Variable frequency drive (HVAC) · BACnet points list

Siemens BT300 HVAC drive (BACnet) BACnet points list

Updated 28 October 2026

Short answer

The BT300 is Siemens' HVAC drive for fans and pumps, with BACnet MS/TP built in; the PICS also lists BACnet IP. It exposes 133 fixed objects: start/stop, enable, direction and reset commands as Binary Outputs, a speed reference and drive readings as Analog Values, fault history, PID values, bypass status and configurable fieldbus data objects.

This page lists 133 BACnet objects for the Siemens BT300 HVAC drive (BACnet) — 43 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
BT300 HVAC drive (BACnet)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
133 (43 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
BACnet application software 1.1, firmware 1.1
Also known as
BT300, Siemens BT300, BT300 VFD, BT300 frequency converter, BT300 HVAC drive
Source document
Siemens BT300 BACnet Protocol Implementation Conformance Statement (PICS) · rev. 2015-12-28
Download CSV 133 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Siemens BT300 HVAC drive (BACnet)

Integration in brief

Write BO 4 to start and stop, keep BO 3 run enable on, and send the speed reference to AV 0 in percent. Read BV 2 running status, AV 3 output frequency, AV 5 current and BV 4 fault, and reset trips with BO 6. BV 30 FB CONTROL and BV 31 FB REFERENCE select fieldbus control and reference; check the BT300 manual for how the drive must be set.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 4CMD RUN STOPStart/stop from the BMSCommand
BO 3RUN ENABLERun enable; must be on to runCommand
AV 0SPEED REFSpeed reference in %Command
BO 6FAULT RESETReset a tripped driveWrite
BV 2RUNSTP STATRunning statusRead
AV 3OUTPUT FREQOutput frequency in HzRead
AV 5MOTOR CRRNTMotor ampsRead
AV 10KW HOURSEnergy counter, kWhRead
BV 4FAULT STATUSAny active drive faultRead
AV 16ACTIVE FAULTActive fault codeRead

Enable & remote start

BO 4 CMD RUN STOP starts and stops the drive and BO 3 RUN ENABLE must be enabled. BV 30 FB CONTROL and BV 31 FB REFERENCE are writable selectors for fieldbus control and reference; the PICS does not explain them, so confirm the control place and reference source settings in the BT300 manual.

