Easy BACnet
  1. Home
  2. BACnet points lists
  3. Siemens
  4. RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)

Fan coil room thermostat · BACnet points list

Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The RDF4..BN thermostats control 2-pipe or 4-pipe fan coils with 1-speed, 3-speed or ECM fans and expose their settings over BACnet MS/TP. The BMS can write the operating mode, Comfort setpoint, fan speed, room temperature, changeover, window and presence values; most other objects are the thermostat's P-parameters.

This page lists 65 BACnet objects for the Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) — 49 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)
Equipment
Fan coil room thermostat
Equipment type
VAV boxes & fan coils
BACnet objects
65 (49 writable)
Transport
BACnet MS/TP
Firmware
V1.0.1, V1.0.2
Default device instance
10
Also known as
RDF400BN, RDF400BN-BK, RDF440BN, RDF440BN-BK, RDF460BN, RDF460BN-BK, RDF4..BN
Source document
RDF4..BN.., RDF4..MB.., RDF440, RDF440-BK Room thermostat Basic Documentation · A6V14153583 · rev. 2026-08-19
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Siemens’s current documentation and the live device before use. Not official Siemens information. Terms of use.

BMS integration notes: Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)

Integration in brief

Command the room operating mode through MV 21 and the Comfort setpoint through AV 16, and read the active setpoint, present mode and room temperature back. Fan speed is MV 2. Window, presence, keycard and changeover can be fed from the BMS through BV 6 and BV 8-10.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 21ROpModSwiOperating mode: 1 = Protection, 2 = Economy, 4 = ComfortWrite
AV 16SpCmfComfort setpoint, °CWrite
MV 2FanSpdCmdFan speed: 1 = auto, 2-4 = low/med/highWrite
MV 1PrOpModPresent operating modeRead
AI 0TRRoom temperatureRead
AV 0SpTRActive room setpointRead
AV 1HReqHeating demand, %Read
AV 2CReqCooling demand, %Read
MV 23FltFault, 1 = no faultRead

Sensors & values from the BMS

AV 4 TRBus takes a room temperature from the bus; MV 10 P11 can show it on the display. Window contact, presence and keycard can also be written via BV 8-10.

