Networked room thermostat · BACnet points list

Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) BACnet points list

Updated 28 October 2026

Short answer

The RDY2000BN is a touchscreen commercial thermostat with BACnet MS/TP built in. It stages up to three cooling and three heating stages from its relays, has four configurable inputs and three configurable auxiliary outputs, and holds its own weekly schedule. The conventional (14900) and heat pump (14901) applications expose the same 136 objects; SystemType selects between them.

This page lists 136 BACnet objects for the Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) — 87 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)
Equipment
Networked room thermostat
Equipment type
Thermostats, sensors & meters
BACnet objects
136 (87 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
4194303
Also known as
RDY2000BN, RDY2000, Application 14900, Application 14901
Source document
RDY2000BN BACnet Thermostat Conventional Application 14900 Application Note · 140-1231 · rev. 2020-02-11
Download CSV 136 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)

Integration in brief

Set the MS/TP MAC address and baud rate, then command the system mode with HeatCoolMode (MV 23) and occupancy with SchedMode (MV 24), and adjust the comfort setpoints. Read the effective mode, room operating mode and IndoorTmpEff for status, and ExtFault and OverCurrent for alarms. Write at a priority higher than 16.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 23HeatCoolModeCool, heat, auto or off; factory default is OffCommand
MV 24SchedModeComfort, economy or protect (occupancy)Command
BV 0FanModeFan Auto or ManualCommand
AV 32ComfortClgSPOccupied cooling setpointWrite
AV 33ComfortHtgSPOccupied heating setpointWrite
MV 25ModeEffCurrent mode: cooling, heating or offRead
MV 26RM OP MODECurrent room operating modeRead
AV 52IndoorTmpEffRoom temperature used for controlRead
BV 18ExtFaultExternal fault input activeRead
BV 25OverCurrentRelays shut off on overcurrentRead

Enable & remote start

HeatCoolMode (MV 23) is the system mode command; its factory Relinquish_Default is Off, so the unit will not heat or cool until it is commanded or the default is changed. SchedMode (MV 24) sets Comfort, Economy or Protect; the internal schedule writes it too, and an occupancy input forces Comfort.

Sensors & values from the BMS

A universal input can be set as a voltage input, taken out of service and written from the network, so a BMS value can stand in for a physical sensor (for example IndoorTmpRmt with Input1-4 = InTemRem). IndoorTmpEff then uses that value alone or averaged with the built-in sensor.

