VAV terminal unit controller (actuator) · BACnet points list

Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) BACnet points list

Updated 7 November 2026

Short answer

The DXR1.E10PL is a damper actuator with a built-in BACnet IP room controller and airflow sensor for VAV, VVT and fan-powered boxes. This entry is the HvacFnct33 object set: supply damper, hot water valve (3-position, PWM or 0-10 V) and 1-3 stage or modulating electric reheat outputs, box differential pressure, air quality and humidity inputs, fan state inputs, KNX PL-Link room unit and sensor values, room operating mode, comfort/economy/protection setpoints, air quality setpoints, and the supply airflow setpoint, measured flow and limits.

This page lists 65 BACnet objects for the Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Siemens’s own free documentation, linked below.

Manufacturer
Siemens
Model
OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)
Equipment
VAV terminal unit controller (actuator)
Equipment type
Valves & actuators
BACnet objects
65 (34 writable)
Transport
BACnet IP
Firmware
FW 04.91.16.8, application type version 5.001
Also known as
DXR1.E10PL-112/US, DXR1.E10PL-113/US, DXR1.E10PL, Zone Controller Actuator, OpenAir Intelligent VAV Actuator, Actuating DXR, HvacFnct33
Source document
Zone Controller Actuator Variable Air Volume, Variable Volume Temperature, and Fan-Powered Box BACnet Objects · A6V14595742 · rev. 2025-05-29
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Siemens’s current documentation and the live device before use. Not official Siemens information. Terms of use.

BMS integration notes: Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)

Integration in brief

Command the room operating mode (MV 9) and the room setpoint (AV 50) at priority 15, then read room temperature, heating/cooling state, supply airflow, fan state and the damper and heating positions.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 9ROpModRoom operating mode (protection/economy/comfort)Command
AV 50SpTRRoom temperature setpoint, °F (priority 15)Command
AV 57RTempEffective room temperatureRead
MV 17HCStaHeating/cooling stateRead
BI 4FanStaFan state (on/off)Read
AV 97VavSuAirFlMeasured supply airflow, cfmRead
AV 95VavSuSpAirFlSupply airflow setpoint, cfmCommand
AO 0VavSuPosSupply damper position, %Command
AO 11HclVlvPosHot water heating valve position, %Command

Enable & remote start

The doc says the room operating mode is normally controlled from the BMS and must be written at priority 15; scheduled or manual central commands also use priority 15.

Sensors & values from the BMS

Room temperature, humidity and air quality come from a KNX PL-Link room unit or sensor, or from wired inputs; the effective values are AV 57 (temperature), AV 55 (humidity) and AV 56 (air quality).

