 "manufacturer": "Siemens",
 "manufacturer_slug": "siemens",
 "model": "BT300 HVAC drive (BACnet)",
 "model_slug": "bt300",
 "aliases": [
  "BT300",
  "Siemens BT300",
  "BT300 VFD",
  "BT300 frequency converter",
  "BT300 HVAC drive"
 ],
 "equipment_type": "Variable frequency drive (HVAC)",
 "applies_to": "Siemens Building Technologies BT300 HVAC variable frequency drives, all voltage and power ranges, BACnet firmware 1.1.",
 "summary": "The BT300 is Siemens' HVAC drive for fans and pumps, with BACnet MS/TP built in; the PICS also lists BACnet IP. It exposes 133 fixed objects: start/stop, enable, direction and reset commands as Binary Outputs, a speed reference and drive readings as Analog Values, fault history, PID values, bypass status and configurable fieldbus data objects.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": "BACnet application software 1.1, firmware 1.1",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Access comes from each object's present-value entry in the PICS; writable objects with a priority array are shown as commandable.",
  "The summary table spells 'Binray Input'; BI 0-5 are the drive's digital inputs.",
  "FBDATAOUT and FB DATA IN objects carry whatever process data the drive is set up to map; the PICS does not say what.",
  "AV 44 CURRENT LMT lists its units as enumeration 3, which is amperes in BACnet.",
  "MS/TP baud rates 9600, 19200, 38400 and 76800; on BACnet IP it can register as a foreign device (it is not a BBMD).",
  "AV 40-50 are drive parameters (limits, ramps, motor nameplate); writing them changes the drive setup."
 ],
 "source": {
  "title": "Siemens BT300 BACnet Protocol Implementation Conformance Statement (PICS)",
  "doc_number": null,
  "revision_date": "2015-12-28",
  "url": "https://www.bacnetinternational.net/catalog/manu/siemens/Siemens_BT300_PICS_20151228.pdf"
 },
 "integration": {
  "summary": "Write BO 4 to start and stop, keep BO 3 run enable on, and send the speed reference to AV 0 in percent. Read BV 2 running status, AV 3 output frequency, AV 5 current and BV 4 fault, and reset trips with BO 6. BV 30 FB CONTROL and BV 31 FB REFERENCE select fieldbus control and reference; check the BT300 manual for how the drive must be set.",
  "minimum_points": [
   {
    "ref": "BO 4",
    "name": "CMD RUN STOP",
    "why": "Start/stop from the BMS"
   },
   {
    "ref": "BO 3",
    "name": "RUN ENABLE",
    "why": "Run enable; must be on to run"
   },
   {
    "ref": "AV 0",
    "name": "SPEED REF",
    "why": "Speed reference in %"
   },
   {
    "ref": "BO 6",
    "name": "FAULT RESET",
    "why": "Reset a tripped drive"
   },
   {
    "ref": "BV 2",
    "name": "RUNSTP STAT",
    "why": "Running status"
   },
   {
    "ref": "AV 3",
    "name": "OUTPUT FREQ",
    "why": "Output frequency in Hz"
   },
   {
    "ref": "AV 5",
    "name": "MOTOR CRRNT",
    "why": "Motor amps"
   },
   {
    "ref": "AV 10",
    "name": "KW HOURS",
    "why": "Energy counter, kWh"
   },
   {
    "ref": "BV 4",
    "name": "FAULT STATUS",
    "why": "Any active drive fault"
   },
   {
    "ref": "AV 16",
    "name": "ACTIVE FAULT",
    "why": "Active fault code"
   }
  ],
  "enable": "BO 4 CMD RUN STOP starts and stops the drive and BO 3 RUN ENABLE must be enabled. BV 30 FB CONTROL and BV 31 FB REFERENCE are writable selectors for fieldbus control and reference; the PICS does not explain them, so confirm the control place and reference source settings in the BT300 manual.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet MS/TP master at 9600, 19200, 38400 or 76800 baud; BACnet IP (with foreign device registration) is also listed in the PICS.",
   "No default device instance is given in the PICS.",
   "Max masters and max info frames exist on MS/TP only."