Network setup

Watch out for

Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

136 of 136 shown
Type
Multi-state
Access
Show
Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) BACnet Points List
DescriptionStates
DEV4194303RDYDevice objectRead
AI0UI1.NTC10KUniversal input 1 as 10K NTC (troubleshooting only)°FRead
AI1UI1.10VUniversal input 1 as 0-10 V (troubleshooting only)°FRead
AI2UI2.NTC10KUniversal input 2 as 10K NTC (troubleshooting only)°FRead
AI3UI2.10VUniversal input 2 as 0-10 V (troubleshooting only)°FRead
AI4UI3.NTC10KUniversal input 3 as 10K NTC (troubleshooting only)°FRead
AI5UI3.10VUniversal input 3 as 0-10 V (troubleshooting only)°FRead
AI6UI4.NTC10KUniversal input 4 as 10K NTC (troubleshooting only)°FRead
AI7UI4.10VUniversal input 4 as 0-10 V (troubleshooting only)°FRead
AI8OnbrdTmpBuilt-in temperature sensor°FRead
AI9OnbrdRHBuilt-in humidity sensor%RHRead
BI0DI1Digital input 1Read0=DI1 inactive, 1=DI1 active
BI1DI2Digital input 2Read0=DI2 Inactive, 1=DI2 active
BI2DI3Digital input 3Read0=DI3 Inactive, 1=DI3 active
BI3DI4Digital input 4Read0=DI4 Inactive, 1=DI4 active
BO0O/BO/B relay outputCommand0=RelayOff, 1=Relay On
BO1FanCmdFan relay (G)Command0=RelayOff, 1=Relay On
BO2Y1Cooling stage 1 relayCommand0=RelayOff, 1=Relay On
BO3Y2Cooling stage 2 relayCommand0=RelayOff, 1=Relay On
BO4W1Heating stage 1 relayCommand0=RelayOff, 1=Relay On
BO5W2Heating stage 2 relayCommand0=RelayOff, 1=Relay On
BO6AuxOutput1Auxiliary relay OUT1Command0=RelayOff, 1=Relay On
BO7AuxOutput2Auxiliary relay OUT2Command0=RelayOff, 1=Relay On
BO8AuxOutput3Auxiliary relay OUT3Command0=RelayOff, 1=Relay On
AV0HmdySpHumidification setpoint (aux output = Humid)%RHWrite
AV1DeHmdySpDehumidification setpoint (aux output = Dehumid)%RHWrite
AV2CO2SetpointCO2 setpoint (aux output = AirQual, CO2 input)ppmWrite
AV3ChgOvrDBMinimum gap between heating and cooling setpoints°FWrite
AV4TmpOffsetRoom temperature calibration offset°FWrite
AV5ChgOvrDlyDelay before auto heat/cool changeoverminWrite
AV6MinOnTimeHtHeating minimum on timeminWrite
AV7MinOffTimeHtHeating minimum off timeminWrite
AV8MinOffTimeClCooling minimum off timeminWrite
AV9MinOnTimeClCooling minimum on timeminWrite
AV10OccMinRunOccupied minimum run timeminWrite
AV11StgDlyHtHeating stage-up delayminWrite
AV12StgDlyClCooling stage-up delayminWrite
AV13HeatStgNumber of heating stagesWrite
AV14AuxHeatStgNumber of auxiliary heat stagesWrite
AV15HrsOvrRideLocal setpoint override durationhWrite
AV16UvLampSrvcUV lamp service intervaldaysWrite
AV17HmdfrSrvcHumidifier service intervaldaysWrite
AV18FilterSrvcFilter service intervaldaysWrite
AV19BackLightDisplay backlight timesWrite
AV20TmpIn1LowInput 1 scaling, low end°FWrite
AV21TmpIn1HighInput 1 scaling, high end°FWrite
AV22TmpIn2LowInput 2 scaling, low end°FWrite
AV23TmpIn2HighInput 2 scaling, high end°FWrite
AV24TmpIn3LowInput 3 scaling, low end°FWrite
AV25TmpIn3HighInput 3 scaling, high end°FWrite
AV26TmpIn4LowInput 4 scaling, low end°FWrite
AV27TmpIn4HighInput 4 scaling, high end°FWrite
AV28InstallPWInstaller menu passwordWrite
AV29ExpertPWExpert menu passwordWrite
AV30HeatingSpEffective heating setpoint in use°FRead
AV31CoolingSpEffective cooling setpoint in use°FRead
AVmin32ComfortClgSPComfort (occupied) cooling setpoint°FWrite
AVmin33ComfortHtgSPComfort (occupied) heating setpoint°FWrite
AV34EconClgSPEconomy cooling setpoint°FWrite
AV35EconHtgSPEconomy heating setpoint°FWrite
AV36CoolStgNumber of cooling stagesWrite
AV37PreOcpyPrgPre-occupancy purge timehWrite
AV38MS/TP MACMS/TP MAC addressWrite
AV39ProtClgSPProtection cooling setpoint°FWrite
AV40ProtHtgSPProtection heating setpoint°FWrite
AV41UnitNumberUnit numberWrite
AV42HEAT LIMITHighest heating setpoint allowed°FWrite
AV43COOL LIMITLowest cooling setpoint allowed°FWrite
AV44APPLICATIONApplication number (write SystemType to change)Read
AV45IndoorTmpRmtRemote indoor temperature (input set to InTemRem)°FRead
AV46CO2CO2 reading (input set to CO2 0-10)ppmRead
AV47SupplyTmpSupply air temperature (input set to Sup Temp)°FRead
AV48ReturnTmpReturn air temperature (input set to Ret Temp)°FRead
AV49OutDoorTmpOutdoor temperature (input set to Out Temp)°FRead
AV50IndoorTmpAvgAverage of remote and built-in temperature°FRead
AV51HumidityHumidity reading (input set to Hum 0-10)%RHRead
AVmin52IndoorTmpEffEffective room temperature used for control°FRead
AV53FanRunTimeFan run timeminRead
BVmin0FanModeFan mode: Auto or ManualCommand0=Auto, 1=Manual
