Power and energy meter (multifunction) · BACnet points list
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) BACnet points list
Updated 6 November 2026
The Acuvim-L serves 71 fixed, read-only Analog Inputs over BACnet: voltage, current, power, power factor, unbalance, demand, energy totals and per-phase energy, and THD. BACnet MS/TP runs on the meter's RS-485 port once Protocol 1 is set to BACnet; BACnet IP needs the AXM-WEB2 add-on module. The same object list applies to both.
This page lists 71 BACnet objects for the Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
- Equipment
- Power and energy meter (multifunction)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 71 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
For BACnet MS/TP set the address (S01), baud (S02), Protocol 1 = BACnet (S38), max info frames (S51) and device ID (S52). For BACnet IP enable BACnet in the AXM-WEB2 web page, set port and instance, save and reboot. Read total kW, imported kWh, demand, power factor, current and voltage.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 18 | Total Active Power | Total real power, kW | Read |
| AI 40 | Import Active Energy | Imported energy total, kWh | Read |
| AI 34 | Active Power Demand | Real power demand, kW | Read |
| AI 26 | Total Apparent Power | Total apparent power, kVA | Read |
| AI 30 | Total Power Factor | Three-phase power factor | Read |
| AI 13 | Average Current | Average phase current, A | Read |
| AI 5 | Average Phase Voltage | Average phase voltage, V | Read |
| AI 1 | Frequency | Supply frequency, Hz | Read |
Network setup
- MS/TP: default protocol is Modbus RTU; set S38 Protocol 1 = BACnet. Baud default 19200; max info frames default 10 (1-255); device ID on page S52.
- BACnet IP (AXM-WEB2): Settings > Communications > BACnet/IP; enable, port default 47808, unique device instance; BBMD foreign registration available; save and reboot.
- Acuvim-L-M (no display) from version 6.20: port 1 runs Modbus at 9600 baud for the first 60 s after each power-up, so a mis-set meter can be recovered with Acuview.
Watch out for
- On Acuvim-L-M meters BACnet MS/TP only starts 60 s after power-up.
- BACnet IP is not built in; it needs the AXM-WEB2 module.
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Frequency | Hz | Read | ||
| AI | 2 | Phase A Voltage | V | Read | ||
| AI | 3 | Phase B Voltage | V | Read | ||
| AI | 4 | Phase C Voltage | V | Read | ||
| AImin | 5 | Average Phase Voltage | V | Read | ||
| AI | 6 | Line Voltage AB | V | Read | ||
| AI | 7 | Line Voltage BC | V | Read | ||
| AI | 8 | Line Voltage CA | V | Read | ||
| AI | 9 | Average Line Voltage | V | Read | ||
| AI | 10 | Phase A Current | A | Read | ||
| AI | 11 | Phase B Current | A | Read | ||
| AI | 12 | Phase C Current | A | Read | ||
| AImin | 13 | Average Current | A | Read | ||
| AI | 14 | Neutral Current | A | Read | ||
| AI | 15 | Phase A Active Power | kW | Read | ||
| AI | 16 | Phase B Active Power | kW | Read | ||
| AI | 17 | Phase C Active Power | kW | Read | ||
| AImin | 18 | Total Active Power | kW | Read | ||
| AI | 19 | Phase A Reactive Power | kvar | Read | ||
| AI | 20 | Phase B Reactive Power | kvar | Read | ||
| AI | 21 | Phase C Reactive Power | kvar | Read | ||
| AI | 22 | Total Reactive Power | kvar | Read | ||
| AI | 23 | Phase A Apparent Power | kVA | Read | ||
| AI | 24 | Phase B Apparent Power | kVA | Read | ||
| AI | 25 | Phase C Apparent Power | kVA | Read | ||
| AImin | 26 | Total Apparent Power | kVA | Read | ||
| AI | 27 | Phase A Power Factor | Read | |||
| AI | 28 | Phase B Power Factor | Read | |||
| AI | 29 | Phase C Power Factor | Read | |||
| AImin | 30 | Total Power Factor | Read | |||
| AI | 31 | Voltage Unbalance Factor | % | Read | ||
| AI | 32 | Current Unbalance Factor | % | Read | ||
| AI | 33 | Load Type | Read | |||
| AImin | 34 | Active Power Demand | kW | Read | ||
| AI | 35 | Reactive Power Demand | kvar | Read | ||
| AI | 36 | Apparent Power Demand | kVA | Read | ||
| AI | 37 | Phase A Current Demand | A | Read | ||
| AI | 38 | Phase B Current Demand | A | Read | ||
| AI | 39 | Phase C Current Demand | A | Read | ||
| AImin | 40 | Import Active Energy | kWh | Read | ||
| AI | 41 | Export Active Energy | kWh | Read | ||
| AI | 42 | Import Reactive Energy | kvarh | Read | ||
| AI | 43 | Export Reactive Energy | kvarh | Read | ||
| AI | 44 | Energy Total | kWh | Read | ||
| AI | 45 | Energy Net | kWh | Read | ||
| AI | 46 | Reactive Energy Total | kvarh | Read | ||
| AI | 47 | Reactive Energy Net | kvarh | Read | ||
| AI | 48 | Apparent Energy | kVAh | Read | ||
| AI | 49 | Phase A Import Active Energy | kWh | Read | ||
| AI | 50 | Phase A Export Active Energy | kWh | Read | ||
| AI | 51 | Phase B Import Active Energy | kWh | Read | ||
| AI | 52 | Phase B Export Active Energy | kWh | Read | ||
| AI | 53 | Phase C Import Active Energy | kWh | Read | ||
| AI | 54 | Phase C Export Active Energy | kWh | Read | ||
| AI | 55 | Phase A Import Reactive Energy | kvarh | Read | ||
| AI | 56 | Phase A Export Reactive Energy | kvarh | Read | ||
| AI | 57 | Phase B Import Reactive Energy | kvarh | Read | ||
| AI | 58 | Phase B Export Reactive Energy | kvarh | Read | ||
| AI | 59 | Phase C Import Reactive Energy | kvarh | Read | ||
| AI | 60 | Phase C Export Reactive Energy | kvarh | Read | ||
| AI | 61 | Phase A Apparent Energy | kVAh | Read | ||
| AI | 62 | Phase B Apparent Energy | kVAh | Read | ||
| AI | 63 | Phase C Apparent Energy | kVAh | Read | ||
| AI | 64 | Phase A Voltage THD | % | Read | ||
| AI | 65 | Phase B Voltage THD | % | Read | ||
| AI | 66 | Phase C Voltage THD | % | Read | ||
| AI | 67 | Average Voltage THD | % | Read | ||
| AI | 68 | Phase A Current THD | % | Read | ||
| AI | 69 | Phase B Current THD | % | Read | ||
| AI | 70 | Phase C Current THD | % | Read | ||
| AI | 71 | Average Current THD | % | Read |
No points match these filters.