  ],
  "gotchas": [
   "AV 40-50 change drive limits, ramps and motor data; don't write them cyclically.",
   "FBDATAOUT / FB DATA IN contents depend on the drive's process data mapping.",
   "BO 5 CMD FWD REV active state is REVRSE; leave it off for normal fan and pump rotation."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "ANALOG IN 1",
   "description": "Drive analog input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "ANALOG IN 2",
   "description": "Drive analog input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "ANALOG OUT 1",
   "description": "Drive analog output 1",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "SPEED REF",
   "description": "Speed reference from the BMS, %",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "FREQ STPT",
   "description": "Frequency setpoint in use",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "OUTPUT PCT",
   "description": "Output as % of range",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "OUTPUT FREQ",
   "description": "Output frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "MOTOR SPEED",
   "description": "Motor speed",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "MOTOR CRRNT",
   "description": "Motor current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "MOTOR VLTG",
   "description": "Motor voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "MOTOR TORQUE",
   "description": "Motor torque",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "MOTOR TEMP",
   "description": "Calculated motor temperature",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "LOAD",
   "description": "Motor load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "KW HOURS",
   "description": "Energy counter",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "KW HOURS TOT",
   "description": "Total energy counter",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "OPER DAYS",
   "description": "Operating days",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "OPER HOURS",
   "description": "Operating hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "DC LINK VLTG",
   "description": "DC link voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "DRIVE TEMP",
   "description": "Drive (heatsink) temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "ACTIVE FAULT",
   "description": "Active fault code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "LAST FAULT 1",
   "description": "Most recent fault",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "LAST FAULT 2",
   "description": "Second most recent fault",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "LAST FAULT 3",
   "description": "Third most recent fault",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "FBDATAOUT 01",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "FBDATAOUT 02",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "FBDATAOUT 03",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "FBDATAOUT 04",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "FBDATAOUT 05",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "FBDATAOUT 06",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "FBDATAOUT 07",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "FBDATAOUT 08",
   "description": "Fieldbus process data out (configurable)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "FB DATA IN 1",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "FB DATA IN 2",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "FB DATA IN 3",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "FB DATA IN 4",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "FB DATA IN 5",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "FB DATA IN 6",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "FB DATA IN 7",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "FB DATA IN 8",
   "description": "Fieldbus process data in (configurable)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "FBCTRLWORDLO",
   "description": "Fieldbus control word, low",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "FBCTRLWORDHI",
   "description": "Fieldbus control word, high",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "FBSTATWORDLO",
   "description": "Fieldbus status word, low",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "FBSTATWORDHI",
   "description": "Fieldbus status word, high",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "MIN FREQ",
   "description": "Minimum frequency",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "MAX FREQ",
   "description": "Maximum frequency",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "ACCEL TIME",
   "description": "Acceleration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "DECEL TIME",
   "description": "Deceleration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "CURRENT LMT",
   "description": "Current limit (units listed as enum 3, amperes)",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "MTRNOM CRRNT",
   "description": "Motor nominal current",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "MTRNOM POWER",
   "description": "Motor nominal power",
   "units": "hp",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "MTRNOM SPEED",
   "description": "Motor nominal speed",
   "units": "rpm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "MTRNOM VLTG",
   "description": "Motor nominal voltage",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "MTRNOM FREQ",
   "description": "Motor nominal frequency",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "MOTOR COSPHI",
   "description": "Motor power factor (cos phi)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "BYPASS",
   "description": "Bypass state",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "BYP SAFESTAT",
   "description": "Bypass safety status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "BYP RUN TIME",
   "description": "Bypass run time",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "PID1 GAIN",
   "description": "PID controller 1 value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "PID1 I TIME",
   "description": "PID controller 1 value",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "PID1 D TIME",
   "description": "PID controller 1 value",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "PID1 STATUS",
   "description": "PID controller 1 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "PID1 STPT",
   "description": "PID controller 1 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "PID1 FDBK",
   "description": "PID controller 1 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "PID1 OUTPUT",
   "description": "PID controller 1 value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "PID2 GAIN",
   "description": "PID controller 2 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "PID2 I TIME",
   "description": "PID controller 2 value",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "PID2 D TIME",
   "description": "PID controller 2 value",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "PID2 STATUS",
   "description": "PID controller 2 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "PID2 STPT",
   "description": "PID controller 2 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "PID2 FDBK",
   "description": "PID controller 2 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "PID2 OUTPUT",