BV1RevValveModeReversing valve energized in cooling or heatingWrite0=Cooling, 1=Heating
BV2SemiContFanFan runs continuously when occupiedWrite0=No, 1=Yes
BV3FanOprHeating fan control: gas or electricWrite0=Gas, 1=Electric
BV4Eco_MstEnEconomizer master enableWrite0=Disabled, 1=Enabled
BV5Eco_MstCtrlEconomizer master controlWrite0=Disabled, 1=Enabled
BV6HumidityIndpHumidity control independent of fanWrite0=No, 1=Yes
BV7ChangeoverHeat/cool changeover: manual or automaticWrite0=Manual, 1=Automatic
BV8ClockFormatClock format: 12 or 24 hourWrite0=12-hour, 1=24-hour
BV9AckServiceClear service remindersWrite0=NoAction, 1=Clear
BV10UnitsDisplay units: °F or °CWrite0=Deg F, 1=Deg C
BV11DSTDaylight saving timeWrite0=Disabled, 1=Enabled
BV12SpDispModeSetpoint display: absolute or relativeWrite0=Absolute, 1=Relative
BV13OcupyInputOccupancy input statusRead0=Unocc, 1=Occ
BV14HmdyOnHumidification output onRead0=Off, 1=On
BV15DeHmdyOnDehumidification output onRead0=Off, 1=On
BV16OcupyStatusOccupancy statusRead0=No, 1=Yes
BV17DCVDemand-controlled ventilation activeRead0=Off, 1=On
BVmin18ExtFaultExternal fault inputRead0=Normal, 1=Fault
BV19EcomzrOnEconomizer output onRead0=Off, 1=On
BV20SrvcUvLampUV lamp service dueRead0=No Serv, 1=Service
BV21SrvcHmdyHumidifier service dueRead0=No Serv, 1=Service
BV22SrvcFilterFilter service dueRead0=No Serv, 1=Service
BV23HpCompLockOnHeat pump compressor lockout activeRead0=No Lock, 1=Lock
BV24HpAuxLockOnHeat pump auxiliary heat lockout activeRead0=No Lock, 1=Lock
BVmin25OverCurrentRelay overcurrent (total over 3 A)Read0=Off, 1=On
BV26SchOcupyOccupied by scheduleRead0=No, 1=Yes
BV27HmiOcupyOccupied by local touchscreenRead0=No, 1=Yes
BV28VntlationEffVentilation activeRead0=Off, 1=On
BV29PrePurgeEnPre-occupancy purge activeRead0=Off, 1=On
MV0PeriodsSchedule periods per dayRead1=6 Prds
MV1TmpOvrRideLocal setpoint override limitWrite1=1F/0.5C, 2=2F/1C, 3=3F/1.5C, 4=4F/2C, 5=5F/2.5C, 6=6F/3C, 7=7F/3.5C, 8=8F/4C, 9=9F/4.5C, 10=10F/5C, 11=No Limit
MV2KeyLockKeypad lock levelWrite1=NONE, 2=PARTIAL, 3=FULL
MV3SystemTypeSystem type: conventional or heat pumpWrite1=CONVEN, 2=HEAT P
MV4AuxOut1Function of OUT1Write1=Humid, 2=Dehumid, 3=Occupied, 4=AirQual, 5=EconEn, 6=Not Used
MV5AuxOut2Function of OUT2Write1=Humid, 2=Dehumid, 3=Occupied, 4=AirQual, 5=EconEn, 6=Not Used
MV6AuxOut3Function of OUT3Write1=Humid, 2=Dehumid, 3=Occupied, 4=AirQual, 5=EconEn, 6=Not Used
MV7Input1Function of input 1Write1=InTemRem, 2=InTemAvg, 3=Sup Temp, 4=Ret Temp, 5=Out Temp, 6=Hum 0-10, 7=CO2 0-10, 8=Occ DI, 9=Fault, 10=Not Used
MV8Input2Function of input 2Write1=InTemRem, 2=InTemAvg, 3=Sup Temp, 4=Ret Temp, 5=Out Temp, 6=Hum 0-10, 7=CO2 0-10, 8=Occ DI, 9=Fault, 10=Not Used
MV9Input3Function of input 3Write1=InTemRem, 2=InTemAvg, 3=Sup Temp, 4=Ret Temp, 5=Out Temp, 6=Hum 0-10, 7=CO2 0-10, 8=Occ DI, 9=Fault, 10=Not Used
MV10Input4Function of input 4Write1=InTemRem, 2=InTemAvg, 3=Sup Temp, 4=Ret Temp, 5=Out Temp, 6=Hum 0-10, 7=CO2 0-10, 8=Occ DI, 9=Fault, 10=Not Used
MV11TmpIn1TypeInput 1 typeWrite1=Type2Th, 2=0-10V
MV12TmpIn2TypeInput 2 typeWrite1=Type2Th, 2=0-10V
MV13TmpIn3TypeInput 3 typeWrite1=Type2Th, 2=0-10V
MV14TmpIn4TypeInput 4 typeWrite1=Type2Th, 2=0-10V
MV15StgDifClCooling inter-stage differentialWrite1=1F/0.5C, 2=2F/1C, 3=3F/1.5C, 4=4F/2C, 5=5F/2.5C, 6=6F/3C, 7=7F/3.5C, 8=8F/4C, 9=9F/4.5C, 10=10F/5C
MV16CoolingDBCooling deadbandWrite1=1F/0.5C, 2=2F/1C, 3=3F/1.5C, 4=4F/2C, 5=5F/2.5C
MV17StgDifHtHeating inter-stage differentialWrite1=1F/0.5C, 2=2F/1C, 3=3F/1.5C, 4=4F/2C, 5=5F/2.5C
MV18HeatingDBHeating deadbandWrite1=1F/0.5C, 2=2F/1C, 3=3F/1.5C, 4=4F/2C, 5=5F/2.5C
MV19BaudRateMS/TP baud rateWrite1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto
MV20SchEditModeSchedule edit modeRead1=7 days, 2=5+2, 3=5+1+1, 4=Individ, 5=disable
MV21HpCompLockHeat pump compressor lockout temperatureWrite1=Off, 2=15F/-9C, 3=20F/-7C, 4=25F/-4C, 5=30F/1C, 6=35F/2C, 7=40F/4C, 8=45F/7C
MV22HpAuxLockHeat pump auxiliary heat lockout temperatureWrite1=Off, 2=40F/4C, 3=45F/7C, 4=50F/10C, 5=55F/13C, 6=60F/16C
MVmin23HeatCoolModeSystem mode command: cool, heat, auto, offCommand1=COOLING, 2=HEATING, 3=AUTO, 4=Off
MVmin24SchedModeRoom operating mode command: comfort, economy, protectCommand1=Comfort, 2=Economy, 3=Protect
MVmin25ModeEffEffective mode: cooling, heating or offRead1=COOLING, 2=HEATING, 3=Off
MVmin26RM OP MODEEffective room operating modeRead1=Comfort, 2=Economy, 3=Protect
SCH0WeeklySchedule_1Weekly scheduleRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)

