 "manufacturer": "Accuenergy",
 "manufacturer_slug": "accuenergy",
 "model": "AcuRev 4100 multi-circuit power meter (BACnet)",
 "model_slug": "acurev-4100",
 "aliases": [
  "AcuRev 4100",
  "AcuRev 4100 BACnet points list"
 ],
 "equipment_type": "Multi-circuit power and energy meter (submeter)",
 "applies_to": "Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.",
 "summary": "The AcuRev 4100 meters up to 24 CT input channels plus 12 user-defined summing channels. Real-time, demand and power quality values are read-only Analog Inputs (1-721) and energy totals are Large Analog Values (1-360). Channel 1 of each channel group is printed in full; the other channels follow the same layout in the ranges given in the notes.",
 "bacnet_transport": [],
 "firmware": "v1.03p06",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Per-channel blocks: the list prints channel 1 and then a range for the rest - input channel basics AI 44-204 (7 per channel), user channel basics AI 211-276 (6 per channel; printed as 205-276), input channel demand AI 307-444, user channel demand AI 451-516, input channel power quality AI 546-637 (4 per channel), user channel power quality AI 645-721 (7 per channel), input channel energy LAV 46-252 and user channel energy LAV 262-360 (9 per channel). Only printed objects are listed here.",
  "AI 208 (Susr1_rms) is printed with 'S' in the ID column; it sits between AI 207 and AI 209 and is listed as 208.",
  "Load nature values: 0 resistive, 1 capacitive, 2 inductive.",
  "The list does not say which BACnet transport the meter uses; check the meter manual.",
  "Source: Accuenergy 'BACnet Points List AcuRev4100' spreadsheet, firmware v1.03p06, generated 2026-05-26."
 ],
 "source": {
  "title": "BACnet Points List AcuRev4100",
  "doc_number": null,
  "revision_date": "2026-05-26",
  "url": "https://www.accuenergy.com/wp-content/uploads/AcuRev-4100_BACnet-Object-List.xlsx"
 },
 "integration": {
  "summary": "Everything is read-only. Map the system power, energy and demand objects first, then the channel 1 objects and the matching objects for the other channels using the per-channel offsets in the notes.",
  "minimum_points": [
   {
    "ref": "AI 32",
    "name": "Psys_rms",
    "why": "System real power, kW"
   },
   {
    "ref": "LAV 28",
    "name": "PsysImp_eng",
    "why": "System imported energy, kWh"
   },
   {
    "ref": "AI 296",
    "name": "PsysImp_dema",
    "why": "System import kW demand"
   },
   {
    "ref": "AI 36",
    "name": "PFsys_rms",
    "why": "System power factor"
   },
   {
    "ref": "AI 31",
    "name": "Isys_rms",
    "why": "System average current, A"
   },
   {
    "ref": "AI 2",
    "name": "Ua_rms",
    "why": "Phase A voltage, V"
   },
   {
    "ref": "AI 38",
    "name": "Pchn1_rms",
    "why": "Input channel 1 real power, kW"
   },
   {
    "ref": "LAV 37",
    "name": "PChn1Imp_eng",
    "why": "Input channel 1 imported energy, kWh"
   },
   {
    "ref": "AI 1",
    "name": "Freq_rms",
    "why": "Frequency, Hz"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [],
  "gotchas": [
   "Channel 2-24 and user channel 2-12 objects are not printed by name; work them out from the channel 1 layout and the ranges.",
   "Energy totals are Large Analog Value objects (double precision); some older BMS front ends cannot read LAV."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Freq_rms",
   "description": "Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Ua_rms",
   "description": "Phase A Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Ub_rms",
   "description": "Phase B Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Uc_rms",
   "description": "Phase C Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Uavg_rms",
   "description": "Phase Average Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Uab_rms",
   "description": "Line Voltage AB",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Ubc_rms",
   "description": "Line Voltage BC",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Uca_rms",
   "description": "Line Voltage CA",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Ulavg_rms",
   "description": "Average Line Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "UaAng_rms",
   "description": "Phase A Voltage Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "UbAng_rms",
   "description": "Phase B Voltage Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "UcAng_rms",
   "description": "Phase C Voltage Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Ia_rms",
   "description": "Phase A Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Pa_rms",
   "description": "Phase A Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Qa_rms",
   "description": "Phase A Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Sa_rms",
   "description": "Phase A Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "LNa_rms",
   "description": "Phase A Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "PFa_rms",
   "description": "Phase A Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Ib_rms",
   "description": "Phase B Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Pb_rms",
   "description": "Phase B Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Qb_rms",
   "description": "Phase B Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Sb_rms",
   "description": "Phase B Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "LNb_rms",
   "description": "Phase B Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "PFb_rms",
   "description": "Phase B Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Ic_rms",
   "description": "Phase C Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Pc_rms",
   "description": "Phase C Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Qc_rms",
   "description": "Phase C Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Sc_rms",
   "description": "Phase C Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "LNc_rms",
   "description": "Phase C Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "PFc_rms",
   "description": "Phase C Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "Isys_rms",