Network setup

Watch out for

Siemens BT300 HVAC drive (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

133 of 133 shown
Type
Access
Show
Siemens BT300 HVAC drive (BACnet) BACnet Points List
DescriptionStates
AI0ANALOG IN 1Drive analog input 1Read
AI1ANALOG IN 2Drive analog input 2Read
AO0ANALOG OUT 1Drive analog output 1Command
AVmin0SPEED REFSpeed reference from the BMS, %%Command
AV1FREQ STPTFrequency setpoint in useHzRead
AV2OUTPUT PCTOutput as % of range%Read
AVmin3OUTPUT FREQOutput frequencyHzRead
AV4MOTOR SPEEDMotor speedrpmRead
AVmin5MOTOR CRRNTMotor currentARead
AV6MOTOR VLTGMotor voltageVRead
AV7MOTOR TORQUEMotor torque%Read
AV8MOTOR TEMPCalculated motor temperature%Read
AV9LOADMotor load%Read
AVmin10KW HOURSEnergy counterkWhRead
AV11KW HOURS TOTTotal energy counterkWhRead
AV12OPER DAYSOperating daysdaysRead
AV13OPER HOURSOperating hourshRead
AV14DC LINK VLTGDC link voltageVRead
AV15DRIVE TEMPDrive (heatsink) temperature°CRead
AVmin16ACTIVE FAULTActive fault codeRead
AV17LAST FAULT 1Most recent faultRead
AV18LAST FAULT 2Second most recent faultRead
AV19LAST FAULT 3Third most recent faultRead
AV20FBDATAOUT 01Fieldbus process data out (configurable)Read
AV21FBDATAOUT 02Fieldbus process data out (configurable)Read
AV22FBDATAOUT 03Fieldbus process data out (configurable)Read
AV23FBDATAOUT 04Fieldbus process data out (configurable)Read
AV24FBDATAOUT 05Fieldbus process data out (configurable)Read
AV25FBDATAOUT 06Fieldbus process data out (configurable)Read
AV26FBDATAOUT 07Fieldbus process data out (configurable)Read
AV27FBDATAOUT 08Fieldbus process data out (configurable)Read
AV28FB DATA IN 1Fieldbus process data in (configurable)Command
AV29FB DATA IN 2Fieldbus process data in (configurable)Command
AV30FB DATA IN 3Fieldbus process data in (configurable)Command
AV31FB DATA IN 4Fieldbus process data in (configurable)Command
AV32FB DATA IN 5Fieldbus process data in (configurable)Command
AV33FB DATA IN 6Fieldbus process data in (configurable)Command
AV34FB DATA IN 7Fieldbus process data in (configurable)Command
AV35FB DATA IN 8Fieldbus process data in (configurable)Command
AV36FBCTRLWORDLOFieldbus control word, lowCommand
AV37FBCTRLWORDHIFieldbus control word, highCommand
AV38FBSTATWORDLOFieldbus status word, lowRead
AV39FBSTATWORDHIFieldbus status word, highRead
AV40MIN FREQMinimum frequencyHzWrite
AV41MAX FREQMaximum frequencyHzWrite
AV42ACCEL TIMEAcceleration timesWrite
AV43DECEL TIMEDeceleration timesWrite
AV44CURRENT LMTCurrent limit (units listed as enum 3, amperes)AWrite
AV45MTRNOM CRRNTMotor nominal currentAWrite
AV46MTRNOM POWERMotor nominal powerhpWrite
AV47MTRNOM SPEEDMotor nominal speedrpmWrite
AV48MTRNOM VLTGMotor nominal voltageVWrite
AV49MTRNOM FREQMotor nominal frequencyHzWrite
AV50MOTOR COSPHIMotor power factor (cos phi)Write
AV51BYPASSBypass stateRead
AV52BYP SAFESTATBypass safety statusRead
AV53BYP RUN TIMEBypass run timeRead
AV54PID1 GAINPID controller 1 value%Read
AV55PID1 I TIMEPID controller 1 valuesRead
AV56PID1 D TIMEPID controller 1 valuesRead
AV57PID1 STATUSPID controller 1 valueRead
AV58PID1 STPTPID controller 1 valueRead
AV59PID1 FDBKPID controller 1 valueRead
AV60PID1 OUTPUTPID controller 1 value%Read
AV61PID2 GAINPID controller 2 valueRead
AV62PID2 I TIMEPID controller 2 valuesRead
AV63PID2 D TIMEPID controller 2 valuesRead
AV64PID2 STATUSPID controller 2 valueRead
AV65PID2 STPTPID controller 2 valueRead
AV66PID2 FDBKPID controller 2 valueRead
AV67PID2 OUTPUTPID controller 2 value%Read
AV68ANY PARAMParameter number for generic accessWrite
AV69ANY VALUEValue of the parameter set in AV 68Write
BI0DI1 STATUSDigital input statusRead0=OFF, 1=ON
BI1DI2 STATUSDigital input statusRead0=OFF, 1=ON
BI2DI3 STATUSDigital input statusRead0=OFF, 1=ON
BI3DI4 STATUSDigital input statusRead0=OFF, 1=ON
BI4DI5 STATUSDigital input statusRead0=OFF, 1=ON
BI5DI6 STATUSDigital input statusRead0=OFF, 1=ON
BO0RO1 CMDRelay output 1 commandCommand0=OFF, 1=ON
BO1RO2 CMDRelay output 2 commandCommand0=OFF, 1=ON
BO2RO3 CMDRelay output 3 commandCommand0=OFF, 1=ON
BOmin3RUN ENABLERun enable from the BMSCommand0=DISABL, 1=ENABLE
BOmin4CMD RUN STOPStart/stop commandCommand0=STOP, 1=RUN
BO5CMD FWD REVDirection commandCommand0=FORWRD, 1=REVRSE
BOmin6FAULT RESETFault reset commandWrite0=NORMAL, 1=RESET
BV0READY STATEDrive readyRead0=NOTRDY, 1=READY
BV1RUNENBL STATRun enable statusRead0=DISABL, 1=ENABLE
BVmin2RUNSTP STATRunning statusRead0=STOP, 1=RUN
BV3FWD REV STATDirection statusRead0=FORWRD, 1=REVRSE
BVmin4FAULT STATUSFault activeRead0=NOFLT, 1=FAULT
BV5ALARM STATUSAlarm (warning) activeRead0=NORMAL, 1=ALARM
BV6AT ZEROOutput at zero speedRead0=FALSE, 1=TRUE
BV7AT SETPOINTOutput at setpointRead0=FALSE, 1=TRUE
BV8RO1 STATUSRelay output statusRead0=OFF, 1=ON
BV9RO2 STATUSRelay output statusRead0=OFF, 1=ON
BV10RO3 STATUSRelay output statusRead0=OFF, 1=ON
BV11M1 STATUSMotor 1 contactor stateRead0=OPEN, 1=CLOSED
BV12M2 STATUSMotor 2 contactor stateRead0=OPEN, 1=CLOSED
BV13FBDATAOUT1B0Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV14FBDATAOUT1B1Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV15FBDATAOUT1B2Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV16FBDATAOUT1B3Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV17FBDATAOUT1B4Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV18FBDATAOUT1B5Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV19FBDATAOUT1B6Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV20FBDATAOUT1B7Bit of fieldbus process data out 1Read0=OFF, 1=ON
BV21FBCNTRLBIT10Fieldbus control word bitCommand0=OFF, 1=ON
BV22FBCNTRLBIT11Fieldbus control word bitCommand0=OFF, 1=ON
BV23FBCNTRLBIT12Fieldbus control word bitCommand0=OFF, 1=ON
BV24FBCNTRLBIT13Fieldbus control word bitCommand0=OFF, 1=ON
BV25FBCNTRLBIT14Fieldbus control word bitCommand0=OFF, 1=ON
BV26FBCNTRLBIT15Fieldbus control word bitCommand0=OFF, 1=ON
BV27COAST2STOPCoast-to-stop commandWrite0=READY, 1=YES
BV28RAMP2STOPRamp-to-stop commandWrite0=READY, 1=YES
BV29QUICK STOPQuick stop commandWrite0=READY, 1=YES
BV30FB CONTROLFieldbus control selectCommand0=OFF, 1=ON
BV31FB REFERENCEFieldbus reference selectCommand0=OFF, 1=ON
BV32INTERLOCK 1Interlock input statusRead0=OFF, 1=ON
BV33INTERLOCK 2Interlock input statusRead0=OFF, 1=ON
BV34ENERGY OPTEnergy optimisation statusRead0=OFF, 1=ON
BV35AUTO RESETAuto reset statusRead0=OFF, 1=ON
BV36FIREMODESTATFire mode statusRead0=INACTV, 1=ACTIVE
BV37BYP ACTIVEBypass activeRead0=INACTV, 1=ACTIVE
BV38BYP RUNNINGBypass runningRead0=NO, 1=YES
BV39REM SAFETY 1Remote safety input statusRead0=NOFLT, 1=FAULT
BV40REM SAFETY 2Remote safety input statusRead0=NOFLT, 1=FAULT
BV41REM SAFETY 3Remote safety input statusRead0=NOFLT, 1=FAULT
BV42REM SAFETY 4Remote safety input statusRead0=NOFLT, 1=FAULT
BV43REM SAFETY 5Remote safety input statusRead0=NOFLT, 1=FAULT
BV44REM SAFETY 6Remote safety input statusRead0=NOFLT, 1=FAULT
BV45REM SAFETY 7Remote safety input statusRead0=NOFLT, 1=FAULT
BV46REM SAFETY 8Remote safety input statusRead0=NOFLT, 1=FAULT