How many BACnet points does the Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) have?

This list has 136 BACnet objects: 10 analog inputs, 54 analog values, 4 binary inputs, 9 binary outputs, 30 binary values, 1 device, 1 schedule, 27 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) BACnet points are writable?

87 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901) BACnet documentation?

The source is RDY2000BN BACnet Thermostat Conventional Application 14900 Application Note (140-1231), revision 2020-02-11, published free by Siemens at https://sid.siemens.com/api/khub/documents/PprfbVmiVmRd48QjJgoa~Q/content.

What are the minimum BACnet points to integrate the Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)?

Start with MV 23 HeatCoolMode (Cool, heat, auto or off; factory default is Off); MV 24 SchedMode (Comfort, economy or protect (occupancy)); BV 0 FanMode (Fan Auto or Manual); AV 32 ComfortClgSP (Occupied cooling setpoint); AV 33 ComfortHtgSP (Occupied heating setpoint); MV 25 ModeEff (Current mode: cooling, heating or off); MV 26 RM OP MODE (Current room operating mode); AV 52 IndoorTmpEff (Room temperature used for control); BV 18 ExtFault (External fault input active); BV 25 OverCurrent (Relays shut off on overcurrent).

How do I enable BMS control of the Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)?

HeatCoolMode (MV 23) is the system mode command; its factory Relinquish_Default is Off, so the unit will not heat or cool until it is commanded or the default is changed. SchedMode (MV 24) sets Comfort, Economy or Protect; the internal schedule writes it too, and an occupancy input forces Comfort.

Can the BMS supply sensor values to the Siemens RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)?

A universal input can be set as a voltage input, taken out of service and written from the network, so a BMS value can stand in for a physical sensor (for example IndoorTmpRmt with Input1-4 = InTemRem). IndoorTmpEff then uses that value alone or averaged with the built-in sensor.

How do I check these points on the real RDY2000BN BACnet Commercial Thermostat (Applications 14900 / 14901)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Siemens BACnet points lists

Source: RDY2000BN BACnet Thermostat Conventional Application 14900 Application Note · 140-1231 · rev. 2020-02-11. Object names, instances and units are reproduced as published; descriptions are our own.