   "description": "System Average Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "Psys_rms",
   "description": "System Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Qsys_rms",
   "description": "System Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Ssys_rms",
   "description": "System Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "LNsys_rms",
   "description": "System Load Nature(0:Resistive load 1:Capacitive load 2:Inductive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "PFsys_rms",
   "description": "System Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Ichn1_rms",
   "description": "Input Channel 1 Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Pchn1_rms",
   "description": "Input Channel 1 Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Qchn1_rms",
   "description": "Input Channel 1 Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Schn1_rms",
   "description": "Input Channel 1 Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "LNchn1_rms",
   "description": "Input Channel 1 Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "PFchn1_rms",
   "description": "Input Channel 1 Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Angchn1_rms",
   "description": "Input Channel 1 Current Phase Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "Iusr1_rms",
   "description": "User Channel 1 Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 206,
   "name": "Pusr1_rms",
   "description": "User Channel 1 Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 207,
   "name": "Qusr1_rms",
   "description": "User Channel 1 Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 208,
   "name": "Susr1_rms",
   "description": "User Channel 1 Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 209,
   "name": "LNusr1_rms",
   "description": "User Channel 1 Load Nature (0:Resistive load 1:Capacitive load 2:Inductive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "PFusr1_rms",
   "description": "User Channel 1 Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 277,
   "name": "Ia_dema",
   "description": "Phase A Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 278,
   "name": "PaImp_dema",
   "description": "Phase A Import Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 279,
   "name": "PaExp_dema",
   "description": "Phase A Export Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 280,
   "name": "QaImp_dema",
   "description": "Phase A Import Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 281,
   "name": "QaExp_dema",
   "description": "Phase A Export Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 282,
   "name": "Sa_dema",
   "description": "Phase A Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 283,
   "name": "Ib_dema",
   "description": "Phase B Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 284,
   "name": "PbImp_dema",
   "description": "Phase B Import Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 285,
   "name": "PbExp_dema",
   "description": "Phase B Export Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 286,
   "name": "QbImp_dema",
   "description": "Phase B Import Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 287,
   "name": "QbExp_dema",
   "description": "Phase B Export Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 288,
   "name": "Sb_dema",
   "description": "Phase B Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 289,
   "name": "Ic_dema",
   "description": "Phase C Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 290,
   "name": "PcImp_dema",
   "description": "Phase C Import Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 291,
   "name": "PcExp_dema",
   "description": "Phase C Export Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 292,
   "name": "QcImp_dema",
   "description": "Phase C Import Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 293,
   "name": "QcExp_dema",
   "description": "Phase C Export Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 294,
   "name": "Sc_dema",
   "description": "Phase C Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 295,
   "name": "Isys_dema",
   "description": "System Average Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 296,
   "name": "PsysImp_dema",
   "description": "System Import Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 297,
   "name": "PsysExp_dema",
   "description": "System Export Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 298,
   "name": "QsysImp_dema",
   "description": "System Import Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 299,
   "name": "QsysExp_dema",
   "description": "System Export Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "Ssys_dema",
   "description": "System Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 301,
   "name": "Ichn1_dema",
   "description": "Input Channel 1 Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 302,
   "name": "Pchn1Imp_dema",
   "description": "Input Channel 1 Import Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 303,
   "name": "Pchn1Exp_dema",
   "description": "Input Channel 1 Export Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 304,
   "name": "Qchn1Imp_dema",
   "description": "Input Channel 1 Import Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 305,
   "name": "Qchn1Exp_dema",
   "description": "Input Channel 1 Export Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 306,
   "name": "Schn1_dema",
   "description": "Input Channel 1 Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 445,
   "name": "Iusr1_dema",
   "description": "User Channel 1 Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 446,
   "name": "Pusr1Imp_dema",
   "description": "User Channel 1 Import Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 447,
   "name": "Pusr1Exp_dema",
   "description": "User Channel 1 Export Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 448,
   "name": "Qusr1Imp_dema",
   "description": "User Channel 1 Import Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 449,
   "name": "Qusr1Exp_dema",
