 "manufacturer": "Accuenergy",
 "manufacturer_slug": "accuenergy",
 "model": "Acuvim II V3 power meter (native BACnet, firmware v6.39)",
 "model_slug": "acuvim-ii-v3",
 "aliases": [
  "Acuvim II V3",
  "Acuvim-II V3",
  "Acuvim II V3 BACnet",
  "Acuvim-II_BACnet-Obj-List"
 ],
 "equipment_type": "Power and energy meter",
 "applies_to": "Accuenergy Acuvim II V3 multifunction power meters with firmware v6.39.",
 "summary": "The Acuvim II V3 meter serves 103 read-only Analog Inputs (real-time values, demand, energy, THD, AXM-IO3 analog inputs and AXM-IO pulse counters) and 44 Binary Inputs (AXM-IO digital inputs and 16 alarm channel status flags). Its object map differs from the AXM-BIP and AXM-WEB2 module lists for the older Acuvim II, for example the pulse counters sit on AI 76-103.",
 "bacnet_transport": [],
 "firmware": "v6.39",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "AI 72-103 and BI 1-28 carry data only when the matching AXM-IO module is fitted.",
  "AI 33 load type: 82 resistive, 76 inductive, 67 capacitive.",
  "THD objects AI 64-71 are listed with volts / amperes as units in the spreadsheet.",
  "The spreadsheet does not say which BACnet transport the V3 uses.",
  "Source: Accuenergy 'BACnet Points List Acuvim II V3' spreadsheet, firmware v6.39, generated 2026-10-05; alarm channel status BI 29-44 were added 2026-07-17."
 ],
 "source": {
  "title": "BACnet Points List Acuvim II V3",
  "doc_number": null,
  "revision_date": "2026-10-05",
  "url": "https://www.accuenergy.com/wp-content/uploads/Acuvim-II_BACnet-Obj-List.xlsx"
 },
 "integration": {
  "summary": "All objects are read-only measurements. Map total power, imported energy, demand, PF, current and voltage; I/O module and alarm channel objects only matter when they are set up.",
  "minimum_points": [
   {
    "ref": "AI 18",
    "name": "P_rms",
    "why": "Total real power, kW"
   },
   {
    "ref": "AI 40",
    "name": "Active_Energy_Imp",
    "why": "Imported energy, kWh"
   },
   {
    "ref": "AI 34",
    "name": "P_dema",
    "why": "Real power demand, kW"
   },
   {
    "ref": "AI 30",
    "name": "PF_rms",
    "why": "Total power factor"
   },
   {
    "ref": "AI 13",
    "name": "Iavg_rms",
    "why": "Average current, A"
   },
   {
    "ref": "AI 5",
    "name": "Uavg_rms",
    "why": "Average L-N voltage, V"
   },
   {
    "ref": "AI 1",
    "name": "Freq_rms",
    "why": "Frequency, Hz"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [],
  "gotchas": [
   "AXM-IO objects (AI 72-103, BI 1-28) only read real values when the module is fitted."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Freq_rms",
   "description": "Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Ua_rms",
   "description": "Phase A Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Ub_rms",
   "description": "Phase B Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Uc_rms",
   "description": "Phase C Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Uavg_rms",
   "description": "Average Phase Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Uab_rms",
   "description": "Line Voltage AB",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Ubc_rms",
   "description": "Line Voltage BC",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Uca_rms",
   "description": "Line Voltage CA",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Ulavg_rms",
   "description": "Average Line Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Ia_rms",
   "description": "Phase A Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Ib_rms",
   "description": "Phase B Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Ic_rms",
   "description": "Phase C Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Iavg_rms",
   "description": "Average Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "In_rms",
   "description": "Neutral Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Pa_rms",
   "description": "Phase A Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Pb_rms",
   "description": "Phase B Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Pc_rms",
   "description": "Phase C Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "P_rms",
   "description": "Total Active Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Qa_rms",
   "description": "Phase A Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Qb_rms",
   "description": "Phase B Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Qc_rms",
   "description": "Phase C Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Q_rms",
   "description": "Total Reactive Power",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Sa_rms",
   "description": "Phase A Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Sb_rms",
   "description": "Phase B Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Sc_rms",
   "description": "Phase C Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "S_rms",
   "description": "Total Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "PFa_rms",
   "description": "Phase A Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "PFb_rms",
   "description": "Phase B Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "PFc_rms",
   "description": "Phase C Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "PF_rms",
   "description": "Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "U_unbl",
   "description": "Voltage Unbalance Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "I_unbl",
   "description": "Current Unbalance Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Rlc_val",
   "description": "Load Type (82:Resistive load  76:Inductive load  67:Capacitive load)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "P_dema",
   "description": "Active Power Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Q_dema",
   "description": "Reactive Power Demand",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "S_dema",
