  3. Siemens
  4. BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)

Heat pump unit controller · BACnet points list

Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) BACnet points list

Updated 28 October 2026

Short answer

Application 6673 runs a multi-stage heat pump on a Siemens BACnet PTEC controller over BACnet MS/TP. The cooling and heating loops stage up to three compressors (or compressors plus electric heat) and switch the reversing valve, and an optional mixed air loop drives an outdoor air damper for ventilation and free cooling. It replaces application 2583 of the older Siemens heat pump controller.

This page lists 102 BACnet objects for the Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) — 89 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)
Equipment
Heat pump unit controller
Equipment type
Heat pumps
BACnet objects
102 (89 writable)
Transport
BACnet MS/TP
Firmware
Newer than revision Bx40
Also known as
PTEC 6673, Application 6673, App 6673, 550-490PA, Siemens PTEC heat pump, Application 2583
Source document
BACnet PTEC Controller Heat Pump - Multi-Compressor with Mixed Air and Reversing Valve Control, Application 6673, Application Note · 140-1150 · rev. 2014-07-17
Download CSV 102 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)

Integration in brief

Address the controller on the BACnet MS/TP trunk (manually or with auto addressing). The BMS commands occupancy with DAY.NGT (BO 29) and the day setpoints, enables free cooling with FREE CLG (BO 23) when outdoor air is suitable, and reads room temperature, fan and compressor status, the heat pump alarm input and the error status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 29DAY.NGTDAY = occupied, NIGHT = unoccupiedCommand
BO 23FREE CLGFree cooling allowed (outdoor air cool enough)Command
AO 6DAY CLG STPTOccupied cooling setpoint, °FCommand
AO 7DAY HTG STPTOccupied heating setpoint, °FCommand
BO 5HEAT.COOLCurrent mode: HEAT or COOLCommand
BO 50FANFan on/offCommand
BO 45COMPRESSOR 1Compressor 1 on/offCommand
AI 4ROOM TEMPSpace temperatureRead
BI 26DI 6Heat pump alarm input, if wired to DI 6Read
AO 99ERROR STATUSController error codeCommand

Enable & remote start

Occupancy is DAY.NGT (BO 29). With a wall switch on DI 2 and WALL SWITCH (BO 18) = YES, the switch sets it; standalone with no switch the controller stays in day mode; on a network the field panel or BMS commands DAY.NGT. NGT OVRD (BO 21) shows a temporary night override from the room unit button.

Sensors & values from the BMS

FREE CLG (BO 23) is set by the field panel to say whether outdoor air is cool enough for free cooling; with it DISABL the damper stays at minimum (day) or closed (night).

