load Nature | Read | |||
| AI | 106 | Input Channel 13 Line Current | A | Read | ||
| AI | 107 | Input Channel 13 Active Power | kW | Read | ||
| AI | 108 | Input Channel 13 Reactive Power | kvar | Read | ||
| AI | 109 | Input Channel 13 Apparent Power | kVA | Read | ||
| AI | 110 | Input Channel 13 Power Factor | PF | Read | ||
| AI | 111 | Input Channel 13 Load Nature | Read | |||
| AI | 112 | Input Channel 14 Line Current | A | Read | ||
| AI | 113 | Input Channel 14 Active Power | kW | Read | ||
| AI | 114 | Input Channel 14 Reactive Power | kvar | Read | ||
| AI | 115 | Input Channel 14 Apparent Power | kVA | Read | ||
| AI | 116 | Input Channel 14 Power Factor | PF | Read | ||
| AI | 117 | Input Channel 14 Load Nature | Read | |||
| AI | 118 | Input Channel 15 Line Current | A | Read | ||
| AI | 119 | Input Channel 15 Active Power | kW | Read | ||
| AI | 120 | Input Channel 15 Reactive Power | kvar | Read | ||
| AI | 121 | Input Channel 15 Apparent Power | kVA | Read | ||
| AI | 122 | Input Channel 15 Power Factor | PF | Read | ||
| AI | 123 | Input Channel 15 Load Nature | Read | |||
| AI | 124 | Input Channel 16 Line Current | A | Read | ||
| AI | 125 | Input Channel 16 Active Power | kW | Read | ||
| AI | 126 | Input Channel 16 Reactive Power | kvar | Read | ||
| AI | 127 | Input Channel 16 Apparent Power | kVA | Read | ||
| AI | 128 | Input Channel 16 Power Factor | PF | Read | ||
| AI | 129 | Input Channel 16 Load Nature | Read | |||
| AI | 130 | Input Channel 17 Line Current | A | Read | ||
| AI | 131 | Input Channel 17 Active Power | kW | Read | ||
| AI | 132 | Input Channel 17 Reactive Power | kvar | Read | ||
| AI | 133 | Input Channel 17 Apparent Power | kVA | Read | ||
| AI | 134 | Input Channel 17 Power Factor | PF | Read | ||
| AI | 135 | Input Channel 17 Load Nature | Read | |||
| AI | 136 | Input Channel 18 Line Current | A | Read | ||
| AI | 137 | Input Channel 18 Active Power | kW | Read | ||
| AI | 138 | Input Channel 18 Reactive Power | kvar | Read | ||
| AI | 139 | Input Channel 18 Apparent Power | kVA | Read | ||
| AI | 140 | Input Channel 18 Power Factor | PF | Read | ||
| AI | 141 | Input Channel 18 Load Nature | Read | |||
| AI | 142 | User Channel 1 Active Power | kW | Read | ||
| AI | 143 | User Channel 1 Reactive Power | kvar | Read | ||
| AI | 144 | User Channel 1 Apparent Power | kVA | Read | ||
| AI | 145 | User Channel 1 Power Factor | PF | Read | ||
| AI | 146 | User Channel 1 Load Nature | Read | |||
| AI | 147 | User Channel 2 Active Power | kW | Read | ||
| AI | 148 | User Channel 2 Reactive Power | kvar | Read | ||
| AI | 149 | User Channel 2 Apparent Power | kVA | Read | ||
| AI | 150 | User Channel 2 Power Factor | PF | Read | ||
| AI | 151 | User Channel 2 Load Nature | Read | |||
| AI | 152 | User Channel 3 Active Power | kW | Read | ||
| AI | 153 | User Channel 3 Reactive Power | kvar | Read | ||
| AI | 154 | User Channel 3 Apparent Power | kVA | Read | ||
| AI | 155 | User Channel 3 Power Factor | PF | Read | ||
| AI | 156 | User Channel 3 Load Nature | Read | |||
| AI | 157 | User Channel 4 Active Power | kW | Read | ||
| AI | 158 | User Channel 4 Reactive Power | kvar | Read | ||
| AI | 159 | User Channel 4 Apparent Power | kVA | Read | ||
| AI | 160 | User Channel 4 Power Factor | PF | Read | ||
| AI | 161 | User Channel 4 Load Nature | Read | |||
| AI | 162 | User Channel 5 Active Power | kW | Read | ||
| AI | 163 | User Channel 5 Reactive Power | kvar | Read | ||
| AI | 164 | User Channel 5 Apparent Power | kVA | Read | ||
| AI | 165 | User Channel 5 Power Factor | PF | Read | ||
| AI | 166 | User Channel 5 Load Nature | Read | |||
| AI | 167 | User Channel 6 Active Power | kW | Read | ||
| AI | 168 | User Channel 6 Reactive Power | kvar | Read | ||
| AI | 169 | User Channel 6 Apparent Power | kVA | Read | ||
| AI | 170 | User Channel 6 Power Factor | PF | Read | ||
| AI | 171 | User Channel 6 Load Nature | Read | |||
| AI | 172 | User Channel 7 Active Power | kW | Read | ||
| AI | 173 | User Channel 7 Reactive Power | kvar | Read | ||
| AI | 174 | User Channel 7 Apparent Power | kVA | Read | ||
| AI | 175 | User Channel 7 Power Factor | PF | Read | ||
| AI | 176 | User Channel 7 Load Nature | Read | |||
| AI | 177 | User Channel 8 Active Power | kW | Read | ||
| AI | 178 | User Channel 8 Reactive Power | kvar | Read | ||
| AI | 179 | User Channel 8 Apparent Power | kVA | Read | ||
| AI | 180 | User Channel 8 Power Factor | PF | Read | ||
| AI | 181 | User Channel 8 Load Nature | Read | |||
| AI | 182 | User Channel 9 Active Power | kW | Read | ||
| AI | 183 | User Channel 9 Reactive Power | kvar | Read | ||
| AI | 184 | User Channel 9 Apparent Power | kVA | Read | ||
| AI | 185 | User Channel 9 Power Factor | PF | Read | ||
| AI | 186 | User Channel 9 Load Nature | Read | |||
| AImin | 201 | System Active Energy | kWh | Read | ||
| AI | 202 | System Reactive Energy | kvarh | Read | ||
| AI | 203 | System Apparent Energy | kVAh | Read | ||
| AI | 204 | Phase A Active Energy | kWh | Read | ||
| AI | 205 | Phase A Reactive Energy | kvarh | Read | ||
| AI | 206 | Phase A Apparent Energy | kVAh | Read | ||
| AI | 207 | Phase B Active Energy | kWh | Read | ||
| AI | 208 | Phase B Reactive Energy | kvarh | Read | ||
| AI | 209 | Phase B Apparent Energy | kVAh | Read | ||
| AI | 210 | Phase C Active Energy | kWh | Read | ||
| AI | 211 | Phase C Reactive Energy | kvarh | Read | ||
| AI | 212 | Phase C Apparent Energy | kVAh | Read | ||
| AI | 213 | Input Channel 1 Active Energy | kWh | Read | ||
| AI | 214 | Input Channel 1 Reactive Energy | kvarh | Read | ||
| AI | 215 | Input Channel 1 Apparent Energy | kVAh | Read | ||
| AI | 216 | Input Channel 2 Active Energy | kWh | Read | ||
| AI | 217 | Input Channel 2 Reactive Energy | kvarh | Read | ||
| AI | 218 | Input Channel 2 Apparent Energy | kVAh | Read | ||
| AI | 219 | Input Channel 3 Active Energy | kWh | Read | ||
| AI | 220 | Input Channel 3 Reactive Energy | kvarh | Read | ||
| AI | 221 | Input Channel 3 Apparent Energy | kVAh | Read | ||
| AI | 222 | Input Channel 4 Active Energy | kWh | Read | ||
| AI | 223 | Input Channel 4 Reactive Energy | kvarh | Read | ||
| AI | 224 | Input Channel 4 Apparent Energy | kVAh | Read | ||
| AI | 225 | Input Channel 5 Active Energy | kWh | Read | ||
| AI | 226 | Input Channel 5 Reactive Energy | kvarh | Read | ||
| AI | 227 | Input Channel 5 Apparent Energy | kVAh | Read | ||
| AI | 228 | Input Channel 6 Active Energy | kWh | Read | ||
| AI | 229 | Input Channel 6 Reactive Energy | kvarh | Read | ||
| AI | 230 | Input Channel 6 Apparent Energy | kVAh | Read | ||
| AI | 231 | Input Channel 7 Active Energy | kWh | Read | ||
| AI | 232 | Input Channel 7 Reactive Energy | kvarh | Read | ||
| AI | 233 | Input Channel 7 Apparent Energy | kVAh | Read | ||
| AI | 234 | Input Channel 8 Active Energy | kWh | Read | ||
| AI | 235 | Input Channel 8 Reactive Energy | kvarh | Read | ||
| AI | 236 | Input Channel 8 Apparent Energy | kVAh | Read | ||
| AI | 237 | Input Channel 9 Active Energy | kWh | Read | ||
| AI | 238 | Input Channel 9 Reactive Energy | kvarh | Read | ||
| AI | 239 | Input Channel 9 Apparent Energy | kVAh | Read | ||
| AI | 240 | Input Channel 10 Active Energy | kWh | Read | ||
| AI | 241 | Input Channel 10 Reactive Energy | kvarh | Read | ||
| AI | 242 | Input Channel 10 Apparent Energy | kVAh | Read | ||
| AI | 243 | Input Channel 11 Active Energy | kWh | Read | ||
| AI | 244 | Input Channel 11 Reactive Energy | kvarh | Read | ||
| AI | 245 | Input Channel 11 Apparent Energy | kVAh | Read | ||
| AI | 246 | Input Channel 12 Active Energy | kWh | Read | ||
| AI | 247 | Input Channel 12 Reactive Energy | kvarh | Read | ||
| AI | 248 | Input Channel 12 Apparent Energy | kVAh | Read | ||
| AI | 249 | Input Channel 13 Active Energy | kWh | Read | ||
| AI | 250 | Input Channel 13 Reactive Energy | kvarh | Read | ||
| AI | 251 | Input Channel 13 Apparent Energy | kVAh | Read | ||
| AI | 252 | Input Channel 14 Active Energy | kWh | Read | ||
| AI | 253 | Input Channel 14 Reactive Energy | kvarh | Read | ||
| AI | 254 | Input Channel 14 Apparent Energy | kVAh | Read | ||
| AI | 255 | Input Channel 15 Active Energy | kWh | Read | ||
| AI | 256 | Input Channel 15 Reactive Energy | kvarh | Read | ||
| AI | 257 | Input Channel 15 Apparent Energy | kVAh | Read | ||
| AI | 258 | Input Channel 16 Active Energy | kWh | Read | ||
| AI | 259 | Input Channel 16 Reactive Energy | kvarh | Read | ||
| AI | 260 | Input Channel 16 Apparent Energy | kVAh | Read | ||
| AI | 261 | Input Channel 17 Active Energy | kWh | Read | ||
| AI | 262 | Input Channel 17 Reactive Energy | kvarh | Read | ||
| AI | 263 | Input Channel 17 Apparent Energy | kVAh | Read | ||
| AI | 264 | Input Channel 18 Active Energy | kWh | Read | ||
| AI | 265 | Input Channel 18 Reactive Energy | kvarh | Read | ||
| AI | 266 | Input Channel 18 Apparent Energy | kVAh | Read | ||
| AI | 267 | User Channel 1 Active Energy | kWh | Read | ||
| AI | 268 | User Channel 1 Reactive Energy | kvarh | Read | ||
| AI | 269 | User Channel 1 Apparent Energy | kVAh | Read | ||
| AI | 270 | User Channel 2 Active Energy | kWh | Read | ||
| AI | 271 | User Channel 2 Reactive Energy | kvarh | Read | ||
| AI | 272 | User Channel 2 Apparent Energy | kVAh | Read | ||
| AI | 273 | User Channel 3 Active Energy | kWh | Read | ||
| AI | 274 | User Channel 3 Reactive Energy | kvarh | Read | ||
| AI | 275 | User Channel 3 Apparent Energy | kVAh | Read | ||
| AI | 276 | User Channel 4 Active Energy | kWh | Read | ||
| AI | 277 | User Channel 4 Reactive Energy | kvarh | Read | ||
| AI | 278 | User Channel 4 Apparent Energy | kVAh | Read | ||
| AI | 279 | User Channel 5 Active Energy | kWh | Read | ||
| AI | 280 | User Channel 5 Reactive Energy | kvarh | Read | ||
| AI | 281 | User Channel 5 Apparent Energy | kVAh | Read | ||
| AI | 282 | User Channel 6 Active Energy | kWh | Read | ||
| AI | 283 | User Channel 6 Reactive Energy | kvarh | Read | ||
| AI | 284 | User Channel 6 Apparent Energy | kVAh | Read | ||
| AI | 285 | User Channel 7 Active Energy | kWh | Read | ||
| AI | 286 | User Channel 7 Reactive Energy | kvarh | Read | ||
| AI | 287 | User Channel 7 Apparent Energy | kVAh | Read | ||
| AI | 288 | User Channel 8 Active Energy | kWh | Read | ||
| AI | 289 | User Channel 8 Reactive Energy | kvarh | Read | ||
| AI | 290 | User Channel 8 Apparent Energy | kVAh | Read | ||
| AI | 291 | User Channel 9 Active Energy | kWh | Read | ||
| AI | 292 | User Channel 9 Reactive Energy | kvarh | Read | ||
| AI | 293 | User Channel 9 Apparent Energy | kVAh | Read | ||
| AImin | 301 | System Active Power Demand | kW | Read | ||
| AI | 302 | System Reactive Power Demand | kvar | Read | ||
| AI | 303 | System Apparent Power Demand | kVA | Read | ||
| AI | 304 | Phase A Current Demand | A | Read | ||
| AI | 305 | Phase A Active Power Demand | kW | Read | ||
| AI | 306 | Phase A Reactive Power Demand | kvar | Read | ||
| AI | 307 | Phase A Apparent Power Demand | kVA | Read | ||
| AI | 308 | Phase B Current Demand | A | Read | ||
| AI | 309 | Phase B Active Power Demand | kW | Read | ||
| AI | 310 | Phase B Reactive Power Demand | kvar | Read | ||
| AI | 311 | Phase B Apparent Power Demand | kVA | Read | ||
| AI | 312 | Phase C Current Demand | A | Read | ||
| AI | 313 | Phase C Active Power Demand | kW | Read | ||
| AI | 314 | Phase C Reactive Power Demand | kvar | Read | ||
| AI | 315 | Phase C Apparent Power Demand | kVA | Read | ||
| AI | 316 | Input Channel 1 Current Demand | A | Read | ||
| AI | 317 | Input Channel 1 Active Power Demand | kW | Read | ||
| AI | 318 | Input Channel 1 Reactive Power Demand | kvar | Read | ||
| AI | 319 | Input Channel 1 Apparent Power Demand | kVA | Read | ||
| AI | 320 | Input Channel 2 Current Demand | A | Read | ||
| AI | 321 | Input Channel 2 Active Power Demand | kW | Read | ||
| AI | 322 | Input Channel 2 Reactive Power Demand | kvar | Read | ||
| AI | 323 | Input Channel 2 Apparent Power Demand | kVA | Read | ||
| AI | 324 | Input Channel 3 Current Demand | A | Read | ||
| AI | 325 | Input Channel 3 Active Power Demand | kW | Read | ||
| AI | 326 | Input Channel 3 Reactive Power Demand | kvar | Read | ||
| AI | 327 | Input Channel 3 Apparent Power Demand | kVA | Read | ||
| AI | 328 | Input Channel 4 Current Demand | A | Read | ||
| AI | 329 | Input Channel 4 Active Power Demand | kW | Read | ||
| AI | 330 | Input Channel 4 Reactive Power Demand | kvar | Read | ||
| AI | 331 | Input Channel 4 Apparent Power Demand | kVA | Read | ||
| AI | 332 | Input Channel 5 Current Demand | A | Read | ||
| AI | 333 | Input Channel 5 Active Power Demand | kW | Read | ||
| AI | 334 | Input Channel 5 Reactive Power Demand | kvar | Read | ||
| AI | 335 | Input Channel 5 Apparent Power Demand | kVA | Read | ||
| AI | 336 | Input Channel 6 Current Demand | A | Read | ||
| AI | 337 | Input Channel 6 Active Power Demand | kW | Read | ||
| AI | 338 | Input Channel 6 Reactive Power Demand | kvar | Read | ||
| AI | 339 | Input Channel 6 Apparent Power Demand | kVA | Read | ||
| AI | 340 | Input Channel 7 Current Demand | A | Read | ||
| AI | 341 | Input Channel 7 Active Power Demand | kW | Read | ||
| AI | 342 | Input Channel 7 Reactive Power Demand | kvar | Read | ||
| AI | 343 | Input Channel 7 Apparent Power Demand | kVA | Read | ||
| AI | 344 | Input Channel 8 Current Demand | A | Read | ||
| AI | 345 | Input Channel 8 Active Power Demand | kW | Read | ||
| AI | 346 | Input Channel 8 Reactive Power Demand | kvar | Read | ||
| AI | 347 | Input Channel 8 Apparent Power Demand | kVA | Read | ||
| AI | 348 | Input Channel 9 Current Demand | A | Read | ||
| AI | 349 | Input Channel 9 Active Power Demand | kW | Read | ||
| AI | 350 | Input Channel 9 Reactive Power Demand | kvar | Read | ||
| AI | 351 | Input Channel 9 Apparent Power Demand | kVA | Read | ||
| AI | 352 | Input Channel 10 Current Demand | A | Read | ||
| AI | 353 | Input Channel 10 Active Power Demand | kW | Read | ||
| AI | 354 | Input Channel 10 Reactive Power Demand | kvar | Read | ||
| AI | 355 | Input Channel 10 Apparent Power Demand | kVA | Read | ||
| AI | 356 | Input Channel 11 Current Demand | A | Read | ||
| AI | 357 | Input Channel 11 Active Power Demand | kW | Read | ||
| AI | 358 | Input Channel 11 Reactive Power Demand | kvar | Read | ||
| AI | 359 | Input Channel 11 Apparent Power Demand | kVA | Read | ||
| AI | 360 | Input Channel 12 Current Demand | A | Read | ||
| AI | 361 | Input Channel 12 Active Power Demand | kW | Read | ||
| AI | 362 | Input Channel 12 Reactive Power Demand | kvar | Read | ||
| AI | 363 | Input Channel 12 Apparent Power Demand | kVA | Read | ||