Object ID lookup: Accuenergy Acuvim-L series power and energy meter point IDs by name
AI1FrequencyAI2Phase A VoltageAI3Phase B VoltageAI4Phase C VoltageAI5Average Phase VoltageAI6Line Voltage ABAI7Line Voltage BCAI8Line Voltage CAAI9Average Line VoltageAI10Phase A CurrentAI11Phase B CurrentAI12Phase C CurrentAI13Average CurrentAI14Neutral CurrentAI15Phase A Active PowerAI16Phase B Active PowerAI17Phase C Active PowerAI18Total Active PowerAI19Phase A Reactive PowerAI20Phase B Reactive PowerAI21Phase C Reactive PowerAI22Total Reactive PowerAI23Phase A Apparent PowerAI24Phase B Apparent PowerAI25Phase C Apparent PowerAI26Total Apparent PowerAI27Phase A Power FactorAI28Phase B Power FactorAI29Phase C Power FactorAI30Total Power FactorAI31Voltage Unbalance FactorAI32Current Unbalance FactorAI33Load TypeAI34Active Power DemandAI35Reactive Power DemandAI36Apparent Power DemandAI37Phase A Current DemandAI38Phase B Current DemandAI39Phase C Current DemandAI40Import Active EnergyAI41Export Active EnergyAI42Import Reactive EnergyAI43Export Reactive EnergyAI44Energy TotalAI45Energy NetAI46Reactive Energy TotalAI47Reactive Energy NetAI48Apparent EnergyAI49Phase A Import Active EnergyAI50Phase A Export Active EnergyAI51Phase B Import Active EnergyAI52Phase B Export Active EnergyAI53Phase C Import Active EnergyAI54Phase C Export Active EnergyAI55Phase A Import Reactive EnergyAI56Phase A Export Reactive EnergyAI57Phase B Import Reactive EnergyAI58Phase B Export Reactive EnergyAI59Phase C Import Reactive EnergyAI60Phase C Export Reactive EnergyAI61Phase A Apparent EnergyAI62Phase B Apparent EnergyAI63Phase C Apparent EnergyAI64Phase A Voltage THDAI65Phase B Voltage THDAI66Phase C Voltage THDAI67Average Voltage THDAI68Phase A Current THDAI69Phase B Current THDAI70Phase C Current THDAI71Average Current THD
Integration notes
- The table has no access column; all objects are measurements and are listed as read-only.
- BACnet IP needs an AXM-WEB2 module fitted to the meter; it is configured in the module's web page.
- Names for AI 49-60 wrap over two lines in the manual and are joined here.
- Features differ between the Acuvim-CL and Acuvim-EL models (see the manual's function table).
- Source: Acuvim-L user manual V4.1.12 (March 2026), Table 6-85.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
How many BACnet points does the Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) have?
This list has 71 BACnet objects: 71 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP) BACnet documentation?
The source is Acuvim-L Multifunction Power and Energy Meter User Manual (V4.1.12), revision 2026-03, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/Acuvim-L-Multifunction-Power-and-Energy-Meter-User-Manual-v4.pdf.
What are the minimum BACnet points to integrate the Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)?
Start with AI 18 Total Active Power (Total real power, kW); AI 40 Import Active Energy (Imported energy total, kWh); AI 34 Active Power Demand (Real power demand, kW); AI 26 Total Apparent Power (Total apparent power, kVA); AI 30 Total Power Factor (Three-phase power factor); AI 13 Average Current (Average phase current, A); AI 5 Average Phase Voltage (Average phase voltage, V); AI 1 Frequency (Supply frequency, Hz).
How do I check these points on the real Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (BACnet MS/TP module)
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Accuenergy Acuvim II series power meters fitted with the AXM-BMS BACnet MS/TP communication module.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102 - Power and energy meter (communication module)
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Accuenergy AXM-WEB2 Ethernet / web module fitted to Acuvim II series meters, with optional IO11/12, IO21/22 and IO31/32 modules.
Also known as: AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
Source: Acuvim-L Multifunction Power and Energy Meter User Manual · V4.1.12 · rev. 2026-03. Object names, instances and units are reproduced as published; descriptions are our own.