Network setup

Watch out for

Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

102 of 102 shown
Type
Access
Show
Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) BACnet Points List
DescriptionStates
AO1CTLR ADDRESSController MS/TP addressCommand
AO2APPLICATIONApplication number running in the controllerCommand
AO3RETURN DELAYRestart delay after power failureminCommand
AImin4ROOM TEMPRoom temperature from the room unit°FRead
BOmin5HEAT.COOLCurrent heating/cooling modeCommand0=COOL, 1=HEAT
AOmin6DAY CLG STPTDay (occupied) cooling setpoint°FCommand
AOmin7DAY HTG STPTDay (occupied) heating setpoint°FCommand
AO8NGT CLG STPTNight (unoccupied) cooling setpoint°FCommand
AO9NGT HTG STPTNight (unoccupied) heating setpoint°FCommand
AO10DMPR MIN POSMixed air damper minimum position%Command
AO11RM STPT MINLowest setpoint allowed from the room unit°FCommand
AO12RM STPT MAXHighest setpoint allowed from the room unit°FCommand
AI13RM STPT DIALSetpoint from the room unit dial or keypad°FRead
BO14STPT DIALUse the room unit setpoint dialCommand0=NO, 1=YES
AI15MA TEMPMixed air temperature°FRead
AO16CMP2 ONLoop output that starts compressor 2%Command
AO17CMP2 OFFLoop output that stops compressor 2%Command
BO18WALL SWITCHWall switch connected to DI 2Command0=NO, 1=YES
BI19DI OVRD SWRoom unit night override buttonRead0=OFF, 1=ON
AO20OVRD TIMENight override durationhCommand
BO21NGT OVRDNight override statusCommand0=DAY, 1=NIGHT
AO22RMTMP OFFSETRoom temperature calibration offset°FCommand
BOmin23FREE CLGFree cooling (economizer) enableCommand0=DISABL, 1=ENABLE
BI24DI 2Digital input 2Read0=OFF, 1=ON
BI25DI 5Digital input 5Read0=OFF, 1=ON
BImin26DI 6Digital input 6Read0=OFF, 1=ON
AO27CMP2 MIN OFFCompressor 2 minimum off timeminCommand
AO28CMP2 MIN ONCompressor 2 minimum on timeminCommand
BOmin29DAY.NGTDay/night (occupancy) modeCommand0=DAY, 1=NIGHT
AO34CMP3 ONLoop output that starts compressor 3%Command
AO35CMP3 OFFLoop output that stops compressor 3%Command
AO36CMP3 MIN OFFCompressor 3 minimum off timeminCommand
AO37CMP3 MIN ONCompressor 3 minimum on timeminCommand
BO38DAMPER TYPEMixed air damper actuator: spring return or floatingCommand0=FLOAT, 1=SPRING
AO39AO DIR.REVAnalog output direction reverse (additive code)Command
AO40AOV1Analog output 1 (0-10 V)VCommand
BO41DO 1Digital output 1Command0=OFF, 1=ON
BO42DO 2Digital output 2Command0=OFF, 1=ON
BO43ELEC HEAT 1Electric heat stage 1 outputCommand0=OFF, 1=ON
BO44REV VALVEReversing valve outputCommand0=COOL, 1=HEAT
BOmin45COMPRESSOR 1Compressor 1 outputCommand0=OFF, 1=ON
BO46EHEAT3.CMP2Electric heat 3 or compressor 2 outputCommand0=OFF, 1=ON
BO47EHEAT2.CMP3Electric heat 2 or compressor 3 outputCommand0=OFF, 1=ON
AO48DMPR COMDDamper position command%Command
AO49DMPR POSDamper position (calculated)%Command
BOmin50FANFan commandCommand0=OFF, 1=ON
AO51MTR TIMINGDamper motor full-stroke timesCommand
AI52AI 3Spare analog input 3%Read
AI53AI 4Spare analog input 4°FRead
AO54AOV2Analog output 2 (0-10 V)VCommand
BI55DI 3Digital input 3Read0=OFF, 1=ON
AO56DMPR ROT ANGDamper rotation angleCommand
BI57DI 4Digital input 4Read0=OFF, 1=ON
AO58MTR SETUPMotor enable/reverse setup (additive code)Command
AO59DO DIR.REVDigital output direction reverse (additive code)Command
BO60CYCLE FANCycle the fan with demand in day modeCommand0=NO, 1=YES
AO61FREE CLG ONCooling loop output that starts free cooling%Command
AO62FREE CLG OFFCooling loop output that stops free cooling%Command
AO63CLG P GAINCooling loop proportional gainCommand
AO64CLG I GAINCooling loop integral gainCommand
AO65STPT SPANRoom unit setpoint adjustment span°FCommand
AO67HTG P GAINHeating loop proportional gainCommand
AO68HTG I GAINHeating loop integral gainCommand
BO69HP DO OVRDAllow BACnet commands to fan, compressor, reversing valveCommand0=DISABL, 1=ENABLE
AO71MA P GAINMixed air loop proportional gainCommand
AO72MA I GAINMixed air loop integral gainCommand
AO73MA D GAINMixed air loop derivative gainCommand
AO74MA BIASMixed air loop bias%Command
AO75CMP TOTLNumber of compressorsCommand
AO76EHTG STG CNTNumber of electric heat stagesCommand
AO78CTL TEMPTemperature the controller is controlling to°FCommand
AO79CLG LOOPOUTCooling loop output%Command
AO80HTG LOOPOUTHeating loop output%Command
AO81EHEAT 1 ONHeating loop output that starts electric heat 1%Command
AO82CMP1 ONLoop output that starts compressor 1%Command
AO83CMP1 OFFLoop output that stops compressor 1%Command
AO84RVAL SWITCHLoop output needed to switch the reversing valve%Command
AO85SWITCH LIMITLoop output below which mode may switch%Command
AO86SWITCH TIMEMinimum time before heat/cool switchoverminCommand
AO87CMP1 MIN OFFCompressor 1 minimum off timeminCommand
AO88CMP1 MIN ONCompressor 1 minimum on timeminCommand
AO89RVAL SW TIMECompressor off time before valve switchsCommand
AO90SWITCH DBANDTemperature deadband for heat/cool switchover°FCommand
BO91NGT MA CTLMixed air control at nightCommand0=NO, 1=YES
AO92CTL STPTActive control setpoint°FCommand
AO93MA SETPTMixed air temperature setpoint°FCommand
AO94EHEAT 2 ONHeating loop output that starts electric heat 2%Command
AO95EHEAT 3 ONHeating loop output that starts electric heat 3%Command
AO96CAL TIMERHours between automatic calibrationshCommand
AO97AOV3Analog output 3 (0-10 V)VCommand
AO98LOOP TIMEControl loop intervalsCommand
AOmin99ERROR STATUSController error status codeCommand
AO101CLG BIASCooling loop bias%Command
AO102HTG BIASHeating loop bias%Command
AO103CLG D GAINCooling loop derivative gainCommand
AO104HTG D GAINHeating loop derivative gainCommand
AO120ENTHALPYRoom enthalpyBtu/lbCommand
AO121DEW POINTRoom dew point°FCommand
BO122PPCL STATEPPCL program loaded or emptyCommand0=EMPTY, 1=LOADED
AI123RM CO2Room CO2ppmRead
AO126SENSOR SELRoom unit / sensor select code (additive)Command
AI127RM RHRoom relative humidity%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)

