Fan-powered VAV terminal unit controller · BACnet points list

Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) BACnet points list

Updated 28 October 2026

Short answer

Application 6606 controls a parallel fan-powered VAV box with up to three stages of electric heat on a Siemens BACnet PTEC controller over BACnet MS/TP. The supply damper modulates for cooling; in heating the parallel fan recirculates plenum air and the time-modulated heat stages follow the heating loop. The fan can be set up as the first stage of heat (PARALLEL ON/OFF against the heating loop) or to run only when supply airflow is too low for the coil (against FLOW).

This page lists 98 BACnet objects for the Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) — 83 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)
Equipment
Fan-powered VAV terminal unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
98 (83 writable)
Transport
BACnet MS/TP
Firmware
Newer than revision Bx40
Also known as
PTEC 6606, Application 6606, App 6606, 550-495PA, Siemens parallel fan VAV, fan-powered VAV electric heat
Source document
BACnet PTEC Controller Terminal Box (VAV) - Parallel Fan with Electric Heat, Application 6606, Application Note · 140-1166 · rev. 2014-10-27
Download CSV 98 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)

Integration in brief

Address the controller on the BACnet MS/TP trunk (manually or with auto addressing), then release the box to application control. The BMS commands occupancy with DAY.NGT (BO 29) and the day setpoints, and reads room temperature, airflow, damper position, fan and heat stage status and the error status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 29DAY.NGTDAY = occupied, NIGHT = unoccupiedCommand
AO 6DAY CLG STPTOccupied cooling setpoint, °FCommand
AO 7DAY HTG STPTOccupied heating setpoint, °FCommand
BO 5HEAT.COOLCurrent mode: HEAT or COOLCommand
BO 46FANParallel fan on/offCommand
AI 4ROOM TEMPSpace temperatureRead
AI 35AIR VOLUMEMeasured primary airflow, cfmRead
AO 49DMPR POSPrimary air damper position, %Command
BO 43HEAT STAGE 1Electric heat stage 1 on/offCommand
AO 99ERROR STATUSController error codeCommand

Enable & remote start

Occupancy is DAY.NGT (BO 29). With a wall switch on DI 2 and WALL SWITCH (BO 18) = YES, the switch sets it; standalone with no switch the controller stays in day mode; on a network the field panel or BMS commands DAY.NGT. NGT OVRD (BO 21) shows a temporary night override from the room unit button.

Sensors & values from the BMS

VENT DMD MIN (AO 105) sets the occupied ventilation minimum airflow and can be adjusted by the field panel; the larger of it and the cooling or heating minimum is used.