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BT300 HVAC drive (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens BT300 HVAC drive (BACnet)

How many BACnet points does the Siemens BT300 HVAC drive (BACnet) have?

This list has 133 BACnet objects: 2 analog inputs, 1 analog output, 70 analog values, 6 binary inputs, 7 binary outputs, 47 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens BT300 HVAC drive (BACnet) BACnet points are writable?

43 of the 133 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Siemens BT300 HVAC drive (BACnet) BACnet documentation?

The source is Siemens BT300 BACnet Protocol Implementation Conformance Statement (PICS), revision 2015-12-28, published free by Siemens at https://www.bacnetinternational.net/catalog/manu/siemens/Siemens_BT300_PICS_20151228.pdf.

What are the minimum BACnet points to integrate the Siemens BT300 HVAC drive (BACnet)?

Start with BO 4 CMD RUN STOP (Start/stop from the BMS); BO 3 RUN ENABLE (Run enable; must be on to run); AV 0 SPEED REF (Speed reference in %); BO 6 FAULT RESET (Reset a tripped drive); BV 2 RUNSTP STAT (Running status); AV 3 OUTPUT FREQ (Output frequency in Hz); AV 5 MOTOR CRRNT (Motor amps); AV 10 KW HOURS (Energy counter, kWh); BV 4 FAULT STATUS (Any active drive fault); AV 16 ACTIVE FAULT (Active fault code).

How do I enable BMS control of the Siemens BT300 HVAC drive (BACnet)?

BO 4 CMD RUN STOP starts and stops the drive and BO 3 RUN ENABLE must be enabled. BV 30 FB CONTROL and BV 31 FB REFERENCE are writable selectors for fieldbus control and reference; the PICS does not explain them, so confirm the control place and reference source settings in the BT300 manual.

How do I check these points on the real BT300 HVAC drive (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Siemens BACnet points lists

Source: Siemens BT300 BACnet Protocol Implementation Conformance Statement (PICS) · rev. 2015-12-28. Object names, instances and units are reproduced as published; descriptions are our own.