 "manufacturer": "Siemens",
 "manufacturer_slug": "siemens",
 "model": "BACnet Room Pressure Monitor (RPM / SRCM)",
 "model_slug": "bacnet-room-pressure-monitor-rpm",
 "short_model": "BACnet Room Pressure Monitor",
 "aliases": [
  "Siemens RPM",
  "SRCM",
  "Setra SRCM",
  "Room Condition Monitor"
 ],
 "equipment_type": "Room pressure monitor",
 "applies_to": "The Siemens BACnet Room Pressure Monitor (SRCM device) for single-room differential pressure monitoring with door input and alarm relay.",
 "summary": "A single-room differential pressure monitor sold by Siemens as a standard BACnet device. Its point map has one pressure input, alarm limits and timers, a door input, an alarm-active flag, relay and alarm settings, and selectors for the analog output type, pressure unit and room type. It has no application point; the field panel assigns a project application number.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The point map has no access column; AI and BI are shown read-only and AV, BV and MV writable (the map lists them as logical outputs).",
  "Pressure units follow the pressure unit selector MV 2 (inWC, Pa or cmWC); inH2O is shown here. The map's footnote calls this point 18 (MV_3); point 18 is MV_2 in the table.",
  "The analog output units (mA or V) follow MV 1.",
  "Most binary objects print only placeholder state text (\"Inactive Text\" / \"Active Text\"); those states are left blank here.",
  "Besides the 19 points, the map lists event enrollments and notification classes 1-3 for alarm, pressure out of limit and door open.",
  "The point map does not name the data link. Setra's PICS for the SRCM (Room Condition Monitor, SS-SRCM-BAC-PICS Rev A) lists BACnet MS/TP master at 9600, 19200, 38400 and 76800 baud."
 ],
 "source": {
  "title": "BACnet Room Pressure Monitor Point Map",
  "doc_number": "140-1300",
  "revision_date": "2014-09-03",
  "url": "https://sid.siemens.com/api/khub/documents/mfqHydSg0AIgD_1KIpx8tg/content"
 },
 "integration": {
  "summary": "Read the room pressure (AI 1), the door input (BI 1) and the alarm-active flag (BV 2). Alarm limits, delay and the pressure unit can be set over BACnet. Event enrollments 1-3 can send alarm, out-of-limit and door-open notifications.",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "AI_1",
    "why": "Room differential pressure"
   },
   {
    "ref": "BI 1",
    "name": "DOOR STATUS",
    "why": "Door open/closed input"
   },
   {
    "ref": "BV 2",
    "name": "ALARM ACTIVE",
    "why": "Pressure alarm active"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The device has no application point; the SRCM is set up at the field panel with a project-specific application number from 10000 to 11999."
  ],
  "gotchas": [
   "Changing the pressure unit (MV 2) changes the units of the pressure reading and the alarm limits."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "AI_1",
   "description": "Room differential pressure shown on the display",
   "units": "inH2O",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "AV_1",
   "description": "Analog output value (4-20 mA, 0-5 V or 0-10 V)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "AV_2",
   "description": "Pressure alarm low limit",
   "units": "inH2O",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "AV_3",
   "description": "Pressure alarm high limit",
   "units": "inH2O",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "AV_4",
   "description": "Alarm mute time-out",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "ALARM DELAY",
   "description": "Alarm delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "AV_6",
   "description": "Buzzer volume, 0-4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "DOOR STATUS",
   "description": "Door status input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "BV_1",
   "description": "Relay operate",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "ALARM ACTIVE",
   "description": "Alarm active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "BV_3",
   "description": "Enabled or disabled",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "BV_4",
   "description": "Audible alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "LATCH ALARM",
   "description": "Latch alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "DOOR CONTACT",
   "description": "Door contact",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "BV_7",
   "description": "Supervisor password",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "BV_8",
   "description": "Operator password",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "MV_1",
   "description": "Analog output signal type",
   "units": "",
   "access": "W",
   "states": "1=4-20mA, 2=0-5Vdc, 3=0-10Vdc"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "MV_2",
   "description": "Pressure unit",
   "units": "",
   "access": "W",
   "states": "1=inWC, 2=Pa, 3=CmWC"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "ROOM TYPE",
   "description": "Room pressurization type",
   "units": "",
   "access": "W",
   "states": "1=Positive, 2=Negative, 3=Neutral"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/siemens/bacnet-room-pressure-monitor-rpm",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}