Network setup

Watch out for

Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

98 of 98 shown
Type
Access
Show
Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) BACnet Points List
DescriptionStates
AO1CTLR ADDRESSController MS/TP addressCommand
AO2APPLICATIONApplication number running in the controllerCommand
AO3RMTMP OFFSETRoom temperature calibration offset°FCommand
AImin4ROOM TEMPRoom temperature from the room unit°FRead
BOmin5HEAT.COOLCurrent heating/cooling modeCommand0=COOL, 1=HEAT
AOmin6DAY CLG STPTDay (occupied) cooling setpoint°FCommand
AOmin7DAY HTG STPTDay (occupied) heating setpoint°FCommand
AO8NGT CLG STPTNight (unoccupied) cooling setpoint°FCommand
AO9NGT HTG STPTNight (unoccupied) heating setpoint°FCommand
BI10DI 6Digital input 6Read0=OFF, 1=ON
AO11RM STPT MINLowest setpoint allowed from the room unit°FCommand
AO12RM STPT MAXHighest setpoint allowed from the room unit°FCommand
AI13RM STPT DIALSetpoint from the room unit dial or keypad°FRead
BO14STPT DIALUse the room unit setpoint dialCommand0=NO, 1=YES
AI15AUX TEMP AI5Auxiliary temperature input on AI 5°FRead
AO16FLOW STARTHeating loop % where airflow starts to rise%Command
AO17FLOW ENDHeating loop % where airflow reaches maximum%Command
BO18WALL SWITCHWall switch connected to DI 2Command0=NO, 1=YES
BI19DI OVRD SWRoom unit night override buttonRead0=OFF, 1=ON
AO20OVRD TIMENight override durationhCommand
BO21NGT OVRDNight override statusCommand0=DAY, 1=NIGHT
AO22REHEAT STARTHeating loop % where reheat starts%Command
AO23REHEAT ENDHeating loop % where reheat is at full output%Command
BI24DI 2Digital input 2Read0=OFF, 1=ON
BI25DI 5Digital input 5Read0=OFF, 1=ON
AO26SERIES ONSeries fan ON setting (series fan sequence; not described here)%Command
AO27SERIES OFFSeries fan OFF setting (series fan sequence; not described here)%Command
AO28PARALLEL ONParallel fan start point (heating loop or flow %)%Command
BOmin29DAY.NGTDay/night (occupancy) modeCommand0=DAY, 1=NIGHT
AO30PARALLEL OFFParallel fan stop point (heating loop or flow %)%Command
AO31CLG FLOW MINMinimum airflow in coolingcfmCommand
AO32CLG FLOW MAXMaximum airflow in coolingcfmCommand
AO33HTG FLOW MINMinimum airflow in heatingcfmCommand
AO34HTG FLOW MAXMaximum airflow in heatingcfmCommand
AImin35AIR VOLUMEMeasured airflowcfmRead
AO36FLOW COEFFAirflow pickup correction coefficientCommand
BI40DI 4Digital input 4Read0=OFF, 1=ON
BO41DO 1Digital output 1Command0=OFF, 1=ON
BO42DO 2Digital output 2Command0=OFF, 1=ON
BOmin43HEAT STAGE 1Electric heat stage 1 outputCommand0=OFF, 1=ON
BO44HEAT STAGE 2Electric heat stage 2 outputCommand0=OFF, 1=ON
BO45HEAT STAGE 3Electric heat stage 3 outputCommand0=OFF, 1=ON
BOmin46FANParallel fan on/offCommand0=OFF, 1=ON
BI47DI 3Digital input 3Read0=OFF, 1=ON
AO48DMPR COMDDamper position command%Command
AOmin49DMPR POSDamper position (calculated)%Command
AI50AI 4Spare analog input 4°FRead
AO51MTR1 TIMINGMotor 1 full-stroke timesCommand
AI54AI3Spare analog input 3%Read
AO56DMPR ROT ANGDamper rotation angleCommand
AO58MTR SETUPMotor enable/reverse setup (additive code)Command
AO59DO DIR. REVDigital output direction reverse (additive code)Command
AO63CLG P GAINCooling loop proportional gainCommand
AO64CLG I GAINCooling loop integral gainCommand
AO65CLG D GAINCooling loop derivative gainCommand
AO66AOV 1Analog output 1 (0-10 V)VCommand
AO67HTG P GAINHeating loop proportional gainCommand
AO68HTG I GAINHeating loop integral gainCommand
AO69HTG D GAINHeating loop derivative gainCommand
AO70AOV 2Analog output 2 (0-10 V)VCommand
AO71FLOW P GAINFlow loop proportional gainCommand
AO72FLOW I GAINFlow loop integral gainCommand
AO73FLOW D GAINFlow loop derivative gainCommand
AO74FLOW BIASFlow loop bias%Command
AO75FLOWAirflow as percent of maximum%Command
AO76CTL FLOW MINActive minimum airflowcfmCommand
AO77CTL FLOW MAXActive maximum airflowcfmCommand
AO78CTL TEMPTemperature the controller is controlling to°FCommand
AO79CLG LOOPOUTCooling loop output%Command
AO80HTG LOOPOUTHeating loop output%Command
AO81AVG HEAT OUTAverage auxiliary heat output%Command
AO82STAGE MAXStaged heat maximum, percent%Command
AO83STAGE MINStaged heat minimum, percent%Command
AO85SWITCH LIMITLoop output below which mode may switch%Command
AO86SWITCH TIMEMinimum time before heat/cool switchoverminCommand
BO87CAL MODULECalibration module installedCommand0=NO, 1=YES
AO88STAGE COUNTNumber of electric heat stagesCommand
AO89STAGE TIMEElectric heat cycle timeminCommand
AO90SWITCH DBANDTemperature deadband for heat/cool switchover°FCommand
AO91AOV 3Analog output 3 (0-10 V)VCommand
AO92CTL STPTActive control setpoint°FCommand
AO93FLOW STPTAirflow setpoint, percent%Command
BO94CAL AIRStart air velocity sensor calibrationCommand0=NO, 1=YES
AO95CAL SETUPCalibration setup codeCommand
AO96CAL TIMERHours between automatic calibrationshCommand
AO97DUCT AREAInlet duct area for airflow calculationft²Command
AO98LOOP TIMEControl loop intervalsCommand
AOmin99ERROR STATUSController error status codeCommand
BO102DO 7Digital output 7Command0=OFF, 1=ON
BO103DO 8Digital output 8Command0=OFF, 1=ON
AO104NGT FLOW MINMinimum airflow at nightcfmCommand
AO105VENT DMD MINVentilation demand minimum airflowcfmCommand
AO106STPT SPANRoom unit setpoint adjustment span°FCommand
AI121DEW POINTRoom dew point°FRead
AO124SENSOR SELRoom unit / sensor select code (additive)Command
AI125RM CO2Room CO2ppmRead
AI126RM RHRoom relative humidity%Read
BO127PPCL STATEPPCL program loaded or emptyCommand0=EMPTY, 1=LOADED

