Room pressure monitor · BACnet points list

Siemens BACnet Room Pressure Monitor (RPM / SRCM) BACnet points list

Updated 28 October 2026

Short answer

A single-room differential pressure monitor sold by Siemens as a standard BACnet device. Its point map has one pressure input, alarm limits and timers, a door input, an alarm-active flag, relay and alarm settings, and selectors for the analog output type, pressure unit and room type. It has no application point; the field panel assigns a project application number.

This page lists 19 BACnet objects for the Siemens BACnet Room Pressure Monitor (RPM / SRCM) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
BACnet Room Pressure Monitor (RPM / SRCM)
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
19 (17 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Siemens RPM, SRCM, Setra SRCM, Room Condition Monitor
Source document
BACnet Room Pressure Monitor Point Map · 140-1300 · rev. 2014-09-03
Download CSV 19 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Siemens BACnet Room Pressure Monitor (RPM / SRCM)

Integration in brief

Read the room pressure (AI 1), the door input (BI 1) and the alarm-active flag (BV 2). Alarm limits, delay and the pressure unit can be set over BACnet. Event enrollments 1-3 can send alarm, out-of-limit and door-open notifications.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1AI_1Room differential pressureRead
BI 1DOOR STATUSDoor open/closed inputRead
BV 2ALARM ACTIVEPressure alarm activeWrite

Network setup

Watch out for

Siemens BACnet Room Pressure Monitor (RPM / SRCM) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

19 of 19 shown
Type
Multi-state
Access
Show
Siemens BACnet Room Pressure Monitor (RPM / SRCM) BACnet Points List
DescriptionStates
AImin1AI_1Room differential pressure shown on the displayinH2ORead
AV1AV_1Analog output value (4-20 mA, 0-5 V or 0-10 V)Write
AV2AV_2Pressure alarm low limitinH2OWrite
AV3AV_3Pressure alarm high limitinH2OWrite
AV4AV_4Alarm mute time-outsWrite
AV5ALARM DELAYAlarm delaysWrite
AV6AV_6Buzzer volume, 0-4Write
BImin1DOOR STATUSDoor status inputRead
BV1BV_1Relay operateWrite
BVmin2ALARM ACTIVEAlarm activeWrite
BV3BV_3Enabled or disabledWrite0=Disabled, 1=Enabled
BV4BV_4Audible alarmWrite
BV5LATCH ALARMLatch alarmWrite
BV6DOOR CONTACTDoor contactWrite
BV7BV_7Supervisor passwordWrite
BV8BV_8Operator passwordWrite
MV1MV_1Analog output signal typeWrite1=4-20mA, 2=0-5Vdc, 3=0-10Vdc
MV2MV_2Pressure unitWrite1=inWC, 2=Pa, 3=CmWC
MV3ROOM TYPERoom pressurization typeWrite1=Positive, 2=Negative, 3=Neutral

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Room Pressure Monitor (RPM / SRCM) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens BACnet Room Pressure Monitor (RPM / SRCM)

How many BACnet points does the Siemens BACnet Room Pressure Monitor (RPM / SRCM) have?

This list has 19 BACnet objects: 1 analog input, 6 analog values, 1 binary input, 8 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens BACnet Room Pressure Monitor (RPM / SRCM) BACnet points are writable?

17 of the 19 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Siemens BACnet Room Pressure Monitor (RPM / SRCM) BACnet documentation?

The source is BACnet Room Pressure Monitor Point Map (140-1300), revision 2014-09-03, published free by Siemens at https://sid.siemens.com/api/khub/documents/mfqHydSg0AIgD_1KIpx8tg/content.

What are the minimum BACnet points to integrate the Siemens BACnet Room Pressure Monitor (RPM / SRCM)?

Start with AI 1 AI_1 (Room differential pressure); BI 1 DOOR STATUS (Door open/closed input); BV 2 ALARM ACTIVE (Pressure alarm active).

How do I check these points on the real BACnet Room Pressure Monitor (RPM / SRCM)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Siemens BACnet points lists

Source: BACnet Room Pressure Monitor Point Map · 140-1300 · rev. 2014-09-03. Object names, instances and units are reproduced as published; descriptions are our own.