   "description": "PID controller 2 value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "ANY PARAM",
   "description": "Parameter number for generic access",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "ANY VALUE",
   "description": "Value of the parameter set in AV 68",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "DI1 STATUS",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "DI2 STATUS",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "DI3 STATUS",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "DI4 STATUS",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "DI5 STATUS",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "DI6 STATUS",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "RO1 CMD",
   "description": "Relay output 1 command",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "RO2 CMD",
   "description": "Relay output 2 command",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "RO3 CMD",
   "description": "Relay output 3 command",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "RUN ENABLE",
   "description": "Run enable from the BMS",
   "units": "",
   "access": "C",
   "states": "0=DISABL, 1=ENABLE"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "CMD RUN STOP",
   "description": "Start/stop command",
   "units": "",
   "access": "C",
   "states": "0=STOP, 1=RUN"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "CMD FWD REV",
   "description": "Direction command",
   "units": "",
   "access": "C",
   "states": "0=FORWRD, 1=REVRSE"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "FAULT RESET",
   "description": "Fault reset command",
   "units": "",
   "access": "W",
   "states": "0=NORMAL, 1=RESET"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "READY STATE",
   "description": "Drive ready",
   "units": "",
   "access": "R",
   "states": "0=NOTRDY, 1=READY"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "RUNENBL STAT",
   "description": "Run enable status",
   "units": "",
   "access": "R",
   "states": "0=DISABL, 1=ENABLE"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "RUNSTP STAT",
   "description": "Running status",
   "units": "",
   "access": "R",
   "states": "0=STOP, 1=RUN"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "FWD REV STAT",
   "description": "Direction status",
   "units": "",
   "access": "R",
   "states": "0=FORWRD, 1=REVRSE"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "FAULT STATUS",
   "description": "Fault active",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "ALARM STATUS",
   "description": "Alarm (warning) active",
   "units": "",
   "access": "R",
   "states": "0=NORMAL, 1=ALARM"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "AT ZERO",
   "description": "Output at zero speed",
   "units": "",
   "access": "R",
   "states": "0=FALSE, 1=TRUE"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "AT SETPOINT",
   "description": "Output at setpoint",
   "units": "",
   "access": "R",
   "states": "0=FALSE, 1=TRUE"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "RO1 STATUS",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "RO2 STATUS",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "RO3 STATUS",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "M1 STATUS",
   "description": "Motor 1 contactor state",
   "units": "",
   "access": "R",
   "states": "0=OPEN, 1=CLOSED"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "M2 STATUS",
   "description": "Motor 2 contactor state",
   "units": "",
   "access": "R",
   "states": "0=OPEN, 1=CLOSED"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "FBDATAOUT1B0",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "FBDATAOUT1B1",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "FBDATAOUT1B2",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "FBDATAOUT1B3",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "FBDATAOUT1B4",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "FBDATAOUT1B5",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "FBDATAOUT1B6",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "FBDATAOUT1B7",
   "description": "Bit of fieldbus process data out 1",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "FBCNTRLBIT10",
   "description": "Fieldbus control word bit",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "FBCNTRLBIT11",
   "description": "Fieldbus control word bit",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "FBCNTRLBIT12",
   "description": "Fieldbus control word bit",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "FBCNTRLBIT13",
   "description": "Fieldbus control word bit",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "FBCNTRLBIT14",
   "description": "Fieldbus control word bit",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "FBCNTRLBIT15",
   "description": "Fieldbus control word bit",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "COAST2STOP",
   "description": "Coast-to-stop command",
   "units": "",
   "access": "W",
   "states": "0=READY, 1=YES"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "RAMP2STOP",
   "description": "Ramp-to-stop command",
   "units": "",
   "access": "W",
   "states": "0=READY, 1=YES"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "QUICK STOP",
   "description": "Quick stop command",
   "units": "",
   "access": "W",
   "states": "0=READY, 1=YES"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "FB CONTROL",
   "description": "Fieldbus control select",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "FB REFERENCE",
   "description": "Fieldbus reference select",
   "units": "",
   "access": "C",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "INTERLOCK 1",
   "description": "Interlock input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "INTERLOCK 2",
   "description": "Interlock input status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "ENERGY OPT",
   "description": "Energy optimisation status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "AUTO RESET",
   "description": "Auto reset status",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "FIREMODESTAT",
   "description": "Fire mode status",
   "units": "",
   "access": "R",
   "states": "0=INACTV, 1=ACTIVE"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "BYP ACTIVE",
   "description": "Bypass active",
   "units": "",
   "access": "R",
   "states": "0=INACTV, 1=ACTIVE"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "BYP RUNNING",
   "description": "Bypass running",
   "units": "",
   "access": "R",
   "states": "0=NO, 1=YES"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "REM SAFETY 1",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "REM SAFETY 2",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "REM SAFETY 3",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "REM SAFETY 4",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "REM SAFETY 5",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "REM SAFETY 6",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "REM SAFETY 7",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "REM SAFETY 8",
   "description": "Remote safety input status",
   "units": "",
   "access": "R",
   "states": "0=NOFLT, 1=FAULT"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/siemens/bt300",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}