| AI | 364 | Input Channel 13 Current Demand | A | Read | ||
| AI | 365 | Input Channel 13 Active Power Demand | kW | Read | ||
| AI | 366 | Input Channel 13 Reactive Power Demand | kvar | Read | ||
| AI | 367 | Input Channel 13 Apparent Power Demand | kVA | Read | ||
| AI | 368 | Input Channel 14 Current Demand | A | Read | ||
| AI | 369 | Input Channel 14 Active Power Demand | kW | Read | ||
| AI | 370 | Input Channel 14 Reactive Power Demand | kvar | Read | ||
| AI | 371 | Input Channel 14 Apparent Power Demand | kVA | Read | ||
| AI | 372 | Input Channel 15 Current Demand | A | Read | ||
| AI | 373 | Input Channel 15 Active Power Demand | kW | Read | ||
| AI | 374 | Input Channel 15 Reactive Power Demand | kvar | Read | ||
| AI | 375 | Input Channel 15 Apparent Power Demand | kVA | Read | ||
| AI | 376 | Input Channel 16 Current Demand | A | Read | ||
| AI | 377 | Input Channel 16 Active Power Demand | kW | Read | ||
| AI | 378 | Input Channel 16 Reactive Power Demand | kvar | Read | ||
| AI | 379 | Input Channel 16 Apparent Power Demand | kVA | Read | ||
| AI | 380 | Input Channel 17 Current Demand | A | Read | ||
| AI | 381 | Input Channel 17 Active Power Demand | kW | Read | ||
| AI | 382 | Input Channel 17 Reactive Power Demand | kvar | Read | ||
| AI | 383 | Input Channel 17 Apparent Power Demand | kVA | Read | ||
| AI | 384 | Input Channel 18 Current Demand | A | Read | ||
| AI | 385 | Input Channel 18 Active Power Demand | kW | Read | ||
| AI | 386 | Input Channel 18 Reactive Power Demand | kvar | Read | ||
| AI | 387 | Input Channel 18 Apparent Power Demand | kVA | Read | ||
| AI | 388 | User Channel 1 Active Power Demand | kW | Read | ||
| AI | 389 | User Channel 1 Reactive Power Demand | kvar | Read | ||
| AI | 390 | User Channel 1 Apparent Power Demand | kVA | Read | ||
| AI | 391 | User Channel 2 Active Power Demand | kW | Read | ||
| AI | 392 | User Channel 2 Reactive Power Demand | kvar | Read | ||
| AI | 393 | User Channel 2 Apparent Power Demand | kVA | Read | ||
| AI | 394 | User Channel 3 Active Power Demand | kW | Read | ||
| AI | 395 | User Channel 3 Reactive Power Demand | kvar | Read | ||
| AI | 396 | User Channel 3 Apparent Power Demand | kVA | Read | ||
| AI | 397 | User Channel 4 Active Power Demand | kW | Read | ||
| AI | 398 | User Channel 4 Reactive Power Demand | kvar | Read | ||
| AI | 399 | User Channel 4 Apparent Power Demand | kVA | Read | ||
| AI | 400 | User Channel 5 Active Power Demand | kW | Read | ||
| AI | 401 | User Channel 5 Reactive Power Demand | kvar | Read | ||
| AI | 402 | User Channel 5 Apparent Power Demand | kVA | Read | ||
| AI | 403 | User Channel 6 Active Power Demand | kW | Read | ||
| AI | 404 | User Channel 6 Reactive Power Demand | kvar | Read | ||
| AI | 405 | User Channel 6 Apparent Power Demand | kVA | Read | ||
| AI | 406 | User Channel 7 Active Power Demand | kW | Read | ||
| AI | 407 | User Channel 7 Reactive Power Demand | kvar | Read | ||
| AI | 408 | User Channel 7 Apparent Power Demand | kVA | Read | ||
| AI | 409 | User Channel 8 Active Power Demand | kW | Read | ||
| AI | 410 | User Channel 8 Reactive Power Demand | kvar | Read | ||
| AI | 411 | User Channel 8 Apparent Power Demand | kVA | Read | ||
| AI | 412 | User Channel 9 Active Power Demand | kW | Read | ||
| AI | 413 | User Channel 9 Reactive Power Demand | kvar | Read | ||
| AI | 414 | User Channel 9 Apparent Power Demand | kVA | Read | ||
| AI | 501 | Average Voltage THD | % | Read | ||
| AI | 502 | System Voltage Unbalance Factor | % | Read | ||
| AI | 503 | System Current Unbalance Factor | % | Read | ||
| AI | 504 | Phase A Voltage THD | % | Read | ||
| AI | 505 | Phase A Odd Voltage THD | % | Read | ||
| AI | 506 | Phase A Even Voltage THD | % | Read | ||
| AI | 507 | Phase A Voltage Crest Factor | % | Read | ||
| AI | 508 | Phase A THFF | % | Read | ||
| AI | 509 | Phase B Voltage THD | % | Read | ||
| AI | 510 | Phase B Odd Voltage THD | % | Read | ||
| AI | 511 | Phase B Even Voltage THD | % | Read | ||
| AI | 512 | Phase B Voltage Crest Factor | % | Read | ||
| AI | 513 | Phase B THFF | % | Read | ||
| AI | 514 | Phase C Voltage THD | % | Read | ||
| AI | 515 | Phase C Odd Voltage THD | % | Read | ||
| AI | 516 | Phase C Even Voltage THD | % | Read | ||
| AI | 517 | Phase C Voltage Crest Factor | % | Read | ||
| AI | 518 | Phase C THFF | % | Read | ||
| AI | 519 | Input Channel 1 Current THD | % | Read | ||
| AI | 520 | Input Channel 1 Odd Current THD | % | Read | ||
| AI | 521 | Input Channel 1 Even Current THD | % | Read | ||
| AI | 522 | Input Channel 1 Current K Factor | % | Read | ||
| AI | 523 | Input Channel 2 Current THD | % | Read | ||
| AI | 524 | Input Channel 2 Odd Current THD | % | Read | ||
| AI | 525 | Input Channel 2 Even Current THD | % | Read | ||
| AI | 526 | Input Channel 2 Current K Factor | % | Read | ||
| AI | 527 | Input Channel 3 Current THD | % | Read | ||
| AI | 528 | Input Channel 3 Odd Current THD | % | Read | ||
| AI | 529 | Input Channel 3 Even Current THD | % | Read | ||
| AI | 530 | Input Channel 3 Current K Factor | % | Read | ||
| AI | 531 | Input Channel 4 Current THD | % | Read | ||
| AI | 532 | Input Channel 4 Odd Current THD | % | Read | ||
| AI | 533 | Input Channel 4 Even Current THD | % | Read | ||
| AI | 534 | Input Channel 4 Current K Factor | % | Read | ||
| AI | 535 | Input Channel 5 Current THD | % | Read | ||
| AI | 536 | Input Channel 5 Odd Current THD | % | Read | ||
| AI | 537 | Input Channel 5 Even Current THD | % | Read | ||
| AI | 538 | Input Channel 5 Current K Factor | % | Read | ||
| AI | 539 | Input Channel 6 Current THD | % | Read | ||
| AI | 540 | Input Channel 6 Odd Current THD | % | Read | ||
| AI | 541 | Input Channel 6 Even Current THD | % | Read | ||
| AI | 542 | Input Channel 6 Current K Factor | % | Read | ||
| AI | 543 | Input Channel 7 Current THD | % | Read | ||
| AI | 544 | Input Channel 7 Odd Current THD | % | Read | ||
| AI | 545 | Input Channel 7 Even Current THD | % | Read | ||
| AI | 546 | Input Channel 7 Current K Factor | % | Read | ||
| AI | 547 | Input Channel 8 Current THD | % | Read | ||
| AI | 548 | Input Channel 8 Odd Current THD | % | Read | ||
| AI | 549 | Input Channel 8 Even Current THD | % | Read | ||
| AI | 550 | Input Channel 8 Current K Factor | % | Read | ||
| AI | 551 | Input Channel 9 Current THD | % | Read | ||
| AI | 552 | Input Channel 9 Odd Current THD | % | Read | ||
| AI | 553 | Input Channel 9 Even Current THD | % | Read | ||
| AI | 554 | Input Channel 9 Current K Factor | % | Read | ||
| AI | 555 | Input Channel 10 Current THD | % | Read | ||
| AI | 556 | Input Channel 10 Odd Current THD | % | Read | ||
| AI | 557 | Input Channel 10 Even Current THD | % | Read | ||
| AI | 558 | Input Channel 10 Current K Factor | % | Read | ||
| AI | 559 | Input Channel 11 Current THD | % | Read | ||
| AI | 560 | Input Channel 11 Odd Current THD | % | Read | ||
| AI | 561 | Input Channel 11 Even Current THD | % | Read | ||
| AI | 562 | Input Channel 11 Current K Factor | % | Read | ||
| AI | 563 | Input Channel 12 Current THD | % | Read | ||
| AI | 564 | Input Channel 12 Odd Current THD | % | Read | ||
| AI | 565 | Input Channel 12 Even Current THD | % | Read | ||
| AI | 566 | Input Channel 12 Current K Factor | % | Read | ||
| AI | 567 | Input Channel 13 Current THD | % | Read | ||
| AI | 568 | Input Channel 13 Odd Current THD | % | Read | ||
| AI | 569 | Input Channel 13 Even Current THD | % | Read | ||
| AI | 570 | Input Channel 13 Current K Factor | % | Read | ||
| AI | 571 | Input Channel 14 Current THD | % | Read | ||
| AI | 572 | Input Channel 14 Odd Current THD | % | Read | ||
| AI | 573 | Input Channel 14 Even Current THD | % | Read | ||
| AI | 574 | Input Channel 14 Current K Factor | % | Read | ||
| AI | 575 | Input Channel 15 Current THD | % | Read | ||
| AI | 576 | Input Channel 15 Odd Current THD | % | Read | ||
| AI | 577 | Input Channel 15 Even Current THD | % | Read | ||
| AI | 578 | Input Channel 15 Current K Factor | % | Read | ||
| AI | 579 | Input Channel 16 Current THD | % | Read | ||
| AI | 580 | Input Channel 16 Odd Current THD | % | Read | ||
| AI | 581 | Input Channel 16 Even Current THD | % | Read | ||
| AI | 582 | Input Channel 16 Current K Factor | % | Read | ||
| AI | 583 | Input Channel 17 Current THD | % | Read | ||
| AI | 584 | Input Channel 17 Odd Current THD | % | Read | ||
| AI | 585 | Input Channel 17 Even Current THD | % | Read | ||
| AI | 586 | Input Channel 17 Current K Factor | % | Read | ||
| AI | 587 | Input Channel 18 Current THD | % | Read | ||
| AI | 588 | Input Channel 18 Odd Current THD | % | Read | ||
| AI | 589 | Input Channel 18 Even Current THD | % | Read | ||
| AI | 590 | Input Channel 18 Current K Factor | % | Read | ||
| AI | 591 | User Channel 1 Current Unbalance | % | Read | ||
| AI | 592 | User Channel 2 Current Unbalance | % | Read | ||
| AI | 593 | User Channel 3 Current Unbalance | % | Read | ||
| AI | 594 | User Channel 4 Current Unbalance | % | Read | ||
| AI | 595 | User Channel 5 Current Unbalance | % | Read | ||
| AI | 596 | User Channel 6 Current Unbalance | % | Read | ||
| AI | 601 | DI1 COUNTER | Read | |||
| AI | 602 | DI2 COUNTER | Read | |||
| AI | 603 | DI3 COUNTER | Read | |||
| AI | 604 | DI4 COUNTER | Read | |||
| AI | 605 | DI5 COUNTER | Read | |||
| AI | 606 | DI6 COUNTER | Read | |||
| AI | 607 | DI7 COUNTER | Read | |||
| AI | 608 | DI8 COUNTER | Read | |||
| AI | 609 | DI9 COUNTER | Read | |||
| AI | 610 | DI10 COUNTER | Read | |||
| AI | 611 | DI11 COUNTER | Read | |||
| AI | 612 | DI12 COUNTER | Read | |||
| AI | 613 | DI13 COUNTER | Read | |||
| AI | 614 | DI14 COUNTER | Read | |||
| AI | 615 | DI15 COUNTER | Read | |||
| AI | 616 | DI16 COUNTER | Read | |||
| AI | 617 | DI17 COUNTER | Read | |||
| AI | 618 | DI18 COUNTER | Read | |||
| AI | 701 | System Active Power Demand Peak | kW | Read | ||
| AI | 702 | System Reactive Power Demand Peak | kvar | Read | ||
| AI | 703 | System Apparent Power Demand Peak | kVA | Read | ||
| AI | 704 | Phase A Active Power Demand Peak | kW | Read | ||
| AI | 705 | Phase A Reactive Power Demand Peak | kvar | Read | ||
| AI | 706 | Phase A Apparent Power Demand Peak | kVA | Read | ||
| AI | 707 | Phase B Active Power Demand Peak | kW | Read | ||
| AI | 708 | Phase B Reactive Power Demand Peak | kvar | Read | ||
| AI | 709 | Phase B Apparent Power Demand Peak | kVA | Read | ||
| AI | 710 | Phase C Active Power Demand Peak | kW | Read | ||
| AI | 711 | Phase C Reactive Power Demand Peak | kvar | Read | ||
| AI | 712 | Phase C Apparent Power Demand Peak | kVA | Read | ||
| AI | 713 | Input Channel 1 Active Power Demand Peak | kW | Read | ||
| AI | 714 | Input Channel 1 Reactive Power Demand Peak | kvar | Read | ||
| AI | 715 | Input Channel 1 Apparent Power Demand Peak | kVA | Read | ||
| AI | 716 | Input Channel 2 Active Power Demand Peak | kW | Read | ||
| AI | 717 | Input Channel 2 Reactive Power Demand Peak | kvar | Read | ||
| AI | 718 | Input Channel 2 Apparent Power Demand Peak | kVA | Read | ||
| AI | 719 | Input Channel 3 Active Power Demand Peak | kW | Read | ||
| AI | 720 | Input Channel 3 Reactive Power Demand Peak | kvar | Read | ||
| AI | 721 | Input Channel 3 Apparent Power Demand Peak | kVA | Read | ||
| AI | 722 | Input Channel 4 Active Power Demand Peak | kW | Read | ||
| AI | 723 | Input Channel 4 Reactive Power Demand Peak | kvar | Read | ||
| AI | 724 | Input Channel 4 Apparent Power Demand Peak | kVA | Read | ||
| AI | 725 | Input Channel 5 Active Power Demand Peak | kW | Read | ||
| AI | 726 | Input Channel 5 Reactive Power Demand Peak | kvar | Read | ||
| AI | 727 | Input Channel 5 Apparent Power Demand Peak | kVA | Read | ||
| AI | 728 | Input Channel 6 Active Power Demand Peak | kW | Read | ||
| AI | 729 | Input Channel 6 Reactive Power Demand Peak | kvar | Read | ||
| AI | 730 | Input Channel 6 Apparent Power Demand Peak | kVA | Read | ||
| AI | 731 | Input Channel 7 Active Power Demand Peak | kW | Read | ||
| AI | 732 | Input Channel 7 Reactive Power Demand Peak | kvar | Read | ||
| AI | 733 | Input Channel 7 Apparent Power Demand Peak | kVA | Read | ||
| AI | 734 | Input Channel 8 Active Power Demand Peak | kW | Read | ||
| AI | 735 | Input Channel 8 Reactive Power Demand Peak | kvar | Read | ||
| AI | 736 | Input Channel 8 Apparent Power Demand Peak | kVA | Read | ||
| AI | 737 | Input Channel 9 Active Power Demand Peak | kW | Read | ||
| AI | 738 | Input Channel 9 Reactive Power Demand Peak | kvar | Read | ||
| AI | 739 | Input Channel 9 Apparent Power Demand Peak | kVA | Read | ||
| AI | 740 | Input Channel 10 Active Power Demand Peak | kW | Read | ||
| AI | 741 | Input Channel 10 Reactive Power Demand Peak | kvar | Read | ||
| AI | 742 | Input Channel 10 Apparent Power Demand Peak | kVA | Read | ||
| AI | 743 | Input Channel 11 Active Power Demand Peak | kW | Read | ||
| AI | 744 | Input Channel 11 Reactive Power Demand Peak | kvar | Read | ||
| AI | 745 | Input Channel 11 Apparent Power Demand Peak | kVA | Read | ||
| AI | 746 | Input Channel 12 Active Power Demand Peak | kW | Read | ||
| AI | 747 | Input Channel 12 Reactive Power Demand Peak | kvar | Read | ||
| AI | 748 | Input Channel 12 Apparent Power Demand Peak | kVA | Read | ||
| AI | 749 | Input Channel 13 Active Power Demand Peak | kW | Read | ||
| AI | 750 | Input Channel 13 Reactive Power Demand Peak | kvar | Read | ||
| AI | 751 | Input Channel 13 Apparent Power Demand Peak | kVA | Read | ||
| AI | 752 | Input Channel 14 Active Power Demand Peak | kW | Read | ||
| AI | 753 | Input Channel 14 Reactive Power Demand Peak | kvar | Read | ||
| AI | 754 | Input Channel 14 Apparent Power Demand Peak | kVA | Read | ||
| AI | 755 | Input Channel 15 Active Power Demand Peak | kW | Read | ||
| AI | 756 | Input Channel 15 Reactive Power Demand Peak | kvar | Read | ||
| AI | 757 | Input Channel 15 Apparent Power Demand Peak | kVA | Read | ||
| AI | 758 | Input Channel 16 Active Power Demand Peak | kW | Read | ||
| AI | 759 | Input Channel 16 Reactive Power Demand Peak | kvar | Read | ||
| AI | 760 | Input Channel 16 Apparent Power Demand Peak | kVA | Read | ||
| AI | 761 | Input Channel 17 Active Power Demand Peak | kW | Read | ||
| AI | 762 | Input Channel 17 Reactive Power Demand Peak | kvar | Read | ||
| AI | 763 | Input Channel 17 Apparent Power Demand Peak | kVA | Read | ||
| AI | 764 | Input Channel 18 Active Power Demand Peak | kW | Read | ||
| AI | 765 | Input Channel 18 Reactive Power Demand Peak | kvar | Read | ||
| AI | 766 | Input Channel 18 Apparent Power Demand Peak | kVA | Read | ||