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)

How many BACnet points does the Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) have?

This list has 98 BACnet objects: 9 analog inputs, 67 analog outputs, 6 binary inputs, 16 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) BACnet points are writable?

83 of the 98 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat) BACnet documentation?

The source is BACnet PTEC Controller Terminal Box (VAV) - Parallel Fan with Electric Heat, Application 6606, Application Note (140-1166), revision 2014-10-27, published free by Siemens at https://sid.siemens.com/api/khub/documents/VnTLRBZ5tDMCqHOqURBoJg/content.

What are the minimum BACnet points to integrate the Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)?

Start with BO 29 DAY.NGT (DAY = occupied, NIGHT = unoccupied); AO 6 DAY CLG STPT (Occupied cooling setpoint, °F); AO 7 DAY HTG STPT (Occupied heating setpoint, °F); BO 5 HEAT.COOL (Current mode: HEAT or COOL); BO 46 FAN (Parallel fan on/off); AI 4 ROOM TEMP (Space temperature); AI 35 AIR VOLUME (Measured primary airflow, cfm); AO 49 DMPR POS (Primary air damper position, %); BO 43 HEAT STAGE 1 (Electric heat stage 1 on/off); AO 99 ERROR STATUS (Controller error code).

How do I enable BMS control of the Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)?

Occupancy is DAY.NGT (BO 29). With a wall switch on DI 2 and WALL SWITCH (BO 18) = YES, the switch sets it; standalone with no switch the controller stays in day mode; on a network the field panel or BMS commands DAY.NGT. NGT OVRD (BO 21) shows a temporary night override from the room unit button.

Can the BMS supply sensor values to the Siemens BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)?

VENT DMD MIN (AO 105) sets the occupied ventilation minimum airflow and can be adjusted by the field panel; the larger of it and the cooling or heating minimum is used.

How do I check these points on the real BACnet PTEC VAV Controller - Application 6606 (Parallel Fan with Electric Heat)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Siemens BACnet points lists

Source: BACnet PTEC Controller Terminal Box (VAV) - Parallel Fan with Electric Heat, Application 6606, Application Note · 140-1166 · rev. 2014-10-27. Object names, instances and units are reproduced as published; descriptions are our own.