Network setup

Watch out for

Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

65 of 65 shown
Type
Multi-stateOther
Access
Show
Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TRRoom temperature; -100 = out of service°CRead
AI1AInX1Analog input X1 (temperature or 0-100 %, per X1 setup)°C or %Read
AVmin0SpTRRoom temperature setpoint (active); 0 = OFF°CRead
AVmin1HReqHeating request, 0-100%Read
AVmin2CReqCooling request, 0-100%Read
AV3MsrdValAdjP13 room temperature reading adjustment, -5 to 5KWrite
AV4TRBusRoom temperature written via bus, -20 to 70°CWrite
AV5FanVarSpdVariable (ECM) fan speed, 0-100%Read
AV6SpHEcoP22 Economy heating setpoint; 0 = OFF°CWrite
AV7SpCEcoP23 Economy cooling setpoint; 0 = OFF°CWrite
AV8ZeEgZP41 dead zone, 0.5-5KWrite
AV9SpDiffP42 setpoint differential, 0.5-5KWrite
AV10XpHysHtgP43 heating switching differential, 0.5-6KWrite
AV11XpHysClgP44 cooling switching differential, 0.5-6KWrite
AV12SpHPrtP50 Protection heating setpoint; 0 = OFF°CWrite
AV13SpCPrtP51 Protection cooling setpoint; 0 = OFF°CWrite
AV14SpCChovrHCP64 changeover switch point, cooling, 10-25°CWrite
AV15SpHChovrHCP65 changeover switch point, heating, 27-40°CWrite
AVmin16SpCmfComfort setpoint, 5-40 (limits P20/P21)°CWrite
AV17FanSpdMaxP72 ECM fan high speed%Write
AV18FanSpdMedP73 ECM fan medium speed%Write
AV19FanSpdMinP74 ECM fan low speed%Write
BI0DInX1Digital input X1Read0=Off, 1=On
BI1InD1Input D1Read0=Off, 1=On
BV0EnHclElClgP40 electric heater in cooling modeWrite0=Disable, 1=Enable
BV1EnFanSttKickP71 fan start kickWrite0=Disable, 1=Enable
BV2EnNFCP81 NFCWrite0=Disable, 1=Enable
BV3EnPwdP82 passwordWrite0=Disable, 1=Enable
BV4ResetParP89 reset parametersWrite0=Disable, 1=Enable
BV5FrcOpModPrtForce Protection modeWrite0=Disable, 1=Enable
BV6ChovrModHeating/cooling changeover via busWrite0=Heating, 1=Cooling
BV7SttUpdCnfStart/update configurationRead0=Update, 1=Start
BV8WndContWindow contact via busWrite0=Open, 1=Close
BV9PscDetPresence detector via busWrite0=Absent, 1=Present
BV10KeycardHotel keycard via busWrite0=No, 1=Yes
MV0PrAplPresent applicationRead1=No application, 2=2-pipe 2-wire on/off valve, 3=2-pipe modulating valve, 4=2-pipe 3-wire on/off valve, 5=2-pipe 3-position valve, 6=2-pipe el. heat 2-wire on/off valve, 7=4-pipe 2-wire on/off valve, 8=4-pipe modulating valve, 9=2-pipe el. heat modulating valve
MVmin1PrOpModPresent operating modeRead1=Protection, 2=Economy, 4=Comfort
MVmin2FanSpdCmdFan speed commandWrite1=Auto, 2=Low speed, 3=Medium speed, 4=High speed
MV3OpStaFanFan operating stateRead1=Automatic, 2=Manual
MV4Fan3SpdThree-speed fan stateRead1=Off, 2=Low speed, 3=Medium speed, 4=High speed
MV5AplP01 applicationWrite1=2-pipe H/C changeover, 2=2-pipe electrical heating coil, 3=4-pipe
MV6CtlSeqP02 control sequenceWrite1=Heating only, 2=Cooling only, 3=H/C changeover auto, 4=H/C changeover manual, 5=Heating and cooling (4-pipe)
MV7FanTypP03 fan typeWrite1=1-speed fan, 2=3-speed fan, 3=ECM fan
MV8ActrTypP04 valve actuator typeWrite1=2-wire on/off, 2=3-wire on/off, 3=3-position, 4=Modulating
MV9OpModSelP10 operating mode selectionWrite1=Comfort, Protection; 2=Comfort, Economy, Protection
MV10DsplyInfoP11 standard displayWrite1=Room temperature, 2=Temperature setpoint, 3=Temperature via bus
MV11TunitP12 temperature unitWrite1=Celsius, 2=Fahrenheit
MV12AddDsplyInfoP14 additional display infoWrite1=Off, 2=Temperature in °C and °F, 3=Temperature setpoint, 4=Time of day am/pm
MV13KeypadP15 keypad lockWrite1=Unlock, 2=Lock except on/off, 3=Lock except setpoint, 4=Lock setpoint, 5=Lock fan, 6=Lock operating mode, 7=Lock all
MV14FanOpZeEgZP30 fan operation in dead zoneWrite1=Disable, 2=Low speed heating and cooling, 3=Low speed cooling only
MV15CnfInX1P60 function of input X1Write1=No input, 2=Room temp external sensor (AI), 3=H/C changeover (AI/DI), 4=Window contact (DI), 5=Fault input (DI), 6=Monitor input (DI), 7=Monitor input (AI), 8=Presence detector (DI), 9=Hotel presence detector (DI), 10=Modulating valve state (AI)
MV16SigTypInX1P61 signal type of input X1Write1=Normally open, 2=Normally closed, 3=NTC 3k, 4=NTC 10k, 5=DC 0-10 V
MV17CnfInD1P62 function of input D1Write1=No input, 2=Not used, 3=H/C changeover, 4=Window contact, 5=Fault input, 6=Monitor input, 7=Not used, 8=Presence detector, 9=Hotel presence detector
MV18PosInD1P63 contact type of input D1Write1=Normally open, 2=Normally closed
MV19OphCnfP75 fan operating hours counterWrite1=Enable, 2=Disable, 3=Reset
MV20RsttAfPwrFailP80 mode after power failureWrite1=Previous operating mode, 2=Comfort mode, 3=Protection mode
MVmin21ROpModSwiRoom operating mode commandWrite1=Protection, 2=Economy, 3=Not used, 4=Comfort, 5=Not used
MV22TestModY1Y2Test mode for outputs Y1/Y2 (10 min)Read1=Released, 2=Y1, Y2 on, 3=Y1, Y2 off, 4=Y1 off, Y2 on, 5=Y1 on, Y2 off
MVmin23FltFaultRead1=No fault, 2=Built-in sensor, 3=Input X1, 4=Input D1, 5=Not used, 6=Sensor X1 defective, 7=Communication
MV24AuHTypP05 auxiliary electric heating type (RDF440BN..)Write1=None, 2=Single stage, 3=2-stage, 4=3-stage el. heating
PIV0OphFanFan operating hours, 0-1999hRead
PIV1TnTCtrP45 temporary Comfort timer, 0-120minWrite
PIV2TiRun0to100P46 actuator running time, 20-300sWrite
PIV3FanKickEcoModP70 fan kick in Economy; 360 = fan keeps runningminWrite
PIV4PwdP83 password, 00-99Write
Object ID lookup: Siemens RDF4..BN point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)

How many BACnet points does the Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) have?

This list has 65 BACnet objects: 2 analog inputs, 20 analog values, 2 binary inputs, 11 binary values, 25 multi-state values, 5 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) BACnet points are writable?

49 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP) BACnet documentation?

The source is RDF4..BN.., RDF4..MB.., RDF440, RDF440-BK Room thermostat Basic Documentation (A6V14153583), revision 2026-08-19, published free by Siemens at https://sid.siemens.com/r/A6V14153583.

What are the minimum BACnet points to integrate the Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)?

Start with MV 21 ROpModSwi (Operating mode: 1 = Protection, 2 = Economy, 4 = Comfort); AV 16 SpCmf (Comfort setpoint, °C); MV 2 FanSpdCmd (Fan speed: 1 = auto, 2-4 = low/med/high); MV 1 PrOpMod (Present operating mode); AI 0 TR (Room temperature); AV 0 SpTR (Active room setpoint); AV 1 HReq (Heating demand, %); AV 2 CReq (Cooling demand, %); MV 23 Flt (Fault, 1 = no fault).

Can the BMS supply sensor values to the Siemens RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)?

AV 4 TRBus takes a room temperature from the bus; MV 10 P11 can show it on the display. Window contact, presence and keycard can also be written via BV 8-10.

How do I check these points on the real RDF4..BN room thermostats RDF400BN / RDF440BN / RDF460BN (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Siemens BACnet points lists

Source: RDF4..BN.., RDF4..MB.., RDF440, RDF440-BK Room thermostat Basic Documentation · A6V14153583 · rev. 2026-08-19. Object names, instances and units are reproduced as published; descriptions are our own.