| AI | 767 | User Channel 1 Active Power Demand Peak | kW | Read | ||
| AI | 768 | User Channel 1 Reactive Power Demand Peak | kvar | Read | ||
| AI | 769 | User Channel 1 Apparent Power Demand Peak | kVA | Read | ||
| AI | 770 | User Channel 2 Active Power Demand Peak | kW | Read | ||
| AI | 771 | User Channel 2 Reactive Power Demand Peak | kvar | Read | ||
| AI | 772 | User Channel 2 Apparent Power Demand Peak | kVA | Read | ||
| AI | 773 | User Channel 3 Active Power Demand Peak | kW | Read | ||
| AI | 774 | User Channel 3 Reactive Power Demand Peak | kvar | Read | ||
| AI | 775 | User Channel 3 Apparent Power Demand Peak | kVA | Read | ||
| AI | 776 | User Channel 4 Active Power Demand Peak | kW | Read | ||
| AI | 777 | User Channel 4 Reactive Power Demand Peak | kvar | Read | ||
| AI | 778 | User Channel 4 Apparent Power Demand Peak | kVA | Read | ||
| AI | 779 | User Channel 5 Active Power Demand Peak | kW | Read | ||
| AI | 780 | User Channel 5 Reactive Power Demand Peak | kvar | Read | ||
| AI | 781 | User Channel 5 Apparent Power Demand Peak | kVA | Read | ||
| AI | 782 | User Channel 6 Active Power Demand Peak | kW | Read | ||
| AI | 783 | User Channel 6 Reactive Power Demand Peak | kvar | Read | ||
| AI | 784 | User Channel 6 Apparent Power Demand Peak | kVA | Read | ||
| AI | 785 | User Channel 7 Active Power Demand Peak | kW | Read | ||
| AI | 786 | User Channel 7 Reactive Power Demand Peak | kvar | Read | ||
| AI | 787 | User Channel 7 Apparent Power Demand Peak | kVA | Read | ||
| AI | 788 | User Channel 8 Active Power Demand Peak | kW | Read | ||
| AI | 789 | User Channel 8 Reactive Power Demand Peak | kvar | Read | ||
| AI | 790 | User Channel 8 Apparent Power Demand Peak | kVA | Read | ||
| AI | 791 | User Channel 9 Active Power Demand Peak | kW | Read | ||
| AI | 792 | User Channel 9 Reactive Power Demand Peak | kvar | Read | ||
| AI | 793 | User Channel 9 Apparent Power Demand Peak | kVA | Read | ||
| AI | 801 | Phase A Voltage 2nd Harmonic | % | Read | ||
| AI | 802 | Phase A Voltage 3rd Harmonic | % | Read | ||
| AI | 803 | Phase A Voltage 4th Harmonic | % | Read | ||
| AI | 804 | Phase A Voltage 5th Harmonic | % | Read | ||
| AI | 805 | Phase A Voltage 6th Harmonic | % | Read | ||
| AI | 806 | Phase A Voltage 7th Harmonic | % | Read | ||
| AI | 807 | Phase A Voltage 8th Harmonic | % | Read | ||
| AI | 808 | Phase A Voltage 9th Harmonic | % | Read | ||
| AI | 809 | Phase A Voltage 10th Harmonic | % | Read | ||
| AI | 810 | Phase A Voltage 11th Harmonic | % | Read | ||
| AI | 811 | Phase A Voltage 12th Harmonic | % | Read | ||
| AI | 812 | Phase A Voltage 13th Harmonic | % | Read | ||
| AI | 813 | Phase A Voltage 14th Harmonic | % | Read | ||
| AI | 814 | Phase A Voltage 15th Harmonic | % | Read | ||
| AI | 815 | Phase A Voltage 16th Harmonic | % | Read | ||
| AI | 816 | Phase A Voltage 17th Harmonic | % | Read | ||
| AI | 817 | Phase A Voltage 18th Harmonic | % | Read | ||
| AI | 818 | Phase A Voltage 19th Harmonic | % | Read | ||
| AI | 819 | Phase A Voltage 20th Harmonic | % | Read | ||
| AI | 820 | Phase A Voltage 21st Harmonic | % | Read | ||
| AI | 821 | Phase A Voltage 22nd Harmonic | % | Read | ||
| AI | 822 | Phase A Voltage 23rd Harmonic | % | Read | ||
| AI | 823 | Phase A Voltage 24th Harmonic | % | Read | ||
| AI | 824 | Phase A Voltage 25th Harmonic | % | Read | ||
| AI | 825 | Phase A Voltage 26th Harmonic | % | Read | ||
| AI | 826 | Phase A Voltage 27th Harmonic | % | Read | ||
| AI | 827 | Phase A Voltage 28th Harmonic | % | Read | ||
| AI | 828 | Phase A Voltage 29th Harmonic | % | Read | ||
| AI | 829 | Phase A Voltage 30th Harmonic | % | Read | ||
| AI | 830 | Phase A Voltage 31st Harmonic | % | Read | ||
| AI | 831 | Phase B Voltage 2nd Harmonic | % | Read | ||
| AI | 832 | Phase B Voltage 3rd Harmonic | % | Read | ||
| AI | 833 | Phase B Voltage 4th Harmonic | % | Read | ||
| AI | 834 | Phase B Voltage 5th Harmonic | % | Read | ||
| AI | 835 | Phase B Voltage 6th Harmonic | % | Read | ||
| AI | 836 | Phase B Voltage 7th Harmonic | % | Read | ||
| AI | 837 | Phase B Voltage 8th Harmonic | % | Read | ||
| AI | 838 | Phase B Voltage 9th Harmonic | % | Read | ||
| AI | 839 | Phase B Voltage 10th Harmonic | % | Read | ||
| AI | 840 | Phase B Voltage 11th Harmonic | % | Read | ||
| AI | 841 | Phase B Voltage 12th Harmonic | % | Read | ||
| AI | 842 | Phase B Voltage 13th Harmonic | % | Read | ||
| AI | 843 | Phase B Voltage 14th Harmonic | % | Read | ||
| AI | 844 | Phase B Voltage 15th Harmonic | % | Read | ||
| AI | 845 | Phase B Voltage 16th Harmonic | % | Read | ||
| AI | 846 | Phase B Voltage 17th Harmonic | % | Read | ||
| AI | 847 | Phase B Voltage 18th Harmonic | % | Read | ||
| AI | 848 | Phase B Voltage 19th Harmonic | % | Read | ||
| AI | 849 | Phase B Voltage 20th Harmonic | % | Read | ||
| AI | 850 | Phase B Voltage 21st Harmonic | % | Read | ||
| AI | 851 | Phase B Voltage 22nd Harmonic | % | Read | ||
| AI | 852 | Phase B Voltage 23rd Harmonic | % | Read | ||
| AI | 853 | Phase B Voltage 24th Harmonic | % | Read | ||
| AI | 854 | Phase B Voltage 25th Harmonic | % | Read | ||
| AI | 855 | Phase B Voltage 26th Harmonic | % | Read | ||
| AI | 856 | Phase B Voltage 27th Harmonic | % | Read | ||
| AI | 857 | Phase B Voltage 28th Harmonic | % | Read | ||
| AI | 858 | Phase B Voltage 29th Harmonic | % | Read | ||
| AI | 859 | Phase B Voltage 30th Harmonic | % | Read | ||
| AI | 860 | Phase B Voltage 31st Harmonic | % | Read | ||
| AI | 861 | Phase C Voltage 2nd Harmonic | % | Read | ||
| AI | 862 | Phase C Voltage 3rd Harmonic | % | Read | ||
| AI | 863 | Phase C Voltage 4th Harmonic | % | Read | ||
| AI | 864 | Phase C Voltage 5th Harmonic | % | Read | ||
| AI | 865 | Phase C Voltage 6th Harmonic | % | Read | ||
| AI | 866 | Phase C Voltage 7th Harmonic | % | Read | ||
| AI | 867 | Phase C Voltage 8th Harmonic | % | Read | ||
| AI | 868 | Phase C Voltage 9th Harmonic | % | Read | ||
| AI | 869 | Phase C Voltage 10th Harmonic | % | Read | ||
| AI | 870 | Phase C Voltage 11th Harmonic | % | Read | ||
| AI | 871 | Phase C Voltage 12th Harmonic | % | Read | ||
| AI | 872 | Phase C Voltage 13th Harmonic | % | Read | ||
| AI | 873 | Phase C Voltage 14th Harmonic | % | Read | ||
| AI | 874 | Phase C Voltage 15th Harmonic | % | Read | ||
| AI | 875 | Phase C Voltage 16th Harmonic | % | Read | ||
| AI | 876 | Phase C Voltage 17th Harmonic | % | Read | ||
| AI | 877 | Phase C Voltage 18th Harmonic | % | Read | ||
| AI | 878 | Phase C Voltage 19th Harmonic | % | Read | ||
| AI | 879 | Phase C Voltage 20th Harmonic | % | Read | ||
| AI | 880 | Phase C Voltage 21st Harmonic | % | Read | ||
| AI | 881 | Phase C Voltage 22nd Harmonic | % | Read | ||
| AI | 882 | Phase C Voltage 23rd Harmonic | % | Read | ||
| AI | 883 | Phase C Voltage 24th Harmonic | % | Read | ||
| AI | 884 | Phase C Voltage 25th Harmonic | % | Read | ||
| AI | 885 | Phase C Voltage 26th Harmonic | % | Read | ||
| AI | 886 | Phase C Voltage 27th Harmonic | % | Read | ||
| AI | 887 | Phase C Voltage 28th Harmonic | % | Read | ||
| AI | 888 | Phase C Voltage 29th Harmonic | % | Read | ||
| AI | 889 | Phase C Voltage 30th Harmonic | % | Read | ||
| AI | 890 | Phase C Voltage 31st Harmonic | % | Read | ||
| AI | 891 | Input Channel 1 Current 2nd Harmonic | % | Read | ||
| AI | 892 | Input Channel 1 Current 3rd Harmonic | % | Read | ||
| AI | 893 | Input Channel 1 Current 4th Harmonic | % | Read | ||
| AI | 894 | Input Channel 1 Current 5th Harmonic | % | Read | ||
| AI | 895 | Input Channel 1 Current 6th Harmonic | % | Read | ||
| AI | 896 | Input Channel 1 Current 7th Harmonic | % | Read | ||
| AI | 897 | Input Channel 1 Current 8th Harmonic | % | Read | ||
| AI | 898 | Input Channel 1 Current 9th Harmonic | % | Read | ||
| AI | 899 | Input Channel 1 Current 10th Harmonic | % | Read | ||
| AI | 900 | Input Channel 1 Current 11th Harmonic | % | Read | ||
| AI | 901 | Input Channel 1 Current 12th Harmonic | % | Read | ||
| AI | 902 | Input Channel 1 Current 13th Harmonic | % | Read | ||
| AI | 903 | Input Channel 1 Current 14th Harmonic | % | Read | ||
| AI | 904 | Input Channel 1 Current 15th Harmonic | % | Read | ||
| AI | 905 | Input Channel 1 Current 16th Harmonic | % | Read | ||
| AI | 906 | Input Channel 1 Current 17th Harmonic | % | Read | ||
| AI | 907 | Input Channel 1 Current 18th Harmonic | % | Read | ||
| AI | 908 | Input Channel 1 Current 19th Harmonic | % | Read | ||
| AI | 909 | Input Channel 1 Current 20th Harmonic | % | Read | ||
| AI | 910 | Input Channel 1 Current 21st Harmonic | % | Read | ||
| AI | 911 | Input Channel 1 Current 22nd Harmonic | % | Read | ||
| AI | 912 | Input Channel 1 Current 23rd Harmonic | % | Read | ||
| AI | 913 | Input Channel 1 Current 24th Harmonic | % | Read | ||
| AI | 914 | Input Channel 1 Current 25th Harmonic | % | Read | ||
| AI | 915 | Input Channel 1 Current 26th Harmonic | % | Read | ||
| AI | 916 | Input Channel 1 Current 27th Harmonic | % | Read | ||
| AI | 917 | Input Channel 1 Current 28th Harmonic | % | Read | ||
| AI | 918 | Input Channel 1 Current 29th Harmonic | % | Read | ||
| AI | 919 | Input Channel 1 Current 30th Harmonic | % | Read | ||
| AI | 920 | Input Channel 1 Current 31st Harmonic | % | Read | ||
| AI | 921 | Input Channel 2 Current 2nd Harmonic | % | Read | ||
| AI | 922 | Input Channel 2 Current 3rd Harmonic | % | Read | ||
| AI | 923 | Input Channel 2 Current 4th Harmonic | % | Read | ||
| AI | 924 | Input Channel 2 Current 5th Harmonic | % | Read | ||
| AI | 925 | Input Channel 2 Current 6th Harmonic | % | Read | ||
| AI | 926 | Input Channel 2 Current 7th Harmonic | % | Read | ||
| AI | 927 | Input Channel 2 Current 8th Harmonic | % | Read | ||
| AI | 928 | Input Channel 2 Current 9th Harmonic | % | Read | ||
| AI | 929 | Input Channel 2 Current 10th Harmonic | % | Read | ||
| AI | 930 | Input Channel 2 Current 11th Harmonic | % | Read | ||
| AI | 931 | Input Channel 2 Current 12th Harmonic | % | Read | ||
| AI | 932 | Input Channel 2 Current 13th Harmonic | % | Read | ||
| AI | 933 | Input Channel 2 Current 14th Harmonic | % | Read | ||
| AI | 934 | Input Channel 2 Current 15th Harmonic | % | Read | ||
| AI | 935 | Input Channel 2 Current 16th Harmonic | % | Read | ||
| AI | 936 | Input Channel 2 Current 17th Harmonic | % | Read | ||
| AI | 937 | Input Channel 2 Current 18th Harmonic | % | Read | ||
| AI | 938 | Input Channel 2 Current 19th Harmonic | % | Read | ||
| AI | 939 | Input Channel 2 Current 20th Harmonic | % | Read | ||
| AI | 940 | Input Channel 2 Current 21st Harmonic | % | Read | ||
| AI | 941 | Input Channel 2 Current 22nd Harmonic | % | Read | ||
| AI | 942 | Input Channel 2 Current 23rd Harmonic | % | Read | ||
| AI | 943 | Input Channel 2 Current 24th Harmonic | % | Read | ||
| AI | 944 | Input Channel 2 Current 25th Harmonic | % | Read | ||
| AI | 945 | Input Channel 2 Current 26th Harmonic | % | Read | ||
| AI | 946 | Input Channel 2 Current 27th Harmonic | % | Read | ||
| AI | 947 | Input Channel 2 Current 28th Harmonic | % | Read | ||
| AI | 948 | Input Channel 2 Current 29th Harmonic | % | Read | ||
| AI | 949 | Input Channel 2 Current 30th Harmonic | % | Read | ||
| AI | 950 | Input Channel 2 Current 31st Harmonic | % | Read | ||
| AI | 951 | Input Channel 3 Current 2nd Harmonic | % | Read | ||
| AI | 952 | Input Channel 3 Current 3rd Harmonic | % | Read | ||
| AI | 953 | Input Channel 3 Current 4th Harmonic | % | Read | ||
| AI | 954 | Input Channel 3 Current 5th Harmonic | % | Read | ||
| AI | 955 | Input Channel 3 Current 6th Harmonic | % | Read | ||
| AI | 956 | Input Channel 3 Current 7th Harmonic | % | Read | ||
| AI | 957 | Input Channel 3 Current 8th Harmonic | % | Read | ||
| AI | 958 | Input Channel 3 Current 9th Harmonic | % | Read | ||
| AI | 959 | Input Channel 3 Current 10th Harmonic | % | Read | ||
| AI | 960 | Input Channel 3 Current 11th Harmonic | % | Read | ||
| AI | 961 | Input Channel 3 Current 12th Harmonic | % | Read | ||
| AI | 962 | Input Channel 3 Current 13th Harmonic | % | Read | ||
| AI | 963 | Input Channel 3 Current 14th Harmonic | % | Read | ||
| AI | 964 | Input Channel 3 Current 15th Harmonic | % | Read | ||
| AI | 965 | Input Channel 3 Current 16th Harmonic | % | Read | ||
| AI | 966 | Input Channel 3 Current 17th Harmonic | % | Read | ||
| AI | 967 | Input Channel 3 Current 18th Harmonic | % | Read | ||
| AI | 968 | Input Channel 3 Current 19th Harmonic | % | Read | ||
| AI | 969 | Input Channel 3 Current 20th Harmonic | % | Read | ||
| AI | 970 | Input Channel 3 Current 21st Harmonic | % | Read | ||
| AI | 971 | Input Channel 3 Current 22nd Harmonic | % | Read | ||
| AI | 972 | Input Channel 3 Current 23rd Harmonic | % | Read | ||
| AI | 973 | Input Channel 3 Current 24th Harmonic | % | Read | ||
| AI | 974 | Input Channel 3 Current 25th Harmonic | % | Read | ||
| AI | 975 | Input Channel 3 Current 26th Harmonic | % | Read | ||
| AI | 976 | Input Channel 3 Current 27th Harmonic | % | Read | ||
| AI | 977 | Input Channel 3 Current 28th Harmonic | % | Read | ||
| AI | 978 | Input Channel 3 Current 29th Harmonic | % | Read | ||
| AI | 979 | Input Channel 3 Current 30th Harmonic | % | Read | ||
| AI | 980 | Input Channel 3 Current 31st Harmonic | % | Read | ||
| AI | 981 | Input Channel 4 Current 2nd Harmonic | % | Read | ||
| AI | 982 | Input Channel 4 Current 3rd Harmonic | % | Read | ||
| AI | 983 | Input Channel 4 Current 4th Harmonic | % | Read | ||
| AI | 984 | Input Channel 4 Current 5th Harmonic | % | Read | ||
| AI | 985 | Input Channel 4 Current 6th Harmonic | % | Read | ||
| AI | 986 | Input Channel 4 Current 7th Harmonic | % | Read | ||
| AI | 987 | Input Channel 4 Current 8th Harmonic | % | Read | ||
| AI | 988 | Input Channel 4 Current 9th Harmonic | % | Read | ||
| AI | 989 | Input Channel 4 Current 10th Harmonic | % | Read | ||
| AI | 990 | Input Channel 4 Current 11th Harmonic | % | Read | ||
| AI | 991 | Input Channel 4 Current 12th Harmonic | % | Read | ||
| AI | 992 | Input Channel 4 Current 13th Harmonic | % | Read | ||
| AI | 993 | Input Channel 4 Current 14th Harmonic | % | Read | ||
| AI | 994 | Input Channel 4 Current 15th Harmonic | % | Read | ||
| AI | 995 | Input Channel 4 Current 16th Harmonic | % | Read | ||
| AI | 996 | Input Channel 4 Current 17th Harmonic | % | Read | ||
| AI | 997 | Input Channel 4 Current 18th Harmonic | % | Read | ||
| AI | 998 | Input Channel 4 Current 19th Harmonic | % | Read | ||
| AI | 999 | Input Channel 4 Current 20th Harmonic | % | Read | ||
| AI | 1000 | Input Channel 4 Current 21st Harmonic | % | Read | ||
| AI | 1001 | Input Channel 4 Current 22nd Harmonic | % | Read | ||
| AI | 1002 | Input Channel 4 Current 23rd Harmonic | % | Read | ||