Network setup

Watch out for

Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

65 of 65 shown
Type
Multi-state
Access
Show
Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) BACnet Points List
DescriptionStates
AOmin0VavSuPosSupply air VAV position%Command
AOmin11HclVlvPosHeating coil valve position%Command
AO12HclVlvPosHeating coil valve position%Command
AO13HclVlvPosHeating coil valve position%Command
AO14HclVlvPosHeating coil valve position%Command
AO15HclVlvPosHeating coil valve position%Command
BO4HclElPosHeating coil electric positionCommand0=Off, 1=On
BO5HclElPosHeating coil electric positionCommand0=Off, 1=On
BO6HclEl1StPosHeating coil electric pos.first stageCommand0=Off, 1=On
BO9HclEl2StPosHeating coil electric pos.second stageCommand0=Off, 1=On
BO8HclEl1StPosHeating coil electric pos.first stageCommand0=Off, 1=On
BO11HclEl2StPosHeating coil electric pos.second stageCommand0=Off, 1=On
BO12HclEl3StPosHeating coil electric pos.third stageCommand0=Off, 1=On
BO7HclEl1StPosHeating coil electric pos.first stageCommand0=Off, 1=On
BO10HclEl2StPosHeating coil electric pos.second stageCommand0=Off, 1=On
BO13HclEl3StPosHeating coil electric pos.third stageCommand0=Off, 1=On
AO16HclElPosHeating coil electric position%Command
AI12VavSuDiffPSupply air VAV differential pressureinH2ORead
AI15AQualRRoom air qualityppmRead
AI16AQualRRoom air qualityppmRead
AI17HuRelRRelative air humidity for room%RHRead
AI18HuRelRRelative air humidity for room%RHRead
BImin4FanStaFan stateRead0=Off, 1=On
BI5FanStaFan stateRead0=Off, 1=On
BI6FanStaFan stateRead0=Off, 1=On
MV131ROpUn(1)Room operator unit 1 device statusRead1=Operational, 2=Device stopped, 3=Device not assigned, 4=Device missing, 5=Configuring device, 6=Unused, 7=Missing or wrong configuration, 8=Searching
AI59TRRoom temperature°FRead
AV327SpShftInSetpoint shift input value°FRead
BV144PscBtnInPresence button input valueRead0=Absent, 1=Present
MV169ROpUn(1)Room operator unit 1 device statusRead1=Operational, 2=Device stopped, 3=Device not assigned, 4=Device missing, 5=Configuring device, 6=Unused, 7=Missing or wrong configuration, 8=Searching
AI75TRRoom temperature°FRead
AV409SpShftInSetpoint shift input value°FRead
BV211PscBtnInPresence button input valueCommand0=Absent, 1=Present
AI74AQualRRoom air qualityppmRead
AI73HuRelRRelative air humidity for room%RHRead
MV191Sen(1)Sensor 1 device statusRead1=Operational, 2=Device stopped, 3=Device not assigned, 4=Device missing, 5=Configuring device, 6=Unused
AI94TRRoom temperature°FRead
MV193Sen(1)Sensor 1 device statusRead1=Operational, 2=Device stopped, 3=Device not assigned, 4=Device missing, 5=Configuring device, 6=Unused, 7=Missing or wrong configuration, 8=Searching
AI97TRRoom temperature°FRead
AI98HuRelRRelative air humidity for room%RHRead
MV194AQualRIndRuRoom air quality ind.for room op.unitRead1=Undefined, 2=Poor, 3=Okay, 4=Good
AI99AQualRRoom air qualityppmRead
MVmin9ROpModRoom operating modeCommand1=Protection, 2=Economy, 3=Pre-comfort, 4=Comfort
AVmin50SpTRRoom temperature setpoint°FCommand
AVmin57RTempRoom temperature°FRead
AV55RHuRelRelative humidity for room%RHRead
AV56RAQualRoom air qualityppmRead
MVmin17HCStaHeating/cooling stateRead1=Neither, 2=Heating, 3=Cooling
AV37SpCCmfCooling setpoint for comfort°FCommand
AV39SpCEcoCooling setpoint for economy°FCommand
AV40SpCPrtCooling setpoint for protection°FCommand
AV32PrSpCPresent cooling setpoint°FRead
AV19SpHCmfHeating setpoint for comfort°FCommand
AV21SpHEcoHeating setpoint for economy°FCommand
AV22SpHPrtHeating setpoint for protection°FCommand
AV14PrSpHPresent heating setpoint°FRead
AV10SpAQualRCmfSetpoint room air quality for comfortppmCommand
AV11SpAQualRPcfSetp.room air quality for pre-comfortppmCommand
AV12SpAQualREcoSetpoint room air quality for economyppmCommand
AVmin95VavSuSpAirFlSupply air VAV setpoint for air vol.flowcfmCommand
AVmin97VavSuAirFlSupply air VAV air volume flowcfmRead
AV88VavSuAirFlMaxCSupply air VAV max.air vol.flow f.cool.cfmCommand
AV89VavSuAirFlMinCSupply air VAV min.air vol.flow f.cool.cfmCommand
AV90VavSuAirFlMaxHSupply air VAV max.air vol.flow f.heat.cfmCommand
AV91VavSuAirFlMinHSupply air VAV min.air vol.flow f.heat.cfmCommand
Object ID lookup: Siemens DXR1.E10PL (HvacFnct33) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)

How many BACnet points does the Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) have?

This list has 65 BACnet objects: 13 analog inputs, 7 analog outputs, 23 analog values, 3 binary inputs, 10 binary outputs, 2 binary values, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) BACnet points are writable?

34 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors) BACnet documentation?

The source is Zone Controller Actuator Variable Air Volume, Variable Volume Temperature, and Fan-Powered Box BACnet Objects (A6V14595742), revision 2025-05-29, published free by Siemens at https://sid.siemens.com/api/khub/documents/lI1Ts8xUke93FIiwBFgwSQ/content.

What are the minimum BACnet points to integrate the Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)?

Start with MV 9 ROpMod (Room operating mode (protection/economy/comfort)); AV 50 SpTR (Room temperature setpoint, °F (priority 15)); AV 57 RTemp (Effective room temperature); MV 17 HCSta (Heating/cooling state); BI 4 FanSta (Fan state (on/off)); AV 97 VavSuAirFl (Measured supply airflow, cfm); AV 95 VavSuSpAirFl (Supply airflow setpoint, cfm); AO 0 VavSuPos (Supply damper position, %); AO 11 HclVlvPos (Hot water heating valve position, %).

How do I enable BMS control of the Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)?

The doc says the room operating mode is normally controlled from the BMS and must be written at priority 15; scheduled or manual central commands also use priority 15.

Can the BMS supply sensor values to the Siemens OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)?

Room temperature, humidity and air quality come from a KNX PL-Link room unit or sensor, or from wired inputs; the effective values are AV 57 (temperature), AV 55 (humidity) and AV 56 (air quality).

How do I check these points on the real OpenAir Zone Controller Actuator DXR1.E10PL - HvacFnct33 (with fan state, room units and sensors)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Siemens BACnet points lists