How many BACnet points does the Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) have?

This list has 102 BACnet objects: 7 analog inputs, 70 analog outputs, 6 binary inputs, 19 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) BACnet points are writable?

89 of the 102 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve) BACnet documentation?

The source is BACnet PTEC Controller Heat Pump - Multi-Compressor with Mixed Air and Reversing Valve Control, Application 6673, Application Note (140-1150), revision 2014-07-17, published free by Siemens at https://sid.siemens.com/api/khub/documents/HepZL2pKvNz58kz_wM7wsw/content.

What are the minimum BACnet points to integrate the Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)?

Start with BO 29 DAY.NGT (DAY = occupied, NIGHT = unoccupied); BO 23 FREE CLG (Free cooling allowed (outdoor air cool enough)); AO 6 DAY CLG STPT (Occupied cooling setpoint, °F); AO 7 DAY HTG STPT (Occupied heating setpoint, °F); BO 5 HEAT.COOL (Current mode: HEAT or COOL); BO 50 FAN (Fan on/off); BO 45 COMPRESSOR 1 (Compressor 1 on/off); AI 4 ROOM TEMP (Space temperature); BI 26 DI 6 (Heat pump alarm input, if wired to DI 6); AO 99 ERROR STATUS (Controller error code).

How do I enable BMS control of the Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)?

Occupancy is DAY.NGT (BO 29). With a wall switch on DI 2 and WALL SWITCH (BO 18) = YES, the switch sets it; standalone with no switch the controller stays in day mode; on a network the field panel or BMS commands DAY.NGT. NGT OVRD (BO 21) shows a temporary night override from the room unit button.

Can the BMS supply sensor values to the Siemens BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)?

FREE CLG (BO 23) is set by the field panel to say whether outdoor air is cool enough for free cooling; with it DISABL the damper stays at minimum (day) or closed (night).

How do I check these points on the real BACnet PTEC Heat Pump Controller - Application 6673 (Multi-Compressor, Mixed Air, Reversing Valve)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.