| AI | 1003 | Input Channel 4 Current 24th Harmonic | % | Read | ||
| AI | 1004 | Input Channel 4 Current 25th Harmonic | % | Read | ||
| AI | 1005 | Input Channel 4 Current 26th Harmonic | % | Read | ||
| AI | 1006 | Input Channel 4 Current 27th Harmonic | % | Read | ||
| AI | 1007 | Input Channel 4 Current 28th Harmonic | % | Read | ||
| AI | 1008 | Input Channel 4 Current 29th Harmonic | % | Read | ||
| AI | 1009 | Input Channel 4 Current 30th Harmonic | % | Read | ||
| AI | 1010 | Input Channel 4 Current 31st Harmonic | % | Read | ||
| AI | 1011 | Input Channel 5 Current 2nd Harmonic | % | Read | ||
| AI | 1012 | Input Channel 5 Current 3rd Harmonic | % | Read | ||
| AI | 1013 | Input Channel 5 Current 4th Harmonic | % | Read | ||
| AI | 1014 | Input Channel 5 Current 5th Harmonic | % | Read | ||
| AI | 1015 | Input Channel 5 Current 6th Harmonic | % | Read | ||
| AI | 1016 | Input Channel 5 Current 7th Harmonic | % | Read | ||
| AI | 1017 | Input Channel 5 Current 8th Harmonic | % | Read | ||
| AI | 1018 | Input Channel 5 Current 9th Harmonic | % | Read | ||
| AI | 1019 | Input Channel 5 Current 10th Harmonic | % | Read | ||
| AI | 1020 | Input Channel 5 Current 11th Harmonic | % | Read | ||
| AI | 1021 | Input Channel 5 Current 12th Harmonic | % | Read | ||
| AI | 1022 | Input Channel 5 Current 13th Harmonic | % | Read | ||
| AI | 1023 | Input Channel 5 Current 14th Harmonic | % | Read | ||
| AI | 1024 | Input Channel 5 Current 15th Harmonic | % | Read | ||
| AI | 1025 | Input Channel 5 Current 16th Harmonic | % | Read | ||
| AI | 1026 | Input Channel 5 Current 17th Harmonic | % | Read | ||
| AI | 1027 | Input Channel 5 Current 18th Harmonic | % | Read | ||
| AI | 1028 | Input Channel 5 Current 19th Harmonic | % | Read | ||
| AI | 1029 | Input Channel 5 Current 20th Harmonic | % | Read | ||
| AI | 1030 | Input Channel 5 Current 21st Harmonic | % | Read | ||
| AI | 1031 | Input Channel 5 Current 22nd Harmonic | % | Read | ||
| AI | 1032 | Input Channel 5 Current 23rd Harmonic | % | Read | ||
| AI | 1033 | Input Channel 5 Current 24th Harmonic | % | Read | ||
| AI | 1034 | Input Channel 5 Current 25th Harmonic | % | Read | ||
| AI | 1035 | Input Channel 5 Current 26th Harmonic | % | Read | ||
| AI | 1036 | Input Channel 5 Current 27th Harmonic | % | Read | ||
| AI | 1037 | Input Channel 5 Current 28th Harmonic | % | Read | ||
| AI | 1038 | Input Channel 5 Current 29th Harmonic | % | Read | ||
| AI | 1039 | Input Channel 5 Current 30th Harmonic | % | Read | ||
| AI | 1040 | Input Channel 5 Current 31st Harmonic | % | Read | ||
| AI | 1041 | Input Channel 6 Current 2nd Harmonic | % | Read | ||
| AI | 1042 | Input Channel 6 Current 3rd Harmonic | % | Read | ||
| AI | 1043 | Input Channel 6 Current 4th Harmonic | % | Read | ||
| AI | 1044 | Input Channel 6 Current 5th Harmonic | % | Read | ||
| AI | 1045 | Input Channel 6 Current 6th Harmonic | % | Read | ||
| AI | 1046 | Input Channel 6 Current 7th Harmonic | % | Read | ||
| AI | 1047 | Input Channel 6 Current 8th Harmonic | % | Read | ||
| AI | 1048 | Input Channel 6 Current 9th Harmonic | % | Read | ||
| AI | 1049 | Input Channel 6 Current 10th Harmonic | % | Read | ||
| AI | 1050 | Input Channel 6 Current 11th Harmonic | % | Read | ||
| AI | 1051 | Input Channel 6 Current 12th Harmonic | % | Read | ||
| AI | 1052 | Input Channel 6 Current 13th Harmonic | % | Read | ||
| AI | 1053 | Input Channel 6 Current 14th Harmonic | % | Read | ||
| AI | 1054 | Input Channel 6 Current 15th Harmonic | % | Read | ||
| AI | 1055 | Input Channel 6 Current 16th Harmonic | % | Read | ||
| AI | 1056 | Input Channel 6 Current 17th Harmonic | % | Read | ||
| AI | 1057 | Input Channel 6 Current 18th Harmonic | % | Read | ||
| AI | 1058 | Input Channel 6 Current 19th Harmonic | % | Read | ||
| AI | 1059 | Input Channel 6 Current 20th Harmonic | % | Read | ||
| AI | 1060 | Input Channel 6 Current 21st Harmonic | % | Read | ||
| AI | 1061 | Input Channel 6 Current 22nd Harmonic | % | Read | ||
| AI | 1062 | Input Channel 6 Current 23rd Harmonic | % | Read | ||
| AI | 1063 | Input Channel 6 Current 24th Harmonic | % | Read | ||
| AI | 1064 | Input Channel 6 Current 25th Harmonic | % | Read | ||
| AI | 1065 | Input Channel 6 Current 26th Harmonic | % | Read | ||
| AI | 1066 | Input Channel 6 Current 27th Harmonic | % | Read | ||
| AI | 1067 | Input Channel 6 Current 28th Harmonic | % | Read | ||
| AI | 1068 | Input Channel 6 Current 29th Harmonic | % | Read | ||
| AI | 1069 | Input Channel 6 Current 30th Harmonic | % | Read | ||
| AI | 1070 | Input Channel 6 Current 31st Harmonic | % | Read | ||
| AI | 1071 | Input Channel 7 Current 2nd Harmonic | % | Read | ||
| AI | 1072 | Input Channel 7 Current 3rd Harmonic | % | Read | ||
| AI | 1073 | Input Channel 7 Current 4th Harmonic | % | Read | ||
| AI | 1074 | Input Channel 7 Current 5th Harmonic | % | Read | ||
| AI | 1075 | Input Channel 7 Current 6th Harmonic | % | Read | ||
| AI | 1076 | Input Channel 7 Current 7th Harmonic | % | Read | ||
| AI | 1077 | Input Channel 7 Current 8th Harmonic | % | Read | ||
| AI | 1078 | Input Channel 7 Current 9th Harmonic | % | Read | ||
| AI | 1079 | Input Channel 7 Current 10th Harmonic | % | Read | ||
| AI | 1080 | Input Channel 7 Current 11th Harmonic | % | Read | ||
| AI | 1081 | Input Channel 7 Current 12th Harmonic | % | Read | ||
| AI | 1082 | Input Channel 7 Current 13th Harmonic | % | Read | ||
| AI | 1083 | Input Channel 7 Current 14th Harmonic | % | Read | ||
| AI | 1084 | Input Channel 7 Current 15th Harmonic | % | Read | ||
| AI | 1085 | Input Channel 7 Current 16th Harmonic | % | Read | ||
| AI | 1086 | Input Channel 7 Current 17th Harmonic | % | Read | ||
| AI | 1087 | Input Channel 7 Current 18th Harmonic | % | Read | ||
| AI | 1088 | Input Channel 7 Current 19th Harmonic | % | Read | ||
| AI | 1089 | Input Channel 7 Current 20th Harmonic | % | Read | ||
| AI | 1090 | Input Channel 7 Current 21st Harmonic | % | Read | ||
| AI | 1091 | Input Channel 7 Current 22nd Harmonic | % | Read | ||
| AI | 1092 | Input Channel 7 Current 23rd Harmonic | % | Read | ||
| AI | 1093 | Input Channel 7 Current 24th Harmonic | % | Read | ||
| AI | 1094 | Input Channel 7 Current 25th Harmonic | % | Read | ||
| AI | 1095 | Input Channel 7 Current 26th Harmonic | % | Read | ||
| AI | 1096 | Input Channel 7 Current 27th Harmonic | % | Read | ||
| AI | 1097 | Input Channel 7 Current 28th Harmonic | % | Read | ||
| AI | 1098 | Input Channel 7 Current 29th Harmonic | % | Read | ||
| AI | 1099 | Input Channel 7 Current 30th Harmonic | % | Read | ||
| AI | 1100 | Input Channel 7 Current 31st Harmonic | % | Read | ||
| AI | 1101 | Input Channel 8 Current 2nd Harmonic | % | Read | ||
| AI | 1102 | Input Channel 8 Current 3rd Harmonic | % | Read | ||
| AI | 1103 | Input Channel 8 Current 4th Harmonic | % | Read | ||
| AI | 1104 | Input Channel 8 Current 5th Harmonic | % | Read | ||
| AI | 1105 | Input Channel 8 Current 6th Harmonic | % | Read | ||
| AI | 1106 | Input Channel 8 Current 7th Harmonic | % | Read | ||
| AI | 1107 | Input Channel 8 Current 8th Harmonic | % | Read | ||
| AI | 1108 | Input Channel 8 Current 9th Harmonic | % | Read | ||
| AI | 1109 | Input Channel 8 Current 10th Harmonic | % | Read | ||
| AI | 1110 | Input Channel 8 Current 11th Harmonic | % | Read | ||
| AI | 1111 | Input Channel 8 Current 12th Harmonic | % | Read | ||
| AI | 1112 | Input Channel 8 Current 13th Harmonic | % | Read | ||
| AI | 1113 | Input Channel 8 Current 14th Harmonic | % | Read | ||
| AI | 1114 | Input Channel 8 Current 15th Harmonic | % | Read | ||
| AI | 1115 | Input Channel 8 Current 16th Harmonic | % | Read | ||
| AI | 1116 | Input Channel 8 Current 17th Harmonic | % | Read | ||
| AI | 1117 | Input Channel 8 Current 18th Harmonic | % | Read | ||
| AI | 1118 | Input Channel 8 Current 19th Harmonic | % | Read | ||
| AI | 1119 | Input Channel 8 Current 20th Harmonic | % | Read | ||
| AI | 1120 | Input Channel 8 Current 21st Harmonic | % | Read | ||
| AI | 1121 | Input Channel 8 Current 22nd Harmonic | % | Read | ||
| AI | 1122 | Input Channel 8 Current 23rd Harmonic | % | Read | ||
| AI | 1123 | Input Channel 8 Current 24th Harmonic | % | Read | ||
| AI | 1124 | Input Channel 8 Current 25th Harmonic | % | Read | ||
| AI | 1125 | Input Channel 8 Current 26th Harmonic | % | Read | ||
| AI | 1126 | Input Channel 8 Current 27th Harmonic | % | Read | ||
| AI | 1127 | Input Channel 8 Current 28th Harmonic | % | Read | ||
| AI | 1128 | Input Channel 8 Current 29th Harmonic | % | Read | ||
| AI | 1129 | Input Channel 8 Current 30th Harmonic | % | Read | ||
| AI | 1130 | Input Channel 8 Current 31st Harmonic | % | Read | ||
| AI | 1131 | Input Channel 9 Current 2nd Harmonic | % | Read | ||
| AI | 1132 | Input Channel 9 Current 3rd Harmonic | % | Read | ||
| AI | 1133 | Input Channel 9 Current 4th Harmonic | % | Read | ||
| AI | 1134 | Input Channel 9 Current 5th Harmonic | % | Read | ||
| AI | 1135 | Input Channel 9 Current 6th Harmonic | % | Read | ||
| AI | 1136 | Input Channel 9 Current 7th Harmonic | % | Read | ||
| AI | 1137 | Input Channel 9 Current 8th Harmonic | % | Read | ||
| AI | 1138 | Input Channel 9 Current 9th Harmonic | % | Read | ||
| AI | 1139 | Input Channel 9 Current 10th Harmonic | % | Read | ||
| AI | 1140 | Input Channel 9 Current 11th Harmonic | % | Read | ||
| AI | 1141 | Input Channel 9 Current 12th Harmonic | % | Read | ||
| AI | 1142 | Input Channel 9 Current 13th Harmonic | % | Read | ||
| AI | 1143 | Input Channel 9 Current 14th Harmonic | % | Read | ||
| AI | 1144 | Input Channel 9 Current 15th Harmonic | % | Read | ||
| AI | 1145 | Input Channel 9 Current 16th Harmonic | % | Read | ||
| AI | 1146 | Input Channel 9 Current 17th Harmonic | % | Read | ||
| AI | 1147 | Input Channel 9 Current 18th Harmonic | % | Read | ||
| AI | 1148 | Input Channel 9 Current 19th Harmonic | % | Read | ||
| AI | 1149 | Input Channel 9 Current 20th Harmonic | % | Read | ||
| AI | 1150 | Input Channel 9 Current 21st Harmonic | % | Read | ||
| AI | 1151 | Input Channel 9 Current 22nd Harmonic | % | Read | ||
| AI | 1152 | Input Channel 9 Current 23rd Harmonic | % | Read | ||
| AI | 1153 | Input Channel 9 Current 24th Harmonic | % | Read | ||
| AI | 1154 | Input Channel 9 Current 25th Harmonic | % | Read | ||
| AI | 1155 | Input Channel 9 Current 26th Harmonic | % | Read | ||
| AI | 1156 | Input Channel 9 Current 27th Harmonic | % | Read | ||
| AI | 1157 | Input Channel 9 Current 28th Harmonic | % | Read | ||
| AI | 1158 | Input Channel 9 Current 29th Harmonic | % | Read | ||
| AI | 1159 | Input Channel 9 Current 30th Harmonic | % | Read | ||
| AI | 1160 | Input Channel 9 Current 31st Harmonic | % | Read | ||
| AI | 1161 | Input Channel 10 Current 2nd Harmonic | % | Read | ||
| AI | 1162 | Input Channel 10 Current 3rd Harmonic | % | Read | ||
| AI | 1163 | Input Channel 10 Current 4th Harmonic | % | Read | ||
| AI | 1164 | Input Channel 10 Current 5th Harmonic | % | Read | ||
| AI | 1165 | Input Channel 10 Current 6th Harmonic | % | Read | ||
| AI | 1166 | Input Channel 10 Current 7th Harmonic | % | Read | ||
| AI | 1167 | Input Channel 10 Current 8th Harmonic | % | Read | ||
| AI | 1168 | Input Channel 10 Current 9th Harmonic | % | Read | ||
| AI | 1169 | Input Channel 10 Current 10th Harmonic | % | Read | ||
| AI | 1170 | Input Channel 10 Current 11th Harmonic | % | Read | ||
| AI | 1171 | Input Channel 10 Current 12th Harmonic | % | Read | ||
| AI | 1172 | Input Channel 10 Current 13th Harmonic | % | Read | ||
| AI | 1173 | Input Channel 10 Current 14th Harmonic | % | Read | ||
| AI | 1174 | Input Channel 10 Current 15th Harmonic | % | Read | ||
| AI | 1175 | Input Channel 10 Current 16th Harmonic | % | Read | ||
| AI | 1176 | Input Channel 10 Current 17th Harmonic | % | Read | ||
| AI | 1177 | Input Channel 10 Current 18th Harmonic | % | Read | ||
| AI | 1178 | Input Channel 10 Current 19th Harmonic | % | Read | ||
| AI | 1179 | Input Channel 10 Current 20th Harmonic | % | Read | ||
| AI | 1180 | Input Channel 10 Current 21st Harmonic | % | Read | ||
| AI | 1181 | Input Channel 10 Current 22nd Harmonic | % | Read | ||
| AI | 1182 | Input Channel 10 Current 23rd Harmonic | % | Read | ||
| AI | 1183 | Input Channel 10 Current 24th Harmonic | % | Read | ||
| AI | 1184 | Input Channel 10 Current 25th Harmonic | % | Read | ||
| AI | 1185 | Input Channel 10 Current 26th Harmonic | % | Read | ||
| AI | 1186 | Input Channel 10 Current 27th Harmonic | % | Read | ||
| AI | 1187 | Input Channel 10 Current 28th Harmonic | % | Read | ||
| AI | 1188 | Input Channel 10 Current 29th Harmonic | % | Read | ||
| AI | 1189 | Input Channel 10 Current 30th Harmonic | % | Read | ||
| AI | 1190 | Input Channel 10 Current 31st Harmonic | % | Read | ||
| AI | 1191 | Input Channel 11 Current 2nd Harmonic | % | Read | ||
| AI | 1192 | Input Channel 11 Current 3rd Harmonic | % | Read | ||
| AI | 1193 | Input Channel 11 Current 4th Harmonic | % | Read | ||
| AI | 1194 | Input Channel 11 Current 5th Harmonic | % | Read | ||
| AI | 1195 | Input Channel 11 Current 6th Harmonic | % | Read | ||
| AI | 1196 | Input Channel 11 Current 7th Harmonic | % | Read | ||
| AI | 1197 | Input Channel 11 Current 8th Harmonic | % | Read | ||
| AI | 1198 | Input Channel 11 Current 9th Harmonic | % | Read | ||
| AI | 1199 | Input Channel 11 Current 10th Harmonic | % | Read | ||
| AI | 1200 | Input Channel 11 Current 11th Harmonic | % | Read | ||
| AI | 1201 | Input Channel 11 Current 12th Harmonic | % | Read | ||
| AI | 1202 | Input Channel 11 Current 13th Harmonic | % | Read | ||
| AI | 1203 | Input Channel 11 Current 14th Harmonic | % | Read | ||
| AI | 1204 | Input Channel 11 Current 15th Harmonic | % | Read | ||
| AI | 1205 | Input Channel 11 Current 16th Harmonic | % | Read | ||
| AI | 1206 | Input Channel 11 Current 17th Harmonic | % | Read | ||
| AI | 1207 | Input Channel 11 Current 18th Harmonic | % | Read | ||
| AI | 1208 | Input Channel 11 Current 19th Harmonic | % | Read | ||
| AI | 1209 | Input Channel 11 Current 20th Harmonic | % | Read | ||
| AI | 1210 | Input Channel 11 Current 21st Harmonic | % | Read | ||
| AI | 1211 | Input Channel 11 Current 22nd Harmonic | % | Read | ||
| AI | 1212 | Input Channel 11 Current 23rd Harmonic | % | Read | ||
| AI | 1213 | Input Channel 11 Current 24th Harmonic | % | Read | ||
| AI | 1214 | Input Channel 11 Current 25th Harmonic | % | Read | ||
| AI | 1215 | Input Channel 11 Current 26th Harmonic | % | Read | ||
| AI | 1216 | Input Channel 11 Current 27th Harmonic | % | Read | ||
| AI | 1217 | Input Channel 11 Current 28th Harmonic | % | Read | ||