   "description": "Apparent Power Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Ia_dema",
   "description": "Phase A Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Ib_dema",
   "description": "Phase B Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Ic_dema",
   "description": "Phase C Current Demand",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Active_Energy_Imp",
   "description": "Import Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Active_Energy_Exp",
   "description": "Export Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Reactive_Energy_Imp",
   "description": "Import Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Reactive_Energy_Exp",
   "description": "Export Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Active_Energy_Total",
   "description": "Active Energy Total",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Active_Energy_Net",
   "description": "Active Energy Net",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Reactive_Energy_Total",
   "description": "Reactive Energy Total",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Reactive_Energy_Net",
   "description": "Reactive Energy Net",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Apparent_Energy",
   "description": "Apparent Energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "Active_Energy_Imp_A",
   "description": "Phase A Import Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "Active_Energy_Exp_A",
   "description": "Phase A Export Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "Active_Energy_Imp_B",
   "description": "Phase B Import Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "Active_Energy_Exp_B",
   "description": "Phase B Export Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "Active_Energy_Imp_C",
   "description": "Phase C Import Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "Active_Energy_Exp_C",
   "description": "Phase C Export Active Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Reactive_Energy_Imp_A",
   "description": "Phase A Import Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Reactive_Energy_Exp_A",
   "description": "Phase A Export Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "Reactive_Energy_Imp_B",
   "description": "Phase B Import Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "Reactive_Energy_Exp_B",
   "description": "Phase B Export Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "Reactive_Energy_Imp_C",
   "description": "Phase C Import Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "Reactive_Energy_Exp_C",
   "description": "Phase C Export Reactive Energy",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "Apparent_Energy_A",
   "description": "Phase A Apparent Energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "Apparent_Energy_B",
   "description": "Phase B Apparent Energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "Apparent_Energy_C",
   "description": "Phase C Apparent Energy",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "V1_thd",
   "description": "Voltage 1 THD",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "V2_thd",
   "description": "Voltage 2 THD",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "V3_thd",
   "description": "Voltage 3 THD",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "V_thd",
   "description": "Average Voltage THD",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "I1_thd",
   "description": "Current 1 THD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "I2_thd",
   "description": "Current 2 THD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "I3_thd",
   "description": "Current 3 THD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "I_thd",
   "description": "Average Current THD",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "IO31_ai1",
   "description": "IO31 Analog Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "IO31_ai2",
   "description": "IO31 Analog Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "IO32_ai1",
   "description": "IO32 Analog Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "IO32_ai2",
   "description": "IO32 Analog Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "IO11_pc1",
   "description": "IO11 Pulse Counter 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "IO11_pc2",
   "description": "IO11 Pulse Counter 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "IO11_pc3",
   "description": "IO11 Pulse Counter 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "IO11_pc4",
   "description": "IO11 Pulse Counter 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "IO11_pc5",
   "description": "IO11 Pulse Counter 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "IO11_pc6",
   "description": "IO11 Pulse Counter 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "IO21_pc1",
   "description": "IO21 Pulse Counter 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "IO21_pc2",
   "description": "IO21 Pulse Counter 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "IO21_pc3",
   "description": "IO21 Pulse Counter 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "IO21_pc4",
   "description": "IO21 Pulse Counter 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "IO31_pc1",
   "description": "IO31 Pulse Counter 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "IO31_pc2",
   "description": "IO31 Pulse Counter 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "IO31_pc3",
   "description": "IO31 Pulse Counter 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "IO31_pc4",
   "description": "IO31 Pulse Counter 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "IO12_pc1",
   "description": "IO12 Pulse Counter 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "IO12_pc2",
   "description": "IO12 Pulse Counter 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "IO12_pc3",