   "description": "User Channel 1 Export Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 450,
   "name": "Susr1_dema",
   "description": "User Channel 1 Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 517,
   "name": "Vpsm_pq",
   "description": "Voltage Positive Sequence Magnitude",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 518,
   "name": "Vzsm_pq",
   "description": "Voltage Zero Sequence Magnitude",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 519,
   "name": "Vnsm_pq",
   "description": "Voltage Negative Sequence Magnitude",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 520,
   "name": "Vpsa_pq",
   "description": "Voltage Positive Sequence Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 521,
   "name": "Vzsa_pq",
   "description": "Voltage Zero Sequence Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 522,
   "name": "Vnsa_pq",
   "description": "Voltage Negative Sequence Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 523,
   "name": "Vufm_pq",
   "description": "Voltage Unbalance Factor Magnitude",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 524,
   "name": "VThd_A_pq",
   "description": "Phase A Voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 525,
   "name": "VThdO_A_pq",
   "description": "Phase A Voltage THD Odd",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 526,
   "name": "VThdE_A_pq",
   "description": "Phase A Voltage THD Even",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 527,
   "name": "VCF_A_pq",
   "description": "Phase A Voltage Crest Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 528,
   "name": "VThff_A_pq",
   "description": "Phase A Voltage THFF Factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 529,
   "name": "VThd_B_pq",
   "description": "Phase B Voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 530,
   "name": "VThdO_B_pq",
   "description": "Phase B Voltage THD Odd",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 531,
   "name": "VThdE_B_pq",
   "description": "Phase B Voltage THD Even",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 532,
   "name": "VCF_B_pq",
   "description": "Phase B Voltage Crest Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 533,
   "name": "VThff_B_pq",
   "description": "Phase B Voltage THFF Factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 534,
   "name": "VThd_C_pq",
   "description": "Phase C Voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 535,
   "name": "VThdO_C_pq",
   "description": "Phase C Voltage THD Odd",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 536,
   "name": "VThdE_C_pq",
   "description": "Phase C Voltage THD Even",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 537,
   "name": "VCF_C_pq",
   "description": "Phase C Voltage Crest Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 538,
   "name": "VThff_C_pq",
   "description": "Phase C Voltage THFF Factor",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 539,
   "name": "VavgThd_pq",
   "description": "Average Voltage THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 540,
   "name": "VavgThdO_pq",
   "description": "Average Voltage THD Odd",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 541,
   "name": "VavgThdE_pq",
   "description": "Average Voltage THD Even",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 542,
   "name": "Ichn1Thd_pq",
   "description": "Input Channel 1 Current THD",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 543,
   "name": "Ichn1ThdO_pq",
   "description": "Input Channel 1 Current THD Odd",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 544,
   "name": "Ichn1ThdE_pq",
   "description": "Input Channel 1 Current THD Even",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 545,
   "name": "Ichn1KF_pq",
   "description": "Input Channel 1 Current K Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 638,
   "name": "Iuser1psm_pq",
   "description": "User Channel 1 Current Positive Sequence Magnitude",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 639,
   "name": "Iuser1zsm_pq",
   "description": "User Channel 1 Current Zero Sequence Magnitude",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 640,
   "name": "Iuser1nsm_pq",
   "description": "User Channel 1 Current Negative Sequence Magnitude",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 641,
   "name": "Iuser1psa_pq",
   "description": "User Channel 1 Current Positive Sequence Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 642,
   "name": "Iuser1zsa_pq",
   "description": "User Channel 1 Current Zero Sequence Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 643,
   "name": "Iuser1nsa_pq",
   "description": "User Channel 1 Current Negative Sequence Angle",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 644,
   "name": "Iuser1ufm_pq",
   "description": "User Channel 1 Current Unbalance Factor Magnitude",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 1,
   "name": "PaImp_eng",
   "description": "Phase A active energy import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 2,
   "name": "PaExp_eng",
   "description": "Phase A active energy export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 3,
   "name": "PaNet_eng",
   "description": "Phase A active energy net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 4,
   "name": "PaTotal_eng",
   "description": "Phase A active energy total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 5,
   "name": "QaImp_eng",
   "description": "Phase A reactive energy import",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 6,
   "name": "QaExp_eng",
   "description": "Phase A reactive energy export",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 7,
   "name": "QaNet_eng",
   "description": "Phase A reactive energy net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 8,
   "name": "QaTotal_eng",
   "description": "Phase A reactive energy total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 9,
   "name": "Sa_eng",
   "description": "Phase A apparent energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 10,