| AI | 1218 | Input Channel 11 Current 29th Harmonic | % | Read | ||
| AI | 1219 | Input Channel 11 Current 30th Harmonic | % | Read | ||
| AI | 1220 | Input Channel 11 Current 31st Harmonic | % | Read | ||
| AI | 1221 | Input Channel 12 Current 2nd Harmonic | % | Read | ||
| AI | 1222 | Input Channel 12 Current 3rd Harmonic | % | Read | ||
| AI | 1223 | Input Channel 12 Current 4th Harmonic | % | Read | ||
| AI | 1224 | Input Channel 12 Current 5th Harmonic | % | Read | ||
| AI | 1225 | Input Channel 12 Current 6th Harmonic | % | Read | ||
| AI | 1226 | Input Channel 12 Current 7th Harmonic | % | Read | ||
| AI | 1227 | Input Channel 12 Current 8th Harmonic | % | Read | ||
| AI | 1228 | Input Channel 12 Current 9th Harmonic | % | Read | ||
| AI | 1229 | Input Channel 12 Current 10th Harmonic | % | Read | ||
| AI | 1230 | Input Channel 12 Current 11th Harmonic | % | Read | ||
| AI | 1231 | Input Channel 12 Current 12th Harmonic | % | Read | ||
| AI | 1232 | Input Channel 12 Current 13th Harmonic | % | Read | ||
| AI | 1233 | Input Channel 12 Current 14th Harmonic | % | Read | ||
| AI | 1234 | Input Channel 12 Current 15th Harmonic | % | Read | ||
| AI | 1235 | Input Channel 12 Current 16th Harmonic | % | Read | ||
| AI | 1236 | Input Channel 12 Current 17th Harmonic | % | Read | ||
| AI | 1237 | Input Channel 12 Current 18th Harmonic | % | Read | ||
| AI | 1238 | Input Channel 12 Current 19th Harmonic | % | Read | ||
| AI | 1239 | Input Channel 12 Current 20th Harmonic | % | Read | ||
| AI | 1240 | Input Channel 12 Current 21st Harmonic | % | Read | ||
| AI | 1241 | Input Channel 12 Current 22nd Harmonic | % | Read | ||
| AI | 1242 | Input Channel 12 Current 23rd Harmonic | % | Read | ||
| AI | 1243 | Input Channel 12 Current 24th Harmonic | % | Read | ||
| AI | 1244 | Input Channel 12 Current 25th Harmonic | % | Read | ||
| AI | 1245 | Input Channel 12 Current 26th Harmonic | % | Read | ||
| AI | 1246 | Input Channel 12 Current 27th Harmonic | % | Read | ||
| AI | 1247 | Input Channel 12 Current 28th Harmonic | % | Read | ||
| AI | 1248 | Input Channel 12 Current 29th Harmonic | % | Read | ||
| AI | 1249 | Input Channel 12 Current 30th Harmonic | % | Read | ||
| AI | 1250 | Input Channel 12 Current 31st Harmonic | % | Read | ||
| AI | 1251 | Input Channel 13 Current 2nd Harmonic | % | Read | ||
| AI | 1252 | Input Channel 13 Current 3rd Harmonic | % | Read | ||
| AI | 1253 | Input Channel 13 Current 4th Harmonic | % | Read | ||
| AI | 1254 | Input Channel 13 Current 5th Harmonic | % | Read | ||
| AI | 1255 | Input Channel 13 Current 6th Harmonic | % | Read | ||
| AI | 1256 | Input Channel 13 Current 7th Harmonic | % | Read | ||
| AI | 1257 | Input Channel 13 Current 8th Harmonic | % | Read | ||
| AI | 1258 | Input Channel 13 Current 9th Harmonic | % | Read | ||
| AI | 1259 | Input Channel 13 Current 10th Harmonic | % | Read | ||
| AI | 1260 | Input Channel 13 Current 11th Harmonic | % | Read | ||
| AI | 1261 | Input Channel 13 Current 12th Harmonic | % | Read | ||
| AI | 1262 | Input Channel 13 Current 13th Harmonic | % | Read | ||
| AI | 1263 | Input Channel 13 Current 14th Harmonic | % | Read | ||
| AI | 1264 | Input Channel 13 Current 15th Harmonic | % | Read | ||
| AI | 1265 | Input Channel 13 Current 16th Harmonic | % | Read | ||
| AI | 1266 | Input Channel 13 Current 17th Harmonic | % | Read | ||
| AI | 1267 | Input Channel 13 Current 18th Harmonic | % | Read | ||
| AI | 1268 | Input Channel 13 Current 19th Harmonic | % | Read | ||
| AI | 1269 | Input Channel 13 Current 20th Harmonic | % | Read | ||
| AI | 1270 | Input Channel 13 Current 21st Harmonic | % | Read | ||
| AI | 1271 | Input Channel 13 Current 22nd Harmonic | % | Read | ||
| AI | 1272 | Input Channel 13 Current 23rd Harmonic | % | Read | ||
| AI | 1273 | Input Channel 13 Current 24th Harmonic | % | Read | ||
| AI | 1274 | Input Channel 13 Current 25th Harmonic | % | Read | ||
| AI | 1275 | Input Channel 13 Current 26th Harmonic | % | Read | ||
| AI | 1276 | Input Channel 13 Current 27th Harmonic | % | Read | ||
| AI | 1277 | Input Channel 13 Current 28th Harmonic | % | Read | ||
| AI | 1278 | Input Channel 13 Current 29th Harmonic | % | Read | ||
| AI | 1279 | Input Channel 13 Current 30th Harmonic | % | Read | ||
| AI | 1280 | Input Channel 13 Current 31st Harmonic | % | Read | ||
| AI | 1281 | Input Channel 14 Current 2nd Harmonic | % | Read | ||
| AI | 1282 | Input Channel 14 Current 3rd Harmonic | % | Read | ||
| AI | 1283 | Input Channel 14 Current 4th Harmonic | % | Read | ||
| AI | 1284 | Input Channel 14 Current 5th Harmonic | % | Read | ||
| AI | 1285 | Input Channel 14 Current 6th Harmonic | % | Read | ||
| AI | 1286 | Input Channel 14 Current 7th Harmonic | % | Read | ||
| AI | 1287 | Input Channel 14 Current 8th Harmonic | % | Read | ||
| AI | 1288 | Input Channel 14 Current 9th Harmonic | % | Read | ||
| AI | 1289 | Input Channel 14 Current 10th Harmonic | % | Read | ||
| AI | 1290 | Input Channel 14 Current 11th Harmonic | % | Read | ||
| AI | 1291 | Input Channel 14 Current 12th Harmonic | % | Read | ||
| AI | 1292 | Input Channel 14 Current 13th Harmonic | % | Read | ||
| AI | 1293 | Input Channel 14 Current 14th Harmonic | % | Read | ||
| AI | 1294 | Input Channel 14 Current 15th Harmonic | % | Read | ||
| AI | 1295 | Input Channel 14 Current 16th Harmonic | % | Read | ||
| AI | 1296 | Input Channel 14 Current 17th Harmonic | % | Read | ||
| AI | 1297 | Input Channel 14 Current 18th Harmonic | % | Read | ||
| AI | 1298 | Input Channel 14 Current 19th Harmonic | % | Read | ||
| AI | 1299 | Input Channel 14 Current 20th Harmonic | % | Read | ||
| AI | 1300 | Input Channel 14 Current 21st Harmonic | % | Read | ||
| AI | 1301 | Input Channel 14 Current 22nd Harmonic | % | Read | ||
| AI | 1302 | Input Channel 14 Current 23rd Harmonic | % | Read | ||
| AI | 1303 | Input Channel 14 Current 24th Harmonic | % | Read | ||
| AI | 1304 | Input Channel 14 Current 25th Harmonic | % | Read | ||
| AI | 1305 | Input Channel 14 Current 26th Harmonic | % | Read | ||
| AI | 1306 | Input Channel 14 Current 27th Harmonic | % | Read | ||
| AI | 1307 | Input Channel 14 Current 28th Harmonic | % | Read | ||
| AI | 1308 | Input Channel 14 Current 29th Harmonic | % | Read | ||
| AI | 1309 | Input Channel 14 Current 30th Harmonic | % | Read | ||
| AI | 1310 | Input Channel 14 Current 31st Harmonic | % | Read | ||
| AI | 1311 | Input Channel 15 Current 2nd Harmonic | % | Read | ||
| AI | 1312 | Input Channel 15 Current 3rd Harmonic | % | Read | ||
| AI | 1313 | Input Channel 15 Current 4th Harmonic | % | Read | ||
| AI | 1314 | Input Channel 15 Current 5th Harmonic | % | Read | ||
| AI | 1315 | Input Channel 15 Current 6th Harmonic | % | Read | ||
| AI | 1316 | Input Channel 15 Current 7th Harmonic | % | Read | ||
| AI | 1317 | Input Channel 15 Current 8th Harmonic | % | Read | ||
| AI | 1318 | Input Channel 15 Current 9th Harmonic | % | Read | ||
| AI | 1319 | Input Channel 15 Current 10th Harmonic | % | Read | ||
| AI | 1320 | Input Channel 15 Current 11th Harmonic | % | Read | ||
| AI | 1321 | Input Channel 15 Current 12th Harmonic | % | Read | ||
| AI | 1322 | Input Channel 15 Current 13th Harmonic | % | Read | ||
| AI | 1323 | Input Channel 15 Current 14th Harmonic | % | Read | ||
| AI | 1324 | Input Channel 15 Current 15th Harmonic | % | Read | ||
| AI | 1325 | Input Channel 15 Current 16th Harmonic | % | Read | ||
| AI | 1326 | Input Channel 15 Current 17th Harmonic | % | Read | ||
| AI | 1327 | Input Channel 15 Current 18th Harmonic | % | Read | ||
| AI | 1328 | Input Channel 15 Current 19th Harmonic | % | Read | ||
| AI | 1329 | Input Channel 15 Current 20th Harmonic | % | Read | ||
| AI | 1330 | Input Channel 15 Current 21st Harmonic | % | Read | ||
| AI | 1331 | Input Channel 15 Current 22nd Harmonic | % | Read | ||
| AI | 1332 | Input Channel 15 Current 23rd Harmonic | % | Read | ||
| AI | 1333 | Input Channel 15 Current 24th Harmonic | % | Read | ||
| AI | 1334 | Input Channel 15 Current 25th Harmonic | % | Read | ||
| AI | 1335 | Input Channel 15 Current 26th Harmonic | % | Read | ||
| AI | 1336 | Input Channel 15 Current 27th Harmonic | % | Read | ||
| AI | 1337 | Input Channel 15 Current 28th Harmonic | % | Read | ||
| AI | 1338 | Input Channel 15 Current 29th Harmonic | % | Read | ||
| AI | 1339 | Input Channel 15 Current 30th Harmonic | % | Read | ||
| AI | 1340 | Input Channel 15 Current 31st Harmonic | % | Read | ||
| AI | 1341 | Input Channel 16 Current 2nd Harmonic | % | Read | ||
| AI | 1342 | Input Channel 16 Current 3rd Harmonic | % | Read | ||
| AI | 1343 | Input Channel 16 Current 4th Harmonic | % | Read | ||
| AI | 1344 | Input Channel 16 Current 5th Harmonic | % | Read | ||
| AI | 1345 | Input Channel 16 Current 6th Harmonic | % | Read | ||
| AI | 1346 | Input Channel 16 Current 7th Harmonic | % | Read | ||
| AI | 1347 | Input Channel 16 Current 8th Harmonic | % | Read | ||
| AI | 1348 | Input Channel 16 Current 9th Harmonic | % | Read | ||
| AI | 1349 | Input Channel 16 Current 10th Harmonic | % | Read | ||
| AI | 1350 | Input Channel 16 Current 11th Harmonic | % | Read | ||
| AI | 1351 | Input Channel 16 Current 12th Harmonic | % | Read | ||
| AI | 1352 | Input Channel 16 Current 13th Harmonic | % | Read | ||
| AI | 1353 | Input Channel 16 Current 14th Harmonic | % | Read | ||
| AI | 1354 | Input Channel 16 Current 15th Harmonic | % | Read | ||
| AI | 1355 | Input Channel 16 Current 16th Harmonic | % | Read | ||
| AI | 1356 | Input Channel 16 Current 17th Harmonic | % | Read | ||
| AI | 1357 | Input Channel 16 Current 18th Harmonic | % | Read | ||
| AI | 1358 | Input Channel 16 Current 19th Harmonic | % | Read | ||
| AI | 1359 | Input Channel 16 Current 20th Harmonic | % | Read | ||
| AI | 1360 | Input Channel 16 Current 21st Harmonic | % | Read | ||
| AI | 1361 | Input Channel 16 Current 22nd Harmonic | % | Read | ||
| AI | 1362 | Input Channel 16 Current 23rd Harmonic | % | Read | ||
| AI | 1363 | Input Channel 16 Current 24th Harmonic | % | Read | ||
| AI | 1364 | Input Channel 16 Current 25th Harmonic | % | Read | ||
| AI | 1365 | Input Channel 16 Current 26th Harmonic | % | Read | ||
| AI | 1366 | Input Channel 16 Current 27th Harmonic | % | Read | ||
| AI | 1367 | Input Channel 16 Current 28th Harmonic | % | Read | ||
| AI | 1368 | Input Channel 16 Current 29th Harmonic | % | Read | ||
| AI | 1369 | Input Channel 16 Current 30th Harmonic | % | Read | ||
| AI | 1370 | Input Channel 16 Current 31st Harmonic | % | Read | ||
| AI | 1371 | Input Channel 17 Current 2nd Harmonic | % | Read | ||
| AI | 1372 | Input Channel 17 Current 3rd Harmonic | % | Read | ||
| AI | 1373 | Input Channel 17 Current 4th Harmonic | % | Read | ||
| AI | 1374 | Input Channel 17 Current 5th Harmonic | % | Read | ||
| AI | 1375 | Input Channel 17 Current 6th Harmonic | % | Read | ||
| AI | 1376 | Input Channel 17 Current 7th Harmonic | % | Read | ||
| AI | 1377 | Input Channel 17 Current 8th Harmonic | % | Read | ||
| AI | 1378 | Input Channel 17 Current 9th Harmonic | % | Read | ||
| AI | 1379 | Input Channel 17 Current 10th Harmonic | % | Read | ||
| AI | 1380 | Input Channel 17 Current 11th Harmonic | % | Read | ||
| AI | 1381 | Input Channel 17 Current 12th Harmonic | % | Read | ||
| AI | 1382 | Input Channel 17 Current 13th Harmonic | % | Read | ||
| AI | 1383 | Input Channel 17 Current 14th Harmonic | % | Read | ||
| AI | 1384 | Input Channel 17 Current 15th Harmonic | % | Read | ||
| AI | 1385 | Input Channel 17 Current 16th Harmonic | % | Read | ||
| AI | 1386 | Input Channel 17 Current 17th Harmonic | % | Read | ||
| AI | 1387 | Input Channel 17 Current 18th Harmonic | % | Read | ||
| AI | 1388 | Input Channel 17 Current 19th Harmonic | % | Read | ||
| AI | 1389 | Input Channel 17 Current 20th Harmonic | % | Read | ||
| AI | 1390 | Input Channel 17 Current 21st Harmonic | % | Read | ||
| AI | 1391 | Input Channel 17 Current 22nd Harmonic | % | Read | ||
| AI | 1392 | Input Channel 17 Current 23rd Harmonic | % | Read | ||
| AI | 1393 | Input Channel 17 Current 24th Harmonic | % | Read | ||
| AI | 1394 | Input Channel 17 Current 25th Harmonic | % | Read | ||
| AI | 1395 | Input Channel 17 Current 26th Harmonic | % | Read | ||
| AI | 1396 | Input Channel 17 Current 27th Harmonic | % | Read | ||
| AI | 1397 | Input Channel 17 Current 28th Harmonic | % | Read | ||
| AI | 1398 | Input Channel 17 Current 29th Harmonic | % | Read | ||
| AI | 1399 | Input Channel 17 Current 30th Harmonic | % | Read | ||
| AI | 1400 | Input Channel 17 Current 31st Harmonic | % | Read | ||
| AI | 1401 | Input Channel 18 Current 2nd Harmonic | % | Read | ||
| AI | 1402 | Input Channel 18 Current 3rd Harmonic | % | Read | ||
| AI | 1403 | Input Channel 18 Current 4th Harmonic | % | Read | ||
| AI | 1404 | Input Channel 18 Current 5th Harmonic | % | Read | ||
| AI | 1405 | Input Channel 18 Current 6th Harmonic | % | Read | ||
| AI | 1406 | Input Channel 18 Current 7th Harmonic | % | Read | ||
| AI | 1407 | Input Channel 18 Current 8th Harmonic | % | Read | ||
| AI | 1408 | Input Channel 18 Current 9th Harmonic | % | Read | ||
| AI | 1409 | Input Channel 18 Current 10th Harmonic | % | Read | ||
| AI | 1410 | Input Channel 18 Current 11th Harmonic | % | Read | ||
| AI | 1411 | Input Channel 18 Current 12th Harmonic | % | Read | ||
| AI | 1412 | Input Channel 18 Current 13th Harmonic | % | Read | ||
| AI | 1413 | Input Channel 18 Current 14th Harmonic | % | Read | ||
| AI | 1414 | Input Channel 18 Current 15th Harmonic | % | Read | ||
| AI | 1415 | Input Channel 18 Current 16th Harmonic | % | Read | ||
| AI | 1416 | Input Channel 18 Current 17th Harmonic | % | Read | ||
| AI | 1417 | Input Channel 18 Current 18th Harmonic | % | Read | ||
| AI | 1418 | Input Channel 18 Current 19th Harmonic | % | Read | ||
| AI | 1419 | Input Channel 18 Current 20th Harmonic | % | Read | ||
| AI | 1420 | Input Channel 18 Current 21st Harmonic | % | Read | ||
| AI | 1421 | Input Channel 18 Current 22nd Harmonic | % | Read | ||
| AI | 1422 | Input Channel 18 Current 23rd Harmonic | % | Read | ||
| AI | 1423 | Input Channel 18 Current 24th Harmonic | % | Read | ||
| AI | 1424 | Input Channel 18 Current 25th Harmonic | % | Read | ||
| AI | 1425 | Input Channel 18 Current 26th Harmonic | % | Read | ||
| AI | 1426 | Input Channel 18 Current 27th Harmonic | % | Read | ||
| AI | 1427 | Input Channel 18 Current 28th Harmonic | % | Read | ||
| AI | 1428 | Input Channel 18 Current 29th Harmonic | % | Read | ||
| AI | 1429 | Input Channel 18 Current 30th Harmonic | % | Read | ||
| AI | 1430 | Input Channel 18 Current 31st Harmonic | % | Read |
No points match these filters.