   "description": "IO12 Pulse Counter 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "IO12_pc4",
   "description": "IO12 Pulse Counter 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "IO12_pc5",
   "description": "IO12 Pulse Counter 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "IO12_pc6",
   "description": "IO12 Pulse Counter 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "IO22_pc1",
   "description": "IO22 Pulse Counter 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "IO22_pc2",
   "description": "IO22 Pulse Counter 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "IO22_pc3",
   "description": "IO22 Pulse Counter 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "IO22_pc4",
   "description": "IO22 Pulse Counter 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "IO32_pc1",
   "description": "IO32 Pulse Counter 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "IO32_pc2",
   "description": "IO32 Pulse Counter 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "IO32_pc3",
   "description": "IO32 Pulse Counter 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "IO32_pc4",
   "description": "IO32 Pulse Counter 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "IO11_di1",
   "description": "IO11 Digital Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "IO11_di2",
   "description": "IO11 Digital Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "IO11_di3",
   "description": "IO11 Digital Input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "IO11_di4",
   "description": "IO11 Digital Input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "IO11_di5",
   "description": "IO11 Digital Input 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "IO11_di6",
   "description": "IO11 Digital Input 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "IO21_di1",
   "description": "IO21 Digital Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "IO21_di2",
   "description": "IO21 Digital Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "IO21_di3",
   "description": "IO21 Digital Input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "IO21_di4",
   "description": "IO21 Digital Input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "IO31_di1",
   "description": "IO31 Digital Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "IO31_di2",
   "description": "IO31 Digital Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "IO31_di3",
   "description": "IO31 Digital Input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "IO31_di4",
   "description": "IO31 Digital Input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "IO12_di1",
   "description": "IO12 Digital Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "IO12_di2",
   "description": "IO12 Digital Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "IO12_di3",
   "description": "IO12 Digital Input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "IO12_di4",
   "description": "IO12 Digital Input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "IO12_di5",
   "description": "IO12 Digital Input 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "IO12_di6",
   "description": "IO12 Digital Input 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "IO22_di1",
   "description": "IO22 Digital Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "IO22_di2",
   "description": "IO22 Digital Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "IO22_di3",
   "description": "IO22 Digital Input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "IO22_di4",
   "description": "IO22 Digital Input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "IO32_di1",
   "description": "IO32 Digital Input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "IO32_di2",
   "description": "IO32 Digital Input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "IO32_di3",
   "description": "IO32 Digital Input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "IO32_di4",
   "description": "IO32 Digital Input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "AlarmStatus1",
   "description": "Alarm Channel 1 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "AlarmStatus2",
   "description": "Alarm Channel 2 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "AlarmStatus3",
   "description": "Alarm Channel 3 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "AlarmStatus4",
   "description": "Alarm Channel 4 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "AlarmStatus5",
   "description": "Alarm Channel 5 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "AlarmStatus6",
   "description": "Alarm Channel 6 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "AlarmStatus7",
   "description": "Alarm Channel 7 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "AlarmStatus8",
   "description": "Alarm Channel 8 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "AlarmStatus9",
   "description": "Alarm Channel 9 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "AlarmStatus10",
   "description": "Alarm Channel 10 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "AlarmStatus11",
   "description": "Alarm Channel 11 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "AlarmStatus12",
   "description": "Alarm Channel 12 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "AlarmStatus13",
   "description": "Alarm Channel 13 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "AlarmStatus14",
   "description": "Alarm Channel 14 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "AlarmStatus15",
   "description": "Alarm Channel 15 Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "AlarmStatus16",
   "description": "Alarm Channel 16 Status",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/accuenergy/acuvim-ii-v3",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}