   "name": "PbImp_eng",
   "description": "Phase B active energy import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 11,
   "name": "PbExp_eng",
   "description": "Phase B active energy export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 12,
   "name": "PbNet_eng",
   "description": "Phase B active energy net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 13,
   "name": "PbTotal_eng",
   "description": "Phase B active energy total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 14,
   "name": "QbImp_eng",
   "description": "Phase B reactive energy import",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 15,
   "name": "QbExp_eng",
   "description": "Phase B reactive energy export",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 16,
   "name": "QbNet_eng",
   "description": "Phase B reactive energy net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 17,
   "name": "QbTotal_eng",
   "description": "Phase B reactive energy total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 18,
   "name": "Sb_eng",
   "description": "Phase B apparent energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 19,
   "name": "PcImp_eng",
   "description": "Phase C active energy import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 20,
   "name": "PcExp_eng",
   "description": "Phase C active energy export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 21,
   "name": "PcNet_eng",
   "description": "Phase C active energy net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 22,
   "name": "PcTotal_eng",
   "description": "Phase C active energy total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 23,
   "name": "QcImp_eng",
   "description": "Phase C reactive energy import",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 24,
   "name": "QcExp_eng",
   "description": "Phase C reactive energy export",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 25,
   "name": "QcNet_eng",
   "description": "Phase C reactive energy net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 26,
   "name": "QcTotal_eng",
   "description": "Phase C reactive energy total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 27,
   "name": "Sc_eng",
   "description": "Phase C apparent energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 28,
   "name": "PsysImp_eng",
   "description": "System active energy import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 29,
   "name": "PsysExp_eng",
   "description": "System active energy export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 30,
   "name": "PsysNet_eng",
   "description": "System active energy net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 31,
   "name": "PsysTotal_eng",
   "description": "System active energy total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 32,
   "name": "QsysImp_eng",
   "description": "System reactive energy import",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 33,
   "name": "QsysExp_eng",
   "description": "System reactive energy export",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 34,
   "name": "QsysNet_eng",
   "description": "System reactive energy net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 35,
   "name": "QsysTotal_eng",
   "description": "System reactive energy total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 36,
   "name": "Ssys_eng",
   "description": "System apparent energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 37,
   "name": "PChn1Imp_eng",
   "description": "Input Channel 1 active energy import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 38,
   "name": "PChn1Exp_eng",
   "description": "Input Channel 1 active energy export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 39,
   "name": "PChn1Net_eng",
   "description": "Input Channel 1 active energy net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 40,
   "name": "PChn1Total_eng",
   "description": "Input Channel 1 active energy total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 41,
   "name": "QChn1Imp_eng",
   "description": "Input Channel 1 reactive energy import",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 42,
   "name": "QChn1Exp_eng",
   "description": "Input Channel 1 reactive energy export",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 43,
   "name": "QChn1Net_eng",
   "description": "Input Channel 1 reactive energy net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 44,
   "name": "QChn1Total_eng",
   "description": "Input Channel 1 reactive energy total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 45,
   "name": "SChn1_eng",
   "description": "Input Channel 1 apparent energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 253,
   "name": "PUser1Imp_eng",
   "description": "User Channel 1 active energy import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 254,
   "name": "PUser1Exp_eng",
   "description": "User Channel 1 active energy export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 255,
   "name": "PUser1Net_eng",
   "description": "User Channel 1 active energy net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 256,
   "name": "PUser1Total_eng",
   "description": "User Channel 1 active energy total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 257,
   "name": "QUser1Imp_eng",
   "description": "User Channel 1 reactive energy import",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 258,
   "name": "QUser1Exp_eng",
   "description": "User Channel 1 reactive energy export",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 259,
   "name": "QUser1Net_eng",
   "description": "User Channel 1 reactive energy net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 260,
   "name": "QUser1Total_eng",
   "description": "User Channel 1 reactive energy total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 261,
   "name": "SUser1_eng",
   "description": "User Channel 1 apparent energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/accuenergy/acurev-4100",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}