Object ID lookup: Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module point IDs by name
AI1Average FrequencyAI2Average Line-to-Neutral VoltageAI3Average Line-to-Line VoltageAI4Average Line CurrentAI5System Active PowerAI6System Reactive PowerAI7System Apparent PowerAI8System Power FactorAI9System Load NatureAI10Phase A Line-to-Neutral VoltageAI11Phase A-B Line-to-Line VoltageAI12Phase A Line CurrentAI13Phase A Active PowerAI14Phase A Reactive PowerAI15Phase A Apparent PowerAI16Phase A Power FactorAI17Phase A Load NatureAI18Phase B Line-to-Neutral VoltageAI19Phase B-C Line-to-Line VoltageAI20Phase B Line CurrentAI21Phase B Active PowerAI22Phase B Reactive PowerAI23Phase B Apparent PowerAI24Phase B Power FactorAI25Phase B Load NatureAI26Phase C Line-to-Neutral VoltageAI27Phase C-A Line-to-Line VoltageAI28Phase C Line CurrentAI29Phase C Active PowerAI30Phase C Reactive PowerAI31Phase C Apparent PowerAI32Phase C Power FactorAI33Phase C Load NatureAI34Input Channel 1 Line CurrentAI35Input Channel 1 Active PowerAI36Input Channel 1 Reactive PowerAI37Input Channel 1 Apparent PowerAI38Input Channel 1 Power FactorAI39Input Channel 1 Load NatureAI40Input Channel 2 Line CurrentAI41Input Channel 2 Active PowerAI42Input Channel 2 Reactive PowerAI43Input Channel 2 Apparent PowerAI44Input Channel 2 Power FactorAI45Input Channel 2 Load NatureAI46Input Channel 3 Line CurrentAI47Input Channel 3 Active PowerAI48Input Channel 3 Reactive PowerAI49Input Channel 3 Apparent PowerAI50Input Channel 3 Power FactorAI51Input Channel 3 Load NatureAI52Input Channel 4 Line CurrentAI53Input Channel 4 Active PowerAI54Input Channel 4 Reactive PowerAI55Input Channel 4 Apparent PowerAI56Input Channel 4 Power FactorAI57Input Channel 4 Load NatureAI58Input Channel 5 Line CurrentAI59Input Channel 5 Active PowerAI60Input Channel 5 Reactive PowerAI61Input Channel 5 Apparent PowerAI62Input Channel 5 Power FactorAI63Input Channel 5 Load NatureAI64Input Channel 6 Line CurrentAI65Input Channel 6 Active PowerAI66Input Channel 6 Reactive PowerAI67Input Channel 6 Apparent PowerAI68Input Channel 6 Power FactorAI69Input Channel 6 Load NatureAI70Input Channel 7 Line CurrentAI71Input Channel 7 Active PowerAI72Input Channel 7 Reactive PowerAI73Input Channel 7 Apparent PowerAI74Input Channel 7 Power FactorAI75Input Channel 7 Load NatureAI76Input Channel 8 Line CurrentAI77Input Channel 8 Active PowerAI78Input Channel 8 Reactive PowerAI79Input Channel 8 Apparent PowerAI80Input Channel 8 Power FactorAI81Input Channel 8 Load NatureAI82Input Channel 9 Line CurrentAI83Input Channel 9 Active PowerAI84Input Channel 9 Reactive PowerAI85Input Channel 9 Apparent PowerAI86Input Channel 9 Power FactorAI87Input Channel 9 Load NatureAI88Input Channel 10 Line CurrentAI89Input Channel 10 Active PowerAI90Input Channel 10 Reactive PowerAI91Input Channel 10 Apparent PowerAI92Input Channel 10 Power FactorAI93Input Channel 10 Load NatureAI94Input Channel 11 Line CurrentAI95Input Channel 11 Active PowerAI96Input Channel 11 Reactive PowerAI97Input Channel 11 Apparent PowerAI98Input Channel 11 Power FactorAI99Input Channel 11 Load NatureAI100Input Channel 12 Line CurrentAI101Input Channel 12 Active PowerAI102Input Channel 12 Reactive PowerAI103Input Channel 12 Apparent PowerAI104Input Channel 12 Power FactorAI105Input Channel 12 Load NatureAI106Input Channel 13 Line CurrentAI107Input Channel 13 Active PowerAI108Input Channel 13 Reactive PowerAI109Input Channel 13 Apparent PowerAI110Input Channel 13 Power FactorAI111Input Channel 13 Load NatureAI112Input Channel 14 Line CurrentAI113Input Channel 14 Active PowerAI114Input Channel 14 Reactive PowerAI115Input Channel 14 Apparent PowerAI116Input Channel 14 Power FactorAI117Input Channel 14 Load NatureAI118Input Channel 15 Line CurrentAI119Input Channel 15 Active PowerAI120Input Channel 15 Reactive PowerAI121Input Channel 15 Apparent PowerAI122Input Channel 15 Power FactorAI123Input Channel 15 Load NatureAI124Input Channel 16 Line CurrentAI125Input Channel 16 Active PowerAI126Input Channel 16 Reactive PowerAI127Input Channel 16 Apparent PowerAI128Input Channel 16 Power FactorAI129Input Channel 16 Load NatureAI130Input Channel 17 Line CurrentAI131Input Channel 17 Active PowerAI132Input Channel 17 Reactive PowerAI133Input Channel 17 Apparent PowerAI134Input Channel 17 Power FactorAI135Input Channel 17 Load NatureAI136Input Channel 18 Line CurrentAI137Input Channel 18 Active PowerAI138Input Channel 18 Reactive PowerAI139Input Channel 18 Apparent PowerAI140Input Channel 18 Power FactorAI141Input Channel 18 Load NatureAI142User Channel 1 Active PowerAI143User Channel 1 Reactive PowerAI144User Channel 1 Apparent PowerAI145User Channel 1 Power FactorAI146User Channel 1 Load NatureAI147User Channel 2 Active PowerAI148User Channel 2 Reactive PowerAI149User Channel 2 Apparent PowerAI150User Channel 2 Power FactorAI151User Channel 2 Load NatureAI152User Channel 3 Active PowerAI153User Channel 3 Reactive PowerAI154User Channel 3 Apparent PowerAI155User Channel 3 Power FactorAI156User Channel 3 Load NatureAI157User Channel 4 Active PowerAI158User Channel 4 Reactive PowerAI159User Channel 4 Apparent PowerAI160User Channel 4 Power FactorAI161User Channel 4 Load NatureAI162User Channel 5 Active PowerAI163User Channel 5 Reactive PowerAI164User Channel 5 Apparent PowerAI165User Channel 5 Power FactorAI166User Channel 5 Load NatureAI167User Channel 6 Active PowerAI168User Channel 6 Reactive PowerAI169User Channel 6 Apparent PowerAI170User Channel 6 Power FactorAI171User Channel 6 Load NatureAI172User Channel 7 Active PowerAI173User Channel 7 Reactive PowerAI174User Channel 7 Apparent PowerAI175User Channel 7 Power FactorAI176User Channel 7 Load NatureAI177User Channel 8 Active PowerAI178User Channel 8 Reactive PowerAI179User Channel 8 Apparent PowerAI180User Channel 8 Power FactorAI181User Channel 8 Load NatureAI182User Channel 9 Active PowerAI183User Channel 9 Reactive PowerAI184User Channel 9 Apparent PowerAI185User Channel 9 Power FactorAI186User Channel 9 Load NatureAI201System Active EnergyAI202System Reactive EnergyAI203System Apparent EnergyAI204Phase A Active EnergyAI205Phase A Reactive EnergyAI206Phase A Apparent EnergyAI207Phase B Active EnergyAI208Phase B Reactive EnergyAI209Phase B Apparent EnergyAI210Phase C Active EnergyAI211Phase C Reactive EnergyAI212Phase C Apparent EnergyAI213Input Channel 1 Active EnergyAI214Input Channel 1 Reactive EnergyAI215Input Channel 1 Apparent EnergyAI216Input Channel 2 Active EnergyAI217Input Channel 2 Reactive EnergyAI218Input Channel 2 Apparent EnergyAI219Input Channel 3 Active EnergyAI220Input Channel 3 Reactive EnergyAI221Input Channel 3 Apparent EnergyAI222Input Channel 4 Active EnergyAI223Input Channel 4 Reactive EnergyAI224Input Channel 4 Apparent EnergyAI225Input Channel 5 Active EnergyAI226Input Channel 5 Reactive EnergyAI227Input Channel 5 Apparent EnergyAI228Input Channel 6 Active EnergyAI229Input Channel 6 Reactive EnergyAI230Input Channel 6 Apparent EnergyAI231Input Channel 7 Active EnergyAI232Input Channel 7 Reactive EnergyAI233Input Channel 7 Apparent EnergyAI234Input Channel 8 Active EnergyAI235Input Channel 8 Reactive EnergyAI236Input Channel 8 Apparent EnergyAI237Input Channel 9 Active EnergyAI238Input Channel 9 Reactive EnergyAI239Input Channel 9 Apparent EnergyAI240Input Channel 10 Active EnergyAI241Input Channel 10 Reactive EnergyAI242Input Channel 10 Apparent EnergyAI243Input Channel 11 Active EnergyAI244Input Channel 11 Reactive EnergyAI245Input Channel 11 Apparent EnergyAI246Input Channel 12 Active EnergyAI247Input Channel 12 Reactive EnergyAI248Input Channel 12 Apparent EnergyAI249Input Channel 13 Active EnergyAI250Input Channel 13 Reactive EnergyAI251Input Channel 13 Apparent EnergyAI252Input Channel 14 Active EnergyAI253Input Channel 14 Reactive EnergyAI254Input Channel 14 Apparent EnergyAI255Input Channel 15 Active EnergyAI256Input Channel 15 Reactive EnergyAI257Input Channel 15 Apparent EnergyAI258Input Channel 16 Active EnergyAI259Input Channel 16 Reactive EnergyAI260Input Channel 16 Apparent EnergyAI261Input Channel 17 Active EnergyAI262Input Channel 17 Reactive EnergyAI263Input Channel 17 Apparent EnergyAI264Input Channel 18 Active EnergyAI265Input Channel 18 Reactive EnergyAI266Input Channel 18 Apparent EnergyAI267User Channel 1 Active EnergyAI268User Channel 1 Reactive EnergyAI269User Channel 1 Apparent EnergyAI270User Channel 2 Active EnergyAI271User Channel 2 Reactive EnergyAI272User Channel 2 Apparent EnergyAI273User Channel 3 Active EnergyAI274User Channel 3 Reactive EnergyAI275User Channel 3 Apparent EnergyAI276User Channel 4 Active EnergyAI277User Channel 4 Reactive EnergyAI278User Channel 4 Apparent EnergyAI279User Channel 5 Active EnergyAI280User Channel 5 Reactive EnergyAI281User Channel 5 Apparent EnergyAI282User Channel 6 Active EnergyAI283User Channel 6 Reactive EnergyAI284User Channel 6 Apparent EnergyAI285User Channel 7 Active EnergyAI286User Channel 7 Reactive EnergyAI287User Channel 7 Apparent EnergyAI288User Channel 8 Active EnergyAI289User Channel 8 Reactive EnergyAI290User Channel 8 Apparent EnergyAI291User Channel 9 Active EnergyAI292User Channel 9 Reactive EnergyAI293User Channel 9 Apparent EnergyAI301System Active Power DemandAI302System Reactive Power DemandAI303System Apparent Power DemandAI304Phase A Current DemandAI305Phase A Active Power DemandAI306Phase A Reactive Power DemandAI307Phase A Apparent Power DemandAI308Phase B Current DemandAI309Phase B Active Power DemandAI310Phase B Reactive Power DemandAI311Phase B Apparent Power DemandAI312Phase C Current DemandAI313Phase C Active Power DemandAI314Phase C Reactive Power DemandAI315Phase C Apparent Power DemandAI316Input Channel 1 Current DemandAI317Input Channel 1 Active Power DemandAI318Input Channel 1 Reactive Power DemandAI319Input Channel 1 Apparent Power DemandAI320Input Channel 2 Current DemandAI321Input Channel 2 Active Power DemandAI322Input Channel 2 Reactive Power DemandAI323Input Channel 2 Apparent Power DemandAI324Input Channel 3 Current DemandAI325Input Channel 3 Active Power DemandAI326Input Channel 3 Reactive Power DemandAI327Input Channel 3 Apparent Power DemandAI328Input Channel 4 Current DemandAI329Input Channel 4 Active Power DemandAI330Input Channel 4 Reactive Power DemandAI331Input Channel 4 Apparent Power DemandAI332Input Channel 5 Current DemandAI333Input Channel 5 Active Power DemandAI334Input Channel 5 Reactive Power DemandAI335Input Channel 5 Apparent Power DemandAI336Input Channel 6 Current DemandAI337Input Channel 6 Active Power DemandAI338Input Channel 6 Reactive Power DemandAI339Input Channel 6 Apparent Power DemandAI340Input Channel 7 Current DemandAI341Input Channel 7 Active Power DemandAI342Input Channel 7 Reactive Power DemandAI343Input Channel 7 Apparent Power DemandAI344Input Channel 8 Current DemandAI345Input Channel 8 Active Power DemandAI346Input Channel 8 Reactive Power DemandAI347Input Channel 8 Apparent Power DemandAI348Input Channel 9 Current DemandAI349Input Channel 9 Active Power DemandAI350Input Channel 9 Reactive Power DemandAI351Input Channel 9 Apparent Power DemandAI352Input Channel 10 Current DemandAI353Input Channel 10 Active Power DemandAI354Input Channel 10 Reactive Power DemandAI355Input Channel 10 Apparent Power DemandAI356Input Channel 11 Current DemandAI357Input Channel 11 Active Power DemandAI358Input Channel 11 Reactive Power DemandAI359Input Channel 11 Apparent Power DemandAI360Input Channel 12 Current DemandAI361Input Channel 12 Active Power DemandAI362Input Channel 12 Reactive Power DemandAI363Input Channel 12 Apparent Power DemandAI364Input Channel 13 Current DemandAI365Input Channel 13 Active Power DemandAI366Input Channel 13 Reactive Power DemandAI367Input Channel 13 Apparent Power DemandAI368Input Channel 14 Current DemandAI369Input Channel 14 Active Power DemandAI370Input Channel 14 Reactive Power DemandAI371Input Channel 14 Apparent Power DemandAI372Input Channel 15 Current DemandAI373Input Channel 15 Active Power DemandAI374Input Channel 15 Reactive Power DemandAI375Input Channel 15 Apparent Power DemandAI376Input Channel 16 Current DemandAI377Input Channel 16 Active Power DemandAI378Input Channel 16 Reactive Power DemandAI379Input Channel 16 Apparent Power DemandAI380Input Channel 17 Current DemandAI381Input Channel 17 Active Power DemandAI382Input Channel 17 Reactive Power DemandAI383Input Channel 17 Apparent Power DemandAI384Input Channel 18 Current DemandAI385Input Channel 18 Active Power DemandAI386Input Channel 18 Reactive Power DemandAI387Input Channel 18 Apparent Power DemandAI388User Channel 1 Active Power DemandAI389User Channel 1 Reactive Power DemandAI390User Channel 1 Apparent Power DemandAI391User Channel 2 Active Power DemandAI392User Channel 2 Reactive Power DemandAI393User Channel 2 Apparent Power DemandAI394User Channel 3 Active Power DemandAI395User Channel 3 Reactive Power DemandAI396User Channel 3 Apparent Power DemandAI397User Channel 4 Active Power DemandAI398User Channel 4 Reactive Power DemandAI399User Channel 4 Apparent Power DemandAI400User Channel 5 Active Power DemandAI401User Channel 5 Reactive Power DemandAI402User Channel 5 Apparent Power DemandAI403User Channel 6 Active Power DemandAI404User Channel 6 Reactive Power DemandAI405User Channel 6 Apparent Power DemandAI406User Channel 7 Active Power DemandAI407User Channel 7 Reactive Power DemandAI408User Channel 7 Apparent Power DemandAI409User Channel 8 Active Power DemandAI410User Channel 8 Reactive Power DemandAI411User Channel 8 Apparent Power DemandAI412User Channel 9 Active Power DemandAI413User Channel 9 Reactive Power DemandAI414User Channel 9 Apparent Power DemandAI501Average Voltage THDAI502System Voltage Unbalance FactorAI503System Current Unbalance FactorAI504Phase A Voltage THDAI505Phase A Odd Voltage THDAI506Phase A Even Voltage THDAI507Phase A Voltage Crest FactorAI508Phase A THFFAI509Phase B Voltage THDAI510Phase B Odd Voltage THDAI511Phase B Even Voltage THDAI512Phase B Voltage Crest FactorAI513Phase B THFFAI514Phase C Voltage THDAI515Phase C Odd Voltage THDAI516Phase C Even Voltage THDAI517Phase C Voltage Crest FactorAI518Phase C THFFAI519Input Channel 1 Current THDAI520Input Channel 1 Odd Current THDAI521Input Channel 1 Even Current THDAI522Input Channel 1 Current K FactorAI523Input Channel 2 Current THDAI524Input Channel 2 Odd Current THDAI525Input Channel 2 Even Current THDAI526Input Channel 2 Current K FactorAI527Input Channel 3 Current THDAI528Input Channel 3 Odd Current THDAI529Input Channel 3 Even Current THDAI530Input Channel 3 Current K FactorAI531Input Channel 4 Current THDAI532Input Channel 4 Odd Current THDAI533Input Channel 4 Even Current THDAI534Input Channel 4 Current K FactorAI535Input Channel 5 Current THDAI536Input Channel 5 Odd Current THDAI537Input Channel 5 Even Current THDAI538Input Channel 5 Current K FactorAI539Input Channel 6 Current THDAI540Input Channel 6 Odd Current THDAI541Input Channel 6 Even Current THDAI542Input Channel 6 Current K FactorAI543Input Channel 7 Current THDAI544Input Channel 7 Odd Current THDAI545Input Channel 7 Even Current THDAI546Input Channel 7 Current K FactorAI547Input Channel 8 Current THDAI548Input Channel 8 Odd Current THDAI549Input Channel 8 Even Current THDAI550Input Channel 8 Current K FactorAI551Input Channel 9 Current THDAI552Input Channel 9 Odd Current THDAI553Input Channel 9 Even Current THDAI554Input Channel 9 Current K FactorAI555Input Channel 10 Current THDAI556Input Channel 10 Odd Current THDAI557Input Channel 10 Even Current THDAI558Input Channel 10 Current K FactorAI559Input Channel 11 Current THDAI560Input Channel 11 Odd Current THDAI561Input Channel 11 Even Current THDAI562Input Channel 11 Current K FactorAI563Input Channel 12 Current THDAI564Input Channel 12 Odd Current THDAI565Input Channel 12 Even Current THDAI566Input Channel 12 Current K FactorAI567Input Channel 13 Current THDAI568Input Channel 13 Odd Current THDAI569Input Channel 13 Even Current THDAI570Input Channel 13 Current K FactorAI571Input Channel 14 Current THDAI572Input Channel 14 Odd Current THDAI573Input Channel 14 Even Current THDAI574Input Channel 14 Current K FactorAI575Input Channel 15 Current THDAI576Input Channel 15 Odd Current THDAI577Input Channel 15 Even Current THDAI578Input Channel 15 Current K FactorAI579Input Channel 16 Current THDAI580Input Channel 16 Odd Current THDAI581Input Channel 16 Even Current THDAI582Input Channel 16 Current K FactorAI583Input Channel 17 Current THDAI584Input Channel 17 Odd Current THDAI585Input Channel 17 Even Current THDAI586Input Channel 17 Current K FactorAI587Input Channel 18 Current THDAI588Input Channel 18 Odd Current THDAI589Input Channel 18 Even Current THDAI590Input Channel 18 Current K FactorAI591User Channel 1 Current UnbalanceAI592User Channel 2 Current UnbalanceAI593User Channel 3 Current UnbalanceAI594User Channel 4 Current UnbalanceAI595User Channel 5 Current UnbalanceAI596User Channel 6 Current UnbalanceAI601DI1 COUNTERAI602DI2 COUNTERAI603DI3 COUNTERAI604DI4 COUNTERAI605DI5 COUNTERAI606DI6 COUNTERAI607DI7 COUNTERAI608DI8 COUNTERAI609DI9 COUNTERAI610DI10 COUNTERAI611DI11 COUNTERAI612DI12 COUNTERAI613DI13 COUNTERAI614DI14 COUNTERAI615DI15 COUNTERAI616DI16 COUNTERAI617DI17 COUNTERAI618DI18 COUNTERAI701System Active Power Demand PeakAI702System Reactive Power Demand PeakAI703System Apparent Power Demand PeakAI704Phase A Active Power Demand PeakAI705Phase A Reactive Power Demand PeakAI706Phase A Apparent Power Demand PeakAI707Phase B Active Power Demand PeakAI708Phase B Reactive Power Demand PeakAI709Phase B Apparent Power Demand PeakAI710Phase C Active Power Demand PeakAI711Phase C Reactive Power Demand PeakAI712Phase C Apparent Power Demand PeakAI713Input Channel 1 Active Power Demand PeakAI714Input Channel 1 Reactive Power Demand PeakAI715Input Channel 1 Apparent Power Demand PeakAI716Input Channel 2 Active Power Demand PeakAI717Input Channel 2 Reactive Power Demand PeakAI718Input Channel 2 Apparent Power Demand PeakAI719Input Channel 3 Active Power Demand PeakAI720Input Channel 3 Reactive Power Demand PeakAI721Input Channel 3 Apparent Power Demand PeakAI722Input Channel 4 Active Power Demand PeakAI723Input Channel 4 Reactive Power Demand PeakAI724Input Channel 4 Apparent Power Demand PeakAI725Input Channel 5 Active Power Demand PeakAI726Input Channel 5 Reactive Power Demand PeakAI727Input Channel 5 Apparent Power Demand PeakAI728Input Channel 6 Active Power Demand PeakAI729Input Channel 6 Reactive Power Demand PeakAI730Input Channel 6 Apparent Power Demand PeakAI731Input Channel 7 Active Power Demand PeakAI732Input Channel 7 Reactive Power Demand PeakAI733Input Channel 7 Apparent Power Demand PeakAI734Input Channel 8 Active Power Demand PeakAI735Input Channel 8 Reactive Power Demand PeakAI736Input Channel 8 Apparent Power Demand PeakAI737Input Channel 9 Active Power Demand PeakAI738Input Channel 9 Reactive Power Demand PeakAI739Input Channel 9 Apparent Power Demand PeakAI740Input Channel 10 Active Power Demand PeakAI741Input Channel 10 Reactive Power Demand PeakAI742Input Channel 10 Apparent Power Demand PeakAI743Input Channel 11 Active Power Demand PeakAI744Input Channel 11 Reactive Power Demand PeakAI745Input Channel 11 Apparent Power Demand PeakAI746Input Channel 12 Active Power Demand PeakAI747Input Channel 12 Reactive Power Demand PeakAI748Input Channel 12 Apparent Power Demand PeakAI749Input Channel 13 Active Power Demand PeakAI750Input Channel 13 Reactive Power Demand PeakAI751Input Channel 13 Apparent Power Demand PeakAI752Input Channel 14 Active Power Demand PeakAI753Input Channel 14 Reactive Power Demand PeakAI754Input Channel 14 Apparent Power Demand PeakAI755Input Channel 15 Active Power Demand PeakAI756Input Channel 15 Reactive Power Demand PeakAI757Input Channel 15 Apparent Power Demand PeakAI758Input Channel 16 Active Power Demand PeakAI759Input Channel 16 Reactive Power Demand PeakAI760Input Channel 16 Apparent Power Demand PeakAI761Input Channel 17 Active Power Demand PeakAI762Input Channel 17 Reactive Power Demand PeakAI763Input Channel 17 Apparent Power Demand PeakAI764Input Channel 18 Active Power Demand PeakAI765Input Channel 18 Reactive Power Demand PeakAI766Input Channel 18 Apparent Power Demand PeakAI767User Channel 1 Active Power Demand PeakAI768User Channel 1 Reactive Power Demand PeakAI769User Channel 1 Apparent Power Demand PeakAI770User Channel 2 Active Power Demand PeakAI771User Channel 2 Reactive Power Demand PeakAI772User Channel 2 Apparent Power Demand PeakAI773User Channel 3 Active Power Demand PeakAI774User Channel 3 Reactive Power Demand PeakAI775User Channel 3 Apparent Power Demand PeakAI776User Channel 4 Active Power Demand PeakAI777User Channel 4 Reactive Power Demand PeakAI778User Channel 4 Apparent Power Demand PeakAI779User Channel 5 Active Power Demand PeakAI780User Channel 5 Reactive Power Demand PeakAI781User Channel 5 Apparent Power Demand PeakAI782User Channel 6 Active Power Demand PeakAI783User Channel 6 Reactive Power Demand PeakAI784User Channel 6 Apparent Power Demand PeakAI785User Channel 7 Active Power Demand PeakAI786User Channel 7 Reactive Power Demand PeakAI787User Channel 7 Apparent Power Demand PeakAI788User Channel 8 Active Power Demand PeakAI789User Channel 8 Reactive Power Demand PeakAI790User Channel 8 Apparent Power Demand PeakAI791User Channel 9 Active Power Demand PeakAI792User Channel 9 Reactive Power Demand PeakAI793User Channel 9 Apparent Power Demand PeakAI801Phase A Voltage 2nd HarmonicAI802Phase A Voltage 3rd HarmonicAI803Phase A Voltage 4th HarmonicAI804Phase A Voltage 5th HarmonicAI805Phase A Voltage 6th HarmonicAI806Phase A Voltage 7th HarmonicAI807Phase A Voltage 8th HarmonicAI808Phase A Voltage 9th HarmonicAI809Phase A Voltage 10th HarmonicAI810Phase A Voltage 11th HarmonicAI811Phase A Voltage 12th HarmonicAI812Phase A Voltage 13th HarmonicAI813Phase A Voltage 14th HarmonicAI814Phase A Voltage 15th HarmonicAI815Phase A Voltage 16th HarmonicAI816Phase A Voltage 17th HarmonicAI817Phase A Voltage 18th HarmonicAI818Phase A Voltage 19th HarmonicAI819Phase A Voltage 20th HarmonicAI820Phase A Voltage 21st HarmonicAI821Phase A Voltage 22nd HarmonicAI822Phase A Voltage 23rd HarmonicAI823Phase A Voltage 24th HarmonicAI824Phase A Voltage 25th HarmonicAI825Phase A Voltage 26th HarmonicAI826Phase A Voltage 27th HarmonicAI827Phase A Voltage 28th HarmonicAI828Phase A Voltage 29th HarmonicAI829Phase A Voltage 30th HarmonicAI830Phase A Voltage 31st HarmonicAI831Phase B Voltage 2nd HarmonicAI832Phase B Voltage 3rd HarmonicAI833Phase B Voltage 4th HarmonicAI834Phase B Voltage 5th HarmonicAI835Phase B Voltage 6th HarmonicAI836Phase B Voltage 7th HarmonicAI837Phase B Voltage 8th HarmonicAI838Phase B Voltage 9th HarmonicAI839Phase B Voltage 10th HarmonicAI840Phase B Voltage 11th HarmonicAI841Phase B Voltage 12th HarmonicAI842Phase B Voltage 13th HarmonicAI843Phase B Voltage 14th HarmonicAI844Phase B Voltage 15th HarmonicAI845Phase B Voltage 16th HarmonicAI846Phase B Voltage 17th HarmonicAI847Phase B Voltage 18th HarmonicAI848Phase B Voltage 19th HarmonicAI849Phase B Voltage 20th HarmonicAI850Phase B Voltage 21st HarmonicAI851Phase B Voltage 22nd HarmonicAI852Phase B Voltage 23rd HarmonicAI853Phase B Voltage 24th HarmonicAI854Phase B Voltage 25th HarmonicAI855Phase B Voltage 26th HarmonicAI856Phase B Voltage 27th HarmonicAI857Phase B Voltage 28th HarmonicAI858Phase B Voltage 29th HarmonicAI859Phase B Voltage 30th HarmonicAI860Phase B Voltage 31st HarmonicAI861Phase C Voltage 2nd HarmonicAI862Phase C Voltage 3rd HarmonicAI863Phase C Voltage 4th HarmonicAI864Phase C Voltage 5th HarmonicAI865Phase C Voltage 6th HarmonicAI866Phase C Voltage 7th HarmonicAI867Phase C Voltage 8th HarmonicAI868Phase C Voltage 9th HarmonicAI869Phase C Voltage 10th HarmonicAI870Phase C Voltage 11th HarmonicAI871Phase C Voltage 12th HarmonicAI872Phase C Voltage 13th HarmonicAI873Phase C Voltage 14th HarmonicAI874Phase C Voltage 15th HarmonicAI875Phase C Voltage 16th HarmonicAI876Phase C Voltage 17th HarmonicAI877Phase C Voltage 18th HarmonicAI878Phase C Voltage 19th HarmonicAI879Phase C Voltage 20th HarmonicAI880Phase C Voltage 21st HarmonicAI881Phase C Voltage 22nd HarmonicAI882Phase C Voltage 23rd HarmonicAI883Phase C Voltage 24th HarmonicAI884Phase C Voltage 25th HarmonicAI885Phase C Voltage 26th HarmonicAI886Phase C Voltage 27th HarmonicAI887Phase C Voltage 28th HarmonicAI888Phase C Voltage 29th HarmonicAI889Phase C Voltage 30th HarmonicAI890Phase C Voltage 31st HarmonicAI891Input Channel 1 Current 2nd HarmonicAI892Input Channel 1 Current 3rd HarmonicAI893Input Channel 1 Current 4th HarmonicAI894Input Channel 1 Current 5th HarmonicAI895Input Channel 1 Current 6th HarmonicAI896Input Channel 1 Current 7th HarmonicAI897Input Channel 1 Current 8th HarmonicAI898Input Channel 1 Current 9th HarmonicAI899Input Channel 1 Current 10th HarmonicAI900Input Channel 1 Current 11th HarmonicAI901Input Channel 1 Current 12th HarmonicAI902Input Channel 1 Current 13th HarmonicAI903Input Channel 1 Current 14th HarmonicAI904Input Channel 1 Current 15th HarmonicAI905Input Channel 1 Current 16th HarmonicAI906Input Channel 1 Current 17th HarmonicAI907Input Channel 1 Current 18th HarmonicAI908Input Channel 1 Current 19th HarmonicAI909Input Channel 1 Current 20th HarmonicAI910Input Channel 1 Current 21st HarmonicAI911Input Channel 1 Current 22nd HarmonicAI912Input Channel 1 Current 23rd HarmonicAI913Input Channel 1 Current 24th HarmonicAI914Input Channel 1 Current 25th HarmonicAI915Input Channel 1 Current 26th HarmonicAI916Input Channel 1 Current 27th HarmonicAI917Input Channel 1 Current 28th HarmonicAI918Input Channel 1 Current 29th HarmonicAI919Input Channel 1 Current 30th HarmonicAI920Input Channel 1 Current 31st HarmonicAI921Input Channel 2 Current 2nd HarmonicAI922Input Channel 2 Current 3rd HarmonicAI923Input Channel 2 Current 4th HarmonicAI924Input Channel 2 Current 5th HarmonicAI925Input Channel 2 Current 6th HarmonicAI926Input Channel 2 Current 7th HarmonicAI927Input Channel 2 Current 8th HarmonicAI928Input Channel 2 Current 9th HarmonicAI929Input Channel 2 Current 10th HarmonicAI930Input Channel 2 Current 11th HarmonicAI931Input Channel 2 Current 12th HarmonicAI932Input Channel 2 Current 13th HarmonicAI933Input Channel 2 Current 14th HarmonicAI934Input Channel 2 Current 15th HarmonicAI935Input Channel 2 Current 16th HarmonicAI936Input Channel 2 Current 17th HarmonicAI937Input Channel 2 Current 18th HarmonicAI938Input Channel 2 Current 19th HarmonicAI939Input Channel 2 Current 20th HarmonicAI940Input Channel 2 Current 21st HarmonicAI941Input Channel 2 Current 22nd HarmonicAI942Input Channel 2 Current 23rd HarmonicAI943Input Channel 2 Current 24th HarmonicAI944Input Channel 2 Current 25th HarmonicAI945Input Channel 2 Current 26th HarmonicAI946Input Channel 2 Current 27th HarmonicAI947Input Channel 2 Current 28th HarmonicAI948Input Channel 2 Current 29th HarmonicAI949Input Channel 2 Current 30th HarmonicAI950Input Channel 2 Current 31st HarmonicAI951Input Channel 3 Current 2nd HarmonicAI952Input Channel 3 Current 3rd HarmonicAI953Input Channel 3 Current 4th HarmonicAI954Input Channel 3 Current 5th HarmonicAI955Input Channel 3 Current 6th HarmonicAI956Input Channel 3 Current 7th HarmonicAI957Input Channel 3 Current 8th HarmonicAI958Input Channel 3 Current 9th HarmonicAI959Input Channel 3 Current 10th HarmonicAI960Input Channel 3 Current 11th HarmonicAI961Input Channel 3 Current 12th HarmonicAI962Input Channel 3 Current 13th HarmonicAI963Input Channel 3 Current 14th HarmonicAI964Input Channel 3 Current 15th HarmonicAI965Input Channel 3 Current 16th HarmonicAI966Input Channel 3 Current 17th HarmonicAI967Input Channel 3 Current 18th HarmonicAI968Input Channel 3 Current 19th HarmonicAI969Input Channel 3 Current 20th HarmonicAI970Input Channel 3 Current 21st HarmonicAI971Input Channel 3 Current 22nd HarmonicAI972Input Channel 3 Current 23rd HarmonicAI973Input Channel 3 Current 24th HarmonicAI974Input Channel 3 Current 25th HarmonicAI975Input Channel 3 Current 26th HarmonicAI976Input Channel 3 Current 27th HarmonicAI977Input Channel 3 Current 28th HarmonicAI978Input Channel 3 Current 29th HarmonicAI979Input Channel 3 Current 30th HarmonicAI980Input Channel 3 Current 31st HarmonicAI981Input Channel 4 Current 2nd HarmonicAI982Input Channel 4 Current 3rd HarmonicAI983Input Channel 4 Current 4th HarmonicAI984Input Channel 4 Current 5th HarmonicAI985Input Channel 4 Current 6th HarmonicAI986Input Channel 4 Current 7th HarmonicAI987Input Channel 4 Current 8th HarmonicAI988Input Channel 4 Current 9th HarmonicAI989Input Channel 4 Current 10th HarmonicAI990Input Channel 4 Current 11th HarmonicAI991Input Channel 4 Current 12th HarmonicAI992Input Channel 4 Current 13th HarmonicAI993Input Channel 4 Current 14th HarmonicAI994Input Channel 4 Current 15th HarmonicAI995Input Channel 4 Current 16th HarmonicAI996Input Channel 4 Current 17th HarmonicAI997Input Channel 4 Current 18th HarmonicAI998Input Channel 4 Current 19th HarmonicAI999Input Channel 4 Current 20th HarmonicAI1000Input Channel 4 Current 21st HarmonicAI1001Input Channel 4 Current 22nd HarmonicAI1002Input Channel 4 Current 23rd HarmonicAI1003Input Channel 4 Current 24th HarmonicAI1004Input Channel 4 Current 25th HarmonicAI1005Input Channel 4 Current 26th HarmonicAI1006Input Channel 4 Current 27th HarmonicAI1007Input Channel 4 Current 28th HarmonicAI1008Input Channel 4 Current 29th HarmonicAI1009Input Channel 4 Current 30th HarmonicAI1010Input Channel 4 Current 31st HarmonicAI1011Input Channel 5 Current 2nd HarmonicAI1012Input Channel 5 Current 3rd HarmonicAI1013Input Channel 5 Current 4th HarmonicAI1014Input Channel 5 Current 5th HarmonicAI1015Input Channel 5 Current 6th HarmonicAI1016Input Channel 5 Current 7th HarmonicAI1017Input Channel 5 Current 8th HarmonicAI1018Input Channel 5 Current 9th HarmonicAI1019Input Channel 5 Current 10th HarmonicAI1020Input Channel 5 Current 11th HarmonicAI1021Input Channel 5 Current 12th HarmonicAI1022Input Channel 5 Current 13th HarmonicAI1023Input Channel 5 Current 14th HarmonicAI1024Input Channel 5 Current 15th HarmonicAI1025Input Channel 5 Current 16th HarmonicAI1026Input Channel 5 Current 17th HarmonicAI1027Input Channel 5 Current 18th HarmonicAI1028Input Channel 5 Current 19th HarmonicAI1029Input Channel 5 Current 20th HarmonicAI1030Input Channel 5 Current 21st HarmonicAI1031Input Channel 5 Current 22nd HarmonicAI1032Input Channel 5 Current 23rd HarmonicAI1033Input Channel 5 Current 24th HarmonicAI1034Input Channel 5 Current 25th HarmonicAI1035Input Channel 5 Current 26th HarmonicAI1036Input Channel 5 Current 27th HarmonicAI1037Input Channel 5 Current 28th HarmonicAI1038Input Channel 5 Current 29th HarmonicAI1039Input Channel 5 Current 30th HarmonicAI1040Input Channel 5 Current 31st HarmonicAI1041Input Channel 6 Current 2nd HarmonicAI1042Input Channel 6 Current 3rd HarmonicAI1043Input Channel 6 Current 4th HarmonicAI1044Input Channel 6 Current 5th HarmonicAI1045Input Channel 6 Current 6th HarmonicAI1046Input Channel 6 Current 7th HarmonicAI1047Input Channel 6 Current 8th HarmonicAI1048Input Channel 6 Current 9th HarmonicAI1049Input Channel 6 Current 10th HarmonicAI1050Input Channel 6 Current 11th HarmonicAI1051Input Channel 6 Current 12th HarmonicAI1052Input Channel 6 Current 13th HarmonicAI1053Input Channel 6 Current 14th HarmonicAI1054Input Channel 6 Current 15th HarmonicAI1055Input Channel 6 Current 16th HarmonicAI1056Input Channel 6 Current 17th HarmonicAI1057Input Channel 6 Current 18th HarmonicAI1058Input Channel 6 Current 19th HarmonicAI1059Input Channel 6 Current 20th HarmonicAI1060Input Channel 6 Current 21st HarmonicAI1061Input Channel 6 Current 22nd HarmonicAI1062Input Channel 6 Current 23rd HarmonicAI1063Input Channel 6 Current 24th HarmonicAI1064Input Channel 6 Current 25th HarmonicAI1065Input Channel 6 Current 26th HarmonicAI1066Input Channel 6 Current 27th HarmonicAI1067Input Channel 6 Current 28th HarmonicAI1068Input Channel 6 Current 29th HarmonicAI1069Input Channel 6 Current 30th HarmonicAI1070Input Channel 6 Current 31st HarmonicAI1071Input Channel 7 Current 2nd HarmonicAI1072Input Channel 7 Current 3rd HarmonicAI1073Input Channel 7 Current 4th HarmonicAI1074Input Channel 7 Current 5th HarmonicAI1075Input Channel 7 Current 6th HarmonicAI1076Input Channel 7 Current 7th HarmonicAI1077Input Channel 7 Current 8th HarmonicAI1078Input Channel 7 Current 9th HarmonicAI1079Input Channel 7 Current 10th HarmonicAI1080Input Channel 7 Current 11th HarmonicAI1081Input Channel 7 Current 12th HarmonicAI1082Input Channel 7 Current 13th HarmonicAI1083Input Channel 7 Current 14th HarmonicAI1084Input Channel 7 Current 15th HarmonicAI1085Input Channel 7 Current 16th HarmonicAI1086Input Channel 7 Current 17th HarmonicAI1087Input Channel 7 Current 18th HarmonicAI1088Input Channel 7 Current 19th HarmonicAI1089Input Channel 7 Current 20th HarmonicAI1090Input Channel 7 Current 21st HarmonicAI1091Input Channel 7 Current 22nd HarmonicAI1092Input Channel 7 Current 23rd HarmonicAI1093Input Channel 7 Current 24th HarmonicAI1094Input Channel 7 Current 25th HarmonicAI1095Input Channel 7 Current 26th HarmonicAI1096Input Channel 7 Current 27th HarmonicAI1097Input Channel 7 Current 28th HarmonicAI1098Input Channel 7 Current 29th HarmonicAI1099Input Channel 7 Current 30th HarmonicAI1100Input Channel 7 Current 31st HarmonicAI1101Input Channel 8 Current 2nd HarmonicAI1102Input Channel 8 Current 3rd HarmonicAI1103Input Channel 8 Current 4th HarmonicAI1104Input Channel 8 Current 5th HarmonicAI1105Input Channel 8 Current 6th HarmonicAI1106Input Channel 8 Current 7th HarmonicAI1107Input Channel 8 Current 8th HarmonicAI1108Input Channel 8 Current 9th HarmonicAI1109Input Channel 8 Current 10th HarmonicAI1110Input Channel 8 Current 11th HarmonicAI1111Input Channel 8 Current 12th HarmonicAI1112Input Channel 8 Current 13th HarmonicAI1113Input Channel 8 Current 14th HarmonicAI1114Input Channel 8 Current 15th HarmonicAI1115Input Channel 8 Current 16th HarmonicAI1116Input Channel 8 Current 17th HarmonicAI1117Input Channel 8 Current 18th HarmonicAI1118Input Channel 8 Current 19th HarmonicAI1119Input Channel 8 Current 20th HarmonicAI1120Input Channel 8 Current 21st HarmonicAI1121Input Channel 8 Current 22nd HarmonicAI1122Input Channel 8 Current 23rd HarmonicAI1123Input Channel 8 Current 24th HarmonicAI1124Input Channel 8 Current 25th HarmonicAI1125Input Channel 8 Current 26th HarmonicAI1126Input Channel 8 Current 27th HarmonicAI1127Input Channel 8 Current 28th HarmonicAI1128Input Channel 8 Current 29th HarmonicAI1129Input Channel 8 Current 30th HarmonicAI1130Input Channel 8 Current 31st HarmonicAI1131Input Channel 9 Current 2nd HarmonicAI1132Input Channel 9 Current 3rd HarmonicAI1133Input Channel 9 Current 4th HarmonicAI1134Input Channel 9 Current 5th HarmonicAI1135Input Channel 9 Current 6th HarmonicAI1136Input Channel 9 Current 7th HarmonicAI1137Input Channel 9 Current 8th HarmonicAI1138Input Channel 9 Current 9th HarmonicAI1139Input Channel 9 Current 10th HarmonicAI1140Input Channel 9 Current 11th HarmonicAI1141Input Channel 9 Current 12th HarmonicAI1142Input Channel 9 Current 13th HarmonicAI1143Input Channel 9 Current 14th HarmonicAI1144Input Channel 9 Current 15th HarmonicAI1145Input Channel 9 Current 16th HarmonicAI1146Input Channel 9 Current 17th HarmonicAI1147Input Channel 9 Current 18th HarmonicAI1148Input Channel 9 Current 19th HarmonicAI1149Input Channel 9 Current 20th HarmonicAI1150Input Channel 9 Current 21st HarmonicAI1151Input Channel 9 Current 22nd HarmonicAI1152Input Channel 9 Current 23rd HarmonicAI1153Input Channel 9 Current 24th HarmonicAI1154Input Channel 9 Current 25th HarmonicAI1155Input Channel 9 Current 26th HarmonicAI1156Input Channel 9 Current 27th HarmonicAI1157Input Channel 9 Current 28th HarmonicAI1158Input Channel 9 Current 29th HarmonicAI1159Input Channel 9 Current 30th HarmonicAI1160Input Channel 9 Current 31st HarmonicAI1161Input Channel 10 Current 2nd HarmonicAI1162Input Channel 10 Current 3rd HarmonicAI1163Input Channel 10 Current 4th HarmonicAI1164Input Channel 10 Current 5th HarmonicAI1165Input Channel 10 Current 6th HarmonicAI1166Input Channel 10 Current 7th HarmonicAI1167Input Channel 10 Current 8th HarmonicAI1168Input Channel 10 Current 9th HarmonicAI1169Input Channel 10 Current 10th HarmonicAI1170Input Channel 10 Current 11th HarmonicAI1171Input Channel 10 Current 12th HarmonicAI1172Input Channel 10 Current 13th HarmonicAI1173Input Channel 10 Current 14th HarmonicAI1174Input Channel 10 Current 15th HarmonicAI1175Input Channel 10 Current 16th HarmonicAI1176Input Channel 10 Current 17th HarmonicAI1177Input Channel 10 Current 18th HarmonicAI1178Input Channel 10 Current 19th HarmonicAI1179Input Channel 10 Current 20th HarmonicAI1180Input Channel 10 Current 21st HarmonicAI1181Input Channel 10 Current 22nd HarmonicAI1182Input Channel 10 Current 23rd HarmonicAI1183Input Channel 10 Current 24th HarmonicAI1184Input Channel 10 Current 25th HarmonicAI1185Input Channel 10 Current 26th HarmonicAI1186Input Channel 10 Current 27th HarmonicAI1187Input Channel 10 Current 28th HarmonicAI1188Input Channel 10 Current 29th HarmonicAI1189Input Channel 10 Current 30th HarmonicAI1190Input Channel 10 Current 31st HarmonicAI1191Input Channel 11 Current 2nd HarmonicAI1192Input Channel 11 Current 3rd HarmonicAI1193Input Channel 11 Current 4th HarmonicAI1194Input Channel 11 Current 5th HarmonicAI1195Input Channel 11 Current 6th HarmonicAI1196Input Channel 11 Current 7th HarmonicAI1197Input Channel 11 Current 8th HarmonicAI1198Input Channel 11 Current 9th HarmonicAI1199Input Channel 11 Current 10th HarmonicAI1200Input Channel 11 Current 11th HarmonicAI1201Input Channel 11 Current 12th HarmonicAI1202Input Channel 11 Current 13th HarmonicAI1203Input Channel 11 Current 14th HarmonicAI1204Input Channel 11 Current 15th HarmonicAI1205Input Channel 11 Current 16th HarmonicAI1206Input Channel 11 Current 17th HarmonicAI1207Input Channel 11 Current 18th HarmonicAI1208Input Channel 11 Current 19th HarmonicAI1209Input Channel 11 Current 20th HarmonicAI1210Input Channel 11 Current 21st HarmonicAI1211Input Channel 11 Current 22nd HarmonicAI1212Input Channel 11 Current 23rd HarmonicAI1213Input Channel 11 Current 24th HarmonicAI1214Input Channel 11 Current 25th HarmonicAI1215Input Channel 11 Current 26th HarmonicAI1216Input Channel 11 Current 27th HarmonicAI1217Input Channel 11 Current 28th HarmonicAI1218Input Channel 11 Current 29th HarmonicAI1219Input Channel 11 Current 30th HarmonicAI1220Input Channel 11 Current 31st HarmonicAI1221Input Channel 12 Current 2nd HarmonicAI1222Input Channel 12 Current 3rd HarmonicAI1223Input Channel 12 Current 4th HarmonicAI1224Input Channel 12 Current 5th HarmonicAI1225Input Channel 12 Current 6th HarmonicAI1226Input Channel 12 Current 7th HarmonicAI1227Input Channel 12 Current 8th HarmonicAI1228Input Channel 12 Current 9th HarmonicAI1229Input Channel 12 Current 10th HarmonicAI1230Input Channel 12 Current 11th HarmonicAI1231Input Channel 12 Current 12th HarmonicAI1232Input Channel 12 Current 13th HarmonicAI1233Input Channel 12 Current 14th HarmonicAI1234Input Channel 12 Current 15th HarmonicAI1235Input Channel 12 Current 16th HarmonicAI1236Input Channel 12 Current 17th HarmonicAI1237Input Channel 12 Current 18th HarmonicAI1238Input Channel 12 Current 19th HarmonicAI1239Input Channel 12 Current 20th HarmonicAI1240Input Channel 12 Current 21st HarmonicAI1241Input Channel 12 Current 22nd HarmonicAI1242Input Channel 12 Current 23rd HarmonicAI1243Input Channel 12 Current 24th HarmonicAI1244Input Channel 12 Current 25th HarmonicAI1245Input Channel 12 Current 26th HarmonicAI1246Input Channel 12 Current 27th HarmonicAI1247Input Channel 12 Current 28th HarmonicAI1248Input Channel 12 Current 29th HarmonicAI1249Input Channel 12 Current 30th HarmonicAI1250Input Channel 12 Current 31st HarmonicAI1251Input Channel 13 Current 2nd HarmonicAI1252Input Channel 13 Current 3rd HarmonicAI1253Input Channel 13 Current 4th HarmonicAI1254Input Channel 13 Current 5th HarmonicAI1255Input Channel 13 Current 6th HarmonicAI1256Input Channel 13 Current 7th HarmonicAI1257Input Channel 13 Current 8th HarmonicAI1258Input Channel 13 Current 9th HarmonicAI1259Input Channel 13 Current 10th HarmonicAI1260Input Channel 13 Current 11th HarmonicAI1261Input Channel 13 Current 12th HarmonicAI1262Input Channel 13 Current 13th HarmonicAI1263Input Channel 13 Current 14th HarmonicAI1264Input Channel 13 Current 15th HarmonicAI1265Input Channel 13 Current 16th HarmonicAI1266Input Channel 13 Current 17th HarmonicAI1267Input Channel 13 Current 18th HarmonicAI1268Input Channel 13 Current 19th HarmonicAI1269Input Channel 13 Current 20th HarmonicAI1270Input Channel 13 Current 21st HarmonicAI1271Input Channel 13 Current 22nd HarmonicAI1272Input Channel 13 Current 23rd HarmonicAI1273Input Channel 13 Current 24th HarmonicAI1274Input Channel 13 Current 25th HarmonicAI1275Input Channel 13 Current 26th HarmonicAI1276Input Channel 13 Current 27th HarmonicAI1277Input Channel 13 Current 28th HarmonicAI1278Input Channel 13 Current 29th HarmonicAI1279Input Channel 13 Current 30th HarmonicAI1280Input Channel 13 Current 31st HarmonicAI1281Input Channel 14 Current 2nd HarmonicAI1282Input Channel 14 Current 3rd HarmonicAI1283Input Channel 14 Current 4th HarmonicAI1284Input Channel 14 Current 5th HarmonicAI1285Input Channel 14 Current 6th HarmonicAI1286Input Channel 14 Current 7th HarmonicAI1287Input Channel 14 Current 8th HarmonicAI1288Input Channel 14 Current 9th HarmonicAI1289Input Channel 14 Current 10th HarmonicAI1290Input Channel 14 Current 11th HarmonicAI1291Input Channel 14 Current 12th HarmonicAI1292Input Channel 14 Current 13th HarmonicAI1293Input Channel 14 Current 14th HarmonicAI1294Input Channel 14 Current 15th HarmonicAI1295Input Channel 14 Current 16th HarmonicAI1296Input Channel 14 Current 17th HarmonicAI1297Input Channel 14 Current 18th HarmonicAI1298Input Channel 14 Current 19th HarmonicAI1299Input Channel 14 Current 20th HarmonicAI1300Input Channel 14 Current 21st HarmonicAI1301Input Channel 14 Current 22nd HarmonicAI1302Input Channel 14 Current 23rd HarmonicAI1303Input Channel 14 Current 24th HarmonicAI1304Input Channel 14 Current 25th HarmonicAI1305Input Channel 14 Current 26th HarmonicAI1306Input Channel 14 Current 27th HarmonicAI1307Input Channel 14 Current 28th HarmonicAI1308Input Channel 14 Current 29th HarmonicAI1309Input Channel 14 Current 30th HarmonicAI1310Input Channel 14 Current 31st HarmonicAI1311Input Channel 15 Current 2nd HarmonicAI1312Input Channel 15 Current 3rd HarmonicAI1313Input Channel 15 Current 4th HarmonicAI1314Input Channel 15 Current 5th HarmonicAI1315Input Channel 15 Current 6th HarmonicAI1316Input Channel 15 Current 7th HarmonicAI1317Input Channel 15 Current 8th HarmonicAI1318Input Channel 15 Current 9th HarmonicAI1319Input Channel 15 Current 10th HarmonicAI1320Input Channel 15 Current 11th HarmonicAI1321Input Channel 15 Current 12th HarmonicAI1322Input Channel 15 Current 13th HarmonicAI1323Input Channel 15 Current 14th HarmonicAI1324Input Channel 15 Current 15th HarmonicAI1325Input Channel 15 Current 16th HarmonicAI1326Input Channel 15 Current 17th HarmonicAI1327Input Channel 15 Current 18th HarmonicAI1328Input Channel 15 Current 19th HarmonicAI1329Input Channel 15 Current 20th HarmonicAI1330Input Channel 15 Current 21st HarmonicAI1331Input Channel 15 Current 22nd HarmonicAI1332Input Channel 15 Current 23rd HarmonicAI1333Input Channel 15 Current 24th HarmonicAI1334Input Channel 15 Current 25th HarmonicAI1335Input Channel 15 Current 26th HarmonicAI1336Input Channel 15 Current 27th HarmonicAI1337Input Channel 15 Current 28th HarmonicAI1338Input Channel 15 Current 29th HarmonicAI1339Input Channel 15 Current 30th HarmonicAI1340Input Channel 15 Current 31st HarmonicAI1341Input Channel 16 Current 2nd HarmonicAI1342Input Channel 16 Current 3rd HarmonicAI1343Input Channel 16 Current 4th HarmonicAI1344Input Channel 16 Current 5th HarmonicAI1345Input Channel 16 Current 6th HarmonicAI1346Input Channel 16 Current 7th HarmonicAI1347Input Channel 16 Current 8th HarmonicAI1348Input Channel 16 Current 9th HarmonicAI1349Input Channel 16 Current 10th HarmonicAI1350Input Channel 16 Current 11th HarmonicAI1351Input Channel 16 Current 12th HarmonicAI1352Input Channel 16 Current 13th HarmonicAI1353Input Channel 16 Current 14th HarmonicAI1354Input Channel 16 Current 15th HarmonicAI1355Input Channel 16 Current 16th HarmonicAI1356Input Channel 16 Current 17th HarmonicAI1357Input Channel 16 Current 18th HarmonicAI1358Input Channel 16 Current 19th HarmonicAI1359Input Channel 16 Current 20th HarmonicAI1360Input Channel 16 Current 21st HarmonicAI1361Input Channel 16 Current 22nd HarmonicAI1362Input Channel 16 Current 23rd HarmonicAI1363Input Channel 16 Current 24th HarmonicAI1364Input Channel 16 Current 25th HarmonicAI1365Input Channel 16 Current 26th HarmonicAI1366Input Channel 16 Current 27th HarmonicAI1367Input Channel 16 Current 28th HarmonicAI1368Input Channel 16 Current 29th HarmonicAI1369Input Channel 16 Current 30th HarmonicAI1370Input Channel 16 Current 31st HarmonicAI1371Input Channel 17 Current 2nd HarmonicAI1372Input Channel 17 Current 3rd HarmonicAI1373Input Channel 17 Current 4th HarmonicAI1374Input Channel 17 Current 5th HarmonicAI1375Input Channel 17 Current 6th HarmonicAI1376Input Channel 17 Current 7th HarmonicAI1377Input Channel 17 Current 8th HarmonicAI1378Input Channel 17 Current 9th HarmonicAI1379Input Channel 17 Current 10th HarmonicAI1380Input Channel 17 Current 11th HarmonicAI1381Input Channel 17 Current 12th HarmonicAI1382Input Channel 17 Current 13th HarmonicAI1383Input Channel 17 Current 14th HarmonicAI1384Input Channel 17 Current 15th HarmonicAI1385Input Channel 17 Current 16th HarmonicAI1386Input Channel 17 Current 17th HarmonicAI1387Input Channel 17 Current 18th HarmonicAI1388Input Channel 17 Current 19th HarmonicAI1389Input Channel 17 Current 20th HarmonicAI1390Input Channel 17 Current 21st HarmonicAI1391Input Channel 17 Current 22nd HarmonicAI1392Input Channel 17 Current 23rd HarmonicAI1393Input Channel 17 Current 24th HarmonicAI1394Input Channel 17 Current 25th HarmonicAI1395Input Channel 17 Current 26th HarmonicAI1396Input Channel 17 Current 27th HarmonicAI1397Input Channel 17 Current 28th HarmonicAI1398Input Channel 17 Current 29th HarmonicAI1399Input Channel 17 Current 30th HarmonicAI1400Input Channel 17 Current 31st HarmonicAI1401Input Channel 18 Current 2nd HarmonicAI1402Input Channel 18 Current 3rd HarmonicAI1403Input Channel 18 Current 4th HarmonicAI1404Input Channel 18 Current 5th HarmonicAI1405Input Channel 18 Current 6th HarmonicAI1406Input Channel 18 Current 7th HarmonicAI1407Input Channel 18 Current 8th HarmonicAI1408Input Channel 18 Current 9th HarmonicAI1409Input Channel 18 Current 10th HarmonicAI1410Input Channel 18 Current 11th HarmonicAI1411Input Channel 18 Current 12th HarmonicAI1412Input Channel 18 Current 13th HarmonicAI1413Input Channel 18 Current 14th HarmonicAI1414Input Channel 18 Current 15th HarmonicAI1415Input Channel 18 Current 16th HarmonicAI1416Input Channel 18 Current 17th HarmonicAI1417Input Channel 18 Current 18th HarmonicAI1418Input Channel 18 Current 19th HarmonicAI1419Input Channel 18 Current 20th HarmonicAI1420Input Channel 18 Current 21st HarmonicAI1421Input Channel 18 Current 22nd HarmonicAI1422Input Channel 18 Current 23rd HarmonicAI1423Input Channel 18 Current 24th HarmonicAI1424Input Channel 18 Current 25th HarmonicAI1425Input Channel 18 Current 26th HarmonicAI1426Input Channel 18 Current 27th HarmonicAI1427Input Channel 18 Current 28th HarmonicAI1428Input Channel 18 Current 29th HarmonicAI1429Input Channel 18 Current 30th HarmonicAI1430Input Channel 18 Current 31st Harmonic
Integration notes
- Input channel objects (channels 1-18) only report values for channels present on the installed hardware.
- Instances run 1-1430 with gaps between sections.
- Object_Name, Description and COV_Increment are writable and stored; the default COV increment is 0.
- Source: Accuenergy 'BACnet Points List AcuRev2100-WEB2' spreadsheet, firmware v1.22, generated 2026-10-06.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
How many BACnet points does the Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) have?
This list has 1230 BACnet objects: 1230 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP) BACnet documentation?
The source is BACnet Points List AcuRev2100-WEB2, revision 2026-10-06, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/AcuRev2100_BACnet-Object-List.xlsx.
What are the minimum BACnet points to integrate the Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)?
Start with AI 5 System Active Power (System real power, kW); AI 201 System Active Energy (System energy, kWh); AI 301 System Active Power Demand (System kW demand); AI 8 System Power Factor (System power factor); AI 4 Average Line Current (Average line current, A); AI 10 Phase A Line-to-Neutral Voltage (Phase A L-N voltage, V); AI 35 Input Channel 1 Active Power (Input channel 1 real power, kW); AI 1 Average Frequency (Frequency, Hz).
How do I check these points on the real AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet - Power and energy meter (communication module)
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Accuenergy AXM-WEB2 Ethernet / web module fitted to Acuvim II series meters, with optional IO11/12, IO21/22 and IO31/32 modules.
Also known as: AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
Source: BACnet Points List AcuRev2100-WEB2 · rev. 2026-10-06. Object names, instances and units are reproduced